MR9270S en
MR9270S en
Instructions
MR9270S
transparent
mA 1 IN 2 ILO 3 OK
IN T-ON OUT FN
Hz 4 mV 5 24V 6 +-
EXIT
Dear users, thank you for purchasing the products produced by Shanghai Lanyi Electronic Technology Co., Ltd.
Mr.Signal Series Smart Signal Generator: Smart. To get started with Smart
1. Check "Instrument Introduction" and "Instrument Technical Parameters" to understand the main functions of Smart
Signal selection and signal mode, for example, select millivolt output, thermocouple
belongs to millivolt signal, then millivolt output and various thermocouple types are millivolt signal mode. 3. Two
methods of manipulating the output value of a signal. 4. Enter the window and pay attention to the operation
1. Introduction to the
instrument 1.1Smart uses a high-speed ARM processor with powerful performance, and has a man-machine dialogue
interface that is easy to use. The following figure shows the structure of Smart.
TFT color
Modbus master, PID panel,
display
recorder, HART
Communication Interface
USB
Firmware download
FLASH
14500 lithium
battery (900mA*2) Rs485
USB
-1-
Machine Translated by Google Smart Signal Generator
introduction: Program output: the user can let the Smart signal automatically rise and fall output, there are two modes,
the first one: set the start point, end point, number of cycles, and then start working. The second
type: advanced mode, the signal changes are all set by parameters.
Preset value: 9 groups of commonly used signal values can be preset for quick output. Signal
conversion: input signal is converted into output signal, for example: input frequency signal is converted into current
signal, input range is 0-1000hz into 4-20mA. Real-time curve: It can display the change trend of
input and output signals in the form of a curve, the collection time of the curve can be set, and the curve can be
automatically displayed in the range of the maximum and minimum values within a certain period of
time. Engineering quantity display conversion: the signal is displayed as signal value or engineering quantity, and the signal
value corresponds to the engineering quantity linearly, for example: the signal of 4-20mA corresponds to 0-100, that is,
4mA corresponds to 0, 12mA corresponds to 50, and 20mA corresponds to 100, which can be passed
Modbus RTU remote control: It can communicate with configuration software or PLC through RS485 to realize online
setting of the output signal of the instrument and monitor the input signal of the instrument.
Modbus RTU master station: perform communication test, parameter setting, parameter copy, online monitoring and
other operations on slave devices with RS485 MODBUS interface. Instrument tool set: As the
function extension of the instrument, such as: simple paperless recorder, PID controller, etc., please pay attention to the
product website for details, and this manual does not describe it.
USB to Rs485: The instrument can be used as a USB to RS485 virtual serial port, WIN10
-2-
Machine Translated by Google
Smart Signal Generator
Accuracy Resolution Model Range Accuracy Resolution Temperature Drift Coefficient Temperature Drift Coefficient
Current (mA) Current Internal impedance Internal
Passive (XMT) Passive (XMT) 0~24mA 0~24mA 0.1% 0.1% 0.01mA 0.001mA +25PPM +25PPM
24V Loop 24V Loop 0~24mA 0~24mA 0.1% 0.1% 0.01mA 5 digits +25PPM +25PPM 100ÿ 100ÿ
Frequency (Hz) Frequency 0~9999Hz 0~9999Hz 0.03% 0.03% 0.1mV 0.01mV +10PPM 1Mk 1Mk
(Hz) Millivolt (mV) Millivolt -10~110mV -10~110mV 0.05% 0.05% +25PPM +25PPM 2K 2K
(mV) Thermocouple (TC-S) Thermocouple 0-1760ÿ 0-1760ÿ 0.2% 0.2% 1ÿ 1ÿ +25PPM +25PPM 2K 2K
(TC-S) Thermocouple (TC-B) Thermocouple 0-1810ÿ 0-1810ÿ 0.5% 0.5% 1ÿ 1ÿ +25PPM +25PPM 2K 2K
(TC-B) Thermocouple (TC-E) Thermocouple 0-990ÿ 0-990ÿ 0.2% 0.2% 1ÿ 1ÿ +25PPM +25PPM 2K 2K
(TC-K) Thermocouple (TC-R) Thermocouple 0-1760ÿ 0-1760ÿ 0.3% 0.3% 1ÿ 1ÿ +25PPM +25PPM 2K 2K
(TC-R) Thermocouple (TC-J) Thermocouple 0-1190ÿ 0-1190ÿ 0.3% 0.3% 1ÿ 1ÿ +25PPM +25PPM 2K 2K
