8BT2 - Installation and Operating Instructions
8BT2 - Installation and Operating Instructions
INSTALLATION AND
OPERATING
INSTRUCTIONS
DANGER!
As used in these instructions, this means that personal injuries can occur if the relevant
precautionary measures are not taken.
ATTENTION!
As used in these instructions, this means that damage to property or environment can
occur if the relevant precautionary measures are not taken.
NOTE!
As used in these instructions, this points at facilitations of work, particularities for
operation or possible mal-operation.
Symbols used Operation symbol: Identifies an operation. Ask the operator to perform an operation.
Result symbol: Identifies the result of an operation.
Independently of the safety instructions given in these operating instructions, the local
laws, ordinances, guidelines and standards for operation of electrical equipment as well
as for labor, health and environmental protection apply.
Any kind of modification on the product or alteration of the product must be coordinated
with the manufacturer in advance, as uncoordinated modifications or alterations can
cause the expiration of warranty claims, cause danger to life, limb and other legally
protected interests, and the fulfillment of the type tests (according to IEC 62271-200)
may not be guaranteed anymore.
The edition of the standard is only mentioned in the test report applicable at the time of
switchgear manufacture.
Five Safety Rules The Five Safety Rules of Electrical Engineering must generally be observed during
of Electrical operation of the products and components described in these operating instructions:
Engineering • Isolate.
• Secure against reclosing.
• Verify safe isolation from supply.
• Earth and short-circuit.
• Cover or barrier adjacent live parts.
The switchgear corresponds to the relevant laws, prescriptions and standards applicable
at the time of delivery. If correctly used, they provide a high degree of safety by means
of logical mechanical interlocks and shockproof metal enclosure of live parts.
DANGER!
The perfect and safe operation of this switchgear is conditional on:
Qualified personnel in accordance with these instructions are persons who are
familiar with transport, installation, commissioning, maintenance and operation of the
product and have appropriate qualifications for their work.
1000. Cd. 13. Sk. No:1004 , postal code: 41480 , Gebze – Kocaeli / TURKEY
E-mail: [Link]@[Link]
Furthermore, qualified personnel must have the following training and instruction or
authorization:
• Training and instruction or authorization to switch on, switch off, earth and
identify power circuits and equipment / systems as per the relevant safety
standards
• Training and instruction regarding the applicable specifications for the prevention
of accidents and the care and use of appropriate safety equipment
• Training in first aid and behavior in the event of possible accidents
2.1.1. Features
Air insulated 8BT2 36/70/170kV switchgear with the truck type circuit breaker has the
following features:
• Factory-assembled, type-tested, metal-enclosed and metal-clad switchgear for indoor
installation according to IEC 62271-200 / VDE 0671-200
• Loss of service continuity category LSC 2B (or LSC 2A as an option)
• Partition class PM by means of earthed, metallic shutters and partitions
• Internal arc classification: IAC A FLR, Isc 31.5kA, t=1s arc duration
• All switching operations can be performed with high-voltage door closed
• Standard degree of protection IP4X for the metal enclosure according to IEC 60529 / VDE
0470 Part 1
• Metallic, positively driven shutters protect against accidental contact with the live parts
inside the panel
• Logical interlocks between actuation, circuit breaker, disconnecting function and earthing
switch operating mechanism prevent mal-operation
• Feeder / busbar earthing by means of earthing switches with short-circuit making capacity.
• Mechanical position indicators for the withdrawable part and the earthing switch integrated
in the mimic diagram at the panel front
• Position of the switching device truck visible through window in the high-voltage door.
• High flexibility due to various combinations of the basic panel types
• Wall-standing or free-standing arrangement
• Power cable connection from front for wall standing version and from front/rear for free
standing version
• Designed as truck-type switchgear (circuit breaker)
• Panel-internal control cables routed in metallic wiring ducts or steel spiral tubes
• Cable testing without de-energizing the main busbars possible by using the lower shutter
opening tool
• Extension of existing switchgear at both ends without modification of panels
• Use of block-type current transformers
• Type tested closed duct version
• Option: Verification of safe isolation from supply with high-voltage door closed by means of a
voltage detecting system according to IEC 61243-5
SWITCHGEAR
1) without the closed 2) with the closed 1) without the closed 2) with the closed
pressure relief duct pressure relief duct pressure relief duct pressure relief duct
NOTE!
To install the switchgear, the room must have the certain minimum dimensions. Please
observe the following illustrations.
ATTENTION!
Depending on the room height, the pressure relief system of switchgear with the
evacuation ducts must be led to the outside of the switchgear building to be able to
exhaust the hot gas due to an arc fault.
Switchgear Switchgear
Remarks:
Remarks: 2) in between the panel’s side wall and the room’s wall:
1) in between the panel’s side wall and the room’s wall: 500 mm to reach the rear of the switchgear.
100 mm or less than this value, PLEASE CONSULT SIEMENS.
800 mm when the short circuit current is 31.5kA.
500 mm for standard application. 4) Control aisle for panel replacement, from ground area of existing panels:
800 mm when the short circuit current is 31.5kA.
3000 mm
4) Control aisle for panel replacement, from ground area of existing
panels:
2700 mm for the panel type with the gas pressure relief from
the rear
3000 mm for the panel type when the gas pressure relief from
the top
5) 2450mm for the panel type with the gas pressure relief from the rear.
6) 2700mm for the panel type with the gas pressure relief from the top.
7) 200 mm when the short circuit current is 25kA.
800 mm when the short circuit current is 31.5kA
Note: Foundation details are shown on pages 24 and 25. Note: Foundation details are shown on pages 24 and 25.
2) with the closed pressure relief duct 2) with the closed pressure relief duct
Switchgear Switchgear
Remarks:
Remarks: 2) in between the panel’s side wall and the room’s wall:
in between the panel’s side wall and the room’s wall:
3) 500 mm to reach the rear of the switchgear.
100 mm or less than this value, PLEASE CONSULT 4) Control aisle for panel replacement, from ground area of existing panels:
SIEMENS company. 3000 mm
500 mm standard application.
4) Control aisle for panel replacement, from ground area of existing
panels:
3000 mm
Note: Foundation details are shown on pages 24 and 25. Note: Foundation details are shown on pages 24 and 25.
2.1.4. Wall opening details for the outlet of the closed pressure relief duct
There are two ways to let the gas pressure out of the switchgear room, a) from back of the
switchgear and b) from the lateral side of the switchgear. In both ways, the below site works
881-4027.9 * INSTALLATION AND OPERATING INSTRUCTIONS 8BT2 * Revision 03 9
on the wall need to be done:
“Z-detail”
“Z-detail”
Fig1. Wall opening for the transfer of hot gas pressure to the outside (from the rear of the switchgear)
To make this arrangement on the wall, the reference point is the related panel’s arrangement
as seen in fig1. The gap (X dimension) between lateral side of the switchgear and the wall is
important to identify the location of wall opening. The aisle at the back side of the switchgear
(Y dimension) determines the length of the outlet channel. It should be specified during the
order stage to be able to produce the suitable exhaust channels.
“Z-detail”
Fig2. Wall opening for the transfer of hot gas pressure to the outside (from the lateral of the switchgear)
To make this arrangement on the wall, the reference point is the aisle at the front of the
switchgear ( 1500mm or 2241mm dimension) as shown on fig2. The aisle at the lateral
side of the switchgear (X dimension) determines the length of the outlet channel. It should be
specified during the order stage to be able to provide adequate channel.
NOTE!
Please see on page49 – 54 for the detailed information of the assembly of pressure relief
channels.
