LCB2 IP Bag
LCB2 IP Bag
Vintage: 02 / 4
Product Software Data
Administration Page: 1 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
MCS - LCB II
List of Installation Parameters
Document Revision :
Vintage: 02 / 4
Product Software Data
Administration Page: 2 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
1 - SYSTEM
No. Symbol Default Purpose and Range since
0. TOP 2 Top position:
1 (1) 31
1. LOBBY 0 Lobby position:
0 (1) 31
2. BOTTOM 0 Bottom position:
0 (1) 30
3. CFT-P 255 Cafeteria Position:
0 (1) 31
> 31 Disabled
4. OPERAT 1 Operation FCL/DCL/SAPB:
0 FCL
1 DCL
2 SAPB
3 SAPB with Car Coming Light BAF
4 FCL, delete both calls on arrival BAF
5 FCL with single button BAF
5. EN-BSM 0 Enable Basement mode
(for DCL: both Up- and Down Hall Calls at lobby):
0 Disabled
1 Enabled
6. CONFIG 0 General configuration:
0 ETO
1 NAO
2 PAO BAE
7. PI 4 Type of serial Position Indicator:
0 7/16 Segment
1 Multilight via RIB
2 7 Segment-PI and LM-PI via RIB
3 Brazilian 10-Segment
4 OTIS 2000: LCD and ELD
5 Australian Dot Matrix BAG
6 Australian Dot Matrix and Direction Indicator BAG
8. PI-OPT 0 Vendor PI option BAE
0 no option
1 returning to ground floor
2 overloaded
4 out of service
8 lift on firefighting service
note: if more than one of the above options should be
available then you must add the appropriate numbers
(e.g. to select 1+4 you must program 5)
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 3 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
1 - SYSTEM
No. Symbol Default Purpose and Range since
9. ELD-fOPG 20 front door movement time: opening
0 (0.1) 10.0 s
0 = automatic (not yet implemented)
10. ELD-fCLG 20 front door movement time: closing
0 (0.1) 10.0 s
0 = automatic (not yet implemented)
11. ELD-rOPG 20 rear door movement time: opening
0 (0.1) 10.0 s
0 = automatic (not yet implemented)
12. ELD-rCLG 20 rear door movement time: closing
0 (0.1) 10.0 s
0 = automatic (not yet implemented)
13. ELD-LNG 5 set Language for ELD:
0 (1) 19
0=SwiGer, 1=SwiFra, 2=SwiIta, 3=France,
4=Italy, 5=UK, 6=Spain, 7=Netherlnd,
8=Germany, 9=Austria, 10=Sweden, 11=Luxem,
12=Belgium, 13=Portugal, 14=Egypt, 15=Denmark
16=SthAfrica, 17=Finland, 18=Arabia, 19=Kuweit,
20=Moscow, 21=StPetrbrg, 22=not used, 23=AGB, BAE
24=Hungary, 25=Poland, 26=Czech BAE
14. ELD-Sym1 0 Enable Non-Smoking symbol:
0 Disabled
1 symbol is displayed
15. ELD-DOOR 0 Select Type of Door Display: BAC
0: 1 COP for 1 door or
2 COPs for 2 doors
1: only 1 COP for 2 doors
16. ELD-MSG 0 Enables Customer Messages on ELD: BAC
0 no customer messages are displayed
1 customer messages are enabled
(use SETUP-ELD to define the texts)
17. EN-SFR 0 Enable SFR (signal flicker):
0 Disabled
1 Enabled
18. LR-T 20 Light Relay time (IO 0026):
0 (1) 255 s
19. LR-MODE 0 Fan / Light Relay mode option (IO 0026): BAF
0 LR pulls only when door closed (Light)
1 LR pulls even if door is opened (Fan)
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 4 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
1 - SYSTEM
No. Symbol Default Purpose and Range since
20. EN-HLC 0 Enable Hall Lanterns on car calls:
0 Disabled
1 HLC
2 HL also during closing
3 HLC and during door closing
21. HDL-TY 0 Hall Direction/Lantern Type for
OTIS 2000 Hall Button Box:
0 Direction Indicator
1 Hall Lantern
22. HL-SET 0 Hall Lantern/Gong Setup:
0 HL/G at same pins
1 HL/G at different pins (RS4A)
2 NAO Chime board
23. CR-DIR 0 Correction Fast Run Preferred Direction:
0 Down
1 Up
24. CR-DO 0 Door opening after Correction Run BAG
0 no door opens
1 only front door opens
2 only rear door opens
3 both front and rear door will open
note: this is intended for DO2000, because a new init run is
performed after each INS
25. EN-RR 0 Enable Reduced Run (RR):
0 Disabled
1 Enabled (short or medium run)
26. DZCNT 1 Use DZ for SL counting (for Short Run):
0 Disabled (if SLU, SLD are present)
1 Enabled (without SLU, SLD signals)
27. EN-DZI 0 Enable DZI (Door Zone Indicator):
0 Disabled
1 Enabled (only if no Door ByPass)
28. ERO-TYP 0 Define ERO type
0 without limit
1 car stops at terminal landings
(same as TCI-limit)
2 ERO-input disabled (for LCB_II version D2)
29. C-CHK 0 Enable C-Circuit Check:
0 Disabled