0-1290ÿ
Thermocouple (TC-T) Thermocouple (TC-N) Thermocouple 0-1290ÿ
(TC-N) 0.2% 0.2% 1ÿ 1ÿ +25PPM +25PPM 2K 2K
------
Pt100 Pt100 -200~650ÿ -200~650ÿ 0.5% 0.5% 1ÿ 1ÿ +50PPM +100PPM
Resolution Temperature Drift Coefficient Temperature Drift Coefficient Current (mA) Current (mA) 0.01mA 0.01mA +25PPM Voltage (V) Voltage (V) Frequency (Hz) Frequency
millivolt ((mV)
Hz) millivolt (mV)
Internal Impedance Internal
-3-
Machine Translated by Google Smart Signal Generator
Thermocouple (TC-N) Thermocouple (TC-N) 0-1290ÿ 0-1290ÿ 0.2% 0.2% 1ÿ 1ÿ +50PPM +25PPM 2K
2Mk
Pt100 Pt100 -200~650ÿ -200~650ÿ 0.1% 0.5% 1ÿ
0.1ÿ +50PPM +100PPM 2.5k
---
3. Basic operation
3.1 Interface
definition Input-/(24V)
output + output Input+
MR9270S
transparent
mA 1 IN 2 ILO 3 OK
IN T-ON OUT FN
Hz 4 mV 5 24V 6 +-
EXIT
-4-
Machine Translated by Google Smart Signal Generator
Input signal selection Function/Menu key the menu interface, this key is the
EXIT Menu exit direction key: used to select the option to be set or modify
the value.
Output signal
set value
Input signal
display value
real time curve
Press OUT once to pop up the output signal selection interface, and then Press IN once to pop up the input signal selection interface, and then press the
press the position of the keyboard to select the corresponding signal. position of the keyboard to select the corresponding signal.
-5-
Machine Translated by Google
Smart Signal Generator
Press the left and right keys to move the cursor to select the digit to be set, and
This key is the signal switch key, be sure to press this key
T-ON
window. The following figure takes the current setting window as an example. signal setting window. The following figure takes the current setting window as
an example
-6-
Machine Translated by Google Smart Signal Generator
I-TY
Press and hold the key EXIT for 2 seconds to switch between 5 different interfaces, and the following are the other four interfaces.
-7-
Machine Translated by Google Smart Signal Generator
Short key EXIT on the working interface will pop up the numeric keypad window, and the 12 buttons on the numeric keypad
window correspond to the 12 physical keys of the Smart, which are used to quickly set the signal output value. Short press to
realize the first function of the button, and long press to realize the second function, such as long press the number '1' to input a
negative sign.
4. Signal description
T-ON
4.1.2 Current signal open circuit detection: Press to start the signal output, if the interface shows open circuit and flashes,
4.1.3 Current output setting window: Press and hold OUT for two seconds to pop up a window.
-8-
Machine Translated by Google Smart Signal Generator
voltage: Set the current output no-load voltage, the default is 16.5V in order
to save power, some devices must require 24V drive capability. Quantity
range.
meter or
+ PLC
output- output+
4.2.2 Voltage output setting window: Press and hold OUT for two seconds to pop up a window.
-9-
Machine Translated by Google Smart Signal Generator
meter or
+ PLC
output- output+
4.3.1 Passive current output mode: Press O-TY to change the mode.
4.3.2 Passive current output setting window: press and hold OUT for two seconds to pop up a window.
-10-
Machine Translated by Google Smart Signal Generator
input+
Passive output (XMT) output to digital display
null enter- instrument/PLC/isolation safety barrier and other equipment
24V
output- output+
4.4.1 The pulse signal has four modes: press two O-TY seconds to switch modes.
-11-
Machine Translated by Google Smart Signal Generator
4.4.2 Pulse output setting window: Press and hold OUT for two seconds to pop up a window.
pulse signal. It has four ranges. You can enter the pulse
mode.
digital O-TY
tube of the frequency value to be selected by the
Pulse heating, motor speed adjustment, light brightness, magnetic powder clutch braking strength, etc. It
has a wide range of uses and is the best solution for linear drive.