2.1.5. Protection against solid foreign objects, electric shock and water
8BT2 switchgear complies with the following degrees of protection according to IEC 60529:
• IP4X for switchgear enclosure of the operating front and the side walls
• IP2X for between compartments
Basic measures for ensuring EMC are already taken during design and assembly of the
switchgear panels. Among other things, these measures include:
• the low-voltage compartment is an integral part of the panel, which means that the
protection and control devices with the internal wiring are metal-enclosed;
881-4027.9 * INSTALLATION AND OPERATING INSTRUCTIONS 8BT2 * Revision 03 11
• reliable earth connections of the frame parts via toothed contact washers or locking
washers;
• inside the panel, wires are laid in metal ducts;
• spatial separation of sensitive signal wires from wires with high interference voltage
levels;
• limitation of switching over voltages of inductive loads (e.g. relay or contactor coils,
motors) by means of protective circuits with diode, varistor or RC element;
• within the LV compartment, the secondary devices are mounted in defined zones;
• shortest possible connection between corresponding modules in sub-racks;
• consideration of the magnetic leakage fields of conductor bars and cables;
• protection of sub-racks and wiring backplanes against interference by perforated
shielding plates;
• large surface bonding between all modules and devices as well as bonding to the
earthing conductor of the switchgear assembly.
These measures basically enable proper operation of the switchgear itself. The planner
or operator of the switchgear must decide whether additional measures are required
depending on the electromagnetic environment where the switchgear is installed. Such
measures must be implemented by the installation company in charge.
Cable shields must be electrically bonded to be able to carry high frequencies, and
contacted concentrically at the cable ends.
The shields of cables and wires are connected and earthed in the low-voltage
compartment.
Connect the shields to earth potential - with high electrical conductivity and all around as
far as possible. Protect the contact surfaces from corrosion in case of humidity (regular
condensation).
When laying cables into the switchgear assembly, separate the control, signaling and
data cables and other lines with different signal and voltage levels by laying them on
separate racks or riser cable routes.
Corresponding to the different shield designs, there is a number of methods to
perform connection. The planning department or site management determines which
of the methods will be used, taking EMC requirements into account. The preceding
points should always be taken into account.
The shield is connected to cables or wires with clamps contacting all around. If low
demands are placed on EMC, it is also possible to connect the shield directly to earth
potential (combine or twist the shield wires) or via short cable connections. Use cable
lugs or wire-end ferrules at the connecting points.
Always keep the connecting leads of the shields as short as possible (< 10 cm).
If shields are used as protective earth conductors at the same time, the connected
plastic-insulated lead must be marked green/yellow over its entire length. Non-
insulated connections are inadmissible.
2.1.8. Rating plates
The rating plates contain all relevant data for the cubicle and its components.
In this respect, the following limit values for the ambient air temperature must be complied
with as a minimum:
The ambient air temperature
Maximum value +40
Minimum value -5
Maximum value of 24-hour mean +35
When 8BT2 switchgear is used in regions with high air humidity or considerable
temperature fluctuations, there is risk of condensation. The formation of condensation
should be an exception under normal operating conditions. To prevent condensation,
rusting or other serious consequences, the associated preventive measures must be taken
by installing electrical heating equipment in the switchgear. The ambient air must not be
significantly polluted by dust, smoke, corrosive and/or flammable gases, vapors or salt.
In the normal service condition, the site altitude shouldn’t exceed 1000m above sea level
according to IEC 62271-1:2007, clause 2.1.1. If it exceeds 1000m value, Ka correction factor
should be considered as explained below:
8BT2 truck-type circuit-breaker switchgear consists of various panel types which can be
freely combined according to the requirements.
8BT2 truck-type circuit breaker switchgear is of the modular type and has four
compartments.
Wall standing type 8BT2 panel Free standing type 8BT2 panel
B. Busbar compartment
Basic equipment • Version with rated normal current 800 A, 1250 A, 2000 A, 2500 A or 3150 A
• Busbars made of bare flat copper, bolted from panel to panel
• Pressure reliefs upwards into the switchgear-room or into the pressure relief duct.
Additional equipment • Capacitive voltage taps in the post insulators for capacitive voltage detection
• Busbar voltage transformers
• Make-proof busbar earthing switch
• Transverse busbar partition from panel to panel and busbar insulation
C. Cable compartment
Rated normal feeder current Single-core XLPE cables Three-core XLPE cables 1)
Ir [A] Quantity per phase Conductor cross section Quantity per phase Conductor cross section
[mm²] [mm²]
1250 2 500
1250 < …. 2000 4 500 2 300
2000 < … 3150 6 500
1) For the application of three-core cables, please see the deep bottom pan at the clause-
[Link].3 on page62.
NOTE!
Please find the detailed information about the cable termination length at clause-[Link]. on
pages55 and 56.
Basic equipment • Completely partitioned off the panel and removable from the panel as a separate unit
• For accommodation of protection, control, measuring and metering equipment
• Plug-in bus wires and control cables
• Standard version with 750 mm height
• Door hinge on the left
Fig5. Natural ventilation for 2500A rated current Fig6. Air forced ventilation for 3150A rated current
Z-detail
In the normal operation After an internal arc fault
Fig7. Working condition of the ventilation flap on high voltage compartment door
The ventilation window should be open to be able to perform the natural air flow. If not,
the cooling will not be efficiently done. Accordingly, temperature rise value may exceed
the limit.
Openings on the outer enclosure are needed to perform the air circulation in the panel for
2500A and 3150A rated feeder currents. Although slots and meshed flaps are arranged at the
outer of enclosure, IP4X protection degree and the safety conditions in the case of hot gas
release because of an arc fault are still available.
2.4. Components
Additional equipment
for vacuum circuit • Electromagnetic interlocks
breaker • Second shunt release
• Under voltage release
• C.t.-operated release 0.1 s
• Design for higher insulation requirements
Technical data
Spring charging motor
Rated current of miniature circuit
Operating voltage Power consumption
Rated voltage breaker (CB) with C-characteristic [A]
max. [V] min. [V] W [at DC] VA [at AC] 3AH3 type CB 3AH5 type CB
24 DC 26 20 500 - 16 8
48 DC 53 41 500 - 8 6
60 DC 66 51 500 - 6 4
110 DC 121 93 500 - 4 3
220 DC 242 187 500 - 2 2
110 AC 121 93 - 650 4 3
230 AC 244 187 - 650 2 2
Operating times
Operating times at rated voltage at secondary Equipment of circuit Duration
circuit breaker 3AH3 type CB 3AH5 type CB
Closing time - <75 ms <65 ms
st
1 shunt release <60 ms <55 ms
Opening time nd rd
2 and 3 release <55 ms <45 ms
Arcing time - <15 ms <15 ms
st
1 shunt release <80 ms <70 ms
Break time
2nd and 3rd release <60 ms <60 ms
Dead time - 300 ms 300 ms
st
1 shunt release <90 ms <75 ms
CLOSE/OPEN contact time
2nd and 3rd release <70 ms <60 ms
Closing solenoid 45 ms 45 ms
st
Minimum command duration 1 shunt release 40 ms 40 ms
2 and 3rd release
nd
20 ms 20 ms
st
1 shunt release >15 ms >15 ms
Pulse time for CB tripping signal
2 and 3rd release
nd
>10 ms >10 ms
Spring charging time for electrical operation - <15 s <15 s
Closing time: The interval of time between the initiation (command) of the closing operation
and the instant when the contacts touch in all poles.
Opening time: The interval of time between the initiation (command) of the opening operation
and the instant when the contacts separate in all poles.
Arcing time: The interval of time from the first initiation of an arc and the instant of final arc
extinction in all poles.
Break time: The interval of time between the initiation (command) of the opening operation
and the instant of final arc extinction in the last-pole-to-pole (= opening time and arcing time).
Close/open contact time: The interval of time (in a make-break operating cycle) between the
instant when the contacts touch in the first pole in the closing process, and the instant when
the contacts separate in all poles in the subsequent opening process.
NOTE!
