1MRK502068-BEN F en Product Guide Generator Protection REG670 2.1
1MRK502068-BEN F en Product Guide Generator Protection REG670 2.1
R E L I O N ® 670 SERIES
Contents
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no
responsibility for any errors that may appear in this document. Drawings and diagrams are not binding.
© Copyright 2015 ABB. All rights reserved.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or
registered trademarks of their respective holders.
2 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC Issued: March 2019
Revision: F
fault, negative sequence current protections, and so on, Communication via optical connections ensures
are included in the IED. immunity against disturbances.
GUID-99777C26-F53E-4D5D-B0C6-640597A2A2FD v4
The generator differential protection in the REG670 By using patented algorithm REG670 (or any other
adapted to operate correctly for generator applications product from 670 series) can track the power system
where factors as long DC time constants and frequency in quite wide range from 9Hz to 95Hz (for
requirement on short trip time have been considered. 50Hz power system). In order to do that preferably the
three-phase voltage signal from the generator terminals
As many of the protection functions can be used as shall be connected to the IED. Then IED can adopt its
multiple instances there are possibilities to protect filtering algorithm in order to properly measure phasors
more than one object in one IED. It is possible to have of all current and voltage signals connected to the IED.
protection for an auxiliary power transformer integrated This feature is essential for proper operation of the
in the same IED having main protections for the protection during generator start-up and shut-down
generator. The concept thus enables very cost effective procedure.
solutions.
REG670 can be used in applications with the IEC
The REG670 also enables valuable monitoring 61850-9-2LE process bus with up to six merging units
possibilities as many of the process values can be (MU) depending on the other functionality included in
transferred to an operator HMI. the IED.
ABB 3
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
GEN_QA1
59N 2(U0>) MET U MET Usqi
GEN_TRM_VT ROV2 PTOV V MMXU V MSQI
Y
Y
81U
81 f<
f< 81O
81 f>
f> 27 2(3U<) 59 2(3U>) MET UN
SA PTUF
SA PTUF SA PTOF
SA PTOF UV2 PTUV OV2 PTOV VN MMXU
GEN_TRM_CT
50BF 3I>BF 51_67 4(3I>) 50AE U/I> U>/I< MET I
CC RBRF OC4 PTOC AEG PVOC FUF SPVC C MMXU
ROT_INJ_VT
87G 3Id/I>
G 64R Re<
2(i>/U<) GEN PDIF
CV
CVGAPC
GAPC 21 Z< 24 U/f>
ROT_INJ_CT + ZGV PDIS OEX PVPH
RXTTE
4
GEN_SP_CT
MET P/Q 32 P> 37 P< 40 Φ< 46 I2>
CV MMXN GOP PDOP GUP PDUP LEX PDIS NS2 PTOC
52PD PD 50 3I>> 50N IN>> 51N_67N 4(IN>) 87 INd/I 60 Ud> 81 df/dt<> 25 SC/VC
CC PDSC PH PIOC EF PIOC EF4 PTOC CCS SPVC VDC PTOV SA PFRC SES RSYN
Optional Functions
87T 3Id/I> 87 Id> 67N IN> 46I2 4(I2>) 64S R< 64R R< 59THD U3d/N 78 Ucos
T2W PDIF HZ PDIF SDE PSDE NS4 PTOC STTI PHIZ ROTI PHIZ STEF PHIZ PSP PPAM
78 Ucos 84 ↑↓ 60 Ud> 51V 2(I>/U<) 81A f<> 49R θ> 3 Control 3 Control
OOS PPAM TCM YLTC VD SPVC VR PVOC FTA QFVR GR PTTR Q CRSV S CILO
IEC11000068-5-en.vsd
IEC11000068 V5 EN-US
Figure 1. Typical generator protection application with generator differential and back-up protection, including 12 analog inputs
transformers in half 19" case size.
4 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
HV_CT
50BF 3I>BF 51_67 4(3I>) MET Isqi MET I
CC RBRF OC4 PTOC C MSQI C MMXU
HV_NCT 51N_67N 4(IN>)
EF4 PTOC
Y
Unit Step-up Trafo
51_67 4(3I>) MET Isqi MET I
OC4 PTOC C MSQI C MMXU
AUX_CT
EXC_CT MET Isqi MET I 51_67 4(3I>)
C MSQI C MMXU OC4 PTOC
Y
2(U0>
LV_VT_3U0 59N
)
ROV2 PTOV
GEN_QA1
Excitation Trafo
Auxiliary Trafo
GEN_TRM_CT
50BF 3I>BF 51_67 4(3I>) 50AE U/I> U>/I< MET I
AUX_QA1 CC RBRF OC4 PTOC AEG PVOC FUF SPVC C MMXU
ROT_INJ_VT
Auxiliary
87G 3Id/I>
Bus G 64R Re<
2(I>/U<) GEN PDIF
CV
CVGAPC
GAPC 21 Z< 24 U/f>
ROT_INJ_CT + ZGV PDIS OEX PVPH
RXTTE4
GEN_SP_CT
MET P/Q 32 P> 37 P< 40 Φ< 46 I2>
CV MMXN GOP PDOP GUP PDUP LEX PDIS NS2 PTOC
Optional Functions
87T 3Id/I> 87T 3Id/I> 87N IdN/I 46I2 4(I2>) 67N IN> 64S R< 64R R< 78 Ucos 78 Ucos
T2W PDIF T3W PDIF REF PDIF NS4 PTOC SDE PSDE STTI PHIZ ROTI PHIZ PSP PPAM OOS PPAM
84 ↑↓ 60 Ud> 51V 2(I>/U<) 81A f<> 49R θ> 3 Control 3 Control 3 Control Control
TCM YLTC VD SPVC VR PVOC FTA QFVR GR PTTR Q CRSV S CILO S CSWI S SCBR
3 Control 3 Control
S XCBR S XSWI
IEC11000071-5-en.vsd
IEC11000071 V5 EN-US
Figure 2. Enhanced generator protection application with generator differential and back-up protection, including 24 analog inputs in
full 19" case size. Optional pole slip protection, 100% stator earth fault protection and overall differential protection can be
added.
ABB 5
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
HV_CT
50BF 3I>BF 49 θ> MET Isqi MET I 87N IdN/I
CC RBRF TR PTTR C MSQI C MMXU REF PDIF
51N_67N 4(IN>)
Y EF4 PTOC
Unit Step-up Trafo
HV_NCT
87T 3Id/I> 87T 3Id/I>
T2W PDIF T3W PDIF
GEN_QA1
59N 2(U0>) MET U MET Usqi
ROV2 PTOV V MMXU V MSQI
Y Y
81U
81 f<
f< 81O
81 f>
f> 27 2(3U<) 59 2(3U>) MET UN
GEN_TRM_VT
SA
SAPTUF
PTUF SA
SAPTOF
PTOF UV2 PTUV OV2 PTOV VN MMXU
GEN_TRM_CT
50BF I>BF 51_67 4(3I>) 50AE U/I> U>/I< MET I
AUX_QA1
CC RBRF OC4 PTOC AEG PVOC FUF SPVC C MMXU
46I2 4(I2>) 67N IN> 64S R< 64R R< 78 Ucos 78 Ucos 60 Ud> 51V 2(I>/U<) 81A f<>
NS4 PTOC SDE PSDE STTI PHIZ ROTI PHIZ PSP PPAM OOS PPAM VD SPVC VR PVOC FTA QFVR
IEC11000072-5-en.vsd
IEC11000072 V5 EN-US
Figure 3. Unit protection including generator and generator transformer protection with 24 analog inputs in full 19" case size. Optional
pole slip protection and 100% stator earthfault protection can be added.
6 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
2. Available functions
REG670 (C30)
REG670 (A20)
REG670 (B30)
REG670
(Customized)
Differential protection
T2WPDIF 87T Transformer differential protection, two winding 0-2 1-A31 1-A33 1
REFPDIF 87N Restricted earth fault protection, low impedance 0-3 1-A01 1
Impedance protection
ROTIPHIZ 64R Sensitive rotor earth fault protection, injection 0-1 1-B31 1-B31 1-B31
based
STTIPHIZ 64S 100% stator earth fault protection, injection based 0-1 1-B32 1-B32 1-B32
ABB 7
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
REG670 (C30)
REG670 (A20)
REG670 (B30)
REG670
(Customized)
Current protection
NS4PTOC 46I2 Four step directional negative phase sequence 0-2 1-C41 2-C42 2-C42
overcurrent protection
SDEPSDE 67N Sensitive directional residual overcurrent and 0-2 1-C16 1-C16 1-C16
power protection
VRPVOC 51V Voltage restrained overcurrent protection 0-3 3-C36 3-C36 3-C36
Voltage protection
STEFPHIZ 59THD 100% stator earth fault protection, 3rd harmonic 0-1 1-D21 1 1
based
Frequency protection
8 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
REG670 (C30)
REG670 (A20)
REG670 (B30)
REG670
(Customized)
FTAQFVR 81A Frequency time accumulation protection 0-12 12-E03 12-E03 12-E03
Multipurpose protection
General calculation
1) 67 requires voltage
2) 67N requires voltage
ABB 9
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
REG670 (C30)
REG670 (A20)
REG670 (B30)
REG670
Control
APC30 3 Apparatus control for up to 6 bays, max 30 apparatuses 0-1 1-H09 1-H09 1-H09
(6CBs) incl. interlocking
TCMYLTC 84 Tap changer control and supervision, 6 binary inputs 0-4 1-A31 2-A33 2
I103POSCMD IED commands with position and select for IEC 60870-5-103 50 50 50 50
Secondary
system
supervision
VDSPVC 60 Fuse failure supervision based on voltage difference 0-2 1-G03 1-G03 1-G03
Logic
REG670 (C30)
REG670 (A20)
REG670 (B30)
REG670
AND, GATE, INV, Basic configurable logic blocks (see Table 2) 40-280 40-280 40-28 40-28
LLD, OR, 0 0
PULSETIMER,
RSMEMORY,
SRMEMORY,
TIMERSET, XOR
Monitoring
CVMMXN, Measurements 6 6 6 6
VMMXU, CMSQI,
VMSQI, VNMMXU
CMMXU Measurements 10 10 10 10
ABB 11
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
REG670 (C30)
REG670 (A20)
REG670 (B30)
REG670
Metering
12 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
AND 280
GATE 40
INV 420
LLD 40
OR 280
PULSETIMER 40
RSMEMORY 40
SRMEMORY 40
TIMERSET 60
XOR 40
ANDQT 120
INDCOMBSPQT 20
INDEXTSPQT 20
INVALIDQT 22
INVERTERQT 120
ORQT 120
PULSETIMERQT 40
RSMEMORYQT 40
SRMEMORYQT 40
TIMERSETQT 40
XORQT 40
AND 180
GATE 49
INV 180
LLD 49
OR 180
PULSETIMER 59
SLGAPC 74
SRMEMORY 110
TIMERSET 49
VSGAPC 130
XOR 49
ABB 13
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
REG670 (C30)
REG670 (A20)
REG670 (B30)
REG670
(Customized)
Station communication
RS485GEN RS485 1 1 1 1
14 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
REG670 (C30)
REG670 (A20)
REG670 (B30)
REG670
(Customized)
PRP IEC 62439-3 parallel redundancy protocol 0-1 1-P03 1-P03 1-P03
Remote communication
Receive binary status from remote LDCM 6/3/3 6/3/3 6/3/3 6/3/3
ABB 15
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
INTERRSIG
SELFSUPEVLST Self supervision with internal event list
16 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
ABB 17
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
two-winding power
The function can be provided with up to six three-phase transformer with
sets of current inputs if enough HW is available. All unconnected delta
current inputs are provided with percentage bias xx05000049.vsd
tertiary winding
IEC05000049 V1 EN-US
restraint features, making the IED suitable for two- or
two-winding power
three-winding transformer in multi-breaker station transformer with
arrangements. two circuit breakers
xx05000050.vsd
IEC05000050 V1 EN-US
and two CT-sets on
one side
two-winding power
transformer with
two circuit breakers
and two CT-sets on
both sides
xx05000051.vsd
IEC05000051 V1 EN-US
Three-winding applications
three-winding
power transformer
with all three
windings connected
xx05000052.vsd
IEC05000052 V1 EN-US
three-winding
power transformer
with two circuit
breakers and two
CT-sets on one side
xx05000053.vsd
IEC05000053 V1 EN-US
Autotransformer
with two circuit
breakers and two
CT-sets on two out
of three sides
xx05000057.vsd
IEC05000057 V1 EN-US
18 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
IEC05000058-2 V1 EN-US
based on the theory of negative sequence current
Figure 5. Examples of applications of the REFPDIF
component. This element offers the best possible
coverage of power transformer windings turn to turn
faults.