-12-
Machine Translated by Google
Smart Signal Generator
position is vacant, and the rotational speed is measured by this missing tooth. 4.4.6 Pulse signal operation
instructions - Quantitative mode. The main purpose of pulse quantification is to simulate flow quantitative control
sensors. For example, a turbine sensor generates 100 pulses after one liter of water flows through the sensor, then 10
liters of water is 1000 pulses. When writing a PLC quantitative program, the generator can be used to accurately
simulate .
minimum is 0.1mS
-13-
Machine Translated by Google Smart Signal Generator
Press this key to change from stop state to pause, which means ready
T-ON
to start working. Press this key in pause state, the pulse will start to
send.
IN T-ON OUT FN
Hz 4 mV 5 24V 6 +- Press this key in the running state, and the pulse transmission will be paused.
I-TY O-TY REST
Oh 7 1 RTD 8 11 TC 9 1
0 Press this key in the running state to send pulses individually.
EXIT
REST Press this key in the running state, the program stops and resets.
O-TY Press this key in any state to modify the cycle time.
meter or
+
PLC
output- output+
level output
resistance
Open collector output frequency output
instrument or PLC
-14-
Machine Translated by Google
Smart Signal Generator
Millivolt output thermocouple analog output 4.5.2 Millivolt output setting window:
Thermocouples work on site, and measuring instruments generally work indoors. The
temperature difference between the two is large. Since the signal measured by the
thermocouple is based on 0, the thermocouple The signal is weak. In order to transmit
the signal to the measuring instrument end stably, a special compensation lead wire must be used. However, the compensation lead wire enters the point where
the instrument is located and superimposes the temperature transmitted back to the room. Therefore, the superimposed thermoelectric potential must be
removed by cold junction compensation. Let the thermocouple signal be accurately restored. Therefore, during the test, it is found that the temperature displayed
by the instrument does not match the actual temperature or is too high, which means that the temperature of the cold end needs to be set, which is the indoor
temperature.
meter or
+ PLC
output- output+
-15-
Machine Translated by Google Smart Signal Generator
output 4.6.2 Resistance output setting window: Press and hold OUT for two seconds to pop up a window.
meter or
+ PLC
output- output+
-16-
Machine Translated by Google Smart Signal Generator
4.7 24V loop detection (transmitter power supply and current detection are shared with the output port) 4.7.1
4.7.2 24V setting window: Press and hold OUT for two seconds to pop up a window.
Transmitter - + transmitters, and so on. The power supply current of the test equipment
cannot be greater than 24mA, please select the equipment for testing.
output- output+
-17-
Machine Translated by Google Smart Signal Generator
The input (-) can be switched to an independent 24V function, which outputs a single 24V. The 24V
terminal is used in conjunction with the input (+) to test the transmitter. Its main use is to test pneumatic
output - output + input - input + Tip: The difference between 24V loop detection and independent
24V is that the 24V loop detection uses the output signal port to
ÿÿÿ
ÿÿÿ measure the feedback current. The independent 24V port and
activation the output (-) port can form a 24V power supply, and can also
form a transmitter power supply and measure with the input (+).
ÿÿÿÿÿÿ
The feedback current of the transmitter.
4.8.2 Turn on the independent 24V.
Enter the function menu and choose to activate 24V, the status bar will display 24V prompt and flash
24V activation: After this item is ticked, the independent 24V starts to output.
Activation hold: After this item is ticked, every time it is turned on, the 24V state
will remain at the state of the last time it was turned on. On the contrary, the 24V
Pay attention to the wiring method of the independent 24V test two-wire transmitter, the "independent 24V"
terminal is connected to the positive pole, and the input (+) is connected to the negative pole .
Transmitter 1 Transmitter
2 (-) (+) (+) (-)
-18-
Machine Translated by Google Smart Signal Generator
4.9.2 Current input setting window: Press and hold forINtwo seconds to pop up a window.
and the voltage within 30V will not burn out the input
-19-
Machine Translated by Google
Smart Signal Generator
I-TY
4.10.1 Voltage input display mode: Press to switch modes.
+ various sensors
input - input +
-20-
Machine Translated by Google Smart Signal Generator
4.11.2 Pulse input setting window: Press and hold IN for two seconds to pop up a window.
method: The rising edge means that the level rises from
REST ÿ
-21-
Machine Translated by Google Smart Signal Generator
- Sensors with
PNP
frequency output
+
input - input +
Oc gate
frequency
-
output sensor
input - input +
Sensors with open-circuit output are common,
2.5V
such as turbine flowmeters, proximity switches,
2K resistor
etc., are tested with open-circuit input.
