Notifier - Onyxworks - NFN - Gateway 1
Notifier - Onyxworks - NFN - Gateway 1
NFN Gateway
Embedded
Installation & Operation Manual
D
Document 52306
06/01/07 Rev:
P/N: 52306:D ECN: 06-053
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of smoke detec- bedrooms), smoking in bed, and violent explosions (caused by escap-
tors, heat detectors, manual pull stations, audible warning devices, ing gas, improper storage of flammable materials, etc.).
and a fire alarm control panel with remote notification capability—can Heat detectors do not sense particles of combustion and alarm only
provide early warning of a developing fire. Such a system, however, when heat on their sensors increases at a predetermined rate or
does not assure protection against property damage or loss of life reaches a predetermined level. Rate-of-rise heat detectors may be
resulting from a fire. subject to reduced sensitivity over time. For this reason, the rate-of-
The Manufacturer recommends that smoke and/or heat detectors be rise feature of each detector should be tested at least once per year
located throughout a protected premise following the recommenda- by a qualified fire protection specialist. Heat detectors are designed
tions of the current edition of the National Fire Protection Association to protect property, not life.
Standard 72 (NFPA 72), manufacturer's recommendations, State and IMPORTANT! Smoke detectors must be installed in the same room
local codes, and the recommendations contained in the Guide for as the control panel and in rooms used by the system for the connec-
Proper Use of System Smoke Detectors, which is made available at tion of alarm transmission wiring, communications, signaling, and/or
no charge to all installing dealers. These documents can be found at power. If detectors are not so located, a developing fire may damage
http://www.systemsensor.com/html/applicat.html. the alarm system, crippling its ability to report a fire.
A study by the Federal Emergency Management Agency (an agency Audible warning devices such as bells may not alert people if these
of the United States government) indicated that smoke detectors may devices are located on the other side of closed or partly open doors or
not go off in as many as 35% of all fires. While fire alarm systems are are located on another floor of a building. Any warning device may
designed to provide early warning against fire, they do not guarantee fail to alert people with a disability or those who have recently con-
warning or protection against fire. A fire alarm system may not pro- sumed drugs, alcohol or medication. Please note that:
vide timely or adequate warning, or simply may not function, for a
variety of reasons: • Strobes can, under certain circumstances, cause seizures in people
with conditions such as epilepsy.
Smoke detectors may not sense fire where smoke cannot reach the
• Studies have shown that certain people, even when they hear a fire
detectors such as in chimneys, in or behind walls, on roofs, or on the
alarm signal, do not respond or comprehend the meaning of the signal.
other side of closed doors. Smoke detectors also may not sense a
It is the property owner's responsibility to conduct fire drills and other
fire on another level or floor of a building. A second-floor detector, for training exercise to make people aware of fire alarm signals and
example, may not sense a first-floor or basement fire. instruct them on the proper reaction to alarm signals.
Particles of combustion or “smoke” from a developing fire may not • In rare instances, the sounding of a warning device can cause tempo-
reach the sensing chambers of smoke detectors because: rary or permanent hearing loss.
• Barriers such as closed or partially closed doors, walls, or chimneys A fire alarm system will not operate without any electrical power. If
may inhibit particle or smoke flow. AC power fails, the system will operate from standby batteries only for
• Smoke particles may become “cold,” stratify, and not reach the ceiling a specified time and only if the batteries have been properly main-
or upper walls where detectors are located. tained and replaced regularly.
• Smoke particles may be blown away from detectors by air outlets. Equipment used in the system may not be technically compatible
• Smoke particles may be drawn into air returns before reaching the with the control panel. It is essential to use only equipment listed for
detector. service with your control panel.
The amount of “smoke” present may be insufficient to alarm smoke Telephone lines needed to transmit alarm signals from a premise to a
detectors. Smoke detectors are designed to alarm at various levels of central monitoring station may be out of service or temporarily dis-
smoke density. If such density levels are not created by a developing abled. For added protection against telephone line failure, backup
fire at the location of detectors, the detectors will not go into alarm. radio transmission systems are recommended.