1 Enabled
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 5 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
1 - SYSTEM
No. Symbol Default Purpose and Range since
30. MD/AES 0 select use of MD input (P7:9, only MCS220M):
0 not connected
1 MD: DCS-input for Multi Door
(manual plus automatic landing doors)
2 AES: ES-input if RSS or ESB is used
31. CPC-TYP 0 select use of CPC outputs: BAC
0 car position contact
1 'car here' light
2 french SSM
3 Arrival Hall Lantern (AHL-2) BAG
32. N+2 WIRE 0 enable 3-wire buttons: BAC
0 normal car and hall buttons
1 3-wire car buttons
2 3-wire hall buttons
3 3-wire car and hall buttons
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 6 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
2 - OCSS
No. Symbol Default Purpose and Range since
0. CPR-T 20 Car Call Preference:
0 (0.1) 25.5 s
1. ARD-P 255 Automatic Return Device Position:
0 (1) 31
> 31 Disabled
2. ARD-T 0 Set Delay for ARD (Automayic Return Device) mode:
0 (10) 2550 s
3. ARBL-T 0 Delay for Automatic Return To Bottom Landing BAG
0 (10) 2550 s
4. ARBL-PRK 0 ARBL park option BAG
0 stay at bottom after ARBL has been
performed
1 return to previous park landing after ARBL
has been performed
5. CTL/PKS 0 Select CTL or PKS switch:
0 CTL switch is connected at IO no. 10
1 PKS switch is connected at IO no. 10
6. PKS-P 255 Parking Service Position:
0 (1) 31
> 31 Disabled
7. PKS -TY 0 Parking Shutoff Type:
0 ETO
1 NAO
2 ETO with door open after shutdown
8. PKS-T 0 Parking Shutoff Time:
0 (1) 255 s
9. PKS-DO 0 PKS default door:
0 Both doors will open at PKS-P
1 Only front door opens
2 Only rear door opens
10. EN-SHB 0 Enable Separate Hall Buttons:
0 Normal HB-operation
1 Rear HB as Separate Riser
11. DCP-T 50 Time until DCP-mode (delayed car protection):
25 (1) 255 s
12. CTL-DO 0 CTL default door (car to any landing):
0 Both doors will open at CTL-P
1 Only front door opens
2 Only rear door opens
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 7 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
2 - OCSS
No. Symbol Default Purpose and Range since
13. CTL-P 255 CTL (Car To Any Landing) position:
0 (1) 31
> 31 Disabled
14. ANS 0 ANS (anti nuisance service):
0 Disabled
>0 Number of calls to trigger ANS
15. ATT 0 ATT (Attendant Service) type:
0 Start with DCB or RDCB
1 Start with ATTU or ATTD
2 NAO (USA)
16. ISC 0 Independent Service:
0 Start on constant pressure of CCB
1 Start on constant pressure of DCB
2 Start on ISD/ISU
3 NAO (USA)
4 Start on momentary pressure of CCB BAG
17. ISPS-TY 0 Independent Service Park Switch (IO 638) BAE
0 car calls allowed when ISPS active
1 no car calls allowed when ISPS active
18. ISC-T 0 Independent Service Close Timeout BAE
0 (1) 30 s max door open time when FPD is installed
19. CTL-TY 0 Select Car To Landing Type:
0 ETO
1 NAO
20. SPEECH 0 Speech Mode:
0 Floor message on CC only
1 Floor message also on HC
21. CPMT-D 0 Car Position Message Trigger for Vendor type PI BAE
0 (0.1) 25.5 sec
22. DCMT-A 0 Door Close Message Trigger for Vendor type PI BAE
0 (0.1) 25.5 sec
23. DOMT-O 0 Door Open Message Trigger Option for Vendor type PI BAE
0 trigger on opening and reopen
1 trigger on opening only
24. DOC 0 Door Reopen Count:
0 No limit
1 (1) 255 Number of allowed door reopenings
25. DS-CCB 0 Disable CCs behind moving car:
0 CCs behind allowed
1 CCs behind not allowed
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 8 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
2 - OCSS
No. Symbol Default Purpose and Range since
26. DS-DOB 0 Disable DOB button:
0 DOB/RDOB always enabled
1 DOB disabled if door closed
2 RDOB disabled if door closed
3 Both disabled if door closed
27. EN-RB 0 Enable car call Reset Button (IO 627, 725) BAE
1 enabled in ATT mode
2 enabled in CHC mode
4 enabled in EFS mode
8 enabled in ISC mode
note: if more than one of the above options should be
available then you must add the appropriate numbers
(e.g. to select 1+4 you must program 5)
28. DHB-TYP 0 Enable DoorHoldButton for CARGO 2000 (IOs 620,628) BAF
DHB doortime can be canceled by...
0 press DCB or any CCB
1 press DCB or any CCB, or press DHB again
(in this case the DHB-T is a 10-sec-timer!)
