This document provides details of the proposed electrical load and demand for Plot 6/B, a residential/commercial building. It includes the specification of the incoming supply rated at 250A and details of 6 outgoing distribution boards rated from 40A to 63A. The maximum demand is calculated to be 106.32kW taking a diversity of 0.9. The total connected load across the 3 phases is provided.

Uploaded by

hpzen
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
94 views

4.DB Flats (1-7) & SMDB Typical

This document provides details of the proposed electrical load and demand for Plot 6/B, a residential/commercial building. It includes the specification of the incoming supply rated at 250A and details of 6 outgoing distribution boards rated from 40A to 63A. The maximum demand is calculated to be 106.32kW taking a diversity of 0.9. The total connected load across the 3 phases is provided.

Uploaded by

hpzen
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

PROPOSED G + 7 + PH

PROJECT: DETAIL OF CONNECTED LOAD/MAX. DEMAND PLOT NO.:6/B


RESIDENTIAL / COMMERCIAL

OWNER: OWNER: H.H. SHEIKH FAISAL BIN


DB REF. SMDB-TYPICAL (1-7) LOCATION :AL MDR 2
ABDULLA AHMED AL MULLA

CONSULTANT:MODULE ENGINEERING
FED FROM: MDB LOCATION : TYPICAL FLOOR , ELEC RM
CONSULTANTS
PVC/ ECC
CIRCUIT/ SP/ RATING-AMPS FAULT CABLE SIZE CONNECTED LOAD-kW
XLPE SIZE
FEEDER DUTY IC,
TP F/S MCCB SWA/ 2/4x 2/3/4C R-PH Y-PH B-PH TOTAL 1-PH 3-PH REMARKS
DB No. kA mm2
MCB

ISO ACB CVP IC mm2 2mm


INCOMER TP 250 35 1X4CX120 1X1CX70 39.1 39.01 40.025 118.13 6

OUTGOING:
DB-101 TP 63 25 XLPE/SWA/PVC 4CX25 1C X16 8.065 6.095 7.825 21.985 1
DB-102 TP 40 25 XLPE/SWA/PVC 4CX16 1C X16 4.800 4.495 4.700 13.995 1
DB-103 TP 40 25 XLPE/SWA/PVC 4CX16 1C X16 6.465 7.570 7.310 21.345 1
DB-104 TP 40 25 XLPE/SWA/PVC 4CX16 1C X16 6.565 7.570 7.075 21.21 1
DB-105 TP 40 25 XLPE/SWA/PVC 4CX16 1C X16 4.900 5.530 5.420 15.85 1
DB-106 TP 63 25 XLPE/SWA/PVC 4CX25 1C X16 8.305 7.745 7.695 23.745 1

TOTAL CONNECTED LOAD PER PHASE 39.10 39.01 40.03 118.13


MAX.DEMAND (3PH) AT 0.9 DIVERSITY IN
106.32 TOTAL CONNECTED LOAD IN KW 118.13
KW

TEL: ..............................................................
Type of Meter (Rating of Incomer) (2) UP to 60 A(1 Phase)
(3) 125 - 160 A

(4) LV CT160/5A / HV CT .........../..............A


PROPOSED G + 7 + PH
PLOT NO.: 6/B
PROJECT: RESIDENTIAL / COMMERCIAL DETAIL OF CONNECTED LOAD/MAX. DEMAND

OWNER: H.H. SHEIKH FAISAL BIN


LOCATION :AL MDR 2
DB REF. DB-106/ 3BED RM ABDULLA AHMED AL MULLA

FED FROM: SMDB-F1 CONSULTANT: MODULE ENGINEERING CONSULTANTS DB Location: FLAT 106

LOAD PER CIRCUIT-


CONNECTED LOADS/POINTS
WATTS
MCB CCT. Wire ECC Wire
Rating Of Rating Of
SL No. CCT No. RTG. In Room / Area Watts/ Unit REMARKS
Incomer ELCB Size mm2 Size mm2
A
13A S/O C/K HD
SPOT LTG CHND LTG SHA.S/O COVE LTG CALLBELL EX. FAN 13A S/O single 15A S/O GD D/W W/H A/C FCU ISO R Y B
twin FAN