For the detailed information about 3AH series circuit breaker (CB), please consult to the
below catalogues:
3AH3 vacuum CB……3AH3_Catalogue HG11_03_2010
3AH5 vacuum CB……3AH5_Catalogue HG11_05_2010
Additional equipment
for vacuum circuit • Electromagnetic interlocks
breaker
Pictures
2.5. Interlocks
2.6. Accessories
Standard accessories The below accessories are supplied with the switchgear:
Hand crank for racking the switching device truck in and out
Fig8. Test unit for capacitive interface and indicators Fig9. Test unit for phase comparison
8BT2 cubicles are factory assembled and the withdrawable parts are in the service position and the
doors are closed during the dispatch.
They are checked at the works for completeness in terms of the order and simultaneously subjected to
routine test to IEC publication 62271-200, and are therefore tested for correct structure and function.
The busbars are not assembled. The busbar material, fasteners and accessories are packed
separately.
Packing Depending on the kind of transport and country of destination, the transport units can be packed as
follows:
NOTE!
The packing materials of 8BT2 switchgear can be disposed of as classified materials.
Please observe the local regulations for disposal and environmental protection.
Transport unit The switchgear is delivered in transport units. These consist of individual switchpanels
without fitted busbars.
Accessories are packed separately and included with the switchgear.
DANGER!
Risk of injury and damage to the storage place and the stored goods if the storage
space is overloaded.
ATTENTION!
Fire risk. The transport unit is packed in flammable materials.
No smoking.
Keep fire extinguishers in a weatherproof place.
Mark the location of the fire extinguisher.
If the comprehensive accessories, the delivered switchgear or parts thereof have to be stored
before installation, a suitable storage room or place has to be selected and prepared.
Switchgear storage As a rule, the switchgear should be stored in a closed room. The storage room must have
in closed room the following characteristics:
• Floor with adequate load bearing capacity (weights as per delivery note)
• Even floor to enable stable storage
• Well-ventilated and free of dust as far as possible
• Dry and protected against humidity and vermin (e.g. insects, mice, rats)
• Heat to about 10 °C above outside temperature to prevent condensation
• Provide adequate ventilation in heated storage rooms
• Check humidity in the packing every 4 weeks (condensation)
• Do not unpack small parts to avoid corrosion and loss.
Outdoor storage of If the switchgear or parts thereof are delivered in seaworthy crates, these can be stored
Switchgear packed in up to 6 months in other rooms or outdoors. The storage place must have the following
seaworthy crates characteristics:
• Floor with adequate load-bearing capacity (weights as per delivery note)
• Protected against humidity (rain water, flooding, melting water from snow and ice),
pollution, vermin (rats, mice, termites, etc.) and unauthorized access
• Place all crates on planks and square timber for protection against floor humidity
• After 6 months of storage, have the desiccant agent regenerated professionally. To do this,
ask for expert personnel via your regional SIEMENS representative.
In order to obtain an optimum installation sequence and ensure high quality standards, site
installation of the switchgear should only be carried out by specially trained and skilled
personnel or at least by supervised and monitored by responsible persons.
When the installation is in the scope of supply of the manufacturer, the regional SIEMENS
representative requires the following information from you several weeks before the delivery
of the switchgear.
• Sketch of the installation room including the locations and numbers of the individual
cubicles and the storage space for the accessories
• Sketch of the access route from the public road to the switchgear building and information
concerning the condition thereof (meadows, arable soil, sand, gravel, etc.)
• Sketch of the transport route inside the switchgear building with the locations and dimensions
of doors and other narrow points, as well as the floor number of the installation room
• Information about available lifting equipment, e.g. mobile crane, fork-lift truck, lifting
truck, hydraulic jack, roller pads. If no lifting equipment is available, please notify this
explicitly.
4.1.1. General site requirements
Before starting the installation of the switchgear, the below conditions should be completed
properly:
• Lighting and electricity supply
• Switchgear room having ventilation, lockable facilities and dry condition
• Wall opening(s) for outlets of pressure relief ducts
• Cable ducts and channels for laying the power and control cables
• Sufficient ceiling height for the switchgear
• Being ensure about -5 °C indoor temperature class in the switchgear room
Detailed
foundation
drawings
2nd option
Hammer
head screw
C profile
CB 60-10
A-A section in floor drawings A-A section in floor drawings A-A section in floor drawings
4.1.3. Foundation
• A suitable foundation can be a false floor, a double floor or a reinforced-concrete
foundation. The reinforced-concrete floor must be equipped with foundation rails for
supporting the panels.
• As for design and construction of the foundation, the relevant standards DIN 43661
“Fundamentschienen in Innenanlagen der Elektrotechnik” (Foundation rails in electrical
indoor installations) and DIN 18202 “Maßtoleranzen im Hochbau” (Blatt 3) (Measuring
tolerances in structural engineering (Sheet 3)) apply.
• If the foundation has to be resistant to earthquakes, additional points must be considered.
Please ask your regional SIEMENS representative for the advice on this special condition.
• Determine level differences between the installation surfaces of the panels using a
measuring sheet, and compensate them with shims (0.5 to 1.0 mm).
ATTENTION!
During the preparation of the cable gallery, the deep bottom pan’s dimensions (especially
height) should be taken into consideration.
Please see on page62 and 63 for the detail information.
4.1.4. Tools
• These instructions • Various pieces of squared timber
• Measuring sheet of the base frame • Step-ladders
• Lifting truck • Workbench with vise
• Several roller pads (reinforced rollers) • 1/2"and 3/8" ratchet spanners with various extensions
• Several strong boards • Nuts for M10, M13, M16, M17, M18, M19, M24
• Rope or chain with transport shackles • Ring spanners, sizes 10, 13, 16, 17 ,18 ,19, 24
• Transport rods (diameter 25 to 30mm) • Various slotted-head and Torx screwdrivers
• Reinforcing bars, roller crowbars • Side cutter
• Torque wrench (6-260 Nm) • Water pump pliers
• Shim plates 0.5 to 1 mm • Various crimping pliers, stripping pliers, flat nose pliers,
• Phase tape (L1, L2, L3, gn/ye) universal pliers, pointed pliers etc.
• Shell VASELINE 8422 DAB 8 (0.250 kg tube, order no.: • Water level
8BX 2041) • Guide string
• Plumb bob, nylon thread (kite string or similar) • Scriber
• Wire brush, copper sponge • Vacuum cleaner
• Soft, lint-free cloth • Scriber
• Brush, cleaning cloth • Try-square
• Cleaning agent: ARAL 4005 or HAKU 1025/90, HAKU • Tape measure
5067, MTX 60 and household cleaner • Vernier caliper
• Measuring instrument with test probes, measuring cables,
Also useful: clamp-type test probes
• Building site distribution board for 400/230 V AC (50/60 Hz) • Continuity tester (beeper)
• Extensions for 230 V AC (50/60 Hz) • Site illumination
• Hydraulic jack (2 to 3 t, for vertical and horizontal stroke) • Hand lamp
• Sling ropes • Pocket lamp
• Transport rollers • Hammer drill
DANGER!
If incorrectly unloaded, the transport units may fall down and cause injury.
Please ensure that the lifting and transport gear used meets the requirements as
regards construction and load-bearing capacity.
Ensure even weight distribution.
ATTENTION!
If incorrectly unloaded, the transport units may be damaged.
Unload the transport units and set them down as close to the switchgear building as
possible in order to avoid unnecessary ways.
Move the transport units into the building, if possible on their wooden pallets. Only
remove packing where absolutely necessary in order to keep the switchgear as clean
as possible.
Remove foil only in the building, right before assembling the transport units.
Please ensure that the lifting gear used meets the requirements of the weight loads
of the panels from the table (see page22, “Transport weights and dimensions with
packing”) as a minimum.
Fig12. Position of transport fixing bolts Fig13. Bolt to remove inside at front right Fig14. Bolt to remove inside at rear left
on right side (same on left side) (same on left side) (same on right side)
Prepare transport material (e.g. ropes, eyelets, roller pads (reinforced rollers), etc.).
ATTENTION!
