0% found this document useful (0 votes)
47 views8 pages

Footing DC

This document provides definitions and calculations for footing design. It defines 81 terms used in the design and references codes for parameters like percentage tensile reinforcement and shear reinforcement. It also lists properties of the specific footing design like the concrete grade, steel grade, column details, and analysis numbers.

Uploaded by

Thrk Twr
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
47 views8 pages

Footing DC

This document provides definitions and calculations for footing design. It defines 81 terms used in the design and references codes for parameters like percentage tensile reinforcement and shear reinforcement. It also lists properties of the specific footing design like the concrete grade, steel grade, column details, and analysis numbers.

Uploaded by

Thrk Twr
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

Footing Design: Design Calculation Page 1 of 8

FOOTING DESIGN CALCULATIONS


Project Name : Dahanu RD PWAY Store and Office-FND
Client Name : MRVC
Engineer Name : AECOM
Design File : F:\Gravitas\AECOM Dahanu Road\Design\Dahanu RD Store and
Office\STAAD\FND.rcdx
Analysis File : F:\ONEDRI~2\Run1\AECOM\LOT1\PENDIN~1\202109~1
\FORPRE~1\DAHANU~2\STAAD\DAHANU~1.STD
Analysis Last Modified : 26-Sep-21 10:14:14 AM

Definitions:
1. α = Coefficient of Thermal Expansion
2. ε1 = Strain at level considered, Calculated ignoring the
stiffening of the concrete in tension zone
3. εm = Average steel strain at level considered
4. ρact = Percentage steel provided
5. ρcrit = Percentage steel critical as per code
6. A = Plan area of footing base
7. Acr = Distance from the point considered to the surface of the
nearest longitudinal bar
8. AstPrv = Area of tensile reinforcement provided
9. Astrqd = Area of tensile reinforcement required
10. Asv = Area of shear reinforcement required
11. AsvPrv = Area of shear reinforcement provided
12. A1 = Bearing area of footing at slope of 1:2
13. A2 = C/s Area of column
14. B = Width of footing base
15. Beff = Effective width of footing
16. BoffB = Footing offset along B below column in plan
17. BoffT = Footing offset along B above column in plan
18. B1 = Width of sloped footing at top
19. ColOff = Column offset in sloped footing
20. D = Depth of footing
21. Deff = Effective Depth of footing
22. Df = Depth of founding layer
23. Dw = Ground water level
24. Ec = Modulus of elasticity of concrete
25. Es = Modulus of elasticity of steel
26. Foss = Safety factor against sliding
27. Fosu = Safety factor against uplift
28. Fst = Stress in steel
29. L = Length of footing base
30. Leff = Effective length of footing
31. LoffL = Footing offset along L on left side of column
32. LoffR = Footing offset along L on right side of column
33. L1 = Length of sloped footing at top

file:///C:/Users/jazzy/AppData/Local/Temp/tmp1DD4.tmp 15-01-2022
Footing Design: Design Calculation Page 2 of 8

34. Mx = Bending Moment along column D


35. Mx' = Bending Moment along column D due to odd shaped
column
36. Mex = Eccentricity moment along column D
37. Mxx = Total Bending Moment along column D (Mx + Mx' +
Mex)
38. My = Bending Moment along column B
39. My' = Bending Moment along column B due to odd shaped
column
40. Mey = Eccentricity moment along column B
41. Myy = Total Bending Moment along column B (My + My' +
Mey)
42. Muy = Factored moment along column B
43. Muy' = Factored Moment along column B due to odd shaped
column
44. Mux = Factored moment along column D
45. Mux' = Factored Moment along column D due to odd shaped
column
46. Netdown = Net downward load
47. OB = Maximum permissible offset on bottom side of column
in plan
48. OL = Maximum permissible offset on left side of column in
plan
49. OR = Maximum permissible offset on right side of column in
plan
50. OT = Maximum permissible offset on top side of column in
plan
51. P = Axial load for footing sizing
52. P1 = Soil pressure at corner 1
53. P2 = Soil pressure at corner 2
54. P3 = Soil pressure at corner 3
55. P4 = Soil pressure at corner 4
56. Pdelta = Column Load to be transferred by reinforcement
57. Pt = Calculated percentage tensile reinforcement
58. Pu = Factored axial load
59. q = Surcharge Load
60. sp = Spacing Between bars at outer most layer
61. SPu = Upward Soil Pressure
62. SPuL = Upward Soil Pressure from left
63. SPuR = Upward Soil Pressure from right
64. SPuB = Upward Soil Pressure from bottom
65. SPuT = Upward Soil Pressure from top
66. Tc = Design shear strength of concrete
67. Temp1 = Peak Hydration temperature
68. Temp2 = Seasonal Temperature Variations
69. Tv = Nominal shear stress
70. Vu = Design shear force
71. Vus = Strength of shear reinforcement

file:///C:/Users/jazzy/AppData/Local/Temp/tmp1DD4.tmp 15-01-2022
Footing Design: Design Calculation Page 3 of 8