1 R1 10 2.5 2.5 LOBBY & TOILET & LAUNDRY & CORRIDOR 6\1 1 1 35\100 445

2 Y1 10 2.5 2.5 KITCHEN 2 1 1 100 400


63A
100mA 4P 3 B1 10 2.5 2.5 LIVING RM 1 300 300
ELCB
SEC. 1 4 R2 10 2.5 2.5 MAID RM & BATH 1\1\1 1 50\35\100\200 220

5 Y2 10 2.5 2.5 BED RM 1 & BATH & BALCONY 1\3\1 1 50\35\100\200 290

6 B2 10 2.5 2.5 BED RM 2 & BATH & BALCONY 1\2\1\2 1 50\35\100\200 295

63A 7 R3 10 2.5 2.5 TV RM 1 300 300


100mA 4P
ELCB 8 Y3 10 2.5 2.5 BED RM 3 & BATH 1\2\1 1 50\35\100\200 255
SEC. 2
9 B3 10 2.5 2.5 KITCHEN 1 200 200 GAS DETECTOR

10 R4 16 4.0 4.0 LOBBY 1 400 400 12U CABINET

11 Y4 16 4.0 4.0 KITCHEN 2 200 400


63A 30mA
4P 12 B4 16 4.0 4.0 LIVING RM 2 200 400
ELCB 200
13 R5 16 4.0 4.0 MAID RM & BATH 1 200
SEC. 3
14 Y5 16 4.0 4.0 BED RM 1 & BATH 1 200 200

15 B5 16 4.0 4.0 BED RM 2 & BATH 1 200 200

16 R6 16 4.0 4.0 TV RM 1 200 200


63 A TPN ISOLATOR

17 Y6 16 4.0 4.0 BED RM 3 & BATH 1 200 200


63A 30mA
4P 18 B6 20 4.0 4.0 BED RM 1 BATH 1 1500 1500 WATER HEATER
ELCB
19 R7 20 4.0 4.0 LAUNDRY 1 1500 1500
SEC. 4
20 Y7 20 4.0 4.0 KITCHEN 1 1500 1500 FRIDGE

21 B7 SPACE FRIDGE

22 R8 SPACE

23 Y8 20 4.0 4.0 BED RM 2 BATH 1 1500 1500 WATER HEATER


63A 30mA
4P 24 B8 20 4.0 4.0 BED RM 3 BATH 1 1500 1500 WATER HEATER
ELCB
25 R9 20 4.0 4.0 MAID RM BATH 1 1500 1500 WATER HEATER
SEC. 5
26 Y9 SPACE

27 B9 SPACE

63A 28 R10 20 4.0 4.0 T-06BFCU (BED RM2&BED RM3) 1 240 240
100mA 4P
ELCB 29 Y10 32 6.0 6.0 T-06A(LIV&LIT&LOBBY) 1 3000 3000 UVR+TIMER
SEC. 6
30 B10 SPACE

63A 31 R11 20 4.0 4.0 T-06AFCU (LIV&LIT&LOBBY) 1 300 300


100mA 4P
ELCB 32 Y11 SPACE
SEC. 7
33 B11 32 6.0 6.0 T-06C( TV&BED1&LAN&MAID) 1 3000 3000 UVR+TIMER

63A 34 R12 32 6.0 6.0 T-06B(BED RM2&BED RM3) 1 3000 3000 UVR+TIMER
100mA 4P
ELCB 35 Y12 SPACE
SEC. 8
36 B12 20 4.0 4.0 T-06CFCU( TV&BED1&LAN&MAID) 1 300 300
1 X 4/C- 25 mm2 XLPE/SWA/PVC + CL / Ø 8305 7745 7695 WATTS
CABLE SIZE
1 X 1 /C- 16 mm2 CU. GY, ECC TCL / Ø 8.305 7.745 7.695 kW