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 9 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
3 - GROUP
No. Symbol Default Purpose and Range since
0. GRP-NO 1 Car identifier in group:
1 (1) 3
1. GROUP 1 Number of cars in group:
1 (1) 3
2. CNL 1 Cars parking in Lobby:
1 (1) 3
3. MIT-ST 0 MIT (Moderate incomming traffic) Startdelay:
0 (1) 255 s
4. MIT-T 0 MIT Time-Out:
0 (1) 255 s
5. MIT-VD 0 MIT Variable Interval Dispatch:
0 (1) 255 s
6. MIT-DOOR 0 MIT Default Door BAF
0 open door if car is not selected
1 keep door closed if car is not selected
7. MIT-NLB 0 MIT No Lobby Bypass BAF
0 Answer hall calls
1 Don’t answer hall calls
8. DUPK-P 255 Dual Up Peak Border Position:
0 (1) 31
> 31 Disabled
9. DUPK-G 0 Dual Up Peak Group:
0 Car belongs to subgroup 1
1 Car belongs to subgroup 2
10. MOT-T 0 MOT (Moderate Outgoing traffic) Time-Out:
0 (1) 255 s
11. EN-UCB 0 Enable Up Call Bypass:
0 Disabled
1 Enabled
12. TFS-P 255 Transfer Floor Position:
0 (1) 31
> 31 Disabled
13. PARK-1 255 Park Clock Position 1:
0 (1) 31
> 31 Disabled
14. PARK-2 255 Park Clock Position 2:
0 (1) 31
> 31 Disabled
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 10 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
3 - GROUP
No. Symbol Default Purpose and Range since
15. PARK-3 255 Park Clock Position 3:
0 (1) 31
> 31 Disabled
16. PARK-4 255 Park Clock Position 4:
0 (1) 31
> 31 Disabled
17. PARK-5 255 Park Clock Position 5:
0 (1) 31
> 31 Disabled
18. PARK-6 255 Park Clock Position 6:
0 (1) 31
> 31 Disabled
19. PARK-7 255 Park Clock Position 7:
0 (1) 31
> 31 Disabled
20. PARK-8 255 Park Clock Position 8:
0 (1) 31
> 31 Disabled
21. EN-ZBS 0 Enable separate basement zone:
0 No free car parks in basement zone
1 A free car parks in basement zone
22. SEL-COMP 0 Select MCS310 Compatible Communication BAD
0 Triplex - Ring ICD 3.3;
Group consists of MCS120 / 220 / 220M
1 Duplex - Ring ICD 3.0 (MCS310 with G44)
2 Duplex - Ring ICD 3.3 (MCS310 with G57)
23. L-PARK 0 Lobby Park Option (only if SEL-COMP 0)
0 Disabled
1 Enabled
24. PRKDST 0 Minimum Distance to park target to do park run BAD
0 (1) 31
25. EN-GSS 0 Group Successive Starting BAG
0 disabled
1 GSS triggered by remote I/Os GSSI (972),
GSSO (973) for multiple simplex cars
2 GSS triggered by serial group
communication
26. MG-DEL 0 Motor Generator Delay for GSS BAG
0 (1) 255 s
note: this delay depends on the duration of the acceleration
phase
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 11 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
4 - DRIVE
No. Symbol Default Purpose and Range since
0. DRIVE 1 Drive Type:
0 1-SP XADO
1 2-SP, Gamma-L XADO
2 Gamma-S/D XADO
3 Gamma-L with SL XADO
4 Gamma-L with SL ADO
5 2-SP, Gamma-L ADO
6 Gamma-S/D ADO
7 SPEC60
8 Gamma-D NAO XADO
9 Gamma-D NAO ADO
10 Motorized Valve ADO
11 Solenoid Valve ADO
12 Motorized Valve XADO
13 Solenoid Valve XADO
14 LSVF ADO
15 LSVF XADO
16 LSVF-W, OVF20 ADO
17 LSVF-W, OVF20 XADO
18 ULCVF (OVF10) XADO BAD
1. C-TYPE 2 Controller Type:
0 MCS 310 (Europa 2000)
1 MCS 310 CA, HY (Cargo 2000)
2 MCS 120, MCS 220 (OTIS 2000)
3 MCS 220 M
2. 1AT 5 1A Time:
0 (0.1) 25.5 s
3. 2AT 5 2A Time:
0 (0.1) 25.5 s
4. DDP 32 DDP Time (fast run):
0 (1) 45 s
5. 3P 32 3P Time (slow run):
0 (1) 45 s
6. SPEED 100 Speed (fast run mode):
25
40
63
100
160
175
250 cm/s
7. EN-MPD 0 Enable Motor Protection Device:
0 Disabled
1 MPD-3 (immediate stop)
2 MPD-1, MPD-2 (run to target) BAD
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 12 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
4 - DRIVE
No. Symbol Default Purpose and Range since
8. MPD-T 10 Motor Protection Device Time:
0 (1) 254 s
255 wait forever
9. HY-TYP 0 Hydro Drive Type for Hydro:
0 Star - Delta
1 Soft
2 Direct
3 LSCH-2 BAE
10. L-T 10 Set Star/Soft Time for Hydro:
0 (0.1) 25.5 s
11. UX-D 20 Set Star/Delta gap / add. Soft Time (L+UX) for Hydro:
0.06 (0.004) 0.2 s
12. UXT-D 0 Set delay between UX and UXT for Hydro:
(contract option)
0 (0.1) 1 s
13. EN-PLS 1 Enable PLS1 (Oil Max-Pressure Limit Switch)
for Hydro:
0 Disabled
1 Enabled
14. EN-OTS 1 Enable OTS (Oil Over Temperature Switch) for Hydro:
0 Disabled
1 stop at next target
2 immediate stop for AHVS BAF
15. ACD/UXT 0 Select ACD or UXT output for Hydro:
0 ACD and UXT disabled
1 ACD enabled
2 UXT enabled (contract option)
16. P-OFF-D 0 Set Power Off delay for LSVF-W
0, 255 Disabled
1 (1) 254 s
17. P-ON-D 10 Set Power On delay for LSVF-W
8 (1) 20 s
18. EN-J 1 Enable 3-Phase Detection (J-Relay)
0 Disabled
1 Enabled
19. J-T 1 Number of periods necessary to detect a fault
0 (1) 4
20. EN-BCD 1 Enable Brake Current Detection:
0 Disabled
1 Enabled
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 13 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
4 - DRIVE
No. Symbol Default Purpose and Range since
21. BON-D 10 Delay of BCD (after lifted brake)
0 (0.1) 10 s
