Sheet - 6 - Terrace Beam-22-08-22-A1-Terrace Beam

1. The document provides notes for structural drawings including that drawings must be read with architectural drawings, construction must confirm to IS 456:2000, and seismic zone III is considered. 2. STAAD Pro software is used for limit state design analysis and any discrepancies must be brought to the consultant before work execution. 3. Dimensions are in millimeters unless otherwise specified and grade of concrete will be M30 mixed by machine.

Uploaded by

Thrk Twr
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
80 views1 page

Sheet - 6 - Terrace Beam-22-08-22-A1-Terrace Beam

1. The document provides notes for structural drawings including that drawings must be read with architectural drawings, construction must confirm to IS 456:2000, and seismic zone III is considered. 2. STAAD Pro software is used for limit state design analysis and any discrepancies must be brought to the consultant before work execution. 3. Dimensions are in millimeters unless otherwise specified and grade of concrete will be M30 mixed by machine.

Uploaded by

Thrk Twr
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

NOTES

1. ALL STRUCTURAL DRAWINGS SHALL BE READ IN


CONJUCTION WITH CORRESPONDING
ARCHITECTURAL DRAWINGS.
2. ALL PLAIN AND R.C.C. CONSTRUCTION SHALL
CONFIRM TO IS 456 : 2000.
3. SEISMIC ZONE III IS CONSIDERED.
BEAM SCHEDULE (M25:Fe500) (LEVEL: 21.9 m) 4. METHOD OF ANALYSIS IS STAAD PRO. WITH LIMIT
STATE DESIGN.
BOTTOM 5. DISCREPANCY IF ANY SHALL BE BROUGHT TO THE
E G BEAM SIZE(mm) REINFORCEMENT TOP REINFORCEMENT SHEAR STIRRUPS NOTICE OF CONSULTANT BEFORE EXECUTION OF
WORK.
A B C D F H I J NUMBERS B D MID SPAN ET-L TT ET-R Sve-L Svc Sve-R 6. IN CASE OF SUBSTANTIAL CHANGE IN LOADING
PATTERN STRUCTURAL CONSULTANT ARE TO BE
4930 2615 2935 2350 3583 2628 4919
B1,B47 300 600 3-T16 3-T20 3-T16 3-T20 8T@100C/C 8T@200C/C 8T@100C/C REFERRED.
7. EXPOSURE CONDITION ADOPTED IS SEVERE
650 1700 650 B2,B48 300 600 3-T16 3-T20 3-T16 3-T20 8T@100C/C 8T@200C/C 8T@100C/C 8. ALL DIMENSIONS ARE IN MILLIMETERS, UNLESS
OTHERWISE SPECIFIED.
B3,B50 300 600 3-T16 3-T20 3-T16 3-T20 8T@100C/C 8T@200C/C 8T@100C/C 9. GRADE OF CONCRETE MIX SHALL BE M 30 MACHINE
B1 B2 VOID FOR LIFT B3 B4
MIXED & VIBRATED.
9 B4,B51 300 600 3-T16 3-T20 3-T16 3-T20 8T@100C/C 8T@200C/C 8T@100C/C 10. REINFORCEMENT SHALL BE TMT BARS OF GRADE
C4 S1 C5 C6 S2 C7
925 C3 B5 B6 B7 C8 B5,B7,B10,B12 300 450 3-T12 0 3-T12 0 Fe : 500D CONFORMING TO IS 1786 :1985
8T@100C/C 8T@200C/C 8T@100C/C
8 11. NORMAL COVER TO OUTERMOST REINFORCEMENT