LTG = Lighting, Sh. S/O = Shaver Socket Outlet, S/O (1) = Single Socket Outlet, S/O (2 )= Double Socket Outlet, W/M=washing machne, W/H = Water Heater, PUMP, FCU = Fan Coil Unit, ISOL = Isolator Switch For Equipment,MSFD= Motorized Smoke Fire Damper,FLEX OUT= For systems modules. TCL 23.745 kW
PROPOSED G + 7 + PH
PLOT NO.: 6/B
PROJECT: RESIDENTIAL / COMMERCIAL DETAIL OF CONNECTED LOAD/MAX. DEMAND

OWNER: H.H. SHEIKH FAISAL BIN


LOCATION :AL MDR 2
DB REF. DB-105/ 1 BED RM ABDULLA AHMED AL MULLA

FED FROM: SMDB-F1 CONSULTANT: MODULE ENGINEERING CONSULTANTS DB Location: FLAT 105

LOAD PER CIRCUIT-


CONNECTED LOADS/POINTS
MCB WATTS
Rating Of Rating Of CCT. Wire ECC Wire
SL No. CCT No. RTG. In Room / Area Watts/ Unit REMARKS
Incomer ELCB
A Size mm2 Size mm2
13A S/O C/K HD
SPOT LTG CHND LTG SHA.S/O COVELTG CALLBELL EX. FAN 13A S/O single 15A S/O GD D/W W/H A/C FCU ISO R Y B
twin FAN

1 R1 10 2.5 2.5 KITCHEN 2 1 1 1 100 500

2 Y1 10 2.5 2.5 LOBBY & TOILET 3\1 35 140


40A
100mA 4P 3 B1 10 2.5 2.5 MAID RM & BATH 1\1\1 1 50\35\100 220
ELCB
4 R2 10 2.5 2.5 LIVING RM 1 300 300
SEC. 1
5 Y2 10 2.5 2.5 BED RM & BATH 1\3\1 1 50\35\100\200 290

6 B2 10 2.5 2.5 KITCHEN 1 200 200 GAS DETECTOR

7 R3 16 4.0 4.0 KITCHEN 2 200 400

8 Y3 16 4.0 4.0 LOBBY 1 400 400 12U CABINET


40A 30mA
4P 9 B3 16 4.0 4.0 MAID RM 1 200 200
ELCB
10 R4 16 4.0 4.0 LIVING RM 2 200 400
40A TPN ISOLATOR

SEC. 2
11 Y4 16 4.0 4.0 BED RM & BATH 1 200 200

12 B4 20 4.0 4.0 KITCHEN 1 1500 1500

13 R5 20 4.0 4.0 BED RM BATH 1 1500 1500 WATER HEATER

14 Y5 20 4.0 4.0 MAID RM BATH 1 1500 1500 WATER HEATER


40A 30mA
4P 15 B5 SPACE
ELCB 1500
16 R6 20 4.0 4.0 KITCHEN 1 1500 FRIDGE
SEC. 3
17 Y6 SPACE

18 B6 SPACE

40A 19 R7 20 4.0 4.0 T-05AFCU (LIV&KIT&LOBBY) 1 300 300


100mA 4P
ELCB 20 Y7 32 6.0 6.0 T-05A(LIV&KIT&LOBBY) 1 3000 3000 UVR+TIMER
SEC. 4
21 B7 20 4.0 4.0 T-05BFCU (BED&MAID) 1 300 300