note: BON-D=15 is recommended for all VF drives
22. BFLT-T 15 Delay of BCD (after lifted brake)
0 (0.1) 10 s
note: BFLT-T=30 is recommended for all VF drives
23. BOFF-D 15 Delay of BCD (after lifted brake)
0 (0.1) 10 s
note: BOFF-D=15 is recommended for all VF drives
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 14 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
5 - DOORS
No. Symbol Default Purpose and Range since
0. DOOR 2 Type of Doors:
0 FLH
1 9550T & ACG
2 9550T & TLD / DO_2000 (DC-relay)
3 OVL/MRDS & ACG
4 OVL & TLD/CLD
5 DO_2000 without TRO (DO-relay)
6 MCG
7 Kiekert / MLI & ACG
8 Kiekert / MLI & TLD/CLD
9 OVL-Penang & ACG BAD
10 OVL-Penang & CLD/TLD BAD
11 GENERIC (see parameters below) BAE
1. REAR 2 Type of Doors:
0 FLH
1 9550T & ACG
2 9550T & TLD / DO_2000 (DC-relay)
3 OVL/MRDS & ACG
4 OVL & TLD/CLD
5 DO_2000 without TRO (DO-relay)
6 MCG
7 Kiekert / MLI & ACG
8 Kiekert / MLI & TLD/CLD
9 OVL-Penang & ACG BAD
10 OVL-Penang & CLD/TLD BAD
11 GENERIC (see parameters below) BAE
2. MIXDOR 0 Mixed Dooroperators:
0 Same operators front/rear
1 Different operators front/rear
3. EN-DDO 0 Enable DDO (double door operation):
0 Disabled
1 double door on car call and on hall call
2 double door on car call, selected door on BAD
hall call
4. EN-ADM 0 Alternating Door Mode BAE
0 doors can open simultanously
1 ADM preference to front door
2 ADM preference to rear door
5. F:DO-TYP 0 type of DO handling BAE
00 DO never pulled
01 DO pulled when car door fully opened
10 DO pulled during opening
11 DO pulled when car door opening and also
when fully opened
note: only applicable if DOOR=11
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 15 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
5 - DOORS
No. Symbol Default Purpose and Range since
6. F:DC-TYP 0 type of DC handling BAE
00 DC never pulled
01 DC pulled when car door fully closed
10 DC pulled during closing
11 DC pulled when car door closing and also
when fully closed
note: only applicable if DOOR=11
7. F:EN-ACG 0 enable DW input for ACG BAE
0 automatic hoistway doors
1 manual hoistway doors
note: only applicable if DOOR=11
8. F:EN-DCL 0 enable DCL input at IO 694 BAE
0 no DCL switch
1 DCL at IO no. 694
note: only applicable if DOOR=11
9. F:DOL-D 0 automatic DOL simulation BAE
0 DOL at IO no. 0000
0.1 (0.1) 25.5s DOL is simulated after specified
time if no DOL exists
note: only applicable if DOOR=11
10. R:DO-TYP 0 type of RDO handling BAE
00 RDO never pulled
01 RDO pulled when car door fully opened
10 RDO pulled during opening
11 RDO pulled when car door opening and
also when fully opened
note: only applicable if REAR=11
11. R:DC-TYP 0 type of RDC handling BAE
00 RDC never pulled
01 RDC pulled when car door fully closed
10 RDC pulled during closing
11 RDC pulled when car door closing and also
when fully closed
note: only applicable if REAR=11
12. R:EN-ACG 0 enable DW input for ACG BAE
0 automatic rear hoistway doors
1 manual rear hoistway doors
note: only applicable if REAR=11
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 16 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
5 - DOORS
No. Symbol Default Purpose and Range since
13. R:EN-DCL 0 enable RDCL input at IO 695 BAE
0 no RDCL switch
1 RDCL at IO no. 695
note: only applicable if REAR=11
14. R:DOL-D 0 automatic RDOL simulation BAE
0 DOL at IO no. 544
0.1 (0.1) 25.5s RDOL is simulated after specified
time if no RDOL exists
note: only applicable if REAR=11
15. CM-TYP 0 type of CMR handling BAE
00 no CMR
01 CMR is pulled when car door is fully closed
02 CMR is pulled when car door is fully
closed and a demand is present
03 CMR is pulled when car door is fully
closed and the delay CM-D has expired
11 CMR is pulled when car door is closing
and also when car door is fully closed
21 CMR is pulled when car door is closing
and delay CM-D has expired
note: CMR can only pull if DW is active
(i.e. hoistway door is closed)
note: only applicable if DOOR=11 or REAR=11
16. CM-PROT 0 max. ON-time of CMR when car stops in ERO BAE
0 CM not pulled
10 (10) 2540 s CMR drops after specified time
(CMR pulls again when moving or
switched to NOR)
255 no protection: CMR is always pulled
during ERO
note: only applicable if DOOR=11 or REAR=11
17. DO-D 0 delay between CMR and DO BAE
0 (0.1) 25.5 s DO is delayed for the specified time
after CM has been dropped
note: only applicable if DOOR=11 or REAR=11
18. CM-D 0 delay between door movement and CM BAE
a) CM-TYP = 02, 03
0..255 CM pulls 0..25.5s after car door has fully
closed
b) CM-TYP = 21
0..255 CM pulls 0..25.5s after car door has
started to close
note: only applicable if DOOR=11 or REAR=11
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 17 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
5 - DOORS
No. Symbol Default Purpose and Range since
19. TRO-TYP 0 enable TRO output BAE
0 no TRO output
1 TRO at P6:5 for DO2000
(no DC allowed!)