ABB 19
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
can be linked (per zone) through the phase selector or function. This also reduces underreach in the importing
the first starting zone. This can provide fast operate end.
times for evolving faults.
Pole slip protection PSPPPAM SEMOD143246-4 v4
The operation of the phase-selection is primarily based The situation with pole slip of a generator can be caused
on a current change criteria (i.e. delta quantities), by different reasons.
however there is also a phase selection criterion
operating in parallel which bases its operation on A short circuit may occur in the external power grid,
voltage and current phasors exclusively. Additionally the close to the generator. If the fault clearing time is too
directional element provides a fast and correct long, the generator will accelerate so much, that the
directional decision under difficult operating conditions, synchronism cannot be maintained.
including close-in three-phase faults, simultaneous
Undamped oscillations occur in the power system,
faults and faults with only zero-sequence in-feed.During
where generator groups at different locations, oscillate
phase-to-earth faults on heavily loaded power lines
against each other. If the connection between the
there is an adaptive load compensation algorithm that
generators is too weak the magnitude of the oscillations
prevents overreaching of the distance zones in the load
will increase until the angular stability is lost.
exporting end, improving the selectivity of the function.
This also reduces underreach in the importing end. The operation of a generator having pole slip will give
risk of damages to the generator, shaft and turbine.
Distance zones quad with high speed distance for
series compensated networks ZMFCPDIS
GUID-C5C1ADD8-50A5-4485-848C-77D2222B56DC v6
• At each pole slip there will be significant torque
The high speed distance protection (ZMFCPDIS) impact on the generator-turbine shaft.
provides a sub-cycle, down towards a half-cycle operate • In asynchronous operation there will be induction of
time. Its six zone, full scheme protection concept is currents in parts of the generator normally not
entirely suitable in applications with single-phase carrying current, thus resulting in increased heating.
autoreclosing. The consequence can be damages on insulation and
stator/rotor iron.
High speed distance protection ZMFCPDIS is
fundamentally the same function as ZMFPDIS but The Pole slip protection (PSPPPAM) function shall detect
provides more flexibility in zone settings to suit more pole slip conditions and trip the generator as fast as
complex applications, such as series compensated lines. possible if the locus of the measured impedance is
In operation for series compensated networks, the inside the generator-transformer block. If the centre of
parameters of the directional function are altered to pole slip is outside in the power grid, the first action
handle voltage reversal. should be to split the network into two parts, after line
protection action. If this fails there should be operation
Each measurement zone is designed with the flexibility
of the generator PSPPPAM in zone 2, to prevent further
to operate in either quadrilateral or mho characteristic
damages to the generator, shaft and turbine.
mode. This can even be decided separate for the phase-
to-ground or phase-to-phase loops. The six zones can Out-of-step protection OOSPPAM
operate either independent of each other, or their start
GUID-BF2F7D4C-F579-4EBD-9AFC-7C03296BD5D4 v7
The out-of-step protection OOSPPAM function in the IED
can be linked (per zone) through the phase selector or can be used for both generator protection and as well
the first starting zone. This can provide fast operate for line protection applications.
times for evolving faults.
The main purpose of the OOSPPAM function is to detect,
The operation of the phase-selection is primarily based evaluate, and take the required action during pole
on a current change criteria (i.e. delta quantities), slipping occurrences in the power system.
however there is also a phase selection criterion
operating in parallel which bases its operation on The OOSPPAM function detects pole slip conditions and
voltage and current phasors exclusively. Additionally the trips the generator as fast as possible, after the first
directional element provides a fast and correct pole-slip if the center of oscillation is found to be in
directional decision under difficult operating conditions, zone 1, which normally includes the generator and its
including close-in three-phase faults, simultaneous step-up power transformer. If the center of oscillation is
faults and faults with only zero-sequence in-feed. found to be further out in the power system, in zone 2,
more than one pole-slip is usually allowed before the
During phase-to-earth faults on heavily loaded power generator-transformer unit is disconnected. A
lines there is an adaptive load compensation algorithm parameter setting is available to take into account the
that prevents overreaching of the distance zones in the circuit breaker opening time. If there are several out-of-
load exporting end, improving the selectivity of the step relays in the power system, then the one which
20 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
100% stator earth fault protection, injection based The under impedance protection is a three zone full
STTIPHIZ scheme impedance protection using offset mho
characteristics for detecting faults in the generator,
ABB 21
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
generator-transformer and transmission system. The EF4PTOC can be set directional or non-directional
three zones have fully independent measuring loops and independently for each of the steps.
settings. The functionality also comprises an under
voltage seal-in feature to ensure issuing of a trip even if IDir, UPol and IPol can be independently selected to be
the current transformer goes into saturation and, in either zero sequence or negative sequence.
addition, the positive-sequence-based load
Second harmonic blocking can be set individually for
encroachment feature for the second and the third
each step.
impedance zone. Built-in compensation for the step-up
transformer vector group connection is available. EF4PTOC can be used as main protection for phase-to-
earth faults.
All IEC and ANSI inverse time characteristics are Four step negative sequence overcurrent protection
available together with an optional user defined time NS4PTOC GUID-485E9D36-0032-4559-9204-101539A32F47 v5
characteristic. Four step negative sequence overcurrent protection
(NS4PTOC) has an inverse or definite time delay
The directional function needs voltage as it is voltage independent for each step separately.
polarized with memory. The function can be set to be
directional or non-directional independently for each of All IEC and ANSI time delayed characteristics are
the steps. available together with an optional user defined
characteristic.
A second harmonic blocking level can be set for the
function and can be used to block each step individually. The directional function is voltage polarized.
22 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
magnitude of the fault current is almost independent on unnecessary tripping of surrounding breakers at an
the fault location in the network. The protection can be incorrect initiation due to mistakes during testing.
selected to use either the residual current or residual
power component 3U0·3I0·cos j, for operating quantity Pole discordance protection CCPDSC M13269-3 v14
with maintained short circuit capacity. There is also An open phase can cause negative and zero sequence
available one nondirectional 3I0 step and one 3U0 currents which cause thermal stress on rotating
overvoltage tripping step. machines and can cause unwanted operation of zero
sequence or negative sequence current functions.
No specific sensitive current input is needed. SDEPSDE
can be set as low 0.25% of IBase. Normally the own breaker is tripped to correct such a
situation. If the situation persists the surrounding
Thermal overload protection, two time constant breakers should be tripped to clear the unsymmetrical
TRPTTR M13243-3 v10
load situation.
If a power transformer reaches very high temperatures
the equipment might be damaged. The insulation within The Pole discordance protection function CCPDSC
the transformer will experience forced ageing. As a operates based on information from auxiliary contacts
consequence of this the risk of internal phase-to-phase of the circuit breaker for the three phases with
or phase-to-earth faults will increase. additional criteria from unsymmetrical phase currents
when required.
The thermal overload protection estimates the internal
heat content of the transformer (temperature) Directional over/underpower protection GOPPDOP/
continuously. This estimation is made by using a GUPPDUP SEMOD175421-4 v6
thermal model of the transformer with two time The directional over-/under-power protection
constants, which is based on current measurement. GOPPDOP/GUPPDUP can be used wherever a high/low
active, reactive or apparent power protection or
Two warning levels are available. This enables actions in alarming is required. The functions can alternatively be
the power system to be done before dangerous used to check the direction of active or reactive power
temperatures are reached. If the temperature continues flow in the power system. There are a number of
to increase to the trip value, the protection initiates a applications where such functionality is needed. Some
trip of the protected transformer. of them are:
The estimated time to trip before operation is • generator reverse power protection
presented. • generator low forward power protection
• detection of over/under excited generator
Breaker failure protection CCRBRF M11550-6 v16
• detection of reversed active power flow
Breaker failure protection (CCRBRF) ensures a fast • detection of high reactive power flow
backup tripping of the surrounding breakers in case the • excessive line/cable loading with active or reactive
own breaker fails to open. CCRBRF can be current- power
based, contact-based or an adaptive combination of • generator reverse power protection
these two conditions.
Each function has two steps with definite time delay.
A current check with extremely short reset time is used
as check criterion to achieve high security against By using optional metering class CT inputs accuracy of
inadvertent operation. 0,5% can be achieved for steam turbine applications.
Contact check criteria can be used where the fault Voltage-restrained time overcurrent protection
current through the breaker is small. VRPVOC GUID-935E1CE8-601F-40E2-8D22-2FF68420FADF v6
Voltage-restrained time overcurrent protection
CCRBRF can be single- or three-phase initiated to allow (VRPVOC) function can be used as generator backup
use with single phase tripping applications. For the protection against short-circuits.
three-phase version of CCRBRF the current criteria can
be set to operate only if two out of four for example, The overcurrent protection feature has a settable
two phases or one phase plus the residual current start. current level that can be used either with definite time
This gives a higher security to the back-up trip or inverse time characteristic. Additionally, it can be
command. voltage controlled/restrained.
CCRBRF function can be programmed to give a single- or One undervoltage step with definite time characteristic
three-phase re-trip of its own breaker to avoid is also available within the function in order to provide
ABB 23
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
functionality for overcurrent protection with Inadvertently energized generator operates as induction
undervoltage seal-in. motor drawing a large current from the system. The
voltage supervised overcurrent protection is used to
Negative sequence time overcurrent protection for detect the inadvertently energized generator.
machines NS2PTOC GUID-DBF3EC07-D947-4483-ABD1-4F7D29F48D61 v6
Negative-sequence time overcurrent protection for Accidental energizing protection for synchronous
machines NS2PTOC is intended primarily for the generator (AEGPVOC) takes the maximum phase current
protection of generators against possible overheating input and maximum phase to phase voltage inputs from
of the rotor caused by negative sequence current in the the terminal side. AEGPVOC is enabled when the
stator current. terminal voltage drops below the specified voltage level
for the preset time.
The negative sequence currents in a generator may,
among others, be caused by: Stator overload protection GSPTTR GUID-A416C856-E438-4ED4-A43D-D05F718D6A41 v5
The generator overload function, GSPTTR is used to
• Unbalanced loads protect the stator winding against excessive
• Line to line faults temperature as a result of overcurrents. The functions
• Line to earth faults operating characteristic is designed in accordance with
• Broken conductors the American standard IEEE-C50.13.
• Malfunction of one or more poles of a circuit breaker
or a disconnector If internal generator components exceed its design
temperature limit, damage can be the result. Damage to
NS2PTOC can also be used as a backup protection, that generator insulation can range from minor loss of life to
is, to protect the generator in case line protections or complete failure, depending on the severity and
circuit breakers fail to clear unbalanced system faults. duration of the temperature excursion. Excess
temperature can also cause mechanical damage due to
To provide an effective protection for the generator for
thermal expansion. Since temperature increases with
external unbalanced conditions, NS2PTOC is able to
current, it is logical to apply overcurrent elements with
directly measure the negative sequence current.
inverse time characteristics.
NS2PTOC also has a time delay characteristic which
matches the heating characteristic of the generator For its operation the function either measures the true
I 22t = K as defined in standard IEEE C50.13. RMS current of the stator winding or waited sum of the
positive and negative sequence components in the
stator winding.
where:
I2 is negative sequence current expressed The function is designed to work on 50/60 Hz systems.
in per unit of the rated generator
current Rotor overload protection GRPTTR GUID-E3AE6200-DB8D-4C49-A740-09366A333B4F v4
side (LV) side of the excitation transformer. For the HV Reset delay ensures operation for intermittent earth
side measurement ratings of the excitation transformer faults.
shall be given. The use of the DC current is default (i.e.
recommended) measurement for generators with static Overexcitation protection OEXPVPH M13319-3 v9
excitation system. When the DC current is used, the When the laminated core of a power transformer or
function can provide a DC current ripple alarm, due to generator is subjected to a magnetic flux density
possible problem with the static excitation equipment. beyond its design limits, stray flux will flow into non-
The rotor DC current can be also sent to the plant laminated components that are not designed to carry
supervisory system via communication channel or flux. This will cause eddy currents to flow. These eddy
displayed on the IED built-in HMI. currents can cause excessive heating and severe
damage to insulation and adjacent parts in a relatively
The function can also detect undercurrent condition in short time. The function has settable inverse operating
the rotor winding which indicates either under- curves and independent alarm stages.
excitation or loss of excitation condition of the
generator. Voltage differential protection VDCPTOV SEMOD153862-5 v7
A voltage differential monitoring function is available. It
The function is designed to work on 50/60 Hz systems. compares the voltages from two three phase sets of
voltage transformers and has one sensitive alarm step
and one trip step.