For further transport of a cubicle with a floor conveyor or other means of transportation
(reinforced rollers, etc.), a minimum live load of 14.5 kN/m 2 must be considered. Non-
observence of the live load can endanger people or damage the transport units during
further transport.
Please ensure that the lifting and transport gear used meets the requirements
regarding to construction and load-bearing capacity.
Lower the transport unit onto boards placed on roller pads (reinforced rollers), i.e. one
board placed on two roller pads. Distribute the roller pads so as to support the outer
edges of the transport unit (fig15).
Lift one side, then the other side of the transport unit and slowly lower it on the
881-4027.9 * INSTALLATION AND OPERATING INSTRUCTIONS 8BT2 * Revision 03 29
mounting position.
Putting down and Lift transport unit with suitable lifting gear or roller crowbar.
aligning Place the first (i.e. rearmost) transport unit as exactly as possible on its mounting
the transport units position and place the second one at a distance of approx. 200 - 300 mm, so that the
to the switchgear room units can still be aligned before bolting together.
Align the first left-hand or right-hand panel of the row correctly on the base frame and
then align the remaining panels with the first panel.
Lay shim plates under the transport units according to the measuring sheet of the base
frame.
Remove packing and transport materials from the place of installation. Remove any dirt
occurred during transport, as extreme cleanliness is required during installation.
Now the transport units are in the correct order for assembly.
NOTE!
Make sure that there are no transport damages on the panels.
Level the base frame according to DIN 43 661.
Prepare the materials and auxiliary devices required for installation.
ATTENTION!
Apply the tightening torques at the following tables to perform the bolted copper
and joints properly.
NOTE!
The bolted copper joints effects on the performance of the electrical conductivity.
The bolted steel joints effects on the performance of the earthing and mechanical
strength between steel parts.
Use strain washers for the bolted copper joints.
Use contact washers for the bolted steel joints
Bolting panels The panels are bolted together from inside. Set-nuts for interconnecting the panels are
together pressed into the left part of the panel frame, i.e. the panels are bolted together from the right
side to the left panel.
Using the fixing The fixing tools from the supplementary equipment facilitate bolting adjacent panels
tools together.
Assemble the pressure relief duct after bolting the panels and main busbars
together.
For fixing the panels on the floor, three holes with a diameter of 14 mm have been provided
in the panel floor. In the foundation, an elongated hole 25 x 45 mm has been provided each.
Fasten every panel to the foundation at these three points.
Detailed foundation
drawings
Welded floor fixing Bolted floor fixing Floor fixing with dowels
1st option
Floor fixing
types
2nd option
Hammer
head screw
C profile
CB 60-10
A-A section in floor drawings A-A section in floor drawings A-A section in floor drawings
32 Revision 03 * INSTALLATION AND OPERATING INSTRUCTIONS 8BT2 * 881-4027.9
Please make sure that tolerances for laying floor frame are as below:
Evenness tolerance………………±1mm within a measuring length of 1m
Straightness tolerance……………1mm per 1m, (not more than 2mm in total length of the switchgear)
If necessary, place shims in the spaces between the switchpanel and the foundation in the area of
elongated holes.
Bolt the cross members inside Drill elongated holes 25 x 45 mm into the
Procedure Weld the cross members in the panel frame to the C- concrete first, fill with plaster and insert
the area of the holes with a profiles in the foundation using dowels with a diameter of 10 mm
diameter of 17 mm down to anchor bolts and shim plates. including the matching screws.
the U- profile supports in the
foundation. Paint welding seams to prevent
corrosion.
Remove any dirt occurred during drilling or welding work. Extreme cleanliness is required during installation.
Now the switchgear is fastened to the foundation.
Access to the busbar Access to the busbar compartment can only be done from top of the panel by removing the
compartment of pressure relief flaps.
circuit breaker panel
Removing the busbar Remove the fixing bolts of both pressure relief flaps ([Link]. in fig18) over the
pressure relief flaps busbar compartment
The pressure relief flaps over the busbar compartment can be removed.
ATTENTION!
Please ensure that the bolt directions are applied correctly as mentioned at fig19 –
fig28. It is important to provide the sufficient clearances between phases and
earthed parts.
Apply the exact bolt sizes listed in below table due to the critical electrical
clearances between live parts under the voltage. Longer the bolt is used, more
risks it is taken at the insulation.
The threads of the bolts and nuts must be dry and non-greasy.
Check contact surfaces of busbars, brush if necessary and apply a thin film of Shell
Vaseline 8422 DAB 8.
NOTE!
The strain washers at the busbars have one side cambered inwards and one side
cambered outwards. Observe correct position of strain washers for assembly.
Mount the strain washers so that the side cambered outwards points at the bolt
head or the nut.
NOTE!
All bolts used in main busbar assembly are “mushroom head type”.
Rated current Main Busbars Dropper bars (mm) Bolted joints with Nut with Tightening Control
of main (mm) strain washer strain washer torque tightening
busbars torque
800A 40x10 40x10 M12x40 M12
80x10 40x10…….or……80x10 M12x40 M12
1250A
80x10 2x40x10 M12x50 M12
2x80x10 40x10…….or……80x10 M12x50 M12 70 Nm 60 Nm
2000A
2x80x10 2x40x10 M12x60 M12
3x80x10 40x10…….or……80x10 M12x60 M12
2500A / 3150A 3x80x10 2x40x10….or…2x80x10 M12x70 M12
3x80x10 3x80x10 M12x75 M12
Please see the below drawings related to the connection details between main busbars,
dropper bars and intermediate copper spacers according to the different combination of current
ratings.
Fig28. Main busbar / Dropper bars ratings _ 2500A - 3150A / 2500 – 3150A
ATTENTION!
Please ensure that the bolt directions are applied correctly as mentioned at fig29 –
fig33. It is important to provide the sufficient clearances between phases and
earthed parts.
Apply the exact bolt sizes listed in below table due to the critical electrical
clearances between live parts under the voltage. Longer the bolt is used, more
risks you take at the insulation.
The threads of the bolts and nuts must be dry and non-greasy.
Check contact surfaces of busbars, brush if necessary and apply a thin film of Shell
Vaseline 8422 DAB 8.
L1 phase……
L2 phase……
L3 phase……
Depending on the current rating, the copper bar quantity is various in 1 pc ( 1250A), 2pcs
(2000A) and 3 pcs (2500A – 3150A) per phase. In each phase, they are covered together
with heat shrinkable insulation material.
Do not separate copper bars in a phase covered by a common heat shrinkable
insulation material. It will be assembled as a whole.
Do not cause any damage on heat shrinkable insulation material during the
assembly. There is a high risk to have a flashover because of the damaged
insulation material.
NOTE!
The strain washers at the busbars have one side cambered inwards and one side
cambered outwards. Observe correct position of strain washers for assembly.
Mount the strain washers so that the side cambered outwards points at the bolt
head or the nut.
NOTE!
Bolt types for connections of lower main busbars:
Hexagon head bolt without nut, used only at Current Transformer or Post
Insulator connections in the sectionalizing panel.
Please see the following drawings related to the connection details of lower main busbars for
all current rating combinations in the sectionalizing and busriser panels:
Sectionalizing Busriser
Sectionalizing panel at the right hand side – Busriser panel at the left hand side
When locations of Sectionalizing and Busriser panels are reversed, the assembly of lower
main busbar is also reversed. Please see the below sample for 2500A – 3150A rating
assembly (the same method is available for other ratings, 800A, 1250A, 2000A):
Busriser Sectionalizing
NOTE!
For rating 2500A – 3150A, please see the other details in fig32 on page43.
For other ratings (800A, 1250A, 2000A), the sectionalizing and busriser panels will be
reversed on fig29 – 32 drawings as done in fig33.
4.3.4.
4.3.5. Earthing
[Link]. Interconnecting the earthing busbars
The earthing busbars in panels are pre-assembled at the factory. When the switchgear is
installed, the busbars can be interconnected between panels via the copper bridges which
are provided as accessory.