2 TRO at P6:7 for MLI / Kiekert-2
(no DO allowed!)
3 TRO at P6:5 for AT20 BAF
(no DC allowed!)
note: only applicable if DOOR=11 and
DO-TYP=0 resp. DC-TYP=0
note: cut jumper J1 on LCBII !
20. SEL-CMR 0 select separate CM relay output (MCS220M)
0 (one door) CMR at RDC-output (P6:10)
1 (two doors) CMR at RSL (IO no. 785)
NOTE: only applicable for FLH, MCG, ACG
21. CMR-ES 0 CMR handling during Emergency Stop BAF
0 drop CMR during ESR
1 keep CMR pulled during ESR
22. TCI-TYP 0 type of CMR handling during TCI BAF
0 CMR pulls only when TCIB is operated
1 CMR pulls always for CARGO2000
(100% ED required!)
23. DBP-TY 1 Type of Door Bypass circuit:
0 DBP operated (4-relay)
1 LVC operated (3-relay)
24. LDR 0 Limited Door Reversal:
0 Full DOB, full EDP, full LRD
1 Full DOB, limited EDP, full LRD
25. EN-PMO 0 Enable PMO (door time monitoring):
0 Disabled
1 Enabled
26. EN-NDG 0 Enable NDG (nudging):
0 Disabled
1 Enabled
27. NDG-T 20 Nudging Time:
0 (1) 255 s
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 18 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
5 - DOORS
No. Symbol Default Purpose and Range since
28. EN-CK 0 Enable Cancel Doortime with CCB:
0 disabled
1 enable CK
2 enable CBC BAF
3 enable CK and CBC BAF
note: CK = cancel doortime with car button
CBC = cancel car call with car button (press twice)
29. DW-DLY 10 Debouncing Time of Door Contact DW:
0 (0.1) 25.5 s
30. DO-BEL 0 Open Door Bell Timer:
0 (0.1) 25.5 s
31. MIN-C 20 Min Doortime Car:
0 (0.1) 25.5 s
32. MAX-C 40 Max Doortime Car:
0 (0.1) 25.5 s
33. MIN-H 40 Min Doortime Hall:
0 (0.1) 25.5 s
34. MAX-H 60 Max Doortime Hall:
0 (0.1) 25.5 s
35. DOR-T 0 Door reverse time:
0 (0.004) 1 s
36. RDOR-T 0 Rear door reverse time:
0 (0.004) 1 s
37. DTC-T 20 Door Close Protection Time:
10 (1) 254 s DTC-time
255 Disabled
38. DTO-T 20 Door Open Protection Time:
10 (1) 254 s DTO-time
255 Disabled
39. LOB-NT 40 Lobby Door Time:
0 (0.1) 25.5 s
40. CFT-NT 40 Cafeteria Door Time:
0 (0.1) 25.5 s
41. SPB-NT 0 Special DOB Door Time:
0 (0.1) 25.5 s
42. DHB-T 120 DHB Doortime:
0 (1) 255 s for DHB-TYP=0
0 (10) 2550s for DHB-TYP=1 BAF
43. WCO-T 0 Wild Car Door Time:
0 (0.1) 25.5 s
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 19 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
5 - DOORS
No. Symbol Default Purpose and Range since
44. SHO-T 0 Shabat Door Time:
0 (0.1) 25.5 s
45. SHO-LT 0 Shabat Lobby Door Time:
0 (0.1) 25.5 s
46. DAR-T 60 MPD/Hydro Door Open Time:
0 (1) 255 s
47. DXT-T 0 DXT Time (extended door time):
0 (0.1) 25.5 s
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 20 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
6 - POSITION REFERENCE
No. Symbol Default Purpose and Range since
0. LV-MOD 2 Leveling Mode:
0 DZ-STP stop with DZ:
use DZ-DLY (in 4ms units)
Vintage: 02 / 4
Product Software Data
Administration Page: 21 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
6 - POSITION REFERENCE
No. Symbol Default Purpose and Range since
7. IPD-D 0 Delay for IPD:
0 (0.1) 25.5 s (if T-BASE=0)
0 (0.004) 1 s (if T-BASE=1)
8. 1LS-D 0 Delay for 1LS:
0 (0.1) 25.5 s (if T-BASE=0)
0 (0.004) 1 s (if T-BASE=1)
9. 2LS-D 0 Delay for 2LS:
0 (0.1) 25.5 s (if T-BASE=0)
0 (0.004) 1 s (if T-BASE=1)
10. EN-RLV 0 Enable RLV operation:
0 Disabled
1 Enabled
11. RLV-TY 0 RLV - Type:
0 RLV Relevelling
1 DRLV Delayed Relevelling (using DIS1)
12. RL-CNT 3 Limit of RLV steps:
0 (1) 255
13. RL-DIS 255 Set RLV time up (DIS lost):
0 (0.1) 25.5 s
14. RL-UIS 255 Set RLV time down (UIS lost):
0 (0.1) 25.5 s
0 (0.004) 1 s (hydraulic drive)
15. RL-U-D 0 Set RLV delay up:
0 (0.004) 1 s
16. RL-D-D 0 Set RLV delay down:
0 (0.004) 1 s
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 22 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
7 - CARGO
No. Symbol Default Purpose and Range since
0. CA-MOD 0 CARGO mode:
0 no CARGO mode
1 CARGO 2000 (MCS120,MCS220) BAF
(uses DZ at P1:6, LV at P1:11)
2 Class-C2 (not authorized yet)
. LVU-5D 0 Delay for LV stop (UP 0.5 load): until
0 (0.004) 1 s BAE
. LVD-5D 0 Delay for LV stop (DOWN 0.5 load): until
0 (0.004) 1 s BAE
1. BI-T 0 Class C2: time-out for Bolts In:
0 (0.004) 1 s
2. BO-T 0 Class C2: time-out for Bolts Out:
0 (0.004) 1 s
3. MVU-T 0 Class C2: time-out for Move Up:
0 (0.004) 1 s
4. MVD-T 0 Class C2: time-out for Move Down:
0 (0.004) 1 s
5. PLS4-T 0 Class C2: time-out for PLS4:
0 (0.004) 1 s
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 23 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
8 - EMERGENCY
No. Symbol Default Purpose and Range since
0. ES-TYP 0 Define ES-Type:
0 ESS connected
1 ESB connected
(closed door will remain closed)
2 ESB connected
(closed door will open)
3 ES-input disabled
(for LCB_II version GCA 21240 D3
without CI 95-118)
1. ES-LRCU 0 define ES with LRCU check (IOs 964, 965, 966) BAF
0-4 disabled