40A 22 R8 SPACE
100mA 4P
ELCB 23 Y8 SPACE
SEC. 5
24 B8 32 6.0 6.0 T-05B(BED&MAID) 1 3000 3000 UVR+TIMER
1 X 4/C- 16 mm2 XLPE/SWA/PVC + CL / Ø 4900 5530 5420 WATTS
CABLE SIZE
1 X 1 /C- 16 mm2 CU. GY, ECC TCL / Ø 4.9 5.53 5.42 kW

LTG = Lighting, Sh. S/O = Shaver Socket Outlet, S/O (1) = Single Socket Outlet, S/O (2 )= Double Socket Outlet, W/M=washing machne, W/H = Water Heater, PUMP, FCU = Fan Coil Unit, ISOL = Isolator Switch For Equipment,MSFD= Motorized Smoke Fire Damper,FLEX OUT= For systems modules. TCL 15.850 kW
PROPOSED G + 7 + PH
PLOT NO.: 6/B
PROJECT: RESIDENTIAL / COMMERCIAL DETAIL OF CONNECTED LOAD/MAX. DEMAND

OWNER: H.H. SHEIKH FAISAL BIN


LOCATION :AL MDR 2
DB REF. DB-104/ 2BED RM ABDULLA AHMED AL MULLA

FED FROM: SMDB-F1 CONSULTANT: MODULE ENGINEERING CONSULTANTS DB Location: FLAT 104

LOAD PER CIRCUIT-


CONNECTED LOADS/POINTS
MCB WATTS
Rating Of Rating Of CCT. Wire ECC Wire
SL No. CCT No. RTG. In Room / Area Watts/ Unit REMARKS
Incomer ELCB
A Size mm2 Size mm2
13A S/O C/K HD
SPOT LTG CHND LTG SHA.S/O COVELTG CALLBELL EX. FAN 13A S/O single 15A S/O GD D/W W/H A/C FCU ISO R Y B
twin FAN

1 R1 10 2.5 2.5 KITCHEN & LOBBY & CORRIDOR & BATH 4\2\1 1 1 35/100 575

2 Y1 10 2.5 2.5 LIVING RM 1 300 300

40A 3 B1 10 2.5 2.5 BED RM1 & BATH 1\1\1 50\35 120
100mA 4P
ELCB
SEC. 1 4 R2 10 2.5 2.5 M.BED RM & DRESS & BATH 3\1\1 1 50\35\100 290

5 Y2 10 2.5 2.5 TV RM 2 35 70

6 B2 10 2.5 2.5 MAID RM & BATH 1\2\1 1 50\35\100 255

7 R3 16 4.0 4.0 LOBBY 1 400 400 12U CABINET

8 Y3 16 4.0 4.0 LIVING RM 2 200 400

40A 30mA 9 B3 16 4.0 4.0 BED RM1 & BATH 1 200 200
4P
ELCB
SEC. 2 10 R4 16 4.0 4.0 M.BED RM & DRESS & BATH 1 200 200

11 Y4 16 4.0 4.0 TV RM 1 200 200

12 B4 16 4.0 4.0 MAID RM & BATH 1 200 200

13 R5 16 4.0 4.0 KITCHEN 2 200 400

14 Y5 SPACE

40A 30mA 15 B5 20 4.0 4.0 KITCHEN 1 1500 1500


40A TPN ISOLATOR

4P
ELCB
SEC. 3 16 R6 SPACE

17 Y6 20 4.0 4.0 MAID RM BATH 1 1500 1500

18 B6 20 4.0 4.0 BED RM BATH 1 1500 1500 WATER HEATER

19 R7 20 4.0 4.0 KITCHEN 1 1500 1500 FRIDGE


40A 30mA
4P
20 Y7 20 4.0 4.0 M BED RM BATH 1 1500 1500 WATER HEATER
ELCB
SEC. 4
21 B7 SPACE

22 R8 20 4.0 4.0 T-04A FCU (LIV&KIT&LOBBY) 1 300 300


40A
100mA 4P
ELCB 23 Y8 32 6.0 6.0 T-04A (LIV&KIT&LOBBY) 1 3000 3000 UVR+TIMER
SEC. 5
24 B8 32 6.0 6.0 T-04B(M BED RM& BED ) 1 3000 3000 UVR+TIMER

