1 Installation
DANGER
Please install the equipment in the fire-retardant materials (like metal) to prevent fire!
Keep it away from flammable material to prevent fire!
CAUTION
Prevent the lead head or screw from dropping into it to avoid causing damage to the controller!
Install the controller into the place where there is little libration and no direct sunlight.
Install the equipment into the weight-durable places to prevent injuries caused by the dropping of
the equipment.
Do not make the installation if the controller is found broken during unpacking!
Do not make the installation if the shipping list is inconsistent with the goods!
Handle with care; otherwise it may cause damage to the equipment!
Do not touch the elements of the controller with your hands; otherwise it may cause the
electrostatic damage!
2 Wiring
DANGER
The instruction of this manual must be obeyed. The constructions must be carried out by the
professional electrical engineering staffs to prevent from getting an electric shock or injury!
There must be a breaker between the controller and power supply, or it may cause fire!
Please carry out the correct standard earthing of the controller following the specification;
otherwise there may be the risk of getting an electric shock!
CAUTION
The input power supply must not be connected to the output terminals (U, V, W) of the controller.
Pay attention to the marker of the wiring terminals, and do not make the wrong wiring! Otherwise
it may cause the damage to the controller! Make sure that the wiring configuration is complied
with EMC requirements and the local safety standards. Otherwise it may cause accidents!
The communication line must be STP, the lay of which is 20~30 mm, and the shielding layer must
be grounded.
Make sure that the nominal voltage of the product is the same with that of the alternating current
power supply so as to avoid the injury and fire!
Pay attention to check if there is short in the peripheral circuit connected to the controller and
whether the connected circuit is fastened. Otherwise it may cause damage to the controller!
No part of the controller should take withstand test, as the product has taken it in the factory.
Otherwise it may cause accidents!
3 Power-on
DANGER
The controller can only be powered on after the cover board be put in place. Do not open the
cover board after power-on. Never touch any input and output terminal of the controller, or you
may get an electric shock!
All the wirings of the peripheral fittings must be complied with the instruction of this manual, and
be carried out correctly following the circuit connection method provided in this manual.
Otherwise it may cause accidents!
Never change the controller manufactory parameter at will. Or it may cause damage to the
equipment!
Non-professional technician shall be forbidden to detect the signal during the operation.
Otherwise it may cause damage to the people or the equipment!
4 Maintenance, inspection and replacement of components
DANGER
Please do not repair or maintain the equipment lively. Or you may get an electric shock!
Personnel without professional training shall not be allowed to repair or maintain the controller.
Otherwise it may cause damage to the people or the equipment!
The parameter setting must be done after changing the controller; all of the plug-pull plug-ins
must be plugged and pulled with the power off.
The input power needs to be cut off during the maintenance and inspection, do it 5 minutes later
to avoid getting an electric shock.
5 Usage beyond nominal voltage
If the external voltage is not within the allowable working voltage range specified in the manual,
using the controller may cause damage to its parts easily. If it is required, please make a transformation
using the corresponding voltage-boosting or voltage-reducing devices.
Jarless-CON center-opening permanent magnetic VVVF door operator is a doors driving system,
which adopts permanent-magnet synchronous motor drive and stepless speed regulation and
frequency conversion control. The product is highly efficient, reliable and easy to operate. It can reach
the optimum door opening/closing speed curve with low mechanical shock. Jarless-CON
center-opening permanent magnetic VVVF door operator is applicable for a door system with a
700-1200mm net width of door opening.
Its main features are as follow:
1 (Stationary) autotuning of synchronous motor rotational angles
2 Autotuning of door width
3 Automatic opening/closing door demonstration
4 Fault alarm and automatic protection function
5 Optional baffle detection function
6 Synchronous and asynchronous door cutter selection function
7 Function of leveling and pulling the door under power
Jarless-con center opening permanent magnetic VVVF door operator is driven by a permanent
magnetic synchronous motor with synchronous belt drive. It controls the opening and closing door
operation by applying the stepless speed regulation and frequency conversion control technology.
While the synchronous belt is driving, it forces the hanging board of the door to move. And the hanging
board is connected with the car door, so the opening and closing operation of the car door is controlled
in this way.