else time for LRCU selftest
2. ES-SLOW 0 enable slow recover run after ES BAF
0 never (always start fast)
1 start slow after /ES during deceleration
note: only applicable for OVF10, LSVF-W, OVF20
3. EFO-P 255 EFO (emergency fireman operation) position:
0 (1) 31
> 31 Disabled
4. EFO-NC 0 EFO (emergency fireman operation) position: BAE
0 EFO-P
1 Next commitable landing
5. EFO-DC 0 EFO with doors closed:
0 Disabled
1 (1) 255 s DC time
6. EFO-DO 0 EFO default door:
0 Both doors will open at EFO position
1 Only front door opens
2 Only rear door opens
7. EFO-OP 0 EFO override option:
0 No override possible
1 XEFO input overrides EFO after
arrival at return landing
2 After EFS no EFO is permitted if
EFO or AEFO are still active
3 Functions 1 + 2 together
8. EFONDG 0 Enable nudging speed for EFO
0 Door closes with full speed
1 Door closes with nudging speed
9. EFO-REV 0 Allowed Reversal Devices during EFO BAG
0 all devices disabled
1 only SGS/DOS allowed
2 DOB and SGS/DOS allowed
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 24 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
8 - EMERGENCY
No. Symbol Default Purpose and Range since
10. EFO-MP 0 EFO mode priority BAE
1 ISC has priority
2 ATT has priority
4 EHS has priority
note: if more than one of the above options should be
available then you must add the appropriate numbers
(e.g. to select 1+4 you must program 5)
11. EFO-MP-T 0 EFO mode priority time BAE
0 (1) 60 s max duration before EFO is started
12. EFO-SD 0 EFO signal devices BAE
0 no buzzer operation
1 constantly on
2 always flickering
3 constantly without EPO, flickering with EPO
13. ASL-P 255 ASL (alternate service landing) position:
0 (1) 31
> 31 Disabled
14. EFS-TY 0 Type of EFS (Emergency Fireman Service)
(if EFK (ASL) connected):
0 EFO
1 EFS 1 (Aut.)
2 EFS 2 (Man.)
3 ANSI (USA)
4 British Standard
5 Swiss Standard
6 Australia
7 New Zealand
8 EFS 2 (Man. with ESK) BAC
9 New Zealand with DCB BAE
10 GENERIC BAE
15. EFS-DO 0 EFS default door:
0 Both doors will open position
1 Only front door opens
2 Only rear door opens
16. EFSINI 0 EFS initiation of Phase II BAE
1 automatically
2 when ISS operated
4 when ESK operated
8 when CFS operated
16 when 1EFS operated
note: if more than one of the above options should be
available then you must add the appropriate numbers
(e.g. to select 1+4 you must program 5)
note: only applicable if EFS-TY=10
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 25 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
8 - EMERGENCY
No. Symbol Default Purpose and Range since
17. EFSCLD 0 EFS close door type BAE
1 car button (constant pressure)
2 door close button (constant pressure)
4 up/down start buttons
8 CS start button
16 ANSI style ISC
32 car call demand (momentary pressure) BAG
note: if more than one of the above options should be
available then you must add the appropriate numbers
(e.g. to select 1+4 you must program 5)
note: only applicable if EFS-TY=10
18. EFSOPD 0 EFS open door type BAE
1 always automatically
2 when DOB constantly pressed
4 only on 1st arrival
8 Door Hold Function if door not fully opened BAG
or closed (I/Os DDM, RDDM)
note: if more than one of the above options should be
available then you must add the appropriate numbers
(e.g. to select 2+4 you must program 6)
note: valid values are 1, 2, 4 and 6
note: only applicable if EFS-TY=10
19. EFS-EX 0 EFS exit type BAE
0 only if at EFO landing
1 if not moving and door is open
2 at any landing when door is closed
note: only applicable if EFS-TY=10
20. EFS-RT 0 EFS return time
(diration for which EFK must be low to force car back to
EFO landing if EFK is switched on again while in EFS):
0-39 Function disabled
40-255 Time (in 100 ms units) EFK must be low
21. EFS-RC 0 EFS recall type BAE
1 EFK off timeout
2 EFK off, moving
4 ESK off, not moving
8 EFK off, not moving, door closed
16 EFK off, not moving, door opened
32 EFS1 off
note: if more than one of the above options should be
available then you must add the appropriate numbers
(e.g. to select 1+4 you must program 5)
note: only applicable if EFS-TY=10
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 26 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
8 - EMERGENCY
No. Symbol Default Purpose and Range since
. EF-I-INV 0 EFO/EFS input invert BAE
1 EFO input inverted
2 AEFO input inverted
4 EFK input inverted
8 ASL input inverted
note: if more than one of the above options should be
available then you must add the appropriate numbers
(e.g. to select 1+4 you must program 5)
note: only applicable if EFS-TY=10
This parameter has been removed because BAG provides until
the option to invert each input separately. BAG sets the BAF
invert-bit automatically according to the previous setting of
this parameter when updating from a BAE or BAF version.