25 R9 20 4.0 4.0 T-04BFCU (M BED RM& BED ) 1 300 300


40A
100mA 4P
ELCB 26 Y9 SPACE
SEC.6
27 B9 SPACE

28 R10 32 6.0 6.0 T-04C(TV&AMID) 1 3000 3000 UVR+TIMER


40A
100mA 4P
ELCB 29 Y10 20 4.0 4.0 T-04CFCU (TV&AMID) 1 300 300
SEC. 7
30 B10 SPACE

31 R11 10 2.5 2.5 KITCHEN 1 200 200 GAS DETECTOR


40A
100mA 4P
ELCB 32 Y11 SPACE
SEC. 8
33 B11 SPACE
1 X 4/C- 25 mm2 XLPE/SWA/PVC + CL / Ø 6565 7570 7075 WATTS
CABLE SIZE
1 X 1 /C- 16 mm2 CU. GY, ECC TCL / Ø 6.565 7.57 7.075 kW

LTG = Lighting, Sh. S/O = Shaver Socket Outlet, S/O (1) = Single Socket Outlet, S/O (2 )= Double Socket Outlet, W/M=washing machne, W/H = Water Heater, PUMP, FCU = Fan Coil Unit, ISOL = Isolator Switch For Equipment,MSFD= Motorized Smoke Fire Damper,FLEX OUT= For systems modules. TCL 21.210 kW
PROPOSED G + 7 + PH
PLOT NO.: 6/B
PROJECT: RESIDENTIAL / COMMERCIAL DETAIL OF CONNECTED LOAD/MAX. DEMAND

OWNER: H.H. SHEIKH FAISAL BIN


LOCATION :AL MDR 2
DB REF. DB-103/ 2BED RM ABDULLA AHMED AL MULLA

FED FROM: SMDB-F1 CONSULTANT: MODULE ENGINEERING CONSULTANTS DB Location: FLAT 103

LOAD PER CIRCUIT-


CONNECTED LOADS/POINTS
MCB WATTS
Rating Of Rating Of CCT. Wire ECC Wire
SL No. CCT No. RTG. In Room / Area Watts/ Unit REMARKS
Incomer ELCB
A Size mm2 Size mm2
13A S/O C/K HD
SPOT LTG CHND LTG SHA.S/O COVELTG CALLBELL EX. FAN 13A S/O single 15A S/O GD D/W W/H A/C FCU ISO R Y B
twin FAN

1 R1 10 2.5 2.5 KITCHEN & LOBBY & CORRIDOR & BATH 4\2\1 1 2 1 35\100 775

2 Y1 10 2.5 2.5 LIVING RM 1 300 300

40A 1
3 B1 10 2.5 2.5 BED RM1 & BATH 2\1\1 50\35\100 255
100mA 4P
ELCB
SEC. 1 4 R2 10 2.5 2.5 BED RM2 & DRESS & BATH 3\1\1 50\35\100 190