To install a swing-boom asynchronous door cutter: The swing-boom asynchronous door cutter should
be installed on the car door and its swing boom should be connected with the cam handle of the
movable cutter blade. While the car door is operating, with the effect of the swing boom, the cam
handle of the movable blade shall force the movable blade to fold with the fixed blade and clip the roller
of the landing door lock hook, so that the landing door lock unit is opened and the landing door moves
in this way; In the moving process of the door, the door cutter clips the roller tightly all the time; After the
door is closed to the full position, with the effort of the swing-boom, the door cutter will open and
release the roller. In this way, the lock hook will lock up the landing door and car may separate from the
landing door.
To install a synchronous door cutter: The synchronous door cutter should be installed on the hanging
board of the door operator. When the car door is moving, the two blades will simultaneously clip the
roller of the landing door lock hook with the effect of the synchronous belt, so the landing door lock unit
is opened and forces the landing door to move. In the moving process of the door, the door cutter will
clip the roller tightly all the time. After the door is closed to the full position, the cutter will open under the
effort of the door cutter accessories and the car may leave the landing door at this time.
To install an integrated pulling protection asynchronous door cutter: The door cutter should be
installed on the hanging board of the door operator. The movable blade is fixed on the door cutter base
by the link and the link shaft. And a roller assembly is mounted on the movable blade, so when the car
door is operating, this roller assembly will force the movable blade to fold with the fixed blade under the
effect of the door cutter accessories and clip the roller of landing door lock hook to open the landing
door lock unit and force the landing door to move. In the moving process of the door, the door cutter
clips the roller tightly all the time. After the door is closed to the full position, the roller assembly of the
asynchronous door cutter will open under the effect of the door cutter accessories and release the roller
and lock the landing door with the lock hook. The pulling protection theory is as follow: The pulling
protection door cutter of the integrated pulling protection asynchronous door cutter is fixed on the door
cutter base through the joint arm and shaft. Also there are pulling protection hooks mounted on it. When
the door is closed and under the leveling condition, the pulling protection hook is separated from the
hook on the pulling protection accessories because of the effect of unlock roller assembly mounted on
the head of the hall door and the pulling protection door cutter, and then the door operator can be
opened. In the opening process of the door operator, the pulling protection door cutter will make
tangential translation movement but no vertical movement under the action of the unlock roller
assembly mounted on the head of the hall door. However, when the door is closed but not under
leveling condition or is ±260mm away from the leveling position, if there is external force (human
pulling force) acting on the door operator, the car door will be opened gradually. In this process the
pulling protection door cutter will move vertically for some time under the effects of the tangential
translation movement of hanging board of the door operator and its own gravity. At this time the hook on
the pulling protection door cutter will joggle gradually with the hook on the pulling protection
accessories. At last, when the door board is pulled apart for a certain distance (100 mm max.), the hook
on the pulling protection door cutter will hook on to the hooks on the pulling protection accessories, in
which case the door board will be impossible to be pulled open.
2 Installation instruction for door operators
General illustration of door operator installation: see Figure 2-1, Figure 2-2, and Figure 2-3
Door operator
non-integrated car)
or 405 (with
Hanging
board
Rail
Straight
HH (net height of
door opening)
Swing-boom asynchronous door cutter beam
OP (net width of
door opening)
Car door sill line
Maximum space A
between bearings
Door operator
non-integrated car)
or 405 (with
Hanging board
opening)
Integrated pulling protection Straight beam
asynchronous door cutter
Cross Cross
bar
Adjusting bolt
bar
Car straight
beam
紧固螺栓 bolt
Fastening
Upright
Fastening bolt
轿门地坎线
Car door sill line
Car base
Mounting bracket
platform
of door operator
120
Car straight beam
Fastening bolt
Mount the two cross bars with fastening bolts on the car straight beam respectively and hold
the car straight beam with adjusting bolts. Then fix both ends of the two ties respectively on the cross
bars and straight beam with the draw hook, and fasten them with nuts. And then mount the two door
operator mounting boards on the two cross bars respectively and fasten them with bolts. See Figure
2-5 Draw hook
Tie
Fastening
bolt Fastening
bolt
Adjusting bolt
Mounting plate of
door operator
Cross bar
Car straight
beam beabeam
Figure 2-5 Installation of the tie and cross bar of door operator
2.2.1.3 Installation of the car roof
Fix the car roof mounting bracket of door operator on the C type slot on the car roof with
fastening bolts. See Figure 2-6
Figure 2-6 Installation of mounting bracket of door operator (installation of the car roof)
2.2.2 Installation and adjustment of Jarless – con door operator
The connecting bolts should be mounted into the mounting holes on the door head of the door
operator in advance. Then connect the door operator and its mounting bracket with connecting bolts.
