CopelandTM CR Series
For Medium & High Temperature Applications
R22
CRNQ-0500
www.generalcooltrade.com ϼ¨ ÏHo¹] ºI¬npIM
Iú ÂñUo¶ xnA kÃw tk¹¿¶
kÃ{IM tIµU nj I¶ ·IwI¹{nI¨ IM ¹Π½n»Iz¶ SÎIÄnj S¿]
09126343436 : ´Ã£Tv¶ tIµU ½nIµ{
brand products
CRNQ-0500-TFD
HCFC, R-22, 50 Hz, 3 -Phase, 380/420 V
Air Conditioning
Performance Mechanical
Evaporator Temp. (°F) 45 45 Displacment(in^3/Rev): 6.22
Condensing Temp. (°F) 130 100 Displacment(ft^3/hr): 626.45
Return Gas Temp. (°F) 65 65 Overall Length (in): 11.38
Liquid Temp. (°F) 115 85 Overall Width (in): 9.38
Capacity (Btu/hr) 51200 65800 Overall Height (in): 16.13
Power (W): 5000 4130 Mounting Length (in): 7.50
Current (Amps): 8.60 7.10 Mounting Width (in): 7.50
EER (Btu/Wh): 10.20 15.90 Mounting Height (in): 16.50 *
Mass Flow (lbs/hr): 750 850 Suction Size (in),Type: 7/8 Stub
Sound Data @ Discharge Size (in),Type: 1/2 Stub
Sound Power (dBA): 78 Avg 83 Max Initial Oil Charge (oz): 70
Vibration mils(peak-peak): 6.0 Avg 7.0 Max Oil Recharge (oz): 66
Record Date: 1995-03-24 Net Weight (lbs): 82.0
Internal Free Volume (in^3): 560.0
Electrical Horse Power:
*Overall compressor height on Copeland Brand Product's specified
LRA-High*(Amp): 65.0 mounting grommets.
LRA Low* (Amp):
LRA-Half Winding (Amp):
MCC (Amps): 13.5
Capacitors
Max Operating Current(Amp):
RLA, MCC/1.4;use for contactor selection (Amp): 9.6
RLA, MCC/1.56;use for breaker & wire size selection (Amp): 8.7
RPM:
UL File No:
UL File Date: 1984-12-28
*Low and High refer to the low and high nominal voltage ranges for
which the motor is approved.
Alternate Applications
Refrigerant Voltage Phase Freq (Hz) Application
R-22 HCFC 380/460 3 60 Air Conditioning