The 200ft tower foundation design includes: 1) A concrete foundation with a base width of 2000mm, base height of 750mm, and stump size and height of 750mm/150mm above ground and 2500mm below ground. 2) Calculations show the foundation can withstand the tower's maximum uplift of 61.936kN, with a factor of safety of 4.09888837. 3) Reinforcement of the concrete shaft includes 25mm rebar arranged in 8 bars around the perimeter, with minimum lap length of 375mm and lateral ties of 6.25mm diameter.

Uploaded by

fazila fauzi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
92 views3 pages

Padfoot

The 200ft tower foundation design includes: 1) A concrete foundation with a base width of 2000mm, base height of 750mm, and stump size and height of 750mm/150mm above ground and 2500mm below ground. 2) Calculations show the foundation can withstand the tower's maximum uplift of 61.936kN, with a factor of safety of 4.09888837. 3) Reinforcement of the concrete shaft includes 25mm rebar arranged in 8 bars around the perimeter, with minimum lap length of 375mm and lateral ties of 6.25mm diameter.

Uploaded by

fazila fauzi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 3

STABILITY ANALYSIS FOR 200FT TOWER

TECHNICAL DATA
Max Compression 158.973 kN
Max Uplift 61.936 kN
Max Shear 17.608 kN
No Of Legs 3 nos

DESIGN DATA
Safe Bearing Capacity 100 kN/m2
Density Of Concrete 24 kN/m3
Density Of Soil 17 kN/m3

FOUNDATION PROFILE
Base width 2000 mm
Base height 750 mm
Stump size 750 mm
Stump height
- above ground 150 mm
- below ground 2500 mm

Foundation Weight
Concrete VOLUME(m3) DENSITY(kN/m3) WEIGHT(kN)
- Base 3 24 72
- Stump 1.40625 24 33.75
- Stump above ground 0.084375 24 2.025

Sub - Total 4.490625 107.775

Soil
- Soil above base 8.59375 17 146.0938

Total 13.084375 253.8688

CHECK FOR UPLIFT(SAFETY FACTOR)


FOS 4.09888837

DESIGN CALCULATION BASE ON BS 8110:Part 1 & Part 2


fcu 25 N/mm2
fy 410 N/mm2
Cover 40 mm
Assuming bar size 25 mm
d 697.5 mm
Design Of Shaft
Design for compression and bending
Ultimate moment at shaft due to shear force 46.6612 kN-m
d/h 0.93
M/bh2 0.110604 N/mm2
N/bh 0.282619 N/mm2
Refer Chart No: 24
100ASC/bh 0.4 %
ASC 2250 mm2

PROVIDE Y 25 - 8 nos

3.12.8.11 Lap Length


Minimum lap length 375 mm

3.12.7.1 Lateral Ties


Min diameter of ties 6.25 mm

PROVIDE

Pad Design
Assume bearing capacity 100 kN/mm2
Bending moment developed/meter length 78.125 kNm length
Consider the pad as a beam of width 1 meter & depth 0.6 meter
K 0.00642335
compression reinforcement is/not required

Area of tension reinforcement required


z 662.625

As req 330.536256 mm2/m length


Table 3.27 As min 906.75 mm2/m length

PROVIDE

Anchorage length of bolts


Diameter of anchor bolt 32 mm
Number 4 nos
Force 61.936 kN
Force carried by each bolt 15.484 kN/bolt

3.12.8.3 Ultimate bond stress 2 N/mm2


Anchor length 77.05016 mm
PROVIDE