Adjust the position of the door operator after installation. It is required that the door operator rail should
be parallel to the car door sill. Also, the door operator should be kept vertical by checking with
plumbline. Splines can be used to keep parallelism. The bias of parallelism and verticality should be
limited to less than 1 mm. Adjust simultaneously both the door operator center and exit and entrance
center to make them match; Adjust the height of the door operator to make sure it is suitable for
installation of door plate. See Figure 2-7 Installation illustration of upright of door operator, Figure 2-8
Installation illustration of straight beam of door operator, and Figure 2-9 Installation illustration of car
roof of door operator
Connecting
Connecting bolt bolt
Connecting bolt
Connecting bolt
Connecting bolt
Connecting bolt
Connecting
bolt
Connecting
bolt
Figure 2-9 Installation illustration of car roof of door operator
First mount the slide block as shown in Figure 2-10. Then adjust the clearance between the eccentric
and door rail. The clearance should be limited within the range of 0.2 to 0.5 mm.
Measure it with a clearance gauge. See Figure 2-11
Adjusting gasket
Slide block
Downward
idle wheel
Gasket
1. Check and adjust the verticality of the door board with a plumbline to limit the difference within 1 mm.
See Figure 2-13
a’-a ≤1mm.
Figure 2-13 Front view of the car door Figure 2-14 Side view of the car door
configuration configuration
2. The clearance between the car door leaf bottom and the sill surface is 3 to 6 mm, and the clearance
between the car door leaf and the front wall of the car is 4 to 6 mm (the clearances of both sides differ
by less than 1 mm); See Figure 2-14 side view of the car door configuration.
3. The clearance between door leafs are less than 2 mm (i.e. a, a’≤2mm.). Besides, the clearances on
the upper part and the lower part should be uniform (i.e. a’-a ≤0.5mm.). See Figure 2-15 Front view of
the car door configuration
4. The lapping distance of two door leaves should be shorter than 1 mm when the center-opening door
is shut. See Figure 2-16 Top view of the car door configuration
a’≤2mm;
a≤2mm;
a’-a ≤0.5mm.
Figure 2-15 Front view of the car door Figure 2-16 Side view of the car door
configuration configuration
5. After adjusting, fix all the bolts and push the car door to make sure that the car door can slide
smoothly.
6. When the car door is opened completely, the front wall of the car should be flush with the car door.
2.2.4.1 Installation of the synchronous door cutter of integrated car door lock
As is shown in figure 17,the synchronous door cutter of integrated car door lock is installed with
fastening bolts on the hanging board of the door operator .
a. Determine the distance between the door fixed ball and the position A in the center of the
door
b. Under the free state of the door cutter, adjust the right blade to A position
c. Adjust the top of the door knife accessories to make it flush with the scale, ensure hook
clearance 2~3mm.
d. Adjust the verticality of the door knife and the location of the pin to ensure the pin has been
inserted into the middle of the socket
d. Fixed the unlock wire rope to the lower part of the car panel
Figure 2-17
When there is much resistance of operation, adjust the clearance of the lower roller of the hanging
board and the rail to 0.1~0.3 mm as shown in Fig. 2-18 to make the door open and close smoothly.
Roller of the
hanging board
Gradient of door hanging
board (A-B): within ± 1
Rail
A=4±1
0.3
~
0.1
Power supply
Power supply
P2-7 0V
3.2 Outside view of the controller
Note: Those solid circles in the figure represent indicators for corresponding
functions
Power: Constantly on when the power is normal
Preparation/ fault light: Glint when it is normal, constantly on when fault occurs.