6. Voltage protection 95% and 100% Stator earth fault protection based
on 3rd harmonic STEFPHIZ SEMOD143258-4 v9
Two step undervoltage protection UV2PTUV M13789-3 v11
Stator earth fault is a fault type having relatively high
Undervoltages can occur in the power system during fault rate. The generator systems normally have high
faults or abnormal conditions. Two step undervoltage impedance earthing, that is, earthing via a neutral point
protection (UV2PTUV) function can be used to open resistor. This resistor is normally dimensioned to give an
circuit breakers to prepare for system restoration at earth fault current in the range 3 – 15 A at a solid earth-
power outages or as long-time delayed back-up to fault directly at the generator high voltage terminal. The
primary protection. relatively small earth fault currents give much less
thermal and mechanical stress on the generator,
UV2PTUV has two voltage steps, each with inverse or compared to the short circuit case, which is between
definite time delay. conductors of two phases. Anyhow, the earth faults in
the generator have to be detected and the generator
UV2PTUV has a high reset ratio to allow settings close to
has to be tripped, even if longer fault time compared to
system service voltage.
internal short circuits, can be allowed.
Two step overvoltage protection OV2PTOV M13798-3 v14
In normal non-faulted operation of the generating unit
Overvoltages may occur in the power system during
the neutral point voltage is close to zero, and there is no
abnormal conditions such as sudden power loss, tap
zero sequence current flow in the generator. When a
changer regulating failures, and open line ends on long
phase-to-earth fault occurs the neutral point voltage will
lines.
increase and there will be a current flow through the
OV2PTOV has two voltage steps, each of them with neutral point resistor.
inverse or definite time delayed.
To detect an earth fault on the windings of a generating
OV2PTOV has a high reset ratio to allow settings close unit one may use a neutral point overvoltage protection,
to system service voltage. a neutral point overcurrent protection, a zero sequence
overvoltage protection or a residual differential
Two step residual overvoltage protection ROV2PTOV M13808-3 v10
protection. These protections are simple and have
Residual voltages may occur in the power system during served well during many years. However, at best these
earth faults. simple schemes protect only 95% of the stator winding.
They leave 5% close to the neutral end unprotected.
Two step residual overvoltage protection ROV2PTOV
Under unfavorable conditions the blind zone may extend
function calculates the residual voltage from the three-
up to 20% from the neutral.
phase voltage input transformers or measures it from a
single voltage input transformer fed from an open delta The 95% stator earth fault protection measures the
or neutral point voltage transformer. fundamental frequency voltage component in the
generator star point and it operates when the
ROV2PTOV has two voltage steps, each with inverse or
fundamental frequency voltage exceeds the preset
definite time delay.
ABB 25
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
value. By applying this principle approximately 95% of the neutral point 3rd harmonic undervoltage principle or
the stator winding can be protected. In order to protect the terminal side 3rd harmonic overvoltage principle can
the last 5% of the stator winding close to the neutral be applied. However, differential principle is strongly
end the 3rd harmonic voltage measurement can be recommended. Combination of these two measuring
performed. In 100% Stator E/F 3rd harmonic protection principles provides coverage for entire stator winding
either the 3rd harmonic voltage differential principle, against earth faults.
RN Rf Transformer
uN x 1- x uT
Samples of the Samples of the
neutral voltage 1 or 100 % terminal voltage
from which the from which the
fundamental and 3rd harmonic
3rd harmonic voltage is filtered
Neutral point fundamental frequency
voltages are out
over-voltage protection 5% - 100%
filtered out over- voltage protection 10%– 100%
3rd harmonic
Differential
differential
0% – 30%
0% - 30% IEC10000202-1-en.vsd
IEC10000202 V1 EN-US
function. This can be achieved by a proper configuration The field winding, including the rotor winding and the
based on the turbine manufacturer specification. non-rotating excitation equipment, is always insulated
from the metallic parts of the rotor. The insulation
resistance is high if the rotor is cooled by air or by
hydrogen. The insulation resistance is much lower if the
8. Multipurpose protection rotor winding is cooled by water. This is true even if the
insulation is intact. A fault in the insulation of the field
General current and voltage protection CVGAPC circuit will result in a conducting path from the field
ABB 27
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
winding to earth. This means that the fault has caused a The negative sequence detection algorithm is
field earth fault. recommended for IEDs used in isolated or high-
impedance earthed networks. It is based on the
The field circuit of a synchronous generator is normally negative-sequence quantities.
unearthed. Therefore, a single earth fault on the field
winding will cause only a very small fault current. Thus The zero sequence detection is recommended for IEDs
the earth fault does not produce any damage in the used in directly or low impedance earthed networks. It is
generator. Furthermore, it will not affect the operation based on the zero sequence measuring quantities.
of a generating unit in any way. However, the existence
of a single earth fault increases the electric stress at The selection of different operation modes is possible
other points in the field circuit. This means that the risk by a setting parameter in order to take into account the
for a second earth fault at another point on the field particular earthing of the network.
winding has increased considerably. A second earth
A criterion based on delta current and delta voltage
fault will cause a field short-circuit with severe
measurements can be added to the fuse failure
consequences.
supervision function in order to detect a three phase
The rotor earth fault protection is based on injection of fuse failure, which in practice is more associated with
an AC voltage to the isolated field circuit. In non-faulted voltage transformer switching during station
conditions there will be no current flow associated to operations.
this injected voltage. If a rotor earth fault occurs, this
Fuse failure supervision VDSPVC
condition will be detected by the rotor earth fault GUID-6AF2219A-264F-4971-8D03-3B8A9D0CB284 v4
Different protection functions within the protection IED
protection. Depending on the generator owner
operates on the basis of measured voltage at the relay
philosophy this operational state will be alarmed and/or
point. Some example of protection functions are:
the generator will be tripped. An injection unit RXTTE4
and an optional protective resistor on plate are required • Distance protection function.
for correct rotor earth fault protection operation. • Undervoltage function.
• Energisation function and voltage check for the weak
infeed logic.
Synchrocheck, energizing check, and synchronizing Normal security means that only the command is
SESRSYN M12480-3 v15 evaluated and the resulting position is not supervised.
The Synchronizing function allows closing of Enhanced security means that the command is
asynchronous networks at the correct moment including evaluated with an additional supervision of the status
the breaker closing time, which improves the network value of the control object. The command sequence with
stability. enhanced security is always terminated by a
CommandTermination service primitive and an
Synchrocheck, energizing check, and synchronizing
AddCause telling if the command was successful or if
SESRSYN function checks that the voltages on both
something went wrong.
sides of the circuit breaker are in synchronism, or with
at least one side dead to ensure that closing can be Control operation can be performed from the local HMI
done safely. with authority control if so defined.
SESRSYN function includes a built-in voltage selection Interlocking
scheme for double bus and 1½ breaker or ring busbar The interlocking function blocks the possibility to
M13531-3 v4
Apparatus control features: The Switch controller (SCSWI) initializes and supervises
• Select-Execute principle to give high reliability all functions to properly select and operate switching
• Selection function to prevent simultaneous operation primary apparatuses. The Switch controller may handle
• Selection and supervision of operator place and operate on one three-phase device or up to three
• Command supervision one-phase devices.
• Block/deblock of operation
• Block/deblock of updating of position indications
Circuit breaker SXCBR M13489-3 v6
The purpose of Circuit breaker (SXCBR) is to provide the
• Substitution of position and quality indications
actual status of positions and to perform the control
• Overriding of interlocking functions
operations, that is, pass all the commands to primary
• Overriding of synchrocheck
apparatuses in the form of circuit breakers via binary
• Operation counter
output boards and to supervise the switching operation
• Suppression of mid position
and position.
30 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
ABB 31
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
VSGAPC can be controlled from the menu or from a received by the function to 16 binary coded (logic)
symbol on the single line diagram (SLD) on the local HMI. output signals.
Integer to Boolean 16 conversion IB16 The main purpose of the function is to measure and
Integer to boolean 16 conversion function IB16 is used to
SEMOD158373-5 v5
process signals from different measuring transducers.
transform an integer into a set of 16 binary (logical) Many devices used in process control represent various
signals. parameters such as frequency, temperature and DC
battery voltage as low current values, usually in the
Integer to Boolean 16 conversion with logic node range 4-20 mA or 0-20 mA.
representation ITBGAPC
Integer to boolean conversion with logic node
SEMOD158421-5 v8
Alarm limits can be set and used as triggers, e.g. to
representation function ITBGAPC is used to transform generate trip or alarm signals.
an integer which is transmitted over IEC 61850 and
32 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
The function requires that the IED is equipped with the There are three LEDs on the local HMI (green, yellow and
mA input module. red), which will display status information about the IED
and the Disturbance recorder function (triggered).
Disturbance report DRPRDRE M12153-3 v11.1.1
Complete and reliable information about disturbances in The Indication list function shows all selected binary
the primary and/or in the secondary system together input signals connected to the Disturbance recorder
with continuous event-logging is accomplished by the function that have changed status during a disturbance.
disturbance report functionality.
Event recorder DRPRDRE M12033-3 v8
Disturbance report DRPRDRE, always included in the IED, Quick, complete and reliable information about
acquires sampled data of all selected analog input and disturbances in the primary and/or in the secondary
binary signals connected to the function block with a, system is vital, for example, time-tagged events logged
maximum of 40 analog and 128 binary signals. during disturbances. This information is used for
different purposes in the short term (for example
The Disturbance report functionality is a common name corrective actions) and in the long term (for example
for several functions: functional analysis).
• Event list The event recorder logs all selected binary input signals
• Indications connected to the Disturbance recorder function. Each
• Event recorder recording can contain up to 150 time-tagged events.
• Trip value recorder
• Disturbance recorder The event recorder information is available for the
disturbances locally in the IED.
The Disturbance report function is characterized by
great flexibility regarding configuration, starting The event recording information is an integrated part of
conditions, recording times, and large storage capacity. the disturbance record (Comtrade file).
ABB 33
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
The function is characterized by great flexibility and is input signals to the function. In addition, the function
not dependent on the operation of protection functions. generates alarms based on received information.
It can record disturbances not detected by protection
functions. Up to ten seconds of data before the trigger Liquid medium supervision SSIML GUID-3B1A665F-60A5-4343-85F4-AD9C066CBE8D v5
instant can be saved in the disturbance file. Liquid medium supervision SSIML is used for monitoring
the circuit breaker condition. Binary information based
The disturbance recorder information for up to 100 on the oil level in the circuit breaker is used as input
disturbances are saved in the IED and the local HMI is signals to the function. In addition, the function
used to view the list of recordings. generates alarms based on received information.
Generic communication function for Single Point Event counter with limit supervison L4UFCNT
GUID-13157EAB-1686-4D2E-85DF-EC89768F3572 v5
in the substation. It can also be used inside the same The Running hour-meter (TEILGAPC) function is a
IED, to attach a RANGE aspect to an analog value and to function that accumulates the elapsed time when a
permit measurement supervision on that value. given binary signal has been high.
Measured value expander block RANGE_XP The main features of TEILGAPC are:
SEMOD52450-4 v7
The current and voltage measurements functions
• Applicable to very long time accumulation (≤ 99999.9
(CVMMXN, CMMXU, VMMXU and VNMMXU), current and
hours)
voltage sequence measurement functions (CMSQI and
• Supervision of limit transgression conditions and
VMSQI) and IEC 61850 generic communication I/O
rollover/overflow
functions (MVGAPC) are provided with measurement
• Possibility to define a warning and alarm with the
supervision functionality. All measured values can be
resolution of 0.1 hours
supervised with four settable limits: low-low limit, low
• Retain any saved accumulation value at a restart
limit, high limit and high-high limit. The measure value
• Possibilities for blocking and reset
expander block (RANGE_XP) has been introduced to
• Possibility for manual addition of accumulated time
enable translating the integer output signal from the
• Reporting of the accumulated time
measuring functions to 5 binary signals: below low-low
limit, below low limit, normal, above high limit or above
high-high limit. The output signals can be used as
conditions in the configurable logic or for alarming
purpose. 13. Metering
34 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
reactive energy values will happen in both forward and IEC13000239 V2 EN-US
reverse directions. These energy values are available as Figure 7. Local human-machine interface
output signals and also as pulse outputs. Integration of
energy values can be controlled by inputs (STARTACC
The LHMI of the IED contains the following elements:
and STOPACC) and EnaAcc setting and it can be reset to
• Graphical display capable of showing a user defined
initial values with RSTACC input.
single line diagram and provide an interface for
The maximum demand for active and reactive powers controlling switchgear.
are calculated for the set time interval tEnergy and • Navigation buttons and five user defined command
these values are updated every minute through output buttons to shortcuts in the HMI tree or simple
channels. The active and reactive maximum power commands.
demand values are calculated for both forward and • 15 user defined three-color LEDs.
reverse direction and these values can be reset with • Communication port for PCM600.