72. Vx = Shear along major axis


73. Vy = Shear along minor axis
74. Waterpr = Upward water pressure
75. Waterup = Upward force due to water
76. Wcr = Surface Crack Width
77. WFoot = Add. Wt. due to difference in concrete and soil density
78. WFootc = Weight of footing and column with concrete density
79. WSoil = Weight of soil covering footing area
80. Zx = Section modulus of footing base along L
81. Zy = Section modulus of footing base along B

Code References:
IS 456
Parameter Reference
1. Ptmax : Cl. 26.5.2.1
2. Ptmin : Cl. 26.5.2.1
3. Pt : Cl. 38
4. Tc : Cl. 40.2.1
5. Tcmax : Cl. 40.2.3
6. Asv : Cl. 40.4
7. Min Shear Reinf : Cl. 26.5.1.6
8. Max Stirrup Spacing : Cl. 26.5.1.5
9. Punching Shear design : Cl. 31.6.3
10. Load transfer : Cl. 34.4
11. Ptnominal : Cl. 34.5.2
12. Crack width calculation : Annex-F
13. Cracking : Cl. 35.3.2

BS 8007 (For Early / Initial Thermal Cracking)


1. Surface Zone for suspended : Figure A.1
slab
2. Surface Zone for ground : Figure A.2
slab
3. Factors for the calculation : Table A.1
of minimum reinforcement

Design Code : IS 456 : 2000 + IS 13920 : 2016


Footing No : FC6
( 450mm X
Column No : C6,C7,C10,C11,C14,C15,C18,C19,C22,C23
300mm)
Analysis No : 9,16,10,17,11,18,12,19,13,20

Concrete Grade : M25 N/sqmm


Steel Grade : Fe500 N/sqmm
Clear Cover : 40 mm
Df : 4M

file:///C:/Users/jazzy/AppData/Local/Temp/tmp1DD4.tmp 15-01-2022
Footing Design: Design Calculation Page 4 of 8

Dw : 1M

Density of Soil = 18 kN/cum


Soil Bearing Capacity = 400 kN/sqm
Permissible SBC Increase for EQ = 25 %
Permissible SBC Increase for = 25 %
Wind
Live Load Reduction = 50 %
Permissible area of loss of =0 %
contact

Design cross section by : Average pressure

Footing Type : Pad


Footing Size (L x B x D) : 1600mm X 1500mm X 500mm
Without considering Effect of Water
Table
Footing Self Wt., F1 = 30.00 kN
Soil Weight, S1 = 0.00 kN
Total Weight, W1 = F1 + S1
= 30 kN
Offset Along L (Loff) = 575 mm
Offset Along B (Boff) = 600 mm

Check For Maximum Soil Pressure:


Critical Column No = C14
Critical Load Combination = [3] : (LOAD 3: DL) +(LOAD 4: LL) -(LOAD
1: SEISMIC-X)
Pcomb = 915.20 kN
P = Pcomb + W1
P = 945.20 kN
Mx = -0.39 kNm
My = 54.99 kNm
P/A = 393.83 kN/sqm
Mx/Zx = -0.61 kN/sqm
My/Zy = 91.65 kN/sqm
Maximum Soil Pressure = 486.08 kN/sqm
Allowable Soil Pressure = 1.25x400 kN/sqm
= 500 kN/sqm

Check For Minimum Soil Pressure:


Critical Column No = C22
Critical Load Combination = [2] : (LOAD 3: DL) +
(LOAD 4: LL) +(LOAD 1:
SEISMIC-X)
Pcomb = 564.04 kN

file:///C:/Users/jazzy/AppData/Local/Temp/tmp1DD4.tmp 15-01-2022
Footing Design: Design Calculation Page 5 of 8

P = Pcomb + W1
P = 594.04 kN
Mx = 0.76 kNm
My = -57.9 kNm
P/A = 247.51 kN/sqm
Mx/Zx = 1.19 kN/sqm
My/Zy = -96.49 kN/sqm
Minimum Soil Pressure = 149.83 kN/sqm
> 0

Design For Bending:


Bottom Reinforcement Along L:
Critical Column No = C14
Critical Load Combination = [14] : 1.5 (LOAD 3: DL) -1.5 (LOAD 2:
SEISMIC-Z)
Pu = 1092.81 kN
Mux = -76.27 kNm
Muy = -5.34 kNm
P/A = 455.34 kN/sqm
Mx/Zx = -119.17 kN/sqm
My/Zy = -8.91 kN/sqm