Door closed limit input: When the door reaches closed limit, the arrival switches signal inputs, and
the light is on.
Open door input: The opening signal light is constantly on as there is opening signal
Close door input: The closing signal light is constantly on as there is closing signal
Door opened limit output: When the door reaches the opened limit, the light is on, and the
transducer outputs the signal of reaching the opened limit.
Door closed limit output: When the door reaches the closed limit, the light is on, and the transducer
outputs the signal of reaching the closed limit.
Fault output: As fault happens, the light is on, and the transducer outputs the fault
signal.
Protective output: The light is off when there is no motor output, and constantly on when
there is motor output.
3.3 Buttons, knobs and DIP switches
3.3.1 Buttons and DIP switches
Tuning button
learn button
From right to left:
SW1, SW2, SW3, SW4
Running button
run button
3.3.2 Knobs
Operation
parameter display
Down
Value
increase
Up
Value
decrease
Not used
Parameter
settings
1、 Checking parameters
Plug the connecting line into the operator and the Jarless-con transducer and the display at this time is
shown as bellow:
Press the DOWN key , and the operation parameters of the motor will displayed in order. These
parameters are only readable and can not be changed. Refer to Tab. 3-1 for definition of these
parameters.
ESC
2、 Modification of parameters
ESC
This is the interface of the F0 parameter group. In this case, if is pressed, the display will be:
If it's necessary to modify the numbers in the F parameter group (for example modification of F0), press
FUN
SET
the function setting key , and the display will change into the following condition:
This interface means entering into the first parameter in the F0 parameter group.
FUN
SET
① If it’s necessary to check or m odify this parameter, press the function setting key again, and
the display will be
speed
door movement
door closed limit Door opened limit
Limit hold
distance
speed
Limit hold
door movement
door opened
limit door closed
Limit hold
distance
closing signal
opening signal
pulse limit
pulse limit
creepage distance of door and
distance of door cutter movement
Diagram of closing door curve synchronous door cutter > 36mm
asynchronous door cutter > 16mm
speed
time
reopening curve
3.6 Parameter list
Function Name Setting range Default
No.
Monitoring parameter group (server menu 311)
0 Software version
1 Operation frequency 0~50.00 ※
2 Motor rotation speed ※
3 Rotor position 0~359.9 ※
4 Given velocity ※
5 Given output voltage 0~900V ※
6 Given torque current 1.0-> rated torque ※
7 Output current 0~999.9A ※
8 Upper digits of run count ※
9 Lower digits of run count ※
10 DC busbar voltage 9999v ※
11 Encoder position 0~65536 ※
12 UVW position 00 ※
13 Current position 00000 ※
14 INPUT 1 ※
15 INPUT 2 ※
16 Open door input ※
17 Close door input ※
18 Stop ※
F0 (server menu 3311)
Field adjustment parameter Field Adjust) EEPROM
F0-0 Obstruction contact memory 0: disabled 无效
function 1: enabled
F0-1 Running direction reverse 0,1 SW1
F0-2 RUN command source 0~7 4
F0-3 Door range 0~65535 ■
F0-4 Running distance at low 0~100 5
speed of opened door arrival
F0-5 Open Startup unlock speed 5~150mm/s 120
F0-6 Open Startup unlock distance 0~300mm 50
F0-7 Open Acceleration speed 10~2048mm/s/s 1000
F0-8 Open Acceleration fillet 10~2048mm/s/s/s 1000
F0-9 Open Deceleration speed 10~2048mm/s/s 800
F0-10 Open Deceleration fillet 10~2048mm/s/s/s 800
F0-11 Close Arrival speed 5~100mm/s 20
F0-12 Running distance at low 5~100 55
speed of closed door arrival
F0-13 Close Acceleration speed 10~2048mm/s/s 800
F0-14 Close Acceleration fillet 10~2048mm/s/s/s 800
F0-15 Close Deceleration speed 10~2048mm/s/s 600
F0-16 Close Deceleration fillet 10~2048mm/s/s/s 600
F0-17 Close Startup unlock speed 5~150mm/s 35
F0-18 Close Startup unlock distance 0 ~ 30.0% relay vibration resistance 0
F0-19 Password 0~9999 8888/1234
F1 (server menu 3312)
Regulator parameter Regulator)
F1-0 Proportion gain 1 (high 0~10000 400
speed)
F1-1 Integration gain 1 (high 0~10000 300
speed)
F1-2 Proportion gain 2 (low speed) 0~10000 400
F1-3 Integration gain 2 (low speed) 0~10000 300
Function Name Setting range Default
No.