Smoke detectors, even when working properly, have sensing limita- The most common cause of fire alarm malfunction is inadequate
tions. Detectors that have photo-electronic sensing chambers tend to maintenance. To keep the entire fire alarm system in excellent work-
detect smoldering fires better than flaming fires, which have little visi- ing order, ongoing maintenance is required per the manufacturer's
ble smoke. Detectors that have ionizing-type sensing chambers tend recommendations, and UL and NFPA standards. At a minimum, the
to detect fast-flaming fires better than smoldering fires. Because fires requirements of NFPA 72 shall be followed. Environments with large
develop in different ways and are often unpredictable in their growth, amounts of dust, dirt or high air velocity require more frequent mainte-
neither type of detector is necessarily best and a given type of detec- nance. A maintenance agreement should be arranged through the
tor may not provide adequate warning of a fire. local manufacturer's representative. Maintenance should be sched-
uled monthly or as required by National and/or local fire codes and
Smoke detectors cannot be expected to provide adequate warning of should be performed by authorized professional fire alarm installers
fires caused by arson, children playing with matches (especially in
FCC Warning
WARNING: This equipment generates, uses, and can radi- likely to cause interference, in which case the user will be
ate radio frequency energy and if not installed and used in required to correct the interference at his own expense.
accordance with the instruction manual, may cause inter- Canadian Requirements: This digital apparatus does not
ference to radio communications. It has been tested and exceed the Class A limits for radiation noise emissions
found to comply with the limits for class A computing from digital apparatus set out in the Radio Interference
device pursuant to Subpart B of Part 15 of FCC Rules, Regulations of the Canadian Department of Communica-
which is designed to provide reasonable protection against tions.
such interference when operated in a commercial environ-
ment. Operation of this equipment in a residential area is Le present appareil numerique n'emet pas de bruits radio-
electriques depassant les limites applicables aux appareils
numeriques de la classe A prescrites dans le Reglement
Acclimate Plus™, HARSH™, NOTI•FIRE•NET™, VeriFire™, NION™, NOTIFER Intergrated Systems™ and ONYXWorks™ are trademarks, and
ONYX®, FlashScan®, UniNet®, VIEW®, NOTIFIER® are registered trademarks of Honeywell. Simplex® is registered trademark of Tyco
International Ltd. Echelon® is a registered trademark and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint
Corporation. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. LEXAN® is a registered trademark of GE Plastics, a subsidiary of
General Electric Company.
©2006 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
AFP-200 NAM
AFP-300/400 NAM
AFP-1010 SIB-NET
AM2020 SIB-NET
BACnet Gateway NCM-W/F
DAA
DVC NCM-W/F
NFS-320* NCM-W/F
NFS-640 NCM-W/F
NFS2-640* NCM-W/F
NFS-3030 NCM-W/F
NFS2-3030* NCM-W/F
NCA NCM-W/F
NCA-2* NCM-W/F
NCS NCM-W/F
Workstation
Ethernet IP
Connection
Gateway
Embedded
FACP
IP Network
Workstation Workstation
Gateway
Embedded
NFN Network
IP Network
Workstation
Gateway PC
Workstation
Workstation/Echelon
Gateway
Gateway
Embedded
Style 4, 6, or 7
Echelon Network
Wire or Fiber, ULC
Style DCLA, DCLB,
and DCLR
NOTIFY
PAA
ACT-2
Voice Paging Equipment
XPIQ
Speakers
FIRSTVISION
Ethernet (TCP/IP)
Network
Gateway Embedded
NFN Network
NOTE: If if you are connecting NFN Gateway to a NFN Gateway PC and plan on running the
ONYXWorks® Workstation software application also, the Workstation must be set to Supervising
Station Mode (refer to the Workstation manual).
