Technical data sheet                                                                   SFA-S2
Rotary actuator fail-safe for adjusting
dampers in technical building installations
• Air damper size up to approx. 4 m²
• Torque motor 20 Nm
• Nominal voltage AC 24...240 V /
DC 24...125 V
• Control Open/close
• with 2 integrated auxiliary switches
 Technical data
                                 Electrical data    Nominal voltage                                  AC 24...240 V / DC 24...125 V
                                                    Nominal voltage frequency                        50/60 Hz
                                                    Nominal voltage range                            AC 19.2...264 V / DC 21.6...137.5 V
                                                    Power consumption in operation                   7W
                                                    Power consumption in rest position               3.5 W
                                                    Power consumption for wire sizing                18 VA
                                                    Auxiliary switch                                 2 x SPDT, 1 x 10% / 1 x 11...100%
                                                    Switching capacity auxiliary switch              1 mA...3 A (0.5 A inductive), DC 5 V...AC 250 V
                                                    Connection supply / control                      Cable 1 m, 2 x 0.75 mm²
                                                    Connection auxiliary switch                      Cable 1 m, 6 x 0.75 mm²
                                                    Parallel operation                               Yes (note the performance data)
                               Functional data      Torque motor                                     20 Nm
                                                    Torque fail-safe                                 20 Nm
                                                    Direction of motion motor                        selectable by mounting L/R
                                                    Direction of motion fail-safe                    selectable by mounting L/R
                                                    Manual override                                  by means of hand crank and locking switch
                                                    Angle of rotation                                Max. 95°
                                                    Angle of rotation note                           can be limited by adjustable mechanical end
                                                                                                     stop
                                                    Running time motor                               75 s / 90°
                                                    Running time fail-safe                           <20 s @ -20...50°C / <60 s @ -30°C
                                                    Sound power level, motor                         45 dB(A)
                                                    Mechanical interface                             Universal shaft clamp 10...25.4 mm
                                                    Position indication                              Mechanical
                                                    Service life                                     Min. 60'000 fail-safe positions
                                    Safety data     Protection class IEC/EN                          II, reinforced insulation
                                                    Protection class UL                              II, reinforced insulation
                                                    Protection class auxiliary switch IEC/EN         II, reinforced insulation
                                                    Degree of protection IEC/EN                      IP54
                                                    Degree of protection NEMA/UL                     NEMA 2
                                                    Enclosure                                        UL Enclosure Type 2
                                                    EMC                                              CE according to 2014/30/EU
                                                    Low voltage directive                            CE according to 2014/35/EU
                                                    Certification IEC/EN                             IEC/EN 60730-1 and IEC/EN 60730-2-14
                                                    UL Approval                                      cULus according to UL60730-1A, UL60730-2-14
                                                                                                     and CAN/CSA E60730-1
                                                                                                     The UL marking on the actuator depends on
                                                                                                     the production site, the device is UL-compliant
                                                                                                     in any case
                                                    Type of action                                   Type 1.AA.B
www.belimo.com                                     SFA-S2 • en-gb • 2022-12-06 • Subject to change                                            1/4
                                                     Technical data sheet                                                                  SFA-S2
                                   Safety data     Rated impulse voltage supply / control           4 kV
                                                   Rated impulse voltage auxiliary switch           2.5 kV
                                                   Pollution degree                                 3
                                                   Ambient humidity                                 Max. 95% RH, non-condensing
                                                   Ambient temperature                              -30...50°C [-22...122°F]
                                                   Storage temperature                              -40...80°C [-40...176°F]
                                                   Servicing                                        maintenance-free
                                       Weight      Weight                                           2.3 kg
                                                            Safety notes
                                                  • This device has been designed for use in stationary heating, ventilation and air-conditioning
                                                    systems and must not be used outside the specified field of application, especially in aircraft or
                                                    in any other airborne means of transport.
                                                  • Outdoor application: only possible in case that no (sea) water, snow, ice, insolation or
                                                    aggressive gases interfere directly with the device and that it is ensured that the ambient
                                                    conditions remain within the thresholds according to the data sheet at any time.
                                                  • Caution: Power supply voltage!
                                                  • Only authorised specialists may carry out installation. All applicable legal or institutional
                                                    installation regulations must be complied during installation.
                                                  • The device may only be opened at the manufacturer's site. It does not contain any parts that
                                                    can be replaced or repaired by the user.
                                                  • Cables must not be removed from the device.
                                                  • To calculate the torque required, the specifications supplied by the damper manufacturers
                                                    concerning the cross-section, the design, the installation situation and the ventilation
                                                    conditions must be observed.
                                                  • The two switches integrated in the actuator are to be operated either on power supply voltage
                                                    or at safety extra-low voltage. The combination power supply voltage/safety extra-low voltage
                                                    is not permitted.