F1-4 PI transferring threshold value 0~100 5
F1-5 PI transferring band width 0~100 5
F1-6 Speed feedback filter 0~66 (high and low) 33
F1-7 Given proportional part filter of 0~3 0
the torque reference
F1-8 Coupler Speed 0~200 50
F1-9 Control method 0:VF 2
1: Asynchronous motor closed loop
2: Synchronous motor
F1-10 Feedback speed calculation 0: High and low levels are different 1
1: High speed agrees
F1-11 Current loop KP 0~9999 512
F1-12 Current loop KI 0~9999 150
F1-13 Electric torque limit (open 0.00~2.50 2.50
door)
F1-14 lern Limit PU 0.00~2.50 1.50
F1-15 Electric torque limit (close 0.00~2.50 2.50
door)
F1-16 reset Limit PU 0.00~2.50 1.50
F1-17 Motor overload protection 0.1~2.0 1.2
factor
F1-18 PVT protection sensitivity 0~10 0
factor 0:disable
The larger the value is, the lower
the sensitivity is.
F2 (server menu 3313)
Motor parameter Motor Parameters)
F2-0 Motor power 0.1~999.9 W 43.5
F2-1 Number of poles 2~100 016
F2-2 Motor rated rotation speed 1~9999 0180
F2-3 Motor rated frequency 1.00Hz~99.99Hz 24.00
F2-4 Motor rated voltage 0~999V 100
F2-5 Rated current 1.0~999.9 000.8
F2-6 Sheave_d 10~10000mm 00045
F2-7 gear_ratio 1.0~100.0 001.0
F2-8 Rope 1~6 1
F2-9 Magnetic pole original angle 0~65535 ■
F2-10 Stator resistor 0.000~9.999 ohm 7.730/2.790
F2-11 Stator inductance 0.0~999.9mH 357.0/252.4
F2-12 Rotor resistor 0.000~9.999 ohm 5.230/1.820
F2-13 Rotor inductance 0.0~999.9mH 357.0/252.4
F2-14 Mutual inductance 0.0~999.9mH 325.0/240.6
F2-15 No-load current 0.0~999.9A 001.0/2.7
F3 (server menu 3314)
Drive parameter Drive Scaling Parameters)
F3-0 Drive No. 0~100 000
F3-1 Rated voltage 0~1000 0220
F3-2 Rated current 0.0~999.9 002.5
F3-3 Current adjusting coefficient 0.000~9.000 1.600
F3-4 Voltage adjusting coefficient 0.000~9.000 1.050
F3-5 Current limit (overcurrent) 0.0~999.9 005.0
F3-6 Busbar overvoltage point 0.00~2.00 1.6
F3-7 Busbar undervoltage point 0.00~1.00 0.60
F3-8 Input voltage coefficient 0.00~2.00 1.00
F3-9 Brake voltage 0.00~1.00 0.35
Function Name Setting range Default
No.