RSTDMD input.
The LHMI is used for setting, monitoring and controlling.
ABB 35
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Several protocols can be combined in the same IED. IEC 62439-3 Parallel Redundancy Protocol
GUID-A90FDBA7-D4D7-4CBD-9F05-13DCC9971779 v5
Redundant station bus communication according to IEC
IEC 61850-8-1 communication protocol M14787-3 v12
62439-3 Edition 1 and IEC 62439-3 Edition 2 parallel
IEC 61850 Ed.1 or Ed.2 can be chosen by a setting in redundancy protocol (PRP) are available as options when
PCM600. The IED is equipped with single or double ordering IEDs. Redundant station bus communication
optical Ethernet rear ports (order dependent) for IEC according to IEC 62439-3 uses both port AB and port CD
61850-8-1 station bus communication. The IEC 61850-8-1 on the OEM module.
communication is also possible from the electrical
Ethernet front port. IEC 61850-8-1 protocol allows
intelligent electrical devices (IEDs) from different
vendors to exchange information and simplifies system 17. Remote communication
engineering. IED-to-IED communication using GOOSE
and client-server communication over MMS are Analog and binary signal transfer to remote end M12449-6 v2
supported. Disturbance recording file (COMTRADE) Three analog and eight binary signals can be exchanged
uploading can be done over MMS or FTP. between two IEDs. This functionality is mainly used for
the line differential protection. However it can be used
IEC 61850-9-2LE communication protocol
GUID-C3AA21B4-730F-4327-943A-3C77102A80A0 v2
in other products as well. An IED can communicate with
Single optical Ethernet port communication standard up to 4 remote IEDs.
IEC 61850-9-2LE for process bus is provided. IEC
61850-9-2LE allows Non Conventional Instrument Binary signal transfer to remote end, 192 signals M13458-3 v4
Transformers (NCIT) with Merging Units (MU) or stand If the communication channel is used for transfer of
alone Meging Units to exchange information with the binary signals only, up to 192 binary signals can be
IED and simplifies SA engineering. exchanged between two IEDs. For example, this
functionality can be used to send information such as
LON communication protocol SEMOD120140-5 v2
status of primary switchgear apparatus or intertripping
Existing stations with ABB station bus LON can be signals to the remote IED. An IED can communicate with
extended with use of the optical LON interface. This up to 4 remote IEDs.
allows full SA functionality including peer-to-peer
messaging and cooperation between the IEDs. Line data communication module, short and medium
range LDCM SEMOD168481-4 v7
SPA communication protocol SEMOD120134-5 v1
The line data communication module (LDCM) is used for
A single glass or plastic port is provided for the ABB SPA communication between the IEDs situated at distances
protocol. This allows extensions of simple substation <60 km/37miles or from the IED to optical to electrical
automation systems but the main use is for Substation converter with G.703 or G.703E1 interface located on a
Monitoring Systems SMS. distances < 3 km/1.9 miles away. The LDCM module
sends and receives data, to and from another LDCM
IEC 60870-5-103 communication protocol SEMOD120137-5 v3 module. The IEEE/ANSI C37.94 standard format is used.
A single glass or plastic port is provided for the IEC
60870-5-103 standard. This allows design of simple This feature can be for example used in power stations
substation automation systems including equipment to exchange up to 192 binary signals (e.g. tripping,
from different vendors. Disturbance files uploading is signaling, alarming) between the generator and HV
provided. station in power plants
36 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
also be included in the disturbance recording and event- The galvanic X.21 line data communication module is
recording functions. This enables extensive monitoring used for connection to telecommunication equipment,
and evaluation of operation of the IED and for all for example leased telephone lines. The module
associated electrical circuits. supports 64 kbit/s data communication between IEDs.
The milli-ampere input module is used to interface This module includes a GPS receiver used for time
transducer signals in the –20 to +20 mA range from for synchronization. The GTM has one SMA contact for
example OLTC position, temperature or pressure connection to an antenna. It also includes an optical PPS
transducers. The module has six independent, ST-connector output.
galvanically separated channels.
pick-up value setting and a voltage dependent resistor, Figure 9. Case with rear cover and 19” rack mounting kit
is available in a single phase unit and a three phase unit.
Both are mounted on a 1/1 19 inch apparatus plate with
compression type terminals.
A
D
IEC06000182-2-en.vsd
IEC06000182 V2 EN-US
M15243-12 v7
B
C
IEC08000163-2-en.vsd
IEC08000163 V2 EN-US
38 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Case size A B C D E F G H J K
(mm)/
(inches)
6U, 1/2 x 19” 265.9/ 223.7/ 242.1/ 255.8/ 205.7/ 190.5/ 203.7/ - 228.6/ -
10.47 8.81 9.53 10.07 8.10 7.50 8.02 9.00
6U, 3/4 x 19” 265.9/ 336.0/ 242.1/ 255.8/ 318.0/ 190.5/ 316.0/ - 228.6/ -
10.47 13.23 9.53 10.07 12.52 7.50 12.4 9.00
6U, 1/1 x 19” 265.9/ 448.3/ 242.1/ 255.8/ 430.3/ 190.5/ 428.3/ 465.1/ 228.6/ 482.6/19.00
10.47 17.65 9.53 10.07 16.86 7.50 16.86 18.31 9.00
The H and K dimensions are defined by the 19” rack mounting kit.
Stator injection module SIM The REX061 coupling capacitor unit grounding point and
grounding brush of the rotor shaft should be properly
GUID-CF2B2004-97E9-4593-95CB-2E86A01EA779 v2
The SIM module is installed into the REX060 enclosure.
The SIM module generates a square wave voltage signal interconnected.
for injection into the stator circuit via the neutral point
Shunt resistor unit REX062
VT/NGT. The SIM module measures the voltage and GUID-90D6AF74-D9AC-49B8-B2CA-8A94E58ADEA5 v1
REX062 is typically used when injection is done via a
current from the injected signal and the IED
grounding transformer.
consecutively calculates the stator to earth impedance.
If the calculated impedance is lower than the preset COMBIFLEX Injection equipment
value an ALARM and/or TRIP output is set. GUID-BFA755D6-9CE7-4342-B4F9-4E4F525A554A v2
RXTTE4 and optional protective resistor are used to
inject fundamental frequency AC voltage into the rotor
Rotor injection module RIM
GUID-B2CA6C9E-2A24-483C-B9C2-47FFF2BBB283 v2 circuit.
The RIM module is installed into the REX060 enclosure.
The RIM module generates a square wave voltage signal
ABB 39
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
40 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Definitions
Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment
Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets
the specified requirements
Operative range The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to
perform its intended functions according to the specified requirements
Presumptions for Technical Data 6. Parameter SBase used by the tested function is set
GUID-1E949E38-E04D-4374-A086-912C25E9F93C v2
The technical data stated in this document are only valid equal to:
under the following circumstances: – √3 × IBase × UBase
7. The rated secondary quantities have the following
1. Main current transformers with 1 A or 2 A secondary values:
rating are wired to the IED 1 A rated CT inputs. – Rated secondary phase current Ir is either 1 A or 5 A
2. Main current transformer with 5 A secondary rating
depending on selected TRM.
are wired to the IED 5 A rated CT inputs.
– Rated secondary phase-to-phase voltage Ur is
3. CT and VT ratios in the IED are set in accordance with
within the range from 100 V to 120 V.
the associated main instrument transformers. Note
– Rated secondary power for three-phase system S r =
that for functions which measure an analogue signal
√3 × U r × Ir
which do not have corresponding primary quantity
the 1:1 ratio shall be set for the used analogue inputs 8. For operate and reset time testing, the default
on the IED. Example of such functions are: HZPDIF, setting values of the function are used if not explicitly
ROTIPHIZ and STTIPHIZ. stated otherwise.
4. Parameter IBase used by the tested function is set 9. During testing, signals with rated frequency have
equal to the rated CT primary current. been injected if not explicitly stated otherwise.
5. Parameter UBase used by the tested function is set
equal to the rated primary phase-to-phase voltage.
IP15765-1 v2
Energizing quantities, rated values and limits
ABB 41
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Analog inputs
M16988-1 v11 IP15842-1 v1
Table 7. TRM - Energizing quantities, rated values and limits for protection transformer
Description Value
Frequency
Current inputs
Rated current Ir 1 or 5 A
Note! All current and voltage data are specified as RMS values at rated frequency
42 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Table 8. TRM - Energizing quantities, rated values and limits for measuring transformer
Description Value
Frequency
Current inputs
Rated current Ir 1A 5A
Voltage inputs *)
Note! All current and voltage data are specified as RMS values at rated frequency
M6389-1 v4
Power consumption -
each mA-board £2W
each mA input £ 0.1 W
SEMOD55310-2 v8
Number of channels 1 or 2
ABB 43
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Auxiliary DC voltage
M12286-1 v4 IP15843-1 v3
Binary inputs 16 -
Power consumption
24/30 V, 50 mA max. 0.05 W/input -
48/60 V, 50 mA max. 0.1 W/input
110/125 V, 50 mA max. 0.2 W/input
220/250 V, 50 mA max. 0.4 W/input
220/250 V, 110 mA max. 0.5 W/input
44 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Maximum 176 binary input channels The stated operate time for functions
may be activated simultaneously with include the operating time for the
influencing factors within nominal binary inputs and outputs.
range.
M50609-2 v9
Table 13. BIM - Binary input module with enhanced pulse counting capabilities
Binary inputs 16 -
Power consumption
24/30 V max. 0.05 W/input -
48/60 V max. 0.1 W/input
110/125 V max. 0.2 W/input
220/250 V max. 0.4 W/input
* Note: For compliance with surge immunity a debounce filter time setting of 5 ms is required.
ABB 45
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Maximum 176 binary input channels The stated operate time for functions
may be activated simultaneously with include the operating time for the
influencing factors within nominal binary inputs and outputs.
range.
M12573-1 v8.1.1
Binary inputs 8 -
Power consumption -
24/30 V, 50 mA max. 0.05 W/input
48/60 V, 50 mA max. 0.1 W/input
110/125 V, 50 mA max. 0.2 W/input
220/250 V, 50 mA max. 0.4 W/input
220/250 V, 110 mA max. 0.5 W/input
46 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Maximum 176 binary input channels The stated operate time for functions
may be activated simultaneously with include the operating time for the
influencing factors within nominal binary inputs and outputs.
range.