Deff = 452 mm
Beff = 1500 mm
SPu = 574.5 kN/sqm
Mu = SPu X B X Loff X Loff / 2
= 142.46 kNm
Pt = 0.133 %
Ast Rqd (BM) = 900 sqmm
Ast Prv (Distributed Across Total = 12 - T10 @ 140
Width)
= 942 sqmm

Bottom Reinforcement Along B:


Critical Column No = C14
Critical Load Combination = [12] : 1.5 (LOAD 3: DL) -1.5 (LOAD 1:
SEISMIC-X)
Pu = 1245.89 kN
Mux = -0.56 kNm
Muy = 82.17 kNm
P/A = 519.12 kN/sqm
Mx/Zx = -0.87 kN/sqm
My/Zy = 136.96 kN/sqm

Deff = 436 mm
Leff = 1600 mm
SPu = 656.08 kN/sqm

file:///C:/Users/jazzy/AppData/Local/Temp/tmp1DD4.tmp 15-01-2022
Footing Design: Design Calculation Page 6 of 8

Mu = SPu X L X Boff X Boff / 2


= 188.95 kNm
Pt = 0.147 %
Ast Rqd (BM) = 1027 sqmm
Ast Prv (Distributed Across Total
= 14 - T10 @ 125
Length)
= 1100 sqmm

Design For Shear:


One Way Shear Along L:
Critical Section @ d from Column Face
= 452 mm
Critical Column No = C14
Critical Load Combination = [14] : 1.5 (LOAD 3: DL) -1.5 (LOAD 2:
SEISMIC-Z)
Pu = 1092.81 kN
Mux = -76.27 kNm
Muy = -5.34 kNm
P/A = 455.34 kN/sqm
Mx/Zx = -119.17 kN/sqm
My/Zy = -8.91 kN/sqm

Deff = 452 mm
Beff = 1500 mm
SPu = 574.5 kN/sqm
Vu = SPu X (Loff - d) X B
= 106.00 kN
Tv = Vu / (Beff X Deff)
= 0.16 N/sqmm
Tc = 0.28 N/sqmm
Tv < Tc

One Way Shear Along B:


Critical Section @ d from Column Face

= 436 mm
Critical Column No = C14
Critical Load Combination = [12] : 1.5 (LOAD 3: DL) -
1.5 (LOAD 1: SEISMIC-X)
Pu = 1245.89 kN
Mux = -0.56 kNm
Muy = 82.17 kNm
P/A = 519.12 kN/sqm
Mx/Zx = -0.87 kN/sqm
My/Zy = 136.96 kN/sqm

file:///C:/Users/jazzy/AppData/Local/Temp/tmp1DD4.tmp 15-01-2022
Footing Design: Design Calculation Page 7 of 8

Deff = 436 mm
Leff = 1600 mm
SPu = 656.08 kN/sqm
Vu = SPu X (Boff - d) X L
= 172.15 kN
Tv = Vu / (Leff X Deff)
= 0.25 N/sqmm
Tc = 0.3 N/sqmm
Tv < Tc

Design For Punching Shear:


Critical Section @ d/2 from Column Face
= 222 mm

Critical Column No = C19


Critical Load Combination = [11] : 1.5 (LOAD 3: DL) +1.5 (LOAD 1:
SEISMIC-X)
Pu = 1263.72 kN
Mux = -1.25 kNm
Muy = -77.5 kNm
P/A = 526.55 kN/sqm
Mx/Zx = -1.96 kN/sqm
My/Zy = -129.17 kN/sqm

Deff = 444 mm
Leff = 894 mm
Beff = 744 mm
Punching Perimeter = 3276 mm
Punching Area = 1454544 sqmm
SPu = Average Pressure
= 526.55 kN/sqm
Vu = SPu X ((L X B)-(Leff X Beff))
= 913.49 kN
Tv = Vu / Punching Area
= 0.628 N/sqmm
Tc = 1.25 N/sqmm
Tv < Tc

Load Transfer Check For Load Transfer From Column To Footing


Critical Column No = C19
Critical Load Combination = [11] : 1.5 (LOAD 3: DL)
+1.5 (LOAD 1: SEISMIC-
X)
Pu = 1263.72 kN
A2 = 0.14 sqm
A1 = 5.64 sqm
Base Area = 2.4 sqm

file:///C:/Users/jazzy/AppData/Local/Temp/tmp1DD4.tmp 15-01-2022
Footing Design: Design Calculation Page 8 of 8

A1 > Base Area


Thus, A1 = 2.4
Modification Factor = SquareRoot(A1/A2)  < =
2
SquareRoot(A1/A2) = 4.1404
Thus, Modification Factor = 2
Concrete Bearing Capacity = 0.45 X Fck X Modification Factor X Column
Area
= 3037.5 kN
Concrete Bearing Capacity > Pu, Hence Safe.

file:///C:/Users/jazzy/AppData/Local/Temp/tmp1DD4.tmp 15-01-2022