-22-
Machine Translated by Google Smart Signal Generator
4.12.2 Millivolt input setting window: Press and hold IN for two seconds to pop up a window.
+ thermocouple sensor
input - input +
4.13.1 Display mode of resistance input: press switch I-TY to change the mode.
-23-
Machine Translated by Google
Smart Signal Generator
4.13.2 Resistance input setting window: Press and hold IN for two seconds to pop up a window.
Pt100/
Cu50
resistance
input - input +
5. Program output
The programming output can automatically complete N cycles according to the parameters set by the user. This
function is mainly used for aging tests of electric valves or pneumatic valves, or tests such as PLC program
adjustment.
5.1. As shown in the figure, set 4 parameters to quickly output the program.
Signal peak
value at 20mA
Increase and decrease cycle The rising and falling process of the left figure is a cycle,
Run this cycle 100 times.
-24-
Machine Translated by Google Smart Signal Generator
Pop up the programming output window and select Start, and it will automatically return to the main interface, waiting for the user
status icon
Signal start point end point progress timing progress remaining times
stop
Hz 4 mV 5 24V 6 +-
-25-
Machine Translated by Google Smart Signal Generator
5.3. Advanced settings (the last item in the programming output window)
ÿÿÿÿÿÿ
current window.
Tip: After using the custom mode and setting the 6 parameters, when returning to the programming output window, the increase/
decrease cycle will be displayed and the increase/decrease cycle will be recalculated according to the user definition.
-26-
Machine Translated by Google Smart Signal Generator
For this waveform, the subtraction step value can be set to the entire
range, such as the start is 4mA, the end point is 20mA, and the
It is the same as the rising sawtooth wave method, except that the incremental step value
0 T
falling sawtooth
0 T
-27-
Machine Translated by Google Smart Signal Generator
6. Preset value
6.1 Enter the preset window, short press on the main interface to pop
FN up the function menu and select Enable
preset.
After the preset is enabled, the keys on the left three columns of the keyboard are converted to the preset function,
and the right side can be used by pressing FN REST , and pressing EXIT to exit the preset function.
mA 1 IN 2 ILO 3 OK
-28-
Machine Translated by Google Smart Signal Generator
7. Signal conversion
During on-site debugging, if the debugged equipment does not match the secondary instrument, this situation can be solved
by signal conversion, for example, the frequency is converted from 0-100Hz to 4-20mA.
On the main interface, short press FN to pop up the function menu and choose to enable conversion.
Input lower limit/Input lower limit: The signal range of the input
input is
When 0V, the output will follow 0mA, if the user does not
check it, then the output is 4mA, and the output is locked
It will automatically start the signal conversion when it is turned on, and if the key EXIT is pressed during the conversion work ,
the signal conversion will exit. The purpose of power-on activation: If the user wants to plug in the USB power supply for a
long time and work in the signal conversion mode, in order to avoid manually starting this function every time the machine is
restarted, this function is enabled. In order not to cause misoperation, just press once to exit, the instrument Run at startup
8.1 Display large curve interface: In the main interface, press and hold for 2 seconds
EXIT to switch the interface, and the large
curve screen is on the 4th and 5th interfaces.
-29-
Machine Translated by Google Smart Signal Generator
auxiliary timer
time scale
and flash, and the real-time curve will pause to refresh at this time, continue to press this button for 2 seconds, and
the real-time curve will start to refresh. Auxiliary timer reset: The auxiliary timer displays the running time of the
machine, long press the REST clock for 2 seconds to reset the timer. Please use this function flexibly in conjunction
with clearing.
-30-
Machine Translated by Google
Smart Signal Generator
real-time curve.
scaling: Automatically adjust the scale range of the output signal, and
curve. Acquisition time: the refresh interval time of the output curve.
Tip: Modify the acquisition time, the time scale will change automatically, and the
time scale only follows the input signal acquisition time.
-31-
Machine Translated by Google
Smart Signal Generator
EXIT
interface: Select the work interface, which has the same effect as long pressing.
Backlight: Adjust the brightness of the backlight. Setting save: save the output value
set before shutdown. State preservation: the switch state of the output signal is
maintained, (if the signal is turned on every time the power is turned on, this item can be set, and it usually
works with signal conversion). Buzzer: Buzzer switch. Fast Acquisition: Improve the refresh rate of signal input.