M12318-1 v10
Table 15. IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and signal relays Fast signal relays (parallel
reed relay)
Binary outputs 10 2
0.2 s
1.0 s 30 A 0.4 A
10 A 0.4 A
Breaking capacity for AC, cos φ > 0.4 250 V/8.0 A 250 V/8.0 A
ABB 47
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Maximum 72 outputs may be activated The stated operate time for functions
simultaneously with influencing factors include the operating time for the
within nominal range. After 6 ms an binary inputs and outputs.
additional 24 outputs may be
activated. The activation time for the M12584-1 v10
Table 16. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-2)
Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay)
48 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Maximum 72 outputs may be activated The stated operate time for functions
simultaneously with influencing factors include the operating time for the
within nominal range. After 6 ms an binary inputs and outputs.
additional 24 outputs may be
activated. The activation time for the SEMOD175395-2 v9
Table 17. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs
Number of outputs 6 6
Test voltage across open contact, 1 min No galvanic separation No galvanic separation
Continuous 5A 5A
1.0 s 10 A 10 A
0.2 s 30 A 30 A
1.0 s 10 A 10 A
220 V/0.2 A
250 V/0.15 A
ABB 49
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Table 18. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs
Number of outputs 6
Continuous 8A
1.0 s 10 A
0.2 s 30 A
1.0 s 10 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
50 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
M12441-1 v10
Table 19. BOM - Binary output module contact data (reference standard: IEC 61810-2)
Binary outputs 24
Influencing factors
M16705-1 v15 IP15846-1 v1
ABB 51
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
100-250 V DC ±20%
Interruption
interval
0–50 ms No restart
Frequency dependence for distance protection operate value fr ±2.5 Hz for 50 Hz ±2.0%/Hz
fr ±3.0 Hz for 60 Hz
Harmonic frequency dependence (20% content) 2nd, 3rd and 5th harmonic of fr ±2.0%
Harmonic frequency dependence for distance protection (10% 2nd, 3rd and 5th harmonic of fr ±10.0%
content)
Harmonic frequency dependence for high impedance differential 2nd, 3rd and 5th harmonic of fr ±10.0%
protection (10% content)
Harmonic frequency dependence for overcurrent protection 2nd, 3rd and 5th harmonic of fr ±3.0%
52 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Class III
Ring wave immunity test, 100 kHz 2-4 kV IEC 61000-4-12, Class IV
Surge immunity test 2-4 kV, 1.2/50ms high energy IEC 60255-26, Zone A
1-2 kV, BOM and IRF outputs IEC 60255-26, Zone B
Conducted common mode immunity test 15 Hz-150 kHz IEC 61000-4-16, Class IV
Power frequency magnetic field test 1000 A/m, 3 s IEC 61000-4-8, Class V
100 A/m, cont.
Pulse magnetic field immunity test 1000 A/m IEC 61000–4–9, Class V
Damped oscillatory magnetic field test 100 A/m IEC 61000-4-10, Class V
1.4-2.7 GHz
ABB 53
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Change of temperature test Test Nb for 5 cycles at -25°C to +70°C IEC 60068-2-14
Damp heat test, steady state Test Ca for 10 days at +40°C and humidity 93% IEC 60068-2-78
Damp heat test, cyclic Test Db for 6 cycles at +25 to +55°C and humidity 93 to 95% (1 cycle IEC 60068-2-30
= 24 hours)
Test According to
Immunity EN 60255–26
Emissivity EN 60255–26
54 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Class III
Surge immunity test 1-2 kV, and 2-4 kV, 1.2/50 µs IEC 60255-26, Zone A
High energy
Radiated electromagnetic field disturbance test 20 V/m, 80-1000 MHz IEC 60255-26
1.4-2.7 GHz
Radiated electromagnetic field disturbance test 20 V/m, 80-1000 MHz IEEE/ANSI C37.90.2
Impulse voltage test 5.0 kV, 1.2/50 µs, 0.5 J IEC 60255-27
ABB 55
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Impulse voltage test 12.0 kV, 1.2/50 µs, 0.5 J IEC 60664-1
(connections to rotor)
56 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
GUID-9D1F44FC-896B-4907-9609-C32781CA1798 v3
Description Values
REX060
Front IP40
Panel mounted, front IP54
Rear, sides, top, bottom and connection terminals IP20
ABB 57
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
58 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
M13046-1 v14
*Note: Data obtained with single three-phase input current group. The operate and reset times for T2WPDIF/T3WPDIF are valid for an
static output from SOM.
**Note: Data obtained with two three-phase input current groups. The rated symmetrical currents are applied on both sides as pre- and
after-fault currents. The fault is performed by increasing one phase current to double on one side and decreasing same phase current to
zero on the other side.
ABB 59
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
M13062-1 v16.1.1
60 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Definite time delay Ph-Ph and (0.000-60.000) s ±0.2% or ±60 ms whichever is greater
Ph-E operation
ABB 61
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
GUID-6C2EF52A-8166-4A23-9861-38931682AA7D v7
Resistance determining the (0.01 - 5000.00) Pseudo continuous ramp: Ramp of shots:
load impedance area - forward ohm/p ±2.0% of set value ±5.0% of set value
Conditions: Conditions:
Tested at ArgLd = 30 degrees Tested at ArgLd = 30 degrees
Definite time delay to trip, Ph-E (0.000-60.000) s ±0.2% of set value or ±35 ms whichever is greater
and Ph-Ph operation
62 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
GUID-16656307-6B43-47B5-8817-48638FFB5999 v3
Table 42. Distance zones quad with high speed distance for series compensated networks ZMFCPDIS
ABB 63
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
SEMOD175144-2 v9
Typically 20 - 50 kΩ
Alarm time delay at Rf ~ 0 Ω and filter (0.00 - 600.00) s ±0.2% or ±2.00 s whichever is greater
length = 1 s
64 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
GUID-956187E5-A466-47BF-B671-F46548A5DF2E v3
Typically 10 kΩ
Alarm time delay at Rf ~ 0Ω and filter length (0.00 - 600.00) s ±0.2% or ± 2.00 s whichever is greater
=1s
GUID-E8104D00-3183-4F55-89F9-A74B14BFE6FE v4
Table 48. Underimpedance protection for generators and transformersZGVPDIS Technical data
Number of zones 3 -
Min. = 15 ms
Start time at 1.2 to 0.8 x set impedance -
Max. = 35 ms
ABB 65
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
66 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
M12342-1 v21
Independent time delay at 0 to 2 x Iset, step (0.000-60.000) s ±0.2% or ±35 ms whichever is greater
1-4
Minimum operate time for inverse curves , (0.000-60.000) s ±0.2% or ±35 ms whichever is greater
step 1-4
Inverse time characteristics, see table 163, 16 curve types See table 163, table 164 and table 165
table 164 and table 165
ABB 67
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
M12340-2 v8
68 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
M15223-1 v18
Operate current for directional release (1–100)% of IBase For RCA ±60 degrees:
±2.5% of Ir at I ≤ Ir
±2.5% of I at I > Ir
Minimum operate time for inverse curves, (0.000 - 60.000) s ±0.2% or ±35 ms whichever is greater
step 1-4
Inverse time characteristics, see Table 163, 16 curve types See Table 163, Table 164 and Table 165
Table 164 and Table 165
*Note: Operate time and reset time are only valid if harmonic blocking is turned off for a step.
ABB 69
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
GUID-E83AD807-8FE0-4244-A50E-86B9AF92469E v5
Inverse time characteristics, 16 curve types See table 163, table 164 and
see table 163, table 164 and table 165
table 165
70 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
SEMOD173350-2 v13
Table 54. Sensitive directional residual overcurrent and power protection SDEPSDE
Inverse characteristics, see 16 curve types See table "", table "" and table ""
table "", table "" and table ""
ABB 71
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
M13266-2 v9
Alarm level 1 and 2 (50–99)% of heat content ±2.0% of heat content trip
operate value
Reset level temperature (10–95)% of heat content trip ±2.0% of heat content trip
M12353-1 v13
Time delay for re-trip at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
Time delay for back-up trip at 0 to 2 x Iset (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
Time delay for back-up trip at multi-phase (0.000-60.000) s ±0.2% or ±20 ms whichever is greater
start at 0 to 2 x Iset
Additional time delay for a second back-up trip (0.000-60.000) s ±0.2% or ±20 ms whichever is greater
at 0 to 2 x Iset
Time delay for alarm for faulty circuit breaker (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
72 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
M13279-1 v9
S r = 1.732 × U r × I r
Independent time delay to operate for Step (0.01-6000.00) s ±0.2% or ±40 ms whichever is greater
1 and Step 2 at 2 to 0.5 x Sr and k=0.000
SEMOD175159-2 v8
Independent time delay to operate for Step (0.01-6000.00) s ±0.2% or ±40 ms whichever is greater
1 and Step 2 at 0.5 to 2 x Sr and k=0.000
*) To achieve this accuracy for reverse power protection it is also recommended to apply settings k=0.990 and Mode=PosSeq. These
settings will help to minimize the overall measurement error ensuring the best accuracy for this application.
ABB 73
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
GUID-E5718F80-556D-4852-A8F2-90E0F578D763 v9
Table 60. Negative sequence time overcurrent protection for machines NS2PTOC
I 22t = K
Reset time, inverse characteristic, Reset Multiplier = 0.01-20.00 ±5.0% or ±40 ms whichever is greater
step 1 - 2
I 22t = K
Minimum operate time for inverse (0.000-60.000) s ±0.2% or ±35 ms whichever is greater
time characteristic, step 1 - 2
Maximum trip delay at 0.5 x Iset to (0.00-6000.00) s ±0.2% or ±35 ms whichever is greater
2 x Iset, step 1 - 2
Independent time delay at 0.5 x Iset (0.00-6000.00) s ±0.2% or ±35 ms whichever is greater
to 2 x Iset, step 1 - 2
Independent time delay for Alarm (0.00-6000.00) s ±0.2% or ±35 ms whichever is greater
at 0.5 x Iset to 2 x Iset
74 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
GUID-9B1C0C10-8AF9-4D9E-8076-B3E1C238D29A v7
Definite time delay, undervoltage, at 1.2 x Uset to 0.8 x Uset (0.000-60.000) s ±0.2% or ±35 ms whichever is
greater
Definite time delay, overvoltage, at 0.8 x Uset to 1.2 x Uset (0.000-60.000) s ±0.2% or ±35 ms whichever is
greater
GUID-3C80D7DB-2ECA-4429-B1BA-2977C7ECE644 v4
Max. = 170 ms
ABB 75
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
GUID-A1CB5B4F-768E-4B1B-937E-B91EC3EFA2CC v3
76 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Inverse time characteristics for step 1 and step 2, see - See table 167
table 167
Definite time delay, step 1 at 1.2 to 0 x Uset (0.00-6000.00) s ±0.2% or ±40ms whichever is
greater
Definite time delay, step 2 at 1.2 to 0 x Uset (0.000-60.000) s ±0.2% or ±40ms whichever is
greater
ABB 77
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
M13304-1 v12
Inverse time characteristics for steps 1 and 2, see - See table 166
table 166
Definite time delay, low step (step 1) at 0 to 1.2 x Uset (0.00 - 6000.00) s ±0.2% or ±45 ms whichever is
greater
Definite time delay, high step (step 2) at 0 to 1.2 x Uset (0.000-60.000) s ±0.2% or ±45 ms whichever is
greater
78 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
M13317-2 v12
Inverse time characteristics for low and high step, see - See table 168
table 168
Definite time delay low step (step 1) at 0 to 1.2 x Uset (0.00–6000.00) s ± 0.2% or ± 45 ms whichever is
greater
Definite time delay high step (step 2) at 0 to 1.2 x Uset (0.000–60.000) s ± 0.2% or ± 45 ms whichever is
greater
Curve type IEEE or customer defined ±5.0 % or ±45 ms, whichever is greater
(0.18 × k )
IEEE : t =
( M - 1) 2
where M = (E/f)/(Ur/fr)
Minimum time delay for inverse (0.000–60.000) s ±1.0% or ±45 ms, whichever is greater
function
Maximum time delay for inverse (0.00–9000.00) s ±1.0% or ±45 ms, whichever is greater
function
ABB 79
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
SEMOD166919-2 v6
Filter characteristic: -
Fundamental Reject third harmonic by 1–40
Third harmonic Reject fundamental harmonic
by 1–40
80 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Operate time, definite time function at fset + (0.000-60.000)s ±0.2% or ±100 ms whichever is greater
0.02 Hz to fset - 0.02 Hz
Reset time, definite time function at fset - 0.02 (0.000-60.000)s ±0.2% or ±120 ms whichever is greater
Hz to fset + 0.02 Hz
Exponent
é U - UMin ù
t=ê × ( tMax - tMin ) + tMin
ë UNom - UMin úû
EQUATION1182 V1 EN-US (Equation 3)
U=Umeasured
M14964-1 v12
Operate value, start function at symmetrical three-phase voltage (35.00-90.00) Hz ±2.0 mHz
Min. = 65 ms
fn = 60 Hz
Max. = 80 ms
Operate time, definite time function at fset -0.02 Hz to fset +0.02 Hz (0.000-60.000)s ±0.2% ±100 ms
whichever is greater
Reset time, definite time function at fset +0.02 Hz to fset -0.02 Hz (0.000-60.000)s ±0.2% ±120 ms,
whichever is greater
ABB 81
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
M14976-1 v10
Definite time delay for frequency gradient trip (0.000-60.000) s ±0.2% or ±120 ms whichever is
greater
Operate value, frequency high limit level at (35.00 – 90.00) Hz ±2.0 mHz
symmetrical three phase voltage
Operate value, voltage high and low limit (0.0 – 200.0)% of UBase ±0.5% of Ur at U ≤ Ur
for voltage band limit check ±0.5% of U at U > Ur
Operate value, current start level (5.0 – 100.0)% of IBase ±1.0% of Ir or 0.01 A at I≤Ir
Independent time delay for the continuous (0.0 – 6000.0) s ±0.2% or ±200 ms whichever is greater
time limit at fset+0.02 Hz to fset-0.02 Hz
Independent time delay for the (10.0 – 90000.0) s ±0.2% or ±200 ms whichever is greater