NOTE!
Each panel has a fixed earthing bar in the cable compartment. The intermediate copper
bridge to interconnect two adjacent panels is a part of the accessories.
Check the contact surfaces of the earthing busbar. Brush if required and apply a thin
film of Shell Vaseline.8422 which is provided in accessories.
Place the interconnecting earthing bar into the corresponding openings of the two
adjacent panels and bolt it together with the fixed earthing bars of the panels.
Refit the bolted joints of the earthing busbar.
ATTENTION!
The low-voltage compartment weight is up to ~90 kg with the secondary equipment.
Lift low voltage compartment up to height of upper edge of high voltage door with
suitable lifting equipment.
Please see the below drawing for the assembly of the low voltage compartment:
ATTENTION!
Risk of injury.
Be aware of the sharp edges of steel parts during the assembly of the pressure relief ducts.
ATTENTION!
Arc routing plates have enough weight to endanger people.
Do not stay under a suspended arc routing plates before completion of assembly.
Preparations Procedure to be followed if accessibility to the panels is insufficient in the final position:
Mount the arc routing plates onto corresponding panel before positioning the panel on
the final place of installation.
Position the panel on its final place of installation.
Proceed in the same way with the adjacent panel.
Interconnect both arc routing plates before positioning the next panel.
To be able to apply arc routing plates efficiently, min. distances (fig37) should be considered.
Arc routing plates ([Link]. in fig38) are mounted to side holes at the top of the
switchgear as shown in fig38 and fig39. Left and right rear side walls ([Link]. in fig38)
are used to prevent any hot gas damage on people in the switchgear room.
Fig39. Final assembly of the arc routing plates at the wall standing switchgear version
48 Revision 03 * INSTALLATION AND OPERATING INSTRUCTIONS 8BT2 * 881-4027.9
[Link]. Gas pressure relief from the top (Free standing)
NOTE!
The following application is valid up to 25kA short circuit current.
To be able to apply arc routing plates efficiently, the above min. distances should be considered.
Fig42. Final assembly of the arc routing plates at the free standing switchgear version, 25kA
To be able to apply arc routing plates efficiently, the above min. distances should be considered.
Fig45. Final assembly of the arc routing plates at the free standing switchgear version, 31.5kA
Closed pressure
relief duct
Lateral exit is designed and constructed at the right or left side of the switchgear.
Rear exit is designed and constructed at the back of the switchgear.
ATTENTION!
Risk of injury.
Be aware of the sharp edges of steel parts during the assembly of the pressure relief ducts.
ATTENTION!
Pressure relief ducts have enough weight to endanger people.
Do not stay under a suspended pressure relief duct before completion of assembly.
Preparations Procedure to be followed if accessibility to the panels is insufficient in the final position:
Mount the pressure relief duct onto corresponding panel before positioning the panel
on the final place of installation.
Position the panel on its final place of installation.
Proceed in the same way with the adjacent panel.
Interconnect both pressure relief duct before positioning the next panel.
NOTE!
For all connections, the bolt type (M8x25) is used.
Hexagon head bolts with set-nuts which are already pressed on steel parts at
the factory.
Lateral exit
Closed pressure relief duct
Exhaust channel
(lateral exit)
The number of exhaust channels ([Link]. ) depends on the distance between the
switchgear and the wall.
The intermediate frame ([Link]. ) is used whenever the number of exhaust channel
group ([Link]. ) is more than one (fig48).
The connection details of the frame ([Link]. ) to the wall outlet are shown in fig49.
“Z-detail”
“Z-detail”
Exhaust channel
(rear exit)
The number of exhaust channels ([Link]. ) depends on the distance between the
switchgear and the wall.
The intermediate frame ([Link]. ) is used whenever the number of exhaust channel
([Link]. ) is more than one.
The connection details of the frame ([Link]. ) to the wall outlet are as below:
“Z-detail”
“Z-detail”
DANGER!
High voltage! Danger!
NOTE!
Please observe:
Before performing any kind of work in the cable compartment, remove the
associated withdrawable part from the panel (circuit breaker truck, etc.)
DANGER!
High voltage! Danger!
DANGER!
Risk of injury! During operation of electrical equipment and switchgear, parts of this
equipment are under dangerous electrical voltage. Mechanical parts may move quickly,
even remotely controlled.
ATTENTION!
If any work has to be performed in the cable compartment while the main busbar is live:
Open the lower shutter by using the shutter opening tool and remove the bushing
subsequently.
NOTE!
High voltage cables can be connected from;
Preconditions • Earthing switch closed, seem Page 78 – clause 6.10, "Operating the feeder earthing
switch"
• Truck removed from the panel, see Page 71 – clause 6.6, “Racking the switching device
A Cable
compartment
Cable lug
Cable
screen
ATTENTION!
The cable compartment can be destroyed if cable termination with inadequate
dimensions is used.
Use only cable termination with the dimensions shown at above table.
Depending on the manufacturer of the cable terminations, the dimensions may
differ from those shown in fig54 & 55 and above table. If they are different, please
consult Siemens before installation.
If the cables need to be installed while the main busbars are energized, use the lower shutter
opening tool to open the shutter. The upper shutter remains closed.
Fig56. Holes in left sliding rack for padlocking Fig57. Right sliding rack padlocked
Step2………………… Remove the M8 nut and 2 washers from the lower shutter drive lever ([Link]. in fig58)
Step3………………… Move the lower shutter drive lever aside lever ([Link]. in fig58).
Fig58. Lower shutter drive lever Fig59. Lower shutter drive lever
Perform steps 1, 2, 3, 4 on lower shutter drive lever and lower shutter analogously for
the left side.
Fig61. Short instruction label on lower shutter opening tool ([Link]. in fig60).
Unlock the spring mechanism by screwing the knob approx. 180° counter clockwise
(fig62).
Move the knob laterally between end positions to proof the spring mechanism is free
(fig62).
Lower the right end of the lower shutter opening tool to horizontal position.
Release the knob to meet the two slots in the right lower shutter arm with the spring
powered lugs.
Push the knob to the right that surely the lugs meet the holes.
Lock the spring mechanism by screwing the knob clockwise (fig64).
Now, the lower shutter can be operated manually while busbars are energized.
Procedure Push the lower shutter opening tool at the two handles inside the panel until the lower
shutter is fully open (fig65 – 67).
DANGER!
Hazard due to human error
Procedure Remove 18x M10/M8 bolts from the lower bushing (fig68).
Remove the lower bushing (fig69).
DANGER!
High Voltage!
Preconditions • Earthing switch closed, see Page 78 – clause 6.10, "Operating the feeder earthing switch"
• Truck removed from the panel, see Page 71 – clause 6.6, “Racking the switching device
truck to Test position"
• Upper shutter closed
• Lower shutter closed
• High-voltage door closed
There are two possible conditions which there are different processes:
i. Cable compartment without withdrawable VT
ii. Cable compartment with withdrawable VT
Move two operating levers ([Link]. in fig71) at the same time as shown in fig72.
Fig74. Dismounting L2 phase voltage transformer Fig75. Rear access to the cable compartment
Power cable Check contact surfaces of cable terminations, brush if necessary and apply a thin film
installation of Vaseline.
Slip rubber sleeve for the metal floor plates over the cable.
Mount cable termination according to the manufacturer’s instructions.
Pull cable into connection compartment.
Connect cable at the panel connection.
ATTENTION!
The cable compartment can be destroyed if cable terminations with inadequate
dimensions are used.
NOTE!
Deep bottom pans are used in conditions below:
1. Three core power cable is entered to the panel and phases are separated inside
the panel.
2. The cable termination length is longer than the limited value in the application
(please see fig54 & 55 on page55 & 56).
Note: If the 2nd condition is valid, please consult SIEMENS to arrange the exact
dimensions of deep bottom pan according to the cable termination. This is not a
standard application.