1.00:1000V
F3-10 Dead time 2~20 03
F3-11 PWM compensation 0.00~2.00 1.00
F3-12 Overshoot factor 0~100 100
F3-13 Carrier frequency 2~10 KHz 10
F3-14 Running time (hour) 0~65535 H should be saved with ※
power down
F3-15 Running time (minute) 0~59 MIN should be saved with ※
power down
F4 (server menu 3315)
Enhanced parameter Enhanced Parameters)
F4-0 Open/close operation hold 0~99.9s 00.0
time 0: keep continuous operation
Others: stop when the time is up
F4-1 Power on operation speed 10~100mm/s 0100
F4-2 Door range detection speed 10~100mm/s 0100
F4-3 Close arrival respond time 200~3000ms 1400
F4-4 Open arrival respond time 500~3000ms 800
Hold torque after arrival
F4-5 Arrival signal setting 0:with open arrival and close arrival 1
1:without open arrival but close
arrival
2:without open arrival or close
arrival
F4-6 Open Hold torque 0~200.0% 100.0%
F4-7 Close Hold torque 0~200.0% 60.0%
F4-8 Baffle detection identification 0~999ms 200
time 0:No function
F4-9 Baffle torque at high speed 0~200.0% 180.0%
Baffle torque during acceleration
F4-10 Close Retarding torque at 0~200.0% 160.0%
constant speed Retarding torque for when ACC = 0
F4-11 Baffle torque at low speed 0~200.0% 150.0%
Baffle torque during deceleration
F4-12 RY1 function selection 0: open arrival signal (switch or 0
F4-13 RY2 function selection pulse) 7
1: close arrival signal (switch or
pulse)
2: fault output
3: baffle detection output
4: open door output
5: close door output
6: limited open arrival signal
7: Delay 1.0S output after close
limit
8: Delay 0.5S output after close
limit
9: Direct output while close limit
F4-14 Power on mode 0: Listen to the system command 2
1: Self closing
2: If you don't have an order, close
the door first. If you have an order,
listen to the system
F4-15 Open Arrival position 0~1000mm 5
F4-16 Open Speed 0~1000mm/s 508
Function Name Setting range Default
No.
F4-17 Open Arrival speed 5~100mm/s 020
F4-18 Door cutter selection 0:Asynchronous door cutter 3
1:Synchronous door cutter
3: Synchronous door cutter of
integrated car door lock
F4-19 Close Arrival position 0~1000mm 5
F4-20 Close Speed 0~1000mm/s 508
F4-21 Reverse open door 500~9999mm/s/s 5000
Deceleration speed
F4-22 Reverse open door 500~9999mm/s/s/s 5000
Deceleration fillet
F4-23 Demonstration door open 0~999.9s 003.0
hold time
F4-24 Demonstration door close 0~999.9s
hold time 003.0
F4-25 Manual acceleration 10~2048mm/s2 0300
F4-26 Manual deceleration 10~2048mm/s2 0500
F4-27 Manual speed 0~999mm/s 0050
F4-28 Master and slave status 0:Master status. Reopening door is 0
setting possible
1:Slave status. Reopening door is
impossible
F4-29 Empty 0 00000
F5 (server menu 3316)
(VF parameter)
F5-0 AD OFFSET mode 0~2 0
F5-1 Torque boost 0~2.5PU 1.50
F5-2 Automatic reset time of raking 0~100s
door 35
F5-3 AD OFFSET W 0~5000 1860
F5-4 AD OFFSET V 0~5000 1860
F5-5 Filtering time of leveling signal 0~9999ms 800
F5-6 Force open EN 0: DISABLE 1
1: ENABLE
F5-7 Error Reset time ms 1000~9000 5000
F5-8 Power on DCL dly ms 0~9000 0
F5-9 Reset torq time ms 0~3000 500
F5-10 DCL out mask EN 0~1 1
Part number Type Color The best value of PI Pole Frequent bracket
XTA4522AAL BM14743 Black 1500、800、1500、800 8 12 XTA4138BHX
XTA4522ABM BM14794 Black 1500、800、1500、800 8 12 ——
XTA4522ABN PM81842 Slicery 1000、800、1000、800 16 24
white
XTA4138CJT
XTA4522ABT PMM2.3G Slicery 1000、800、1000、800 16 24
white
XTA4522ABV PM81855 Slicery 1000、800、1000、800 16 24
white
XTA4138CYK
XTA4522ABX PMM5.0G Slicery 1000、800、1000、800 16 24
white
3.7 Checking fault
Check the fault code (F6) with the operator. See the following table for common fault related information
(code of common fault):
Operator Name of
serial No. correspondent Possible cause Solution
fault
1 1, Transducer has foreign objects
1, Clear away the foreign
dropping into it
BASE FAULT objects
2, Any two of the three phases of
2, Check motor power line
the motor is short circuit
4 1, Encoder circuit of transducer is
1, Replace transducer
abnormal
PVT lost 2, Check encoder connecting
2, Connection wire of encoder is
wire
disconnected or short circuit
5 1, Something suffocates the
process of opening and closing 1, Check for foreign objects or
MOTOR
door mechanical blockage
OVERLOAD
2, Motor lacks phase during 2, Check motor power line
running of door operator
7 1, Input voltage is too high
1, Check input power supply
DC link OVT 2, Any one of the three phases of
voltage
motor is short connected to
2, Check motor power line
ground
8 Check the input power supply, it
POWER LOST Input power supply is low
should be AC 220 V±20%
3.8 Failure Diagnosis
The door operator 1、If power switch is turned on
displays no power 2、Measure the voltage between L and N in P5 and confirm it's
supply AC220V.