“CAB3/CAB4 Cabinet
Installation” on page 20
“Network Communication
Module Installation” on
page 22
page 35
“Connect the
Configuration PC to the “NCM Address Setting”
NFN Gateway” on on page 35
page 30
“Time Settings” on
page 36
“Add the IP Subnet of the
NFN Gateway into the
Configuration PC” on “Login Password
page 32 Settings” on page 37
“Default Gateway
Connection” on page 33 Finished
This product is intended to be installed in accordance with the Local Authority Having Jurisdiction
(LAHJ) and has been investigated to, and found to be in compliance with the following standards
and documents. Before proceeding, the installer should be familiar with them too.
Underwriters Laboratories U.S. Documents
• UL-294: Access Control System Units, Fifth Edition.
• UL-864: Control Units for Fire Protective Signaling Systems, Ninth Edition.
• UL-1076: Proprietary Burglar Alarm Units and Systems, Fifth Edition.
Underwriters Laboratories Canada Documents
• CAN/ULC-S527-99: Standard for Control Units for Fire Alarm Systems.
National Fire Protection Association Standards
• NFPA 70: National Electrical Code.
• NFPA 72: Installation, Maintenance, and Use of Protective Signaling Systems.
WARNING: Installation
! Improper installation, maintenance, and lack of routine testing could result in system malfunction.
NOTE: The contents of this manual are important and must be kept in close proximity of the
installed equipment. If building ownership is changed, this manual including all other testing and
maintenance information must also be passed to the current owner of the facility. A copy of this
manual was shipped with the equipment and is also available from the manufacturer.
“CAB3/CAB4 Cabinet
Installation” on page 20
“Network Communication
Module Installation” on
page 22
To “Gateway
Configuration Process
Flow Diagram” on
page 29
DB9-NUP Connector -
used for operation as
the network connection
to NFN Network
HDD Power
Connector (P1)
RJ45 Ethernet
Connector (CN2)
Reset Button
Reset Button
The Reset button is used to cycle power to the PC board. It does not affect the settings made to the
software.
Lithium Battery
NOTE: The replacement of the PC Board’s lithium battery is to be performed by a trained technician.
NOTE: The CAB3/CAB4 cabinet is ordered separately. For installation details, refer to the CAB-
3/CAB-4 Series Installation Document, 15330 and or the panel’s or annunciator’s documentation.
Step 2. After the CAB3/CAB4 cabinet is prepared with the CHS-4L chassis installed, perform the
“NFN Gateway Hardware Installation” on page 21.
CAB-3/CAB-4 Series Cabinets
Product Installation Document
1 General
All cabinets are fabricated from 16 gauge steel. The cabinet consists of two basic components: a backbox and a locking
door.
The key-locked door is provided with a pin-type hinge, two keys, and the necessary hardware to mount the door to the
backbox. The backbox has been engineered to provide ease-of-entry for the installer. Knockouts are positioned at
numerous points to let the installer bring conduit into the enclosure easily. Doors can be mounted on the left or right-hand
side. The same hinge works in both configurations, so that this choice can be made in the field. The door opens 180°.
Cabinets are available in four (4) sizes, A through D. The outside dimensions are noted on each enclosure diagram. "A"
size accommodates one chassis, a power supply, and two 26 AH batteries; "D" size accommodates four chassis, a power
supply, and two 26 AH batteries. A trim ring option is available for semi-flush mounting. The CAB-3/CAB-4 Series is
compatible with multiple chassis including the CHS-M2, CHS-M3, CHS-4, CHS-4L, CHS-4N, CHS-BH, CHS-PS, CA-1,
and CA-2. Note: CAB-4 series backboxes and doors are sold separately.
the doors can be opened "barn door" style, permitting an open work
space. Note that in this type of installation it is necessary to leave
enough space between cabinets to insert a key into the locks on the
door frames.