accumulation time limit at fset+0.02 Hz to
fset-0.02 Hz
82 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Independent time delay, overcurrent at 0 to 2 x Iset, step 1 - 2 (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is
greater
Independent time delay, undercurrent at 2 to 0 x Iset, step 1 - (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is
2 greater
Overcurrent (non-directional):
Undercurrent:
Overcurrent:
Inverse time characteristics, see table 163, 164 and table 165 16 curve types See table 163, 164 and table
165
Overcurrent:
Minimum operate time for inverse curves, step 1 - 2 (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is
greater
Voltage level where voltage memory takes over (0.0 - 5.0)% of UBase ±0.5% of Ur
ABB 83
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Independent time delay, overvoltage at 0.8 to 1.2 x Uset, step (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is
1-2 greater
Independent time delay, undervoltage at 1.2 to 0.8 x Uset, (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is
step 1 - 2 greater
Overvoltage:
Undervoltage:
Overvoltage:
Inverse time characteristics, see table 166 4 curve types See table 166
Undervoltage:
Inverse time characteristics, see table 167 3 curve types See table 167
High and low voltage limit, voltage dependent operation, (1.0 - 200.0)% of UBase ±1.0% of Ur at U ≤ Ur
step 1 - 2 ±1.0% of U at U > Ur
Overcurrent:
Undercurrent:
Overvoltage:
Undervoltage:
84 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
SEMOD175176-2 v5
Table 75. Rotor earth fault protection based on General current and voltage protection (CVGAPC) and RXTTE4
ABB 85
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
GUID-7EA9731A-8D56-4689-9072-D72D9CDFD795 v7
Max. = 30 ms
Max. = 30 ms
Independent time delay to operate at 0 to 2 x Iset (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is
greater
Inverse time characteristics, 13 curve types See tables 163 and 164
see tables 163 and 164
Minimum operate time for inverse time characteristics (0.00 - 60.00) s ±0.2% or ±35 ms whichever is
greater
High voltage limit, voltage dependent operation (30.0 - 100.0)% of UBase ±1.0% of Ur
Max. = 30 ms
Max. = 30 ms
Independent time delay to operate, undervoltage at 2 to 0 x (0.00 - 6000.00) s ±0.2% or ±35 ms whichever is
Uset greater
Overcurrent: -
Critical impulse time 10 ms typically at 0 to 2 x Iset
Impulse margin time 15 ms typically
Undervoltage: -
Critical impulse time 10ms typically at 2 to 0 x Uset
Impulse margin time 15 ms typically
86 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
ABB 87
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
GUID-E2EA8017-BB4B-48B0-BEDA-E71FEE353774 v4
88 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of UBase ±0.5% of Ur at U ≤ Ur
±0.5% of U at U > Ur
Frequency difference limit between bus and line for synchrocheck (0.003-1.000) Hz ±2.5 mHz
Phase angle difference limit between bus and line for synchrocheck (5.0-90.0) degrees ±2.0 degrees
Voltage difference limit between bus and line for synchronizing and (0.02-0.5) p.u ±0.5% of Ur
synchrocheck
Time delay output for synchrocheck when angle difference between (0.000-60.000) s ±0.2% or ±35 ms whichever is
bus and line jumps from “PhaseDiff” + 2 degrees to “PhaseDiff” - 2 greater
degrees
tMaxSynch, which resets synchronizing function if no close has been (0.000-6000.00) s ±0.2% or ±35 ms whichever is
made before set time greater
Time delay for energizing check when voltage jumps from 0 to 90% (0.000-60.000) s ±0.2% or ±100 ms whichever is
of Urated greater
Operate time for energizing function when voltage jumps from 0 to Min. = 70 ms –
90% of Urated Max. = 90 ms
ABB 89
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
SEMOD175215-2 v12
Time delay for lower command when fast step down mode is (1.0–100.0) s -
activated
Time delay (long) for automatic control commands (3–1000) s ±0.2% or ±600 ms
whichever is greater
Time delay (short) for automatic control commands (1–1000) s ±0.2% or ±600 ms
whichever is greater
Duration time for the reverse action block signal (30–6000) s ±0.2% or ±600 ms
whichever is greater
Level for number of counted raise/lower within one hour (0–30) operations/hour -
Alarm level of active power in forward and reverse direction at (-9999.99–9999.99) MW ±1.0% of Sr
(10-200)% of Sr and (85-120)% of UBase
Alarm level of reactive power in forward and reverse direction at (-9999.99–9999.99) MVAr ±1.0% of Sr
(10-200)% of Sr and (85-120)% of UBase
Time delay for alarms from power supervision (1–6000) s ±0.2% or ±600 ms
whichever is greater
90 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Time after position change before the value is accepted (1–60) s ±0.2% or ±200 ms
whichever is greater
ABB 91
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Logic M12380-1 v9
3 ms 8 ms 100 ms
SMPPTRC 12 - -
GUID-3AB1EE95-51BF-4CC4-99BD-F4ECDAACB75A v1
3 ms 8 ms 100 ms
TMAGAPC 6 6 -
GUID-A05AF26F-DC98-4E62-B96B-E75D19F20767 v1
3 ms 8 ms 100 ms
ALMCALH - - 5
GUID-70B7357D-F467-4CF5-9F73-641A82D334F5 v1
3 ms 8 ms 100 ms
WRNCALH - - 5
GUID-EAA43288-01A5-49CF-BF5B-9ABF6DC27D85 v1
3 ms 8 ms 100 ms
INDCALH - 5 -
GUID-D1179280-1D99-4A66-91AC-B7343DBA9F23 v1
3 ms 8 ms 100 ms
AND 60 60 160
92 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
GUID-45DF373F-DC39-4E1B-B45B-6B454E8E0E50 v1
3 ms 8 ms 100 ms
GATE 10 10 20
GUID-0EC4192A-EF03-47C0-AEC1-09B68B411A98 v1
3 ms 8 ms 100 ms
INV 90 90 240
GUID-B2E6F510-8766-4381-9618-CE02ED71FFB6 v1
3 ms 8 ms 100 ms
LLD 10 10 20
GUID-35A795D7-A6BD-4669-A023-43C497DBFB01 v1
3 ms 8 ms 100 ms
OR 60 60 160
GUID-E05E5FB1-23E7-4816-84F2-1FBFFDFF2B43 v1
3 ms 8 ms 100 ms
3 ms 8 ms 100 ms
RSMEMORY 10 10 20
GUID-7A0F4327-CA83-4FB0-AB28-7C5F17AE6354 v1
3 ms 8 ms 100 ms
SRMEMORY 10 10 20
GUID-C6C98FE0-F559-45EE-B853-464516775417 v1
3 ms 8 ms 100 ms
ABB 93
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
GUID-0B07F78C-10BD-4070-AFF0-6EE36454AA03 v1
3 ms 8 ms 100 ms
XOR 10 10 20
GUID-23D4121A-4C9A-4072-BBE3-6DB076EDAB79 v1
3 ms 8 ms 100 ms
ANDQT - 20 100
GUID-27DF23C0-A0B2-4BB0-80B5-FC7B7F7FE448 v1
3 ms 8 ms 100 ms
INDCOMBSPQT - 10 10
GUID-C1E61AE5-22CF-4198-97CF-8C8043EE96D2 v1
3 ms 8 ms 100 ms
INDEXTSPQT - 10 10
GUID-77FEBE9B-0882-4E85-8B1A-7671807BFC02 v1
3 ms 8 ms 100 ms
INVALIDQT - 6 6
GUID-F25B94C6-9CC9-48A0-A7A3-47627D2B56E2 v1
3 ms 8 ms 100 ms
INVERTERQT - 20 100
GUID-88B27B3C-26D2-47AF-9878-CC19018171B1 v1
3 ms 8 ms 100 ms
ORQT - 20 100
GUID-61263951-53A8-4113-82B5-3DB3BF0D9449 v1
3 ms 8 ms 100 ms
94 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
GUID-94C803B4-6C5A-4072-AB5C-20DDE98C9A70 v1
3 ms 8 ms 100 ms
RSMEMORYQT - 10 30
GUID-341562FB-6149-495B-8A63-200DF16A5590 v1
3 ms 8 ms 100 ms
SRMEMORYQT - 10 30
GUID-B6231B97-05ED-40E8-B735-1E1A50FDB85F v1
3 ms 8 ms 100 ms
3 ms 8 ms 100 ms
XORQT - 10 30
GUID-19810098-1820-4765-8F0B-7D585FFC0C78 v6
3 ms 8 ms 100 ms
AND 40 40 100
GATE - - 49
INV 40 40 100
LLD - - 49
OR 40 40 100
PULSETIMER 5 5 49
SLGAPC 10 10 54
SRMEMORY - - 110
TIMERSET - - 49
VSGAPC 10 10 110
XOR - - 49
GUID-65A2876A-F779-41C4-ACD7-7662D1E7F1F2 v1
3 ms 8 ms 100 ms
B16I 6 4 8
ABB 95
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
GUID-3820F464-D296-4CAD-8491-F3F997359D79 v1
3 ms 8 ms 100 ms
BTIGAPC 4 4 8
GUID-B45901F4-B163-4696-8220-7F8CAC84D793 v1
3 ms 8 ms 100 ms
IB16 6 4 8
GUID-A339BBA3-8FD0-429D-BB49-809EAC4D53B0 v1
3 ms 8 ms 100 ms
ITBGAPC 4 4 8
GUID-44D82B7D-280F-4F11-B017-784E3047AD0F v3
3 ms 8 ms 100 ms
TIGAPC - 30 -
GUID-B258726E-1129-47C9-94F9-BE634A2085FA v3
Table 116. Elapsed time integrator with limit transgression and overflow supervision TEIGAPC
96 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
3 ms 8 ms 100 ms
TEIGAPC 4 4 4
GUID-F5E124E3-0B85-41AC-9830-A2362FD289F2 v1
Time limit for alarm supervision, tAlarm (0 - 99999.9) hours ±0.1% of set value
Time limit for warning supervision, (0 - 99999.9) hours ±0.1% of set value
tWarning
ABB 97
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
98 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v5
ABB 99
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
M12760-1 v9.1.1
Maximum number of events in the Event list 1000, first in - first out -
Maximum total recording time (3.4 s recording time and maximum number 340 seconds (100 recordings) -
of channels, typical value) at 50 Hz, 280 seconds (80
recordings) at 60 Hz
Time delay for pressure alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Reset time delay for pressure alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for pressure lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Reset time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for temperature lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater
100 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v6
Time delay for oil alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Reset time delay for oil alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for oil lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Reset time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for temperature lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater
GUID-B6799420-D726-460E-B02F-C7D4F1937432 v9
Independent time delay for spring charging (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater
time alarm
Independent time delay for gas pressure (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater
alarm
Independent time delay for gas pressure (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater
lockout
Function Value
Resolution 1 ms
Function Value
Buffer capacity Maximum number of indications presented for single disturbance 352
ABB 101
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
M12702-1 v4
Function Value
Resolution 1 ms
Function Value
Function Value
Maximum total recording time (3.4 s recording time and maximum 340 seconds (100 recordings) at 50 Hz
number of channels, typical value) 280 seconds (80 recordings) at 60 Hz
GUID-C43B8654-60FE-4E20-8328-754C238F4AD0 v2
102 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Metering M13404-2 v5
Energy metering kWh Export/Import, kvarh Input from MMXU. No extra error at steady load
Export/Import
ABB 103
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Function Value
Protocol DNP3.0
Function Value
Function Value
Protocol LON
Function Value
Function Value
104 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
SEMOD117441-2 v5
Insulation 1 kV
Table 147. IEC 62439-3 Edition 1 and Edition 2 parallel redundancy protocol
Function Value
ABB 105
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
M12756-1 v12
Remote communication
Type of LDCM Short range (SR) Medium range (MR) Long range (LR)
Multi-mode fiber
glass 50/125 µm
106 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Hardware
IED
M11778-1 v4 SEMOD53385-1 v1
Table 150. Water and dust protection level according to IEC 60529
Electrical safety
GUID-1CF5B10A-CF8B-407D-8D87-F4B48B43C2B2 v1 GUID-2825B541-DD31-4DAF-B5B3-97555F81A1C2 v1
Pollution degree 2 (normally only non-conductive pollution occurs except that occasionally a temporary conductivity caused by
condensation is to be expected)
Connection system
SEMOD53376-2 v6 SEMOD53371-1 v1
Terminal blocks suitable for ring lug terminals 250 V AC, 20 A 4 mm2 (AWG12)
M12583-1 v5
Terminal blocks suitable for ring lug terminals 300 V AC 3 mm2 (AWG14)
ABB 107
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
108 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Specifications Values
Weight 8.0 kg
Pollution degree 2
GUID-CDBAEE7B-3BCE-4401-B2DA-BF572CFF9DAE v3
Specifications Values
Weight 4.8 kg
Burden, static excitation system X1:1 to X1:7 < 0.5 VA at 100 V external disturbance
Burden, static excitation system X1:1 or X1:7 to 0 V < 1.0 VA at 100 V external disturbance
Burden, brushless excitation system X1:1 and X1:7 to 0 V < 1.5 VA at 100 V external disturbance
Pollution degree 2
ABB 109
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
GUID-E7B9192F-ABD5-4395-94F2-ED0B2F0DFEB7 v3
Specifications Values
Weight 4.5 kg
Pollution degree 2
110 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Data Value
Function Value
Time tagging error with synchronization once/min (minute pulse synchronization), events and sampled ± 1.0 ms typically
measurement values
Time tagging error with SNTP synchronization, sampled measurement values ± 1.0 ms typically
SEMOD55660-2 v3
Function Value
Accuracy +/-1μs
ABB 111
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
SEMOD141136-2 v8
Electrical connector:
Amplitude modulated
– low level 1-3 Vpp
– high level 3 x low level, max 9 Vpp
Accuracy +/-10μs for IRIG-B 00x and +/-100μs for IRIG-B 12x
Optical connector:
112 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Reset characteristic:
tr
t = ×k
(I 2
-1 )
EQUATION1250-SMALL V1 EN-US
I = Imeasured/Iset
ABB 113
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
I = Imeasured/Iset
TR
t = ×k
(I PR
- CR )
EQUATION1253-SMALL V1 EN-US
I = Imeasured/Iset
114 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
I = Imeasured/Iset
æ I ö
t = 5.8 - ç 1.35 × In ÷
è k ø
EQUATION1138-SMALL V1 EN-US
I = Imeasured/Iset
SEMOD116978-2 v9
U> = Uset
U = Umeasured
k ⋅ 480
t = + 0.035
2.0
32 ⋅ U − U > − 0.5
U >
EQUATION1437-SMALL V2 EN-US
k ⋅ 480
t = + 0.035
3.0
32 ⋅ U − U > − 0.5
U >
EQUATION1438-SMALL V2 EN-US
ABB 115
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
U< = Uset
U = Umeasured
k × 480
t = + 0.055
2.0
æ 32 × U < -U - 0.5 ö
ç ÷
è U < ø
EQUATION1432-SMALL V1 EN-US
U< = Uset
U = Umeasured
U< = Uset
U = Umeasured
116 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
U> = Uset
U = Umeasured
ABB 117
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management.