B72
S3 S4 S5 B8 S9 C9 C10 S11 B9 S6 S7 S8
B6,B11 300 450 3-T12 0 3-T12 0 SHALL BE AS UNDER
8T@100C/C 8T@200C/C 8T@100C/C

B78

B87
B55

B57

B63

B68

B91

B95
2000

(a) FOR FOOTING = 60 mm

B73

B74

B83
S12
2710

S13 B9,B8,B45,B46 300 600 3-T16 0 3-T12 0 8T@100C/C 8T@200C/C 8T@100C/C (b) FOR COLUMN = 50 mm
(c) FOR BEAM = 30 mm
B10 B11 B12 B45A,B45B
7 13. LAP LENGTH IN REINFORCEMENT BARS SHALL BE
C11 B14A C12
710

B13 B14 B15 B16 B13,B16,B40,B44 300 600 3-T20 3-T20 3-T16 3-T20 50 TIMES THE DIA OF BARS.
8T@100C/C 8T@200C/C 8T@100C/C
6 B21,B25,B29,B35 14. DESIGN IS SUITABLE FOR ONE ADDITIONAL STOREY
C14 S18 C17 AS PER APPROVED GAD.
C13 S14 S15 C15 C16 S16 S17 C18
S19 S20 S21 S22 B14,B15,B41,B43 300 600 3-T20 3-T20 3-T16 3-T20 15. REFER APPROVED GAD FOR ANY DIMENSIONAL
B17 B18
8T@100C/C 8T@200C/C 8T@100C/C
B19 B20 MISMATCH.
B59

B82
3020

B54

B94
B17,B18,B19,B20 300 600 3-T16 0 3-T12 0 16. BEAM NO.BM-24,28,31,32,33,81,24,28 NOT IN USED.

B89
S23 8T@100C/C 8T@200C/C 8T@100C/C

B62
S24 S25

B86
B67
S26 B36,B37,B38,B39

B71

B77
REFRENCE CODES
B23,B14A,B27 300 600 3-T20 0 3-T12 0 8T@100C/C 8T@200C/C 8T@100C/C 1. IS - 456
B21 B21A B19A B25
5 2. IS - 875
C19 C20 B23 C21 C22 B22,B26 300 600 3-T16 3-T20 3-T16 3-T16 8T@100C/C 8T@200C/C 8T@100C/C 3. IS -13920
1265

4. IS - 1893
B26 B22 B73,B74 300 450 3-T12 3-T12 3-T12 3-T12 8T@100C/C 8T@200C/C 8T@100C/C
S28

B45A

B45B
4
C23 C24 C25 C26 B30,B34,B19A,21A 300 600 3-T12 3-T16 3-T16 0 8T@100C/C 8T@200C/C 8T@100C/C
1315

B29 B30 B27 B34 B35 B42,B49 300 600 3-T16 3-T20 3-T16 3-T20 8T@100C/C 8T@200C/C 8T@100C/C
3 S40
C27 S33 S34 S35 S36 C30

B70

B76
B60,B84 300 600 3-T16 3-T20 3-T12 3-T20 8T@100C/C 8T@200C/C 8T@100C/C
B65

B80
S37 C28 S38 S39 C29 S41
B61
B53

B93
B52,B92 300 600 3-T16 3-T20 3-T16 2-T16 8T@100C/C 8T@200C/C 8T@100C/C
B58

B36 B37 B38 B39


2880

(120THK) S44 S45 8T@100C/C 8T@200C/C 8T@100C/C

B88
S43 B53,B93 300 600 3-T16 3-T20 3-T16 3-T16

B85
S42
B40 B54,B94 300 600 3-T16 3-T20 3-T16 3-T16 8T@100C/C 8T@200C/C 8T@100C/C
B41 B42 B43 B44
2 8T@100C/C 8T@200C/C 8T@100C/C
C32 S46 S47 B55,B95 300 600 3-T12 3-T16 3-T16 3-T20
C31 C33 C34 C35 C36
B56,B57,B90,B91 300 600 3-T16 0 3-T16 0 8T@100C/C 8T@200C/C 8T@100C/C
S52 S53 S54
B69