5 Y2 10 2.5 2.5 TV RM 2 35 70

6 B2 10 2.5 2.5 MAID RM & BATH 1\2\1 50\35\100 155

7 R3 16 4.0 4.0 LOBBY 1 400 400 12U CABINET

8 Y3 16 4.0 4.0 LIVING RM 2 200 400

40A 30mA
9 B3 16 4.0 4.0 BED RM1 & BATH 1 200 200
4P
ELCB
SEC.2 10 R4 16 4.0 4.0 BED RM2 & DRESS & BATH 1 200 200

11 Y4 16 4.0 4.0 TV RM 1 200 200

12 B4 16 4.0 4.0 MAID RM & BATH 1 200 200

13 R5 16 4.0 4.0 KITCHEN 2 200 400

14 Y5 20 4.0 4.0 KITCHEN 1 1500 1500

40A 30mA 1
40A TPN ISOLATOR

15 B5 20 4.0 4.0 KITCHEN 1500 1500 FRIDGE


4P
ELCB
SEC. 3 16 R6 SPACE

17 Y6 20 4.0 4.0 BED RM 1 BATH 1 1500 1500 WATER HEATER

18 B6 SPACE

19 R7 20 4.0 4.0 BED RM 2 BATH 1 1500 1500 WATER HEATER


40A 30mA
4P
ELCB 20 SPACE
SEC. 4
21 B7 20 4.0 4.0 MAID RM BATH 1 1500 1500 WATER HEATER

22 R8 SPACE
40A
100mA 4P
ELCB 23 Y8 20 4.0 4.0 T-03A FCU (LIV&KIT&LOBBY) 1 300 300
SEC. 5
24 B8 32 6.0 6.0 T-03A (LIV&KIT&LOBBY) 1 3000 3000 UVR+TIMER

25 R9 32 6.0 6.0 T-03B(BED1&BED2) 1 3000 3000 UVR+TIMER


40A
100mA 4P
ELCB 26 Y9 20 4.0 4.0 T-03BFCU (BED1&BED2) 1 300 300
SEC. 6
27 B9 SPACE

28 R10 SPACE
40A
100mA 4P
ELCB 29 Y10 32 6.0 6.0 T-03C(TV&AMID&LOBBY) 1 3000 3000 UVR+TIMER
SEC. 7
30 B10 20 4.0 4.0 T-03CFCU (TV&AMID&LOBBY) 1 300 300

40A 31 R11 SPACE


100mA 4P
ELCB 32 Y11 SPACE
SEC. 8
B11 10 2.5 2.5 KITCHEN 1 200 200 GAS DETECTOR
1 X 4/C- 25 mm2 XLPE/SWA/PVC + CL / Ø 6465 7570 7310 WATTS
CABLE SIZE
1 X 1 /C- 16 mm2 CU. GY, ECC TCL / Ø 6.465 7.57 7.31 kW

LTG = Lighting, Sh. S/O = Shaver Socket Outlet, S/O (1) = Single Socket Outlet, S/O (2 )= Double Socket Outlet, W/M=washing machne, W/H = Water Heater, PUMP, FCU = Fan Coil Unit, ISOL = Isolator Switch For Equipment,MSFD= Motorized Smoke Fire Damper,FLEX OUT= For systems modules. TCL 21.345 kW
PROPOSED G + 7 + PH
PLOT NO.: 6/B
PROJECT: RESIDENTIAL / COMMERCIAL DETAIL OF CONNECTED LOAD/MAX. DEMAND

OWNER: H.H. SHEIKH FAISAL BIN


LOCATION :AL MDR 2
DB REF. DB-102/ 1 BED RM ABDULLA AHMED AL MULLA

FED FROM: SMDB-F1 CONSULTANT: MODULE ENGINEERING CONSULTANTS DB Location: FLAT 102

LOAD PER CIRCUIT-


CONNECTED LOADS/POINTS
MCB WATTS
Rating Of Rating Of CCT. Wire ECC Wire
SL No. CCT No. RTG. In Room / Area Watts/ Unit REMARKS
Incomer ELCB
A Size mm2 Size mm2
13A S/O C/K HD
SPOT LTG CHND LTG SHA.S/O COVELTG CALLBELL EX. FAN 13A S/O single 15A S/O GD D/W W/H A/C FCU ISO R Y B
twin FAN

1 R1 10 2.5 2.5 KITCHEN 2 1 1 100 400

2 Y1 10 2.5 2.5 LOBBY & TOILET & LAUNDRY 3\1 1 1 35 340


40A
100mA 4P 3 B1 SPACE
ELCB
4 R2 10 2.5 2.5 LIVING RM 1 300 300
SEC. 1
5 Y2 10 2.5 2.5 BED RM & BATH 2\1\1 1 50\35\100 255