IMPORTANT: Attach the two hinges and two alignment tabs to the
backbox before any equipment is installed. With chassis installed,
space is very limited.
Display Interface Assembly Note: When the door is left-hand
mounted, the Display Interface Assembly (DIA) dress panel cannot be
opened when the door is at less than a 120° angle to the cabinet. If you are using the left-hand mounting option, be sure
that the door can open at least 120°. This is especially important if the cabinet is to be mounted in a closed area, such as a
closet or utility room.
2 1
3
4
6
NOTE: For installation details, refer to the document that ships with NCM board.
Use the Network Control Module PC board configuration that fits your installation needs.
• NCM-W with twisted pair wire.
• NCM-F with fiber-optic cable.
y p y
12 Clintonville Road
Northford, CT 06472-1653 USA
203-484-7161 • FAX 203-484-7118
www.notifier.com
NCM Installation Document
Network Communications Module NCM-W, NCM-F
PN 51533:B 11/29/2005 05-238
1 UL 864 Compliance
1.1 Products Subject to AHJ Approval
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire
Alarm Systems, UL 864 9th Edition.
The following products have not received UL 864 9th Edition certification and may only be used in retrofit applications.
Operation of the NCM-W, NCM-F with products not tested for UL 864 9th Edition has not been evaluated and may not
comply with NFPA 72 and/or the latest edition of UL 864. These applications will require the approval of the local
Authority Having Jurisdiction (AHJ).
• AM2020/AFP1010
• MIB
• NAM-232
2 Product Overview
The Network Communications Module (NCM) provides a means for connecting specific Notifier fire alarm control
products to NOTI•FIRE•NET™. There are two types of NCMs available: NCM-W for connecting nodes with
twisted-pair wire, and NCM-F for connecting nodes with fiber-optic cable.
In most applications, one NCM is required per NOTI•FIRE•NET™ node (including fire alarm control panels and
network annunciators) . Even though the NCM has two NUP ports, only one may be connected to a NOTI•FIRE•NET™.
node. Except in some DVC applications, do not connect two NCMs via NUP ports (aka “NUP to NUP”).
For instructions on the additional capabilities available with the DVC, refer to the DVC Manual.
• Input power requirements: 24 VDC , 0.11 amps, regulated, power-limited compatible power supply UL/ULC listed
for fire protective signalling use.
• Communications circuit requirements: Refer to the NOTI•FIRE•NET™ Manual (Network Version 4.0 and Higher)
for wiring length and threshold information.
Step 2. After this installation is perform “NFN Gateway Power Connection” on page 23.
When using an NCM-W/F, it can be powered by a panel/annunciators power source or the
supplied NFN gateway’s power supply (Figure 2.6).
NOTE: The NCM-W/F it can be powered by customer supplied external power supply, it should
be UL listed for fire protective signaling systems, power limited and regulated.
Earth
+5VDC Output
5V REF Output Black wire
NOTE: For complete details on powering and connecting an NCM-W/F, refer to the document
that was shipped with it.
Earth
+5VDC Output
5V REF Output
PC Board
Customer Supplied Cable PC board to PNET-1
To Internet or Intranet
PNET-1 surge suppressor
NOTE: If you are configuring the NFN Gateway using a PC that is not connected to your IP
network, then you can leave the connection between the PC board and the PNET-1 disconnected
until the gateway configuration is complete (refer to “Connect the Configuration PC to the NFN
Gateway” on page 30.)
Connect to an NCM-W/F
A DB9 to NUP cable is used to connect between the gateway and NFN network. Connect the cable
between to the NFN Gateway PC board’s DB9 connector and a NCM W/F PC board NUP
connector.
• Use a NCM-W for a twisted pair wire connection.
• NCM-F for a fiber-optic cable connection.
Step 4. After these cable connection are made you should perform “NFN Gateway Configuration”
on page 29.
LINE IN
CD Audio
LINE OUT
JP5
Microphone Connection
Connect the microphone to the NFN Gateway Sound Cable MIC-IN connector.