S51

B79
S48 S49 S50
B52

B56

B60

B64

B84

B90

B92
B75
B58,B59,B88,B89 300 600 3-T20 0 3-T16 0 8T@100C/C 8T@200C/C 8T@100C/C
3775

B45 B46
S56 B61,B85 300 600 3-T16 3-T16 3-T16 3-T20 8T@100C/C 8T@200C/C 8T@100C/C
S55
B62,B86 300 600 3-T16 3-T16 3-T16 3-T16 8T@100C/C 8T@200C/C 8T@100C/C
B47 B48 B49 B50 B51
1 B63,B87 300 600 3-T16 3-T16 3-T16 3-T16 8T@100C/C 8T@200C/C 8T@100C/C
C37 C38 C1 C2 C39 C40
B64,B68,B79,B83 300 600 3-T20 0 3-T16 0 8T@100C/C 8T@200C/C 8T@100C/C
B65,B80 300 600 3-T20 0 3-T16 3-T16 8T@100C/C 8T@200C/C 8T@100C/C
TERRACE BEAM LAYOUT
SCALE-1:100 B75,B69 300 600 3-T16 3-T16 3-T16 3-T20 8T@100C/C 8T@200C/C 8T@100C/C

B76,B70 300 600 3-T20 3-T20 3-T16 3-T20 8T@100C/C 8T@200C/C 8T@100C/C

B77,B71 300 600 3-T20 3-T20 3-T16 3-T20 8T@100C/C 8T@200C/C 8T@100C/C
B78,B72 300 600 3-T20 3-T20 3-T16 3-T20 8T@100C/C 8T@200C/C 8T@100C/C

B67,B82 300 600 3-T20 3-T20 3-T16 0 8T@100C/C 8T@200C/C 8T@100C/C

DRAWING NO. : D137/LOT-I/VR/QTR-TYP-II /001/R0 (SHEET 6/7)


Railway:
WESTERN RAILWAY
MUMBAI - DIVISION
C
L OF END SUPPORT C
L OF INTERMEDIATE SUPPORT Project Title: Station:
0.25 L1 0.25 L1 0.25 L2 NOT < Ld VIRAR-DAHANU ROAD VIRAR STATION
COLUMN
# 'Y' = ( Ld+10 d b )

TT TT TT
R.C.C.

TE TT TE TE TT 12# 3 NOs QUADRUPLING

8# @150 c/c
D

LINTEL Drawing Title:


230

BEAM 8# @200 c/c


PROPOSED 01 BLDG S+6 TYPE -II

75
75
BT SPLICE IF REQD. QUARTERS (TOTAL 24 UNITS).
COLUMN

Sv NOT > 150


R.C.C.

2d (Sv end) Sv cent. 2d (Sv end) 2d (Sv end) MAX. PROJECTION 1000 TERRACE BEAM LAYOUT AND RCC DETAILS
L2 16# 3 NOs
L1

AECOM - CEG Joint Venture


REINFORCEMENT DETAILS OF CONTINUES BEAM TYP. DETAIL FOR LINTEL AND CHAJJA 9TH FLOOR, INFINITY TOWER C DLF CYBER CITY,
SCALE-1:50 SCALE-1:50 DLF PHASE II GURGAON 122002, INDIA

DATE :

DRAWN (A) DESIGNED (B) CHECKED (C) APPROVED (D)

1.5 d 1.5 d TT
SECONDARY BEAM
SLAB
d
D

W T = 2 No. #10mm
FOR BEAM OF
MAIN BEAM CLOSE RINGS 650mm DEPTH ONLY MUMBAI RAILWAY
BT VIKAS CORPORATION
B

REINFORCEMENT DETAILS OF
MAIN BEAM SUPPORTING SECONDARY SECTION OF BEAM PROOF CHECKED BY
SCALE-1:50 SCALE-1:50

V. S. WADEKAR
E. D. (CIVIL)/ MRVC STRUCTURAL CONSULTANT

M.D. DIXIT A.V. KULKARNI


XEN / MRVC AGM (CIVIL)/MRVC

SPE / MRVC