API 2000 - SEVENTH EDITION, MARCH 2014
ANNEXURE - F , "Guidance for Inert gas inert gas blanketing of tanks for flash back protection"
LEVEL - 3 (No additional protection against flame propagation from outside to the inside of tank is required)
Required flow rate
Volume of reserve inert gas
Tank Dimensions:
Dia = 1
Height = 2
Slope of cone roof = 5 1
Site Latitude = 21 °
In Flow rate = 0 m3/hr
Out Flow Rate = 1.2 m3/hr
Operating Pressure = 101.325 kPag
Operating Temperature = 47 °C
wall thickness of insulation lin 0.00E+00 m
inside heat transfer co-efficient h 1 W/(m2.K)
thermal conductivity of insulation λin 1 W/(m.K)
Reduction factor for insulation Rin 1.000
C Factor for Lattitude = 6.5
Tank Volume Vtk 1.60 m3
Out flow rate Vpe 2.05 Nm3/hr
Required Nitrogen flow rate = 6.56 Nm3/hr 45.90
Volume of reserve inert gas = 0.191637 m3 @ 101.325 kPag, 65°C
Volume of reserve inert gas = 0.025135 m 3
@ 600 kPag, 25°C
Required Outbrething flowrate = 0.487662 Am3/h Air
Required Outbrething flowrate for PVRV = 0.416036 Nm3/hr Air
Required vaccum capacity for PVRV = 6.331697 Nm3/hr of Air
Required Outbrething flowrate for SAPCV = 0.430895 Nm3/hr of N2
Emergency Relieving
Reference API 2000 : Section 3.3.3.3 : Fire Relief Requirements
Considering hexane
Wetted surface area 631.7115 m2 631.7115 m2
Q 4,129,700 W 208.2
F 0.15 1
L 1519000 j/kg 334900 j/kg
T 338.15 K 288.75 K
M 30.33 86.17
q 1234.486 41200.84 6427.331
Table 1 — Y-factor for various latitudes
Latitude Y-factor
Below 42° 0.32
Between 42° and 58° 0.25
Above 58° 0.2
Table 2 — C-factors
Latitude C-factor for various conditions
Vapour pressure
Hexane or similar
Higher than hexane, or unknown
Average storage temperature °C
°C <25 ≥25 <25 ≥25
Below 42° 4 6.5 6.5 6.5
Between 42° and 58° 3 5 5 5
Above 58° 2.5 4 4 4