                                                  • The device contains electrical and electronic components and must not be disposed of as
                                                    household refuse. All locally valid regulations and requirements must be observed.
 Product features
                          Mode of operation        The actuator is equipped with a universal power supply module that can utilise supply voltages
                                                   of AC 24...240 V and DC 24...125V.
                                                   The actuator moves the damper to the operating position at the same time as tensioning the
                                                   return spring. The damper is turned back to the fail-safe position by spring force when the
                                                   supply voltage is interrupted.
                     Simple direct mounting        Simple direct mounting on the damper shaft with a universal shaft clamp, supplied with an anti-
                                                   rotation device to prevent the actuator from rotating.
                             Manual override       By using the hand crank the damper can be actuated manually and engaged with the locking
                                                   switch at any position. Unlocking is carried out manually or automatically by applying the
                                                   operating voltage.
                 Adjustable angle of rotation      Adjustable angle of rotation with mechanical end stops.
                    High functional reliability    The actuator is overload protected, requires no limit switches and automatically stops when the
                                                   end stop is reached.
                           Flexible signalling     The actuator has one auxiliary switch with a fixed setting and one adjustable auxiliary switch.
                                                   They permit a 10% or 11...100% angle of rotation to be signaled.
 Accessories
                        Electrical accessories     Description                                                                  Type
                                                   Auxiliary switch 2 x SPDT                                                    S2A-F
                                                   Feedback potentiometer 200 Ω                                                 P200A-F
                                                   Feedback potentiometer 1 kΩ                                                  P1000A-F
www.belimo.com                                    SFA-S2 • en-gb • 2022-12-06 • Subject to change                                            2/4
                                                  Technical data sheet                                                                SFA-S2
                      Mechanical accessories    Description                                                                 Type
                                                Shaft extension 240 mm Ø20 mm for damper shaft Ø 8...22.7 mm                AV8-25
                                                End stop indicator                                                          IND-AFB
                                                Shaft clamp reversible, for central mounting, for damper shafts Ø12.7 /     K7-2
                                                19.0 / 25.4 mm
                                                Ball joint suitable for damper crank arm KH8 / KH10, Multipack 10 pcs.      KG10A
                                                Ball joint suitable for damper crank arm KH8, Multipack 10 pcs.             KG8
                                                Damper crank arm Slot width 8.2 mm, clamping range Ø10...18 mm              KH8
                                                Actuator arm, for 3/4" shafts, clamping range Ø10...22 mm, Slot width 8.2   KH-AFB
                                                mm
                                                Form fit insert 10x10 mm, Multipack 20 pcs.                                 ZF10-NSA-F
                                                Form fit insert 12x12 mm, Multipack 20 pcs.                                 ZF12-NSA-F
                                                Form fit insert 15x15 mm, Multipack 20 pcs.                                 ZF15-NSA-F
                                                Form fit insert 16x16 mm, Multipack 20 pcs.                                 ZF16-NSA-F
                                                Mounting kit for linkage operation for flat and side installation           ZG-AFB
                                                Base plate extension                                                        Z-SF
                                                Anti-rotation mechanism 230 mm, Multipack 20 pcs.                           Z-ARS230L
                                                Hand crank 63 mm                                                            ZKN2-B
 Electrical installation
                                                Caution: Power supply voltage!
                                                Parallel connection of other actuators possible. Observe the performance data.
 Wire colours:
 1 = blue
 2 = brown
 S1 = violet
 S2 = red
 S3 = white
 S4 = orange
 S5 = pink
 S6 = grey
 Wiring diagrams
 AC 24...240 V / DC 24...125 V, open/ Auxiliary switch
 close
www.belimo.com                                 SFA-S2 • en-gb • 2022-12-06 • Subject to change                                           3/4
                                       Technical data sheet                                                                 SFA-S2
 Operating controls and indicators
                                       Auxiliary switch settings
                                               Note: Perform settings on the actuator only in deenergised state.
                                       For the auxiliary switch position settings, carry out points 1 to 7 successively.
                                        1   Manual override
                                            Turn the hand crank until the desired switching position is set.
                                        2   Shaft clamp
                                            Edge line A displays the desired switching position of the actuator on the scale.
                                        3   Fasten the locking device
                                            Turn the locking switch to the „Locked padlock“ symbol.
                                        4   Auxiliary switch
                                            Turn rotary knob until the notch points to the arrow symbol.
                                        5   Unlock the locking device
                                            Turn the locking switch to the „Unlocked padlock“ symbol or unlock with the hand
                                            crank.
                                        6   Cable
                                            Connect continuity tester to S4 + S5 or to S4 + S6.
                                        7   Manual override
                                            Turn the hand crank until the desired switching position is set and check whether the
                                            continuity tester shows the switching point.
 Dimensions
 Spindle length
                       Min. 85
                       Min. 15
 Clamping range