22. EF-I-LT 0 EFO/EFS input latching BAE
1 EFO input is latched
2 AEFO input is latched
4 EFK input is latched
8 ASL input is latched
note: if more than one of the above options should be
available then you must add the appropriate numbers
(e.g. to select 1+4 you must program 5)
note: only applicable if EFS-TY=10
23. EN-BAK 0 Enable E2P-backup of EFO/EFS:
0 Disable backup
1 Enable backup
24. HDWPOS 0 Hardware position reference:
0 Disabled
1 One contact per floor
2 Binary coded contacts
3 Signal at every odd floor
25. EPO-P 255 EPO (emergency power operation) Position:
0 (1) 31 EPO A/C (position)
EPO E (hydro: bottom)
= 32 EPO B/D (next floor)
EPO F (hydro: next floor down)
>32 Disabled
26. EPO-DC 0 EPO with doors closed:
0 Disabled
1 (1) 255 s
27. EPO-DO 0 EPO default door:
0 Both doors will open at EPO position
1 Only front door opens
2 Only rear door opens
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 27 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
8 - EMERGENCY
No. Symbol Default Purpose and Range since
28. EPO-PR 0 EPO priority if EFO/EFS:
0 No prio for EPO
1 EPO has priority
29. EQO 0 Earthquake Operation Version:
0 California
1 New Zealand
30. EPS-TYP 0 Express Priority Service:
xx0 automatic ISC
xx1 return to normal
xx2 automatic CHCS
x0x immediate return
x1x stop at next commitable
x2x serve car calls en route
1xx with Tale Tell Lights (EHS-2) BAD
31. EHS-T 0 EHS time-out:
0 Disabled
1 (1) 255 s
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 28 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
9 - SECURITY
No. Symbol Default Purpose and Range since
0. EN-FPD 0 Enable FPD (fireproof doors):
0 Disabled
1 Enabled
1. EN-IST 0 Enable IST (intermittent stop):
0 Disabled
1 In up direction only
2 In down direction only
3 In both directions
5 In up direction only, if ISTS active
6 In down direction only, if ISTS active
7 In both directions, if ISTS active
2. IST-P 255 Intermittent Stop Position:
0 (1) 31
>31 Disabled
3. EN-CRO 0 Enable CRO (card reader operation):
0 Disabled
1 Single contact reader
uses CRO-Mask and IO639 (CRC)
2 Australian Card Key sec type 2
uses IOs 480... (CRS0...) and IO665 (BOS)
signals are lowactive
3 Australian Card Key sec type 1
uses IOs 480... (CRS0...)
signals are lowactive
4 Multi contact reader
uses IOs 480... (CRS0...)
signals are highactive
CRC is override signal
note: CRO-Mask:
1: car call allowed any time
2: car call only when CRC active
4. GCBTYP 0 General Control of Buttons type:
0 disabled
1 GCB-1 (car calls disabled; park run allowed)
2 GCB-2 (all calls disabled)
5. RIOT-P 255 RIOT Operation Position:
0 (1) 31
>31 Disabled
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 29 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
9 - SECURITY
No. Symbol Default Purpose and Range since
6. SACTYP 0 Secure Access Type:
0 SAC disabled
1 SAC enabled, without ISC override
3 SAC enabled, with ISC override
5 SAC enabled, without ISC override,
clear only possible if security enabled
7 SAC enabled, with ISC override,
clear only possible if security enabled
else SAC disabled
7. SAC-D1 255 Secure Access digit 1:
0 disabled
1 (1) 6 use CSA1 - CSA6 as code input
>6 disabled
8. SAC-D2 255 Secure Access digit 2:
0 disabled
1 (1) 6 use CSA1 - CSA6 as code input
>6 disabled
9. SAC-D3 255 Secure Access digit 3:
0 disabled
1 (1) 6 use CSA1 - CSA6 as code input
>6 disabled
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 30 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
10 - TEST
No. Symbol Default Purpose and Range since
0. TPOS 1 255 Test position 1(automatic test run):