Check condition of 1、Frequency converter is outage
motor 2、Pull three-prong of motor out
3、Measure the resistances in every two phases with multi meter.
If the motor is 2.3N*M, then the resistance is 42Ω;If the motor is
5N*M, then the resistance is 37Ω. Value is too large or too
small, then the motor is damaged.
4、Resistances of each phase to the earth is infinitely great. If not,
then the motor is damaged.
5、Rotating pulley manually is smooth and no jammed
Check if encoder on 1、Observe if PVT LOST failure is alarmed from frequency
motor is normal converter , and if it's alarmed, then there is a failure in encoder.
2、Check if the encoder and frequency converter contacts poorly
with a multi meter.
3、Open the cover of motor encoder and check if the bonding wire
of encoder is disconnected.
4、Check if there is a failure in the frequency converter or encoder
with interchange method until the PVT LOST failure is not
alarmed. The frequency converter must be connected to
AC220V and encoder.
Alarming failure on 1、Turn power off for 10 seconds and turn it on then, check if the
frequency converter frequency converter is normal.
2、Observe the ready/failure light, , if it's normally on, then there is
a failure in frequency converter.
Operator can't work The 1、Output light of motor protection is normally on
after adjustment condition 2、Running mode is upper machine control mode
of 3、Either opening or closing input light is normally on.
judgment
Situation Both of 1,2,3 are not satisfied, then change running
1 mode into upper machine control mode, and output
light of motor protection will be normally on. Then
check if the signal from system has sent to door
operator.
Situation 1,2 are satisfied and 3 is not, then check if the signal
2 from system has sent to door operator. Pull out CJ1,
then jump out P2-1and P2-2 to see if the door is
opened, and jump out P2-1and P2-3 to see if the door
is closed. Diagnose if it's problems of system signal
by this way.
Situation 1 is satisfied and 2,3 are not, then change running
3 mode into upper machine control mode and check if
the signal from system has sent to door operator.
Situation 3 is satisfied and 1,2 are not, then change running
4 mode into upper machine control mode
Situation 1,2,3 are all satisfied,the door is not opened by door
5 operator when it receives a opening command from
system
1、 Place the door aboard in the middle, orientation
angle is positioned again until door board moves
slightly.(If the door board is heavy, loose the belt)
Observe the ready/failure light on frequency
converter, if it's normally on, then there is a
failure. Diagnose the type of failure on server.
2、 Check if the motor is damaged according to the
above steps.
3、 Check if the motor is damaged with interchange
method
4 Maintenance
During the elevator maintenance, the door rail should be cleaned and lubricated. Also, the wear of the
door hanging board should be checked. If it exceeds 1.5 mm, adjustment or replacement should be
made in time.
a) The tightness of the synchronous belt should be adjusted regularly. The requirement for the
tightness is shown in Figure 4-1.
15N <20
a) Check if the door could be opened and closed smoothly without any unusual sound.
b) Check regularly the tightness of all the fasteners.
If any problem is found during the above mentioned checking process, measures should be taken
immediately to make sure that the door operator will operate normally.
XTA3052AAN Tension 1
components
XTA4522ABX/ Motor 1
XTA4522ABT
XTA4386ADC001 Socket 3
XTA3189AAG Retainer 4
XTA3446AAK Frequency 1
converter
Note: 1. if the customer needs the spare part of the door operator, please mark on the contract and
provide relative list of spare part.(It's necessary to purchase the spare part separately)
2. The information in this document is subject to change without notice.