Public Address Amplifier Connection
NOTE: The NOTIFY-PAA must be mounted within six feet of the NFN Gateway.
Step 1. Using P/N 75625 audio cable, connect the plug into the LINE-OUT connector of the
sound cable.
Step 2. Connect the bare wires of the 75625 cable to the MUSIC and GND terminals on the public
address amplifier.
Step 3. Use 18AWG-12AWG twisted-pair cable to connect the COM and 25V terminals on the
public address amplifier to the AUDIO IN terminals on the audio coupling transformer.
Step 4. Connect the public address amplifier AC power cord to the primary AC power source.
MIC-IN
LINE IN
CD Audio
LINE OUT
Audio Coupling Transformer
P/N 75625
To next Audio
Coupling Transformer
NOTE: ONYXWorks® system (v3.0 or later) or FIRSTVISION™ (v1.4 or later) are required when
installing this NFN Gateway.
“Connect the
Configuration PC to the “NCM Address Setting”
NFN Gateway” on on page 35
page 30
“Time Settings” on
page 36
“Add the IP Subnet of the
NFN Gateway into the
Configuration PC” on “Login Password
page 32 Settings” on page 37
“Default Gateway
Connection” on page 33 Finished
A Configuration PC is defined as a PC that has the NFN Config Tool installed on it and it is able to
establish an IP connection with the NFN Gateway.
NOTE: A direct connection requires that a cross over Ethernet cable to be made or purchased
by the customer.
PC Board
Step 2. Connect the cross over cable between the Configuration PC network card’s RJ45
connector and the NFN Gateway PC board’s RJ45 connector (refer to "Cross Over Cable
Specifications").
Step 3. You have completed the connections, you need to “Add the IP Subnet of the NFN
Gateway into the Configuration PC” on page 32.
1 White/Orange 1 White/Green
2 Orange 2 Green
3 White/Green 3 White/Orange
4 Blue 4 Blue
5 White/Blue 5 White/Blue
6 Green 6 Orange
7 White/Brown 7 White/Brown
8 Brown 8 Brown
Step 2. Select File >Login to gain editing control of the selected gateway. The Gateway Login
window displays.
Step 3. Type in the gateway password and then click the OK button. The default password is
00000000 (eight zeros). The Property fields now display an asterisk next to the fields that
can be edited.
Step 4. If a IP router is NOT being used skip this step.
a. Click on the Value field adjacent to Gateway Property and then type in the address the
router will be using on your IP network.
b. Press the keyboard enter key.
Step 5. Change the default NFN Gateway IP address so it will be added onto your IP network.
Step 3. Click in the Value field adjacent to SNTP Server Address Property and then type in the
address of the server.
Step 4. Press the keyboard enter key.
Time Zone Configuration
Step 5. Click on the Time Zone Configuration entry in the Nodes column.
Step 6. Click in the Value field adjacent to GMT Minute Offset Property, type in the entry, and
then press the keyboard enter key.
The GMT Minute Offset is to used synchronize the time of day between the gateway and
SNPT Server.
• Use this formula to determine the setting: the US Central Time is minus 6 hours
from GMT, therefore your calculation would be -6 (hours) x 60 (minutes) = -360
minutes.
Step 7. Click in the Value field adjacent to Observe DST and then select True if you want the
gateway to automatically increment or decrement time of day according to Time Zone
Reference setting.
Step 8. Click in the Value field adjacent to Time Zone References field and then select from these
choices:
• US Standard - When selected the DST Begin and DST End settings are automatically
populated with the appropriate settings.
• EU Standard - When selected the DST Begin and DST End settings are automatically
populated with the appropriate settings.
• Custom - When selected you are require perform DST Begin and DST End settings.
Refer to “DST Begin/DST End” on page 41.
Step 9. Now you need to perform “Login Password Settings” on page 37.