0 (1) 31
> 31 Disabled
1. TPOS 2 255 Test position 2(automatic test run):
0 (1) 31
> 31 Disabled
2. TDELAY 255 Test Delay for automatic test run:
0 (1) 255 s
3. NoAdrChk 0 Disable safety check:
address of TCI, 1LS and 2LS regarding to Std-IO-list
0 RSL safety check enabled
1 RSL safety check disabled
4. NoDW_Chk 0 Disable DW-check during NOR:
0 DW is checked when door is opened
1 No DW-check during NOR
5. DEBUG 0 Debug parameter:
0 (1) 255
6. DEBUG1 0 Debug parameter1:
0 (1) 255
7. EN-1CL 0 Enable Init_1CL: default position (Mot_VLV):
0 Disabled
1 Enabled
8. EN-EVT 0 Enable Storage of 10 events into E2PROM:
0 Disabled
1 Enabled
9. EN-CRT 0 Enable contract handling:
operate up to 32 openings
0 Disabled
1 Enabled
10. DISP-ALL 0 display of inputs in M-1-1-2 (System-Status-Inputs) BAF
0 only those inputs are displayed which
are used by the specific configuration
1 all inputs are displayed, even if not available
for the specific configuration
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 31 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
Index
ELD-fCLG 3
1 D ELD-fOPG 3
1AT 11 DAR-T 19 ELD-LNG 3
1LS-D 21 DBP-TY 17 ELD-MSG 3
DCMT-A 7 ELD-rCLG 3
2 DCP-T 6 ELD-rOPG 3
2AT 11 DDP 11 ELD-Sym1 3
2LS-D 21 DEBUG 30 EN-1CL 30
DEBUG1 30 EN-ADM 14
3 DHB-T 19 EN-BAK 26
DHB-TYP 8 EN-BCD 13
3P 11
DISP-ALL 30 EN-BSM 2
A DO-BEL 18 EN-CK 18
DOC 7 EN-CRO 28
ACD/UXT 12 EN-CRT 30
DO-D 16
ANS 7 EN-DDO 14
DOMT-O 7
ARBL-PRK 6 EN-DZI 4
DOOR 14
ARBL-T 6 EN-EVT 30
DOR-T 18
ARD-P 6 EN-FPD 28
DRIVE 11
ARD-T 6 EN-GSS 10
DS-CCB 7
ASL-P 24 EN-HLC 4
DS-DOB 8
ATT 7 EN-IST 28
DTC-T 18
B DTO-T 18 EN-J 12
DUPK-G 9 EN-MPD 12
BFLT-T 13 DUPK-P 9 EN-NDG 17
BI-T 22 DW-DLY 18 EN-OTS 12
BOFF-D 13 DXT-T 19 EN-PLS 12
BON-D 13 DZCNT 4 EN-PMO 17
BO-T 22 DZ-DLY 20 EN-RB 8
BOTTOM 2 DZ-TYP 20 EN-RLV 21
C EN-RR 4
E EN-SFR 3
CA-MOD 22 EF-I-INV 26 EN-SHB 6
C-CHK 4 EF-I-LT 26 EN-UCB 9
CFT-NT 18 EFO-DC 23 EN-ZBS 10
CFT-P 2 EFO-DO 23 EPO-DC 27
CM-D 17 EFO-MP 24 EPO-DO 27
CM-PROT 16 EFO-MP-T 24 EPO-P 27
CMR-ES 17 EFO-NC 23 EPO-PR 27
CM-TYP 16 EFONDG 23 EPS-TYP 27
CNL 9 EFO-OP 23 EQO 27
CONFIG 2 EFO-P 23 ERO-TYP 4
CPC-TYP 5 EFO-SD 24 ES-LRCU 23
CPMT-D 7 EFSCLD 25 ES-SLOW 23
CPR-T 6 EFS-DO 24 ES-TYP 23
CR-DIR 4 EFS-EX 25
CR-DO 4 F
EFSINI 25
CTL/PKS 6 EFSOPD 25 F:DC-TYP 15
CTL-DO 6 EFS-RC 26 F:DOL-D 15
CTL-P 7 EFS-RT 25 F:DO-TYP 15
CTL-TY 7 EFS-TY 24 F:EN-ACG 15
C-TYPE 11 EHS-T 27 F:EN-DCL 15
ELD-DOOR 3
Part: 4 - AA3
OTIS Field Component Manual No.: GCA21240D VIIIa
Vintage: 02 / 4
Product Software Data
Administration Page: 32 / 32
MCS - LCB II
Date: 25-Feb-1998
List of Installation Parameters
G MIN-H 18 R:DOL-D 16
MIT-DOOR 9 R:DO-TYP 15
GCBTYP 28 MIT-NLB 9 R:EN-ACG 16
GROUP 9 MIT-ST 9 R:EN-DCL 16
GRP-NO 9 MIT-T 9 RDOR-T 18
H MIT-VD 9 REAR 14
MIXDOR 14 RIOT-P 28
HDL-TY 4 MOT-T 9 RL-CNT 21
HDWPOS 26 MPD-T 12 RL-D-D 21
HL-SET 4 MVD-T 22 RL-DIS 21
HY-TYP 12 MVU-T 22 RL-U-D 21
I RL-UIS 21
N RLV-TY 21
IPD-D 21 N+2 WIRE 5
IPU-D 20 S
NDG-T 18
ISC 7 NoAdrChk 30 SAC-D1 29
ISC-T 7 NoDW_Chk 30 SAC-D2 29
ISPS-TY 7 SAC-D3 29
IST-P 28 O SACTYP 29
J OPERAT 2 SEL-CMR 17
SEL-COMP 10
J-T 12 P SHO-LT 19
PARK-1 9 SHO-T 19
L
PARK-2 9 SPB-NT 18
LDR 17 PARK-3 10 SPEECH 7
LOBBY 2 PARK-4 10 SPEED 11
LOB-NT 18 PARK-5 10 T
L-PARK 10 PARK-6 10
LR-MODE 3 PARK-7 10 T-BASE 20
LR-T 3 PARK-8 10 TCI-TYP 17
L-T 12 PI 2 TDELAY 30
LVD-5D 22 PI-OPT 2 TFS-P 9
LV-D-D 20 PKS -TY 6 TOP 2
LV-MOD 20 PKS-DO 6 TPOS 1 30
LVU-5D 22 PKS-P 6 TPOS 2 30
LV-U-D 20 PKS-T 6 TRO-TYP 17
M PLS4-T 22
U
P-OFF-D 12
MAX-C 18 P-ON-D 12 UX-D 12
MAX-H 18 PRKDST 10 UXT-D 12
MD/AES 5
MG-DEL 10 R W
MIN-C 18 R:DC-TYP 15 WCO-T 19