Top view
Internal wiring
The circuit diagrams for connecting the control cables are included in the low-voltage
compartment.
Remove main wiring duct covers on left inner side of switching device compartment.
Install connections from the foundation through the main wiring duct into the low-
voltage compartment.
Refit main wiring duct covers.
Connect control cables according to circuit diagrams.
NOTE!
The drawing in fig78 is taken from “Floor drawings” table at page24.
Low voltage
compartment
Control cable
channel
Fig78. Floor opening for control cable Fig79. Control cable channel
at the foundation layout
The control cables are entered to the panel from the floor opening ([Link].2 in fig78). Then,
they are laid down to the low voltage compartment through the cable channel (fig79).
Plug bus wires into bus wire terminal block in low-voltage compartment.
NOTE!
Please be aware of the below table regarding to the torque values during the control
process.
Perform random checks of the control cable connections on devices and terminal blocks.
Check all control cable connections of current transformer terminals in low-voltage
compartment (including slides and jumpers).
If there are any terminal blocks without labels, complete labels using the information given
in the circuit diagrams.
Wipe all bushings and post insulators of the busbars using a soft, lint-free, dry cloth.
4.4.5. Checking and completing protection against adverse environmental influences (protection against
corrosion)
Touch up scratches and impact marks on surface painting
DANGER!
High voltage! Danger!
ATTENTION!
Risk of injury! During operation of electrical equipment and switchgear, parts of this
equipment are under dangerous electrical voltage. Mechanical components may move
quickly, even remotely controlled.
• Operating instructions
• Hand crank for truck operation
• Operating lever for the feeder earthing switch
• Hand crank for the spring energy store
• Double-bit key for the racking mechanism
• Double-bit key for the door of the low-voltage compartment
• Circuit diagrams
• Warning signs
• Earthing and short-circuiting facility (optional)
• Voltage tester or detecting system (optional)
• Lower shutter opening tool (optional)
DANGER!
High voltage! Danger!
If you find out during test operation that a part of the system does not operate in
the way described in this document, you must not put the switchgear into
operation.
DANGER!
High voltage! Danger!
The motors of the circuit breaker operating mechanisms start up and charge the closing
springs.
Checking Rack each truck from TEST position to SERVICE position and back several times. At the
the switching process same time, check whether these positions of the truck are displayed correctly at the
and the position panel and, if applicable, in the control room.
indicators Switch each earthing switch from OPEN to EARTHED position and back several times.
At the same time, check whether these positions are correctly indicated on the panel
and, if applicable, in the control room.
Close and open each circuit breaker several times locally and from remote for test. At the
same time, check whether these positions are correctly indicated on the panel and, if
applicable, in the control room, and whether the auxiliary switches and position switches
operate correctly.
Check the function of the existing shunt closing and shunt opening releases by electrical
operation.
ATTENTION!
If you have determined a malfunction during one of these tests:
Preparations before The operating personnel must have been trained, the installation work checked and test
switching on operation must have been carried out successfully without malfunctions.
Now, you can apply on the operational high voltage to put the switchgear into operation.
DANGER!
High voltage! Danger!
Switch on the operational high voltage only if you have checked the installation
work and performed the test operation without malfunctions.
ATTENTION!
Short-circuit on the busbar if the incoming feeders have different phase sequences.
Ensure that all incoming feeders have the same phase sequence.
Verify phase coincidence between the respective incoming feeder and the busbar.
Switch on tested incoming feeder.
NOTE!
Note any modifications which may have been made during installation or
commissioning in the supplied circuit diagrams.
Send the corrected documentation to the regional SIEMENS representative so
that the modifications can be included.
Switching on If you have a problem with your switchgear, please refer to your installation and operation
instructions for information on usage and trouble shooting. If the fault persists, contact our
SIEMENS Customer Support Center.
Repairs Repairs are carried out by fully trained Siemens engineers, who arrive equipped with original spare
parts for your switchgear.
Before you call To help us deal with your query more quickly, make sure you have the following information at hand:
• Switchgear type
• Switchgear serial number
• Year of manufacture
• Panel number
This information is available on the rating plate on the inside of the high voltage door and the
low voltage compartment door.
DANGER!
High voltage! Danger!
DANGER!
During operation of electrical equipment and switchgear, parts of this equipment are
under dangerous electrical voltage. Mechanical components may move quickly, even
remotely controlled.
DANGER!
Danger by non-observence of local regulations
NOTE!
Perfect and safe operation of the switchgear
The perfect and safe operation of this switchgear is conditional on correct erection
and installation according to the installation instructions.
Earthing switch
CLOSED OPEN
Regarding accessibility to the individual compartments, 8BT2 switchgear fulfills the loss of
service continuity category LSC 2B according to IEC 62271-200.
The degree of protection of the individual compartments between each other is IP2X.
The below operating tools are supplied as standard accessory with the switchgear:
Hand crank for racking the switching device truck in and out
DANGER!
High voltage! Danger!
Isolate the busbars in the busbar compartment and the cable or bar connections in
the connection compartment before opening the high-voltage door. Observe the
Five Safety Rules.
Do not operate the panel with the high voltage door open.
NOTE!
The following instructions for opening and closing the high-voltage door apply to:
Opening the high voltage compartment door Closing the high voltage compartment door
Preconditions • Truck in test position Either without truck or:
• Truck inserted in TEST position
• Low voltage connector plugged in
Procedure Pull the door handle upwards and open the door Pull the door handle upwards and close the door
st nd
1 Close 2
step the step
door
Moving the withdrawable device truck into the panel Moving the withdrawable device truck out of the
panel
Preconditions • Open the high voltage compartment door. • Open the high voltage compartment door.
The high voltage compartment door can only
be opened and the truck can only be racked
if the truck is in TEST position and
interlocked
Procedure Fold the locking gates of the guide rails to the Remove the low voltage connector. To do this,
inside. push the connector lock upwards.
Fold the locking gates of the guide rails to the
inside.
Turn the lateral fixing levers 90° outside.
Plug connection All control wires related to the circuit breaker’s internal circuit are connected to the low voltage
connector (fig82).
Low voltage
connector
socket
Circuit breaker
After inserting the witdrawable truck into the test position in the panel, the connector should be
plugged into the socket on the circuit breaker to be able to provide the electrical connection
between the circuit breaker’s and the low voltage control circuits (Please see fig83 for the
connection).
Fig84. The mechanical interlock between the low voltage connector and the high voltage door.
There is also the mechanical interlock between the low voltage connector and the high voltage
compartment door. If the connector is not plugged in, the door can not be closed. So, the
operation can not be started (Please see the photo in fig84).
Plug coding Although the circuit breaker’s physical dimensions in the switchgear are same, the technical
parameters may be different. For example, in spite of the fact that the nominal current ratings
are different (1250A, 2000A or 2500A), the circuit breaker (rated 1250A) can be put into the
panel rated 2000A.
According to the technical differences, the coding system is applied on plug (Please see photos
in fig85 and 86).
Socket
Circuit breaker
Pin-socket Pin-socket
The pin-socket combination can let the right circuit breaker put into the related panel. So,
NOTE!
The following instructions for racking the withdrawable device truck apply to:
Circuit breaker
Switch disconnector
Voltage transformer with truck in the metering panel
Fig87. Actuating opening and interlock for racking and switching device truck
Racking positions Withdrawable devices (circuit breaker, disconnector, voltage transformers) are mounted on the
truck. It can be racked to two different positions:
• SERVICE position: The contact poles of the switching device are connected with the
busbar and the feeder. The low-voltage connector is plugged in.
• TEST position: The contact poles of the switching device are disconnected from the busbar
and the feeder. In this position e.g. electrical interlocks can be checked. The low-voltage
connector can be unplugged.
ATTENTION!