Please refer to the available functions table for included application functions.
PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.
To obtain the complete ordering code, please combine code from the selection tables, as given in the example below.
The selected qty of each table must be filled in, if no selection is possible the code is 0
Example of a complete code: REG670*2.1-F00X00 - A00002262300000 - B0000040200000000011020111 - C4600262200340004440022311 - D22322100 -
E66312 - F9 - S6 - G532 - H12000010044 - K00000000 - L11 - M120 - P01 - B1X0 - AC - MB - B - A3X0 - D1D1ARGN1N1XXXXXXX -AAFXXX - AX
Impedance protection -
B 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 -
Current protection -
C 00 0 0 00 0 0 0 -
Remote end serial communication - Serial communication unit for station communication
-
Product REG670*
Software version 2.1
Configuration alternatives
REG670 Generator protection F00
REG670 61850-9-2LE Generator protection N00
Selection:
ACT configuration
No ACT configuration downloaded X00
118 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Positio 1 2 3 4 5 6 7 8 9 10 11 12 13 14
n
A 0 0 0 0 0 0 0 0 0
Po 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
siti
on
B 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Pos 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
itio
n
C 00 0 0 00 0 0 0
ABB 119
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Position 1 2 3 4 5 6 7 8
D 0 0
Position 1 2 3 4
E
Position 1
F
120 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Position 1
S
Position 1 2 3
G
Position 1 2 3 4 5 6 7 8 9 10 11
H 0 0 0 0 0 0 0
Position 1 2 3 4 5 6 7 8
K 0 0 0 0 0 0 0 0
Position 1 2
L
Position 1 2
M 0
ABB 121
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Positio 1 2 3 4 5 6 7 8 9 10 11 12 13
n
P 0 0 0 0 0 0 0 0 0 0 0
Function Function Ordering no Position Available qty Selected Notes and rules
identificatio qty
n
Process Bus communication IEC 61850-9-2 1MRK005930-TA 1 0 if F00 is Note: REG670
selected, 6 if customized qty = 0,
N00 is REG670 61850-9-2 qty
selected =6
IEC 62439-3 parallel redundancy protocol PRP 1MRK002924-YB 2 0-1 Note: Not valid in
REG670 61850-9-2LE
product
Note: Requires 2–
channel OEM
First local HMI user dialogue language Selection Notes and Rules
HMI language, English IEC B1
Additional HMI language
No additional HMI language X0
HMI language, English US A12
Selected
Mounting details with IP40 of protection from the front Selection Notes and Rules
No mounting kit included X
19" rack mounting kit for 1/2 x 19" case of 2xRHGS6 or RHGS12 A
19" rack mounting kit for 3/4 x 19" case or 3xRGHS6 B
19" rack mounting kit for 1/1 x 19" case C
Wall mounting kit D Note: Wall mounting not
recommended with
communication modules with
fiber connection (SLM, OEM,
LDCM)
Flush mounting kit E
Flush mounting kit + IP54 mounting seal F
Selected
Connection type for Power supply module Selection Notes and Rules
Compression terminals M
Ringlug terminals N
Connection type for Input/Output modules
Compression terminals P
Ringlug terminals R
Selected
122 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
ABB 123
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
124 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
When ordering I/O modules, observe the maximum quantities according to the table below
Note: Standard order of location for I/O modules is BIM-BOM-SOM-IOM-MIM from left to right as seen from the rear side of the IED, but
can also be freely placed.
Note: The maximum quantity of I/O modules depends on the type of connection terminals.
Case sizes BIM IOM BOM/ MIM Maximum in case
SOM
1/1 x 19”, one (1) TRM 14 6 4 4 14 cards, including a combination of four cards of type BOM, SOM and MIM
1/1 x 19”, two (2) TRM 11 6 4 4 11 cards, including a combination of four cards of type BOM, SOM and MIM
3/4 x 19”, one (1) TRM 8 6 4 4 8 cards, including a combination of four cards of type BOM, SOM and maximun oen
MIM
3/4 x 19”, two (2) TRM 5 5 4 4 5 cards, including a combination of four cards of type BOM, SOM and maximun oen
MIM
1/2 x 19”, one (1) TRM 3 3 3 1 3 cards
ABB 125
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
X41
X51
X61
X71
X81
X91
X101
X111
X121
X131
X141
X151
X161
view) rack, 8 in 3/4 rack with 1 TRM, 5
in 3/4 rack with 2 TRM, 11 in 1/1
1/2 Case with 1 TRM █ █ █
rack with 2 TRM and 14 in 1/1
3/4 Case with 1 TRM █ █ █ █ █ █ █ █ rack with 1 TRM
3/4 Case with 2 TRM █ █ █ █ █
1/1 Case with 1 TRM █ █ █ █ █ █ █ █ █ █ █ █ █ █
1/1 Case with 2 TRM █ █ █ █ █ █ █ █ █ █ █
No board in slot X X X X X X X X X X X X X X
Binary output module A A A A A A A A A A A A A A
24 output relays (BOM)
BIM 16 inputs, RL24-30 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1
VDC, 50 mA
BIM 16 inputs, RL48-60 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1
VDC, 50 mA
BIM 16 inputs, D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1
RL110-125 VDC, 50 mA
BIM 16 inputs, E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1
RL220-250 VDC, 50 mA
BIM 16 inputs, 220-250 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2
VDC, 120mA
BIMp 16 inputs, F F F F F F F F F F F F F F
RL24-30 VDC, 30 mA,
for pulse counting
BIMp 16 inputs, G G G G G G G G G G G G G G
RL48-60 VDC, 30 mA,
for pulse counting
BIMp 16 inputs, H H H H H H H H H H H H H H
RL110-125 VDC, 30 mA,
for pulse counting
BIM 16 inputs, K K K K K K K K K K K K K K
RL220-250 VDC, 30 mA,
for pulse counting
IOM 8 inputs, 10+2 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1
output, RL24-30 VDC,
50 mA
IOM 8 inputs, 10+2 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1
output, RL48-60 VDC,
50 mA
IOM 8 inputs, 10+2 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1 N1
output, RL110-125 VDC,
50 mA
IOM 8 inputs, 10+2 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P1
output, RL220-250
VDC, 50 mA
IOM 8 inputs 10+2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2 P2
output relays, 220-250
VDC, 110mA
IOM with MOV 8 inputs, U U U U U U U U U U U U U U
10-2 output, 24-30 VDC,
30 mA
IOM with MOV 8 inputs, V V V V V V V V V V V V V V
10-2 output, 48-60
VDC, 30 mA
IOM with MOV 8 inputs, W W W W W W W W W W W W W W
10-2 output, 110-125
VDC, 30 mA
IOM with MOV 8 inputs, Y Y Y Y Y Y Y Y Y Y Y Y Y Y
10-2 output, 220-250
VDC, 30 mA
mA input module MIM R R R R R R R R R R R R R R
6 channels
126 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Remote end communication, DNP serial comm. and time synchronization Selection Notes and Rules
modules
Slot position (rear view) Note: The maximum number
X312
X313
X302
X303
X322
X323
and type of LDCM modules
supported depend on the total
amount of modules (BIM, BOM,
LDCM, OEM, GTM, SLM, RS485,
IRIG-B) in the IED.
Available slots in 1/2, 3/4 and 1/1 case with 1TRM █ █ █ █ Note: Max 2 LDCM in 1/2 case
Available slots in 3/4 and 1/1 case with 2 TRM █ █ █ █ █ █
No remote communication board included X X X X X X
Optical short range LDCM A A A A A A Note: Max 4 LDCM (same or
different type) can be selected
Optical medium range, LDCM 1310 nm B B B B B B
in configuration F00. Max 2
Optical long range, LDCM 1550 nm C C C C C C LDCM in configuration N00 (9–
Galvanic X21 line data communication module E E E E E E 2)
Rule: Always place LDCM
modules on the same board to
support redundant
communication; in P30:2 and
P30:3, P31:2 and P31:3 or P32:2
and P32:3
IRIG-B Time synchronization module F F F F F F
Galvanic RS485 communication module G G G G G G
GPS time synchronization module S S S S
Selected
Serial communication unit for station communication Selection Notes and Rules
Slot position (rear view)
X301
X311
ABB 127
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management.
Please refer to the available functions table for included application functions.
PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.
To obtain the complete ordering code, please combine code from the tables, as given in the example below.
Example code: REG670 *2.1-A30X00- A02H02-B1A3-AC-MB-B-A3X0-DAB1RGN1N1XXXXXXX-AXFXXX-AX. Using the code of each position #1-13 specified as
REG670*1-2 2-3 3 3 3 3 3 3 3 3 3 3 3 3-4 4-5-6-7 8-9-10 10 1010-11 11 11 11 11 11 11 11 11 11 11-12 12 12 12 12 12-13 13
# 1 - 2 - 3 - 4 - 5 6 - 7 8 - 9 -
REG670* - - - - - - -
10 - 11 - 12 - 13
- . -
Position
SOFTWARE #1 Notes and Rules
Version number
Version no 2.1
Selection for position #1.