• IP Address - Is used to set the IP address of the NFN Gateway on your IP network.
• Subnet Mask - Is used to set the Subnet of your IP network.
• Gateway - Is used to set the IP address of the default gateway.
Figure 4.3 NFN Config Tool SNTP Configuration Property/Value Field Description
SNPT Server Address - (Simple Network Time Protocol) Is used set the address of the SNPT
server. The NFN Gateway retrieves the SNTP server’s GMT (Greenwich Mean Time). Refer to
the “Time Zone Configuration Fields” on page 41.
NOTE: These fields only need to be modified if Custom has been selected in the Time Zone
Reference field.
To make the settings for the 1st Sunday of March make the following settings in these fields:
• Series Reference - Select 1st from the list of choices.
• Day of Week - Select Sunday from the list of choices.
• Month - Select March from the list of choices.
• Hour - Is used set the hour of the day to begin/end DST time change.
• Hour Reference - Is used set whether the Hour setting is according to Local Time or GMT.
PANEL PROPERTIES
Node - Is used to change the NFN network address of the panel.
VERSIONS
If the NCM Version field is displayed in red, then the version doesn’t match the Local Node entry.
NOTE: The NCM version for panel must match the NCM version displayed in the Local Node
entry. When it does not match the non-matching version is displayed as a red entry. Contact
Technical Services for assistance in acquiring the correct version.
4.3.2 View
All these choices display read only information windows, no editing can be done on the
information displayed from these windows.
• Refresh Gateway List - Used to generate a new list of gateways that will be available and
displayed when the NFN Config Tool’s Address field down arrow is clicked.
• Refresh Nodes List - Used to ping the nodes connected to the current gateway and display their
information.
• Node Table - Displays all the nodes connected to the gateway and their respective version
information.
NOTE: The NCM version for panel must match the NCM version displayed in the Local Node
entry. When it does not match the non-matching version is displayed as a red entry. Contact
Technical Services for assistance in acquiring the correct version. Also panels that do not use an
NCM are displayed as a red entry.
• Connected Clients - Used to display a window which lists the clients that are connected to the
gateway.
4.3.3 Tools
Some menu choices are only displayed when a relative selection is made in Nodes list column.
Right click options are also available for the selection made in the Nodes list column.
• Delete Node - Is used to remove a node from the gateway. The Node must be offline before it
can be deleted.
• Auto Detect Nodes - Is used to force the gateway to detect nodes on the NFN network. The
gateway searches for all online nodes on the NFN network.
• Set Gateway Password - Refer to “Login Password Settings” on page 37.
4.3.4 Help
• About - Display version information.
F M
Mode 40
FCC 40
fiber-optic cable 22
File menu N
descriptions 43 NCM Address 40
NCM PC board 22
G power connection 22
NCM Version
Gateway 40
red display 42
assembly 17
Network Cable Connection 25
Assembly Installation Diagram 21
Network Communication Module Installation 22
configuration 29
Network Interface PC Board 17
Configuration Procedure 34
Node Table 43
default IP Address 32
NFN Gateway Installation & Operation Manual - P/N: 52306:Rev: D 06/01/07 45
Index
O
Observe DST 41
P
password change 37
PNET-1 17
power supply
input current 23
input voltage 23
maximum voltage 23
minimum voltage 23
mounting plate part number 17
output current 23
output voltage 23
Proprietary Supervising Station 12
Public Address Amplifier Connection 27
R
Reboot Gateway 43
Refresh Gateway List 43
Refresh Nodes List 43
S
Set Gateway Password 44
SNPT Server Address 40
Sound Cable 26
Style 7 40
Subnet Mask 40
SUP 40
T
Time Zone Reference 41
Custom 41
EU Standard 41
US Standard 41
Tools menu
descriptions 44
Trouble Reminder 40
twisted pair wire 22
U
ULC 12
V
Version 39
View menu
descriptions 43
www.notifier.com