If there is no auxiliary voltage, both the electrical and the mechanical interlocks are
closed. If the interlocks are eliminated, manual switching operations will be possible
despite an existing electrical interlock, and they can cause operational breakdowns.
Ensure that the intended manual switching operation has been released externally.
Racking the withdrawable truck into SERVICE Racking the withdrawable truck into TEST position
position
Preconditions • Truck completely inserted to the TEST position and • The truck in SERVICE position
interlocked in panel. • Circuit breaker and Switch Disconnector in OPEN
• High voltage compartment door closed. position
• Circuit breaker and Switch Disconnector in OPEN • Feeder earthing switch in OPEN position.
position.
• Feeder earthing switch in OPEN position.
• Low voltage connector plugged in.
Procedure To release the truck: Insert the double bit key into To release the device truck: Insert the double-bit
the actuating opening ([Link]. in fig87) and key into the actuating opening ([Link]. in fig87)
turn 90º clockwise to the “Racking free” position and turn 90° counter-clockwise to the "Racking free"
(manual racking). position (manual racking).
ATTENTION!
If there is no auxiliary voltage, both the electrical and the mechanical interlocks are
closed. If the interlocks are eliminated, manual switching operations will be possible
despite an existing electrical interlock, and they can cause operational breakdowns.
Ensure that the intended manual switching operation has been released externally.
Operate the ON push button of the circuit breaker. Operate the OFF push button of the circuit
breaker.
Circuit breaker
Switch disconnector
Voltage transformer with truck in the metering panel
Fig89. Actuating hole for manual charging of the circuit breaker spring
If the control voltage fails, the closing spring for operating the circuit breaker is no longer
charged automatically. To operate the circuit breaker in spite of this, the closing spring must be
charged manually with the hand crank.
DANGER!
Risk of injury by sudden rotation of hand crank. If you use a hand crank without a
freewheel to charge the spring, the hand crank will rotate when the control voltage is
switched on again (motor starts up) and can lead to injury.
Turn cover of operating shaft ([Link]. in fig89) aside using the rotary button ([Link].
in fig89) located over it.
Push hand crank onto operating shaft.
Turn hand crank clockwise approx. 25 turns until the "spring charged" indication appears
in the inspection window.
Remove hand crank.
The spring is latched automatically. The energy required for the operating sequence
OPEN-CLOSED-OPEN (auto reclosing) is stored in the spring.
The feeder and busbar earthing switches a r e operated bottom-right beside the high-voltage
compartment door.
DANGER!
Once you have started a switching operation, you must complete it; turning back is
blocked. The operating tool cannot be removed at intermediate positions.
ATTENTION!
Safe operation of the earthing switch is not guaranteed if the penetration of the earthing
blade is beyond the tolerance. If the penetration is beyond the tolerance:
ATTENTION!
If the operating lever is not inserted correctly, the earthing switch may be damaged.
Insert the operating lever in the actuating opening as far as it will go.
ATTENTION!
Make sure that there is no electromechanical interlock on the earthing switch.
DANGER!
Danger of burning on hot fuse-links.
Use the personal protective equipment. If not, do not touch fuses before checking
temperature.
Let hot fuse-links cool down before replacing.
ATTENTION!
Voltage transformers are exclusively designed for operation with HV HRC fuse-links.
NOTE!
Tripped fuses can cause hidden damages on the other fuses.
It is highly recommended to replace all fuse-links, even if only one fuse has tripped.
Insert two operating levers ([Link] in fig91) into the slots on both sides of the rear
cover ([Link]. in fig91).
Lift the operating levers to disconnect the withdrawable voltage transformers.
While lifting the operating levers, the rear cover interlock (in fig92) is released.
Fig92. Operating handles for withdrawable voltage transformers (movement for disconnecting)
The voltage transformers are disconnected, the interlocks on both sides are released and
the shutter is closed.
Check by looking through inspection window ([Link] in fig91) that inner shutter is
closed.
Remove the rear cover by means of the handles (fig93).
DANGER!
High voltage! Danger!
Observe the Five Safety Rules due to the fact that the operation can be done
while the line is energized.
Replacing fuse links Remove the cap from the fuse holder of the withdrawable voltage transformer (Please
of the withdrawable see photos in fig94, unscrew two bolts).
voltage transformer Remove the fuse-link ([Link]. in fig95) from the fuse holder ([Link]. in fig95).
Insert the new fuse-link into the holder with the striker at the top.
Mount the cap of the fuse holder.
Fig96. Operating handles for withdrawable voltage transformers (movement for connecting)
The voltage transformers are connected, locking on both sides are locked and the inner
shutter is open.
Check by looking through inspection window ([Link]. in fig91) that the inner shutter
is open.
Remove the two operating levers.
The perfect function of the voltage indicator must have been verified:
• with a test unit according to IEC 78/183/CDV
• on live equipment
The perfect function of the coupling section must have been verified according to:
• IEC 78/183/CDV
Plug voltage indicator in all three phases L1, L2, L3 of the interface.
A1
Operating voltage present
A5
Indication: "Device-Funtion-Test" passed
Open the high-voltage door (see Page71, clause 6.5, “Opening the high-voltage door").
Move the switching device truck out of the panel (see Page71, clause 6.6, "Moving the
switching device truck into and out of the panel").
Use high-voltage tester according to DIN VDE 0681.
DANGER!
High voltage! Danger! If the busbars in the busbar compartment and the cable or bar
connections in the connection compartment have not been isolated, the contacts are live
at operating voltage.
Isolate the busbars in the busbar compartment and the cable or bar connections in
the connection compartment before opening the shutters or before working at the
panel connections.
Observe the Five Safety Rules.
Verify safe isolation from supply.
The earthing and short-circuiting facility is connected to the earthing point at the front of the
panel with an M12 bolt.
881-4027.9 * INSTALLATION AND OPERATING INSTRUCTIONS 8BT2 * Revision 03 87
Fig100. Point of connection for earthing and short-circuiting facility
At the feeder Connect the earthing and short-circuiting facility to the earthing point.
Open the shutters by pushing the levers. If the busbars are energized, use the
lowershutter opening tool (see fig56 – 67, “Use of the lower shutter opening tool”).
Connect the contacts of the earthing and short-circuiting facility to the lower contacts of
the panel and screw tight.
At the busbar Connect the earthing and short-circuiting facility to the earthing point..
Open the busbar shutters by pushing the levers.
Connect the contacts of the earthing and short-circuiting facility to the upper contacts of
the panel and screw tight.
ATTENTION!
Maintenance work may only be performed in a careful manner by trained personnel
familiar with the characteristics of the individual switchgear, in accordance all relevant IEC
safety regulations and those of other technical authorities, and with other overriding
instructions.
Time schedule for Besides the recommended maintenance intervals, additional maintenance measures may be
maintenance required for operational reasons.
measures
General check for paint damages on all panels of a switchgear assembly in the area of
the front doors, the lateral and the rear termination. If required, repair damages.
General check of the switchgear for dust layers. If needed, clean them with vacuum
cleaners.
General check for humidity. To do this, open the high-voltage door of the switching
device compartment of every third panel and check the switching device compartment
for humidity or condensation.
If there is humidity or condensation inside a switching device compartment, determine
the cause thereof. To do this, do also observe the climatic conditions of the switchgear
room, and arrange for suitable measures such as room ventilation or room heating.
General check for partial discharge noises. If there are any partial discharge noises,
determine the cause thereof and take adequate countermeasures.
Check whether the operating tools are complete (see Page70 "Operating tools").
Fixed contacts of
the earthing switch
DANGER!
Working on a closed circuit breaker and on a open circuit breaker with charged spring
energy store can cause dangerous injuries.
Clean insulating parts with a humid cloth and soft cl eani ng agent, e.g. dish cleaner.
Clean all other parts with a lint-free cloth if they are dirty.
Grease relevant parts with Klüber Isoflex Topas L32 (fig102).
NOTE!