128 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Mounting details with IP40 of protection from the front #6 Notes and Rules
No mounting kit included X
19" rack mounting kit for 1/2 x 19" case of 2xRHGS6 or RHGS12 A Note: Only for A20
19" rack mounting kit for 1/1 x 19" case C Note: Only for B30 and C30
Wall mounting kit D Note: Wall mounting not
recommended with
communication modules with
fiber connection (SLM, OEM,
LDCM)
Flush mounting kit E
Flush mounting kit + IP54 mounting seal F
Selection for position #6.
ABB 129
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
130 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Binary input/output module, mA and time synchronization #11 Notes and Rules
boards.
Make BIM with 50 mA inrush current the primary choice. BIM with 50 mA inrush current fulfills additional standards. As a consequence the EMC
withstand capability is further increased.
BIM with 30 mA inrush current is still available.
For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used.
Note: 1BIM and 1 BOM included.
Slot position (rear view) Note: Max 3 positions in 1/2
X31
X41
X51
X61
X71
X81
X91
X101
X111
X121
X131
rack and 11 in 1/1 rack with 2
TRM
1/2 Case with 1 TRM █ █ █ Note: Only for A20
1/1 Case with 2 TRM █ █ █ █ █ █ █ █ █ █ █ Note: Only for B30/C30
No board in slot X X X X X X X X X X X
Binary output module 24 output relays (BOM) A A A A A A A A A A Note: Maximum 4 (BOM+SOM
+MIM) boards.
BIM 16 inputs, RL24-30 VDC, 50 mA B B1 B1 B1 B1 B1 B1 B1 B1 B1
1
BIM 16 inputs, RL48-60 VDC, 50 mA C C1 C1 C1 C1 C1 C1 C1 C1 C1
1
BIM 16 inputs, RL110-125 VDC, 50 mA D D1 D1 D1 D1 D1 D1 D1 D1 D1
1
BIM 16 inputs, RL220-250 VDC, 50 mA E E1 E1 E1 E1 E1 E1 E1 E1 E1
1
BIM 16 inputs, 220-250 VDC, 120mA E E2 E2 E2 E2 E2 E2 E2 E2 E2
2
BIMp 16 inputs, RL24-30 VDC, 30 mA, for pulse counting F F F F F F F F F
BIMp 16 inputs, RL48-60 VDC, 30 mA, for pulse counting G G G G G G G G G
BIMp 16 inputs, RL110-125 VDC, 30 mA, for pulse counting H H H H H H H H H
BIM 16 inputs, RL220-250 VDC, 30 mA, for pulse counting K K K K K K K K K
IOM 8 inputs, 10+2 output, RL24-30 VDC, 50 mA L1 L1 L1 L1 L1 L1 L1 L1 L1
IOM 8 inputs, 10+2 output, RL48-60 VDC, 50 mA M M M M M M M M M
1 1 1 1 1 1 1 1 1
IOM 8 inputs, 10+2 output, RL110-125 VDC, 50 mA N1 N1 N1 N1 N1 N1 N1 N1 N1
IOM 8 inputs, 10+2 output, RL220-250 VDC, 50 mA P1 P1 P1 P1 P1 P1 P1 P1 P1
IOM 8 inputs 10+2 output relays, 220-250 VDC, 110mA P2 P2 P2 P2 P2 P2 P2 P2 P2
IOM with MOV 8 inputs, 10-2 output, 24-30 VDC, 30 mA U U U U U U U U U
IOM with MOV 8 inputs, 10-2 output, 48-60 VDC, 30 mA V V V V V V V V V
IOM with MOV 8 inputs, 10-2 output, 110-125 VDC, 30 mA W W W W W W W W W
IOM with MOV 8 inputs, 10-2 output, 220-250 VDC, 30 mA Y Y Y Y Y Y Y Y Y
mA input module MIM 6 channels R R R R R R R R R Note: MIM not in A20, Maximum
1 MIM board in 1/2 case.
SOM Static output module, 12 outputs, 48-60 VDC T1 T1 T1 T1 T1 T1 T1 T1 T1 Note: SOM must not be placed
in the following positions: 1/2
SOM static outputs module, 12 outputs, 110-250 VDC T2 T2 T2 T2 T2 T2 T2 T2 T2
case slot X51, 1/1 case 2 TRM
slot X131
Selection for position #11.
ABB 131
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Remote end communication, DNP serial comm. and time synchronization #12 Notes and Rules
modules
Slot position (rear view) Note: The maximum number
X312
X313
X302
X303
X322
X323
and type of LDCM modules
supported depend on the total
amount of modules (BIM, BOM,
LDCM, OEM, GTM, SLM, RS485,
IRIG-B) in the IED.
Available slots in 1/2 case with 1TRM █ █ █ █ Note: Max 2 LDCM in 1/2 case
Available slots in 1/1 case with 2 TRM █ █ █ █ █ █
No remote communication board included X X X X X X
Optical short range LDCM A A A A A A Note: Max 2 LDCM (same or
different type) can be selected
Optical medium range, LDCM 1310 nm B B B B B B
Rule: Always place LDCM
modules on the same board to
support redundant
communication; in P30:2 and
P30:3, P31:2 and P31:3 or P32:2
and P32:3
IRIG-B Time synchronization module F F F F F F
Galvanic RS485 communication module G G G G G G
GPS time synchronization module S S S S
Selection for position #12.
Serial communication unit for station communication #13 Notes and Rules
Slot position (rear view)
X301
X311
No communication board included X X
Serial and LON communication module (plastic) A
Serial (plastic) and LON (glass) communication module B
Serial and LON communication module (glass) C
Optical ethernet module, 1 channel glass D
Optical ethernet module, 2 channel glass E
Selection for position #13.
132 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Accessories IP15151-1 v1
GPS antenna and mounting details
M12374-3 v5
Cable for antenna, 40 m (Appx. 131 ft) Quantity: 1MRK 001 665-BA
Two winding transformer with internal neutral on RHGS 6 Case or RHGS 12 Case with mounted RTXP 24
current circuits. Two pcs can be used in applications for and the on/off switch for dc-supply are ordered
three winding transformers in single or multi-breaker separately. Please refer to Section Related documents
arrangement (ordering number RK926 315-BD) for references to corresponding documents.
Protection cover
M15040-3 v5
Protective cover for rear side of RHGS6, 6U, 1/4 x 19” Quantity 1MRK 002 420-AE
:
Protective cover for rear side of terminal, 6U, 1/2 x 19” Quantity 1MRK 002 420-AC
:
Protective cover for rear side of terminal, 6U, 3/4 x 19” Quantity 1MRK 002 420-AB
:
Protective cover for rear side of terminal, 6U, 1/1 x 19” Quantity 1MRK 002 420-AA
:
ABB 133
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
High impedance resistor unit 1-ph with resistor and voltage dependent resistor for 1 2 3
20-100V operating voltage Quantity RK 795 101-MA
:
High impedance resistor unit 3-ph with resistor and voltage dependent resistor for Quantity RK 795 101-MB
20-100V operating voltage :
High impedance resistor unit 1-ph with resistor and voltage dependent resistor for 1 2 3
100-400V operating voltage Quantity RK 795 101-CB
:
High impedance resistor unit 3-ph with resistor and voltage dependent resistor for Quantity RK 795 101-DC
100-400V operating voltage :
134 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Injection equipment
GUID-3447C871-562C-46B4-A36C-0B8B62D38E48 v5
Rule: If injection equipment is ordered, ROTIPHIZ or STTIPHIZSensitive rotor earth fault protection,
injection based (option B31) or 100% stator earth fault protection, injection based (option B32) is required
in the IED.
Injection unit, REX060 Quantity: 1MRK 002 500-AA
The REX060 injection unit requires a connection to a VT across the generator neutral
point earthing resistor. The VT must have a rating of at least 100 VA and a rated
secondary winding voltage of up to 120 V. It must adhere to IEC 61869-3:2011 section
5.5.301 Rated Output Values and the standard values specified according to burden
range II.
Casing
1/2 x 19" rack casing Basic
Backplane module (BPM) Basic
Human machine interface
HMI and logic module (HLM) Basic
Injection modules
Note: One of RIM and SIM have to be selected if REX060 is specified
Rule: Stator injection module (SIM) is required if 100% stator earth fault protection,
injection based (option B32)(STTIPHIZ) is selected/active in REG670
Stator injection module (SIM) 1MRK 002 544-AA
If the generator is earthed via a primary resistor connected between the generator
neutral point and earth, a VT is placed across the primary resistor. SIM is then
connected to the secondary side of the VT. The VT must have a rating of at least 100
VA and a rated secondary winding voltage of up to 120 V. It must adhere to IEC
61869-3:2011 section 5.5.301 Rated Output Values and the standard values specified
according to burden range II.
Rule: Rotor injection module (RIM) is required if Sensitive rotor earth fault protection,
injection based (option B31) (ROTIPHIZ) is selected/active in REG670
Rotor injection module (RIM) 1MRK 002 544-BA
Extra IP54 mounting seal + Flush mounting kit for terminal 1MRK 002 420-EA
Rule: REX061 requires REX060 and that Rotor injection module (RIM) is selected in
REX060 and that Sensitive rotor earth fault protection, injection based (option B31)
(ROTIPHIZ) is selected/active in REG670.
Coupling capacitor unit, REX061 Quantity: 1MRK 002 550-AA
Rule: REX062 requires REX060 and that Stator injection module (SIM) is selected in
REX060 and that 100% stator earth fault protection, injection based (option B32)
(STTIPHIZ) is selected/active in REG670.
Shunt resistor unit, REX062 Quantity: 1MRK 002 555-AA
ABB 135
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
Combiflex
IP15161-1 v1
Key switch for lock-out of settings via LCD-HMI Quantity 1MRK 000 611-A
:
Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used.
SEMOD130267-5 v6
Injection unit for Rotor earth fault protection (RXTTE 4) Quantity 1MRK 002 108-BA
Note: Requires additional COMBIFLEX terminal base RX4, 10A COMBIFLEX sockets and :
appropriate COMBIFLEX mounting accessories for proper operation
Protective resistor on plate Quantity RK795102-AD
:
Front connection cable between LCD-HMI and PC Quantity 1MRK 001 665-CA
:
SEMOD131414-4 v3
Note: One (1) IED Connect CD containing user documentation (Operation manual, Technical
manual, Installation manual, Commissioning manual, Application manual and Getting started
guide), Connectivity packages and LED label template is always included for each IED.
Rule: Specify additional quantity of IED Connect CD requested. Quantity 1MRK 002 290-AD
:
136 ABB
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
User documentation
Rule: Specify the number of printed manuals requested
Application manual IEC Quantity 1MRK 502 065-UEN
:
Communication protocol manual, IEC 61850 Edition 1 IEC Quantity 1MRK 511 349-UEN
:
Communication protocol manual, IEC 61850 Edition 2 IEC Quantity 1MRK 511 350-UEN
:
Communication protocol manual, IEC 60870-5-103 IEC Quantity 1MRK 511 351-UEN
:
ABB 137
1MRK 502 068-BEN F
Generator protection REG670 2.1 IEC
For our reference and statistics we would be pleased to be provided with the following application data:
Type of prime mover: steam , gas , hydro , pumpstorage , nuclear , other ______________________
Documents related to REG670 Document numbers Operation manual IEC:1MRK 500 123-UEN
ANSI:1MRK 500 123-UUS
Application manual IEC:1MRK 502 065-UEN
ANSI:1MRK 502 065-UUS Engineering manual IEC:1MRK 511 355-UEN
ANSI:1MRK 511 355-UUS
Commissioning manual IEC:1MRK 502 067-UEN
ANSI:1MRK 502 067-UUS Installation manual IEC:1MRK 514 024-UEN
ANSI:1MRK 514 024-UUS
Product guide 1MRK 502 068-BEN
Communication protocol 1MRK 511 348-UUS
Technical manual IEC:1MRK 502 066-UEN manual, DNP3
ANSI:1MRK 502 066-UUS
Communication protocol 1MRK 511 351-UEN
Type test certificate IEC:1MRK 502 068-TEN manual, IEC 60870-5-103
ANSI:1MRK 502 068-TUS
Communication protocol 1MRK 511 349-UEN
manual, IEC 61850 Edition 1
138 ABB
139
ABB AB
Substation Automation Products
SE-721 59 Västerås, Sweden
Phone +46 (0) 21 32 50 00
Scan this QR code to visit our website
www.abb.com/substationautomation
1MRK 502 068-BEN