Power supply and start: After plugging in the USB power supply, the instrument will automatically enter the
working state. If it is not checked, the instrument will remain on the charging interface after power on. If the
instrument is plugged into the USB port of the PC, and the driver is normal, the instrument will automatically
start up.
Theme: Change the color scheme of the instrument, using the environment or personal preference selection.
Calibration: Enter the fine-tuning window of the signal, please ensure that there is a high-precision multimeter or signal
the standard Modbus RTU protocol, and can use configuration software or PLC for remote control and monitoring.
-32-
Machine Translated by Google Smart Signal Generator
Key 40002 The key pressed by the 16-bit unsigned read-write instrument
battery power
40004 16-bit unsigned read-only instrument voltage
to press
input letter Value=0 current input, value=1 voltage input, value=2 frequency
40006 16-bit unsigned read and write
number selection Rate input, value = 3 mV input, value = 4 resistor input.
input letter When frequency =, it is level input, when =1, it is NPN output
40008 16-bit unsigned read and write
number type Input, millivolt signal for thermocouple type switching.
-33-
Machine Translated by Google Smart Signal Generator
When the frequency signal is in PWM mode, this value is the frequency
input letter 32-bit signed value, for millivolt input, read-only for thermocouple input
40011
number value 2 integer , the value is the millivolt value of the input, the resistance input and the
about integer
input letter
40015 32-bit floating-point number read-only has the same function as integer display, but the floating-point
value
input letter
40017 32-bit floating-point number read-only has the same function as integer display, but the floating-point type
number value 2
input volume
40019 32-bit floating-point number read-only has the same function as the integer display, but the floating-point representation
about
Output open
40021 16-bit unsigned read and write output signal switch
close
number selection
40023 16-bit unsigned read and write is frequency = 1 is PWM, millivolt signal = 0 is millivolt
number mode
-34-
Machine Translated by Google
Smart Signal Generator
When the output signal frequency = 0, it is level input, when it is = 1, it is NPN input 40024 16-bit unsigned read-write number type input,
when it is millivolt signal, it is thermocouple type switching.
When the frequency signal is in PWM mode, this value is the frequency
output letter 32-bit signed value, when millivolt output, in the case of thermocouple output read-only, this value is the
40027 output millivolt value, resistance output and
number value 2 integer
integer
Process
output signal 40031 32-bit floating-point reading and writing have the same function as integer display, but floating-point representation
Number
value output
signal 40033 32-bit floating-point number read-only has the same function as the integer display, but the floating-point display
Number
value 2
output 40035 32-bit floating-point number read-only has the same function as the integer display, but the floating-point display
about
function is an advanced function of this product and will be upgraded regularly. This instruction only explains the basic
operation. If there is an update, the staff will release it on WeChat, so stay tuned! The Modbus master station is mainly
used for on-site modification of instrument parameters, parameter copy monitoring, and testing whether the
communication is normal. The RS485 interface is used for the communication method, and it has three-pole protection
inside, which can prevent static electricity above 100V, and short-circuit protection, and PTC self-recovery insurance.
-35-
Machine Translated by Google Smart Signal Generator
11.1 The Modbus master station has 5 configurations for users to test different devices.
IN T-ON OUT FN
-36-
Machine Translated by Google Smart Signal Generator
Press the setting key to enter the parameter setting of the master station.
The Modbus master station has two working modes to change the
the run button, and the program starts to poll the variables of the
slave station, refresh the variables in real time, and modify the
program are performed manually, and the program will poll the slave
device once by pressing the read and write button. Modify the
0000.
Number of additions: The number of variables to add, for example, if the number of additions is 10, then the variable address will be
automatically incremented.
-37-
Machine Translated by Google Smart Signal Generator
Variable type:
ushort: 16-bit unsigned integer short: 16-
bit signed integer
Byte-1: 8-bit first byte integer (the variables in the Modbus underlying protocol are all 16-bit data, if
the user wants to take an 8-bit integer, then the byte to take is selected by the user)
annotation role. Data arrangement: After the modbus master reads the variables, it rearranges them.
the main interface of the Modbus master station, press I-TY to pop up the variable operation window.