For the detailed information about 3AH series circuit breaker (CB), please consult to the
below operation manuals:
3AH3 vacuum CB……3AH3_order no: 9229 9860 174 OD
3AH5 vacuum CB……3AH5_order no: 9229 9989 174 OA
The manufacturer’s product liability is not effective if at least one of the following criteria
applies:
90 Revision 03 * INSTALLATION AND OPERATING INSTRUCTIONS 8BT2 * 881-4027.9
• No original Siemens spare parts are used.
• Assemblers who carry out the replacement have not been trained and certified for this work
by Siemens.
• The parts are mounted or adjusted incorrectly.
• Adjustments are not made according to the stipulations of Siemens.
7.2.1. Maintenance
The vacuum circuit breaker is maintenance-free within the range of the permissible operating
cycles. Under normal environmental and operating conditions, the switchgear has maintenance
intervals of 5 years.
Contact:
E-mail: [Link]@[Link]
Replacement of The individual components such as measuring instruments, current transformers, etc can be
components replaced. Please contact your regional SIEMENS representative for replacing components.
7.2.5. Disposal
8BT2 switchgear is an environmentally compatible product.
All metal plates are powder-coated with resistant epoxy resin material.
The switchgear materials should be recycled if possible. The switchgear can be disposed of in
an environmentally compatible manner in compliance with existing legislation.
The components of the switchgear can be recycled as mixed scrap; however, dismantling as far
as possible into sorted scrap with a residual mixed scrap portion is the more environmentally
compatible way.
As delivered by Siemens, the switchgear does not contain hazardous materials as per the
Hazardous Material Regulations applicable in the Federal Republic of Germany. In other
countries, the locally applicable laws and regulations must be followed.
Should you require further information, please contact your regional SIEMENS representative.
8. TROUBLE SHOOTING
Truck interlocking
Fault Cause Remedy
1) Truck can not be moved out of
Truck interlock closed Open truck interlock
panel.
Interlocking lever of LV connector not
2) Door to switching device Fold interlocking lever inwards
folded inwards
compartment.
Locking gates of guide rails not closed Close locking gates of guide rails
Truck
Fault Cause Remedy
Double bit key can not be turned
Circuit breaker in CLOSED position Switch circuit breaker to OPEN position
with open door locking handle.
Operating lever inserted in manual
CLOSE/OPEN operating mechanism of Remove operating lever
Truck ca not be racked to feeder earthing switch
SERVICE position (mechanically). Feeder earthing switch not in OPEN Switch feeder earthing switch to OPEN
position position
General switchgear interlock active Observe general switchgear interlock
Truck can not be racked to TEST
position. Circuit breaker in CLOSED position Switch circuit breaker to OPEN position
Double bit key can not be turned.
Circuit breaker
Fault Cause Remedy
Hand crank for truck inserted Remove hand crank for truck
Switching device truck is intermediate Rack switching device truck to SERVICE
position or TEST position
Circuit breaker can not be closed
Spring not charged Wait for 15 s (motor) or charge manually
Under voltage release not activated Energize the under voltage release
Low voltage connector not plugged in Plug low voltage connector in
Spring energy store is not Apply control voltage or charge spring
No control voltage
charged automatically energy store manually
Switchgear end walls, installation ............................... 31 Truck, trouble shooting ............................................... 104
Switchgear transport without wooden pallets .............16 Vacuum circuit-breaker 3AH, equipment...................... 60
Switching device truck, moving in ............................... 92 Voltage transformers, cable compartment ................... 96
Sector
Division Power Distribution
Schaltanlagenwerk Frankfurt
Carl-Benz-Str. 22
D-60386 Frankfurt
© Siemens AG 2010
Before operating a circuit breaker, several preconditions must be met. The breaker must be in either SERVICE or TEST position, and the feeder earthing switch must be open. The compartment door should be closed, and the low voltage connector plugged in. Additionally, if there is no auxiliary voltage, both electrical and mechanical interlocks might be closed, and any manual operation requires external release confirmation. Failing these checks may lead to operational breakdowns or safety hazards . These steps ensure the safety of personnel and the integrity of the system.
Mechanical and electrical interlocks are crucial for preventing incorrect sequencing and accidental operations of circuit breakers. Mechanical interlocks physically prevent actions unless all safety conditions are met, while electrical interlocks ensure that the breaker operates only under safe electrical states. In the absence of auxiliary voltage, all interlocks are closed to prevent unsafe manual operations which could lead to breakdowns or unsafe conditions . These interlocks ensure that circuit breakers in high-voltage systems operate within safe limits, thereby safeguarding both equipment and personnel from potential hazards.
Arc routing plates are used to safely direct the release of gases produced during electrical arcs, thus protecting equipment and personnel from high pressure or explosive release during faults. During installation, care must be taken due to their significant weight and the risk from sharp edges. They must be assembled before the panels are positioned. Notably, if assembly involves wall standing switchgear up to 25kA short circuit value, minimum distance requirements must be observed for proper clearance and efficiency . Proper assembly is essential to maintain safety and prevent damage.
If control voltage fails, the circuit breaker spring must be manually charged using a hand crank. Firstly, insert the hand crank through the operating shaft after removing the cover. Turn it clockwise approximately 25 times until the 'spring charged' indication is visible. It is critical to use a crank with a freewheel to avoid injury from unexpected rotation if the voltage returns quickly and the motor engages . This manual process ensures that the circuit breaker can still operate independently of external power.
In the TEST position, the contact poles are disconnected, which allows for electrical interlocks to be checked and ensures that manual operations do not activate electrically without external release. The low-voltage connector can be unplugged, and while the truck is locked, the circuit breaker is in an OPEN position . In the SERVICE position, the device is physically connected to the busbar and feeder, and the low voltage connector is required to be plugged in, suitable for operational status and switching without separation . Placement in each position governs operational and safety protocols to prevent accidental engagement.
The bolting process of panels impacts both the structural integrity and safety of a switchgear installation. Panels are fastened using set-nuts and fixing tools that facilitate a secure attachment from right to left, which helps maintain alignment and structure . Proper bolting ensures the panels remain stable under operational stresses and during assembly. Post-assembly checks should include ensuring pressure relief ducts are properly assembled after bolting main busbars, further ensuring that safety protocols are observed during fault conditions . Securely bolted panels are essential to maintain overall system stability and safety.
For the storage of switchgear, it is crucial to provide adequate ventilation, protect against humidity, and ensure the storage ground can support the weight. Indoors, prevent unpacked small parts from corrosion if they are stored longer. For outdoor storage in seaworthy crates, place all crates on planks and ensure the area is protected from water, pollution, and pests . After six months, the desiccant agent used for humidity control should be regenerated by professionals .
The installation environment significantly affects preparations for switchgear setup, requiring detailed information about site conditions. This includes the layout of the installation room, accessibility from roads, internal transport routes, and availability of lifting equipment . These considerations dictate the feasibility of moving and placing large components and ensure that the environment supports efficient and secure setup. Additionally, the environment must accommodate specified temperature and humidity requirements to prevent equipment damage and ensure optimal performance . Proper environmental preparation ensures safety and operational effectiveness.
Mechanical interlocks prevent potentially hazardous operations by ensuring that certain conditions are met before allowing actions. For circuit breakers, the low-voltage plug connector must be engaged, the switching device truck must be in the TEST or SERVICE position, and the high-voltage door must be appropriately closed . The feeder earthing switch can only be operated when the truck is in the TEST position, ensuring that the circuit is open during potential grounding operations . This prevents simultaneous connection to power and ground, which could cause serious safety hazards.
Contact time in a 3AH series vacuum circuit breaker is critical as it defines the duration between the contact closure in the first pole and the separation of contacts in all poles during a make-break operation. This timing affects the reliability and safety of the circuit operation, particularly in high voltage applications, as it determines how quickly a circuit can break or make under load conditions . Proper synchronization of all poles ensures minimal arcing and operational efficiency.