-38-
Machine Translated by Google Smart Signal Generator
Address: Set the device address of other variables to be the same as the address of the selected
variable. Delete: delete a variable. Delete All: Deletes all variables. Quickly modify the variable value:
press on the main interface of the MODBUS master station to pop up a numeric keyboard. Modify the
bit variable: press O-TY on the main interface of the MODBUS master station toO-TY
clear or set the bit.
11.6 Device Scanning: Scan for devices with unknown addresses. Access
Start scanning : scanning needs variable address and instruction parameters, so before entering device scanning,
you must add a variable or use an existing variable. The scanning work screen only has the communication port setting
and the device address range setting. After moving the cursor to “Start Scanning” and pressing the scanning procedure,
I-TY
the scanning program will start immediately.
-39-
Machine Translated by Google Smart Signal Generator
Scanning process: If there is a device response, the corresponding address will be automatically filled in the address table, and the
number of returned devices will be displayed in the address table after the scan is completed. As shown in the figure, Dev=002 means
Change the device address of the variable: If the variable device address you choose is 003, move the cursor
Purpose: In the process of on-site debugging, if the occurrence time of the problem is uncertain, the
function of the recorder can be used to record the signal change trend in the form of a curve. After the
recording is completed, the historical data can be exported to the personal computer , print or screenshot for
analysis. 12.2 Parameter capacity: 20000 record points. Channel: 2. Recording interval: 0.1 seconds - 999.9
seconds.
-40-
Machine Translated by Google
Smart Signal Generator
current clock
Channel 2 scale
Channel 1 Scale
correspond to the
Before using the recorder, the setting of the signal source is the most important part, so first determine what
signal type to use as the signal source. For example: To record the temperature of a Pt100 temperature
sensor, the pressure range of a pressure transmitter is 0-100kpa. The wiring diagram is as follows:
Pressure
Transmitters
Pt100
-+
-41-
Machine Translated by Google Smart Signal Generator
Back to the signal generator interface, the output is switched to 24V loop detection and the mode is range display ,
and the range is changed to 0-100.0 corresponding to 4-20mA. The input signal is switched to resistance input, and
the mode is switched to PT100 input. After the signal display is all normal, enter the function menu and then enter
the recorder.
-42-
Machine Translated by Google
Smart Signal Generator
After configuring the parameters of the recorder, you can start recording. Press
IN it to pop up the time setting.
Since there is no clock battery inside the MR9270S, it must be set manually. After the setting is complete,
the upper left corner of the screen. If the black dot is not flashing and displayed, it means that the recorder has
completed a record.
ÿÿÿÿ
IN hold it for two seconds, and a black dot will appear on the
If you want to stop recording halfway, press and
upper left corner of the screen. Since the recorder can only record once, if you need to restart recording,
you must reset the recorder to restart recording. seconds will reset the logger. Historical data is very
REST
important. In order to avoid misoperation, it must be reset before starting again. 12.5 History Record Press
the interface to switch to the history record interface. When viewing the record, it should be noted that if the
recorder is recording and the recording interval is less than 1 second, please try not to switch back and forth
OUT the history record interface and the real-time interface many times, which may cause Data is lost
between
-43-
Machine Translated by Google
Smart Signal Generator
The duration of
each grid
Lock Cursor: Make the cursor not move, only move the curve. Time
mark +/time mark -: change the time length of the first frame. Step+/
Step-: Change the length of each step the cursor moves, "Step-" is the down key on the keyboard.
Log in to the product website to download the host computer software of the recorder, which is free for users to use. Since
the software will be updated, no explanation will be made here, and the website will have synchronously updated
instructions for use. Before connecting to the host computer, please set the communication mode to "USB Modbus".
Battery: Mr.Signal 2 uses two 14500 lithium batteries, each with a capacity of 900mA. The usage time depends
on the usage. You can use the timer on the main interface to know your own power consumption. When using the
USB interface to charge the battery, In the charging screen, the instrument charges the battery with a current of
1A, press the start button, and the instrument charges with a current of 500A in the main interface. If the instrument
is not used for a long time, the battery can be fully charged and then stored. The power consumption current after
-44-
Machine Translated by Google
Smart Signal Generator
Self-inspection: During on-site debugging, there are many kinds of difficult and miscellaneous diseases. Before testing, please
ÿÿÿÿ
confirm that the testing equipment is normal. The instrument can input and output at the same time, so you can test yourself to
ensure that it is normal before testing to ensure that you do not take detours. The site is complicated , there is no guarantee that the
-45-