6 B2 10 2.5 2.5 KITCHEN 1 200 200 GAS DETECTOR

7 R3 16 4.0 4.0 KITCHEN 2 200 400

8 Y3 16 4.0 4.0 LOBBY 1 400 400 12U CABENIT


40A 30mA
4P 9 B3 SPACE
ELCB
10 R4 16 4.0 4.0 LIVING RM 2 200\400 400
40 A TPN ISOLATOR

SEC. 2
11 Y4 16 4.0 4.0 BED RM & BATH 1 200\400 200

12 B4 SPACE

13 R5 20 4.0 4.0 BED RM BATH 1 1500 1500 WATER HEATER

14 Y5 SPACE
40A 30mA
4P 15 B5 SPACE
ELCB
16 R6 20 4.0 4.0 LAUNDRY 1 1500 1500
SEC. 3
17 Y6 SPACE

18 B6 20 4.0 4.0 KITCHEN 1 1500 1500 FRIDGE

40A 19 R7 SPACE
100mA 4P
20 Y7 20 4.0 4.0 T-02A FCU (LIV&KIT) 1 300 300
ELCB
SEC. 4
21 B7 32 6.0 6.0 T-02A (LIV&KIT) 1 3000 3000 UVR+TIMER

40A 22 R8 20 4.0 4.0 T-02BFCU (BED&LAN) 1 300 300


100mA 4P
ELCB 23 Y8 32 6.0 6.0 T-02B(BED &LAN) 1 3000 3000 UVR+TIMER
SEC. 5
24 B8 SPACE
1 X 4/C- 16 mm2 XLPE/SWA/PVC + CL / Ø 4800 4495 4700 WATTS
CABLE SIZE
1 X 1 /C- 16 mm2 CU. GY, ECC TCL / Ø 4.8 4.495 4.7 kW

LTG = Lighting, Sh. S/O = Shaver Socket Outlet, S/O (1) = Single Socket Outlet, S/O (2 )= Double Socket Outlet, W/M=washing machne, W/H = Water Heater, PUMP, FCU = Fan Coil Unit, ISOL = Isolator Switch For Equipment,MSFD= Motorized Smoke Fire Damper,FLEX OUT= For systems modules. TCL 13.995 kW
PROPOSED G + 7 + PH
PLOT NO.: 6/B
PROJECT: RESIDENTIAL / COMMERCIAL DETAIL OF CONNECTED LOAD/MAX. DEMAND

OWNER: H.H. SHEIKH FAISAL BIN


LOCATION :AL MDR 2
DB REF. DB-101/ 2BED RM ABDULLA AHMED AL MULLA

FED FROM: SMDB-F1 CONSULTANT: MODULE ENGINEERING CONSULTANTS DB Location: FLAT 101

LOAD PER CIRCUIT-


CONNECTED LOADS/POINTS
MCB WATTS
Rating Of Rating Of CCT. Wire ECC Wire
SL No. CCT No. RTG. In Room / Area Watts/ Unit REMARKS
Incomer ELCB
A Size mm2 Size mm2
13A S/O C/K HD
SPOT LTG CHND LTG SHA.S/O COVELTG CALLBELL EX. FAN 13A S/O single 15A S/O GD D/W W/H A/C FCU ISO R Y B
twin FAN

1 R1 10 2.5 2.5 LOBBY & TOILET & LAUNDRY 6\1 1 1 35\100 445

2 Y1 10 2.5 2.5 KITCHEN 2 1 1 100 400

63A 3 B1 10 2.5 2.5 LIVING RM 1 300 300


100mA 4P
ELCB 4 R2 10 2.5 2.5 MAID RM & BATH 1\1\1 1 50\35\100 220
SEC. 1
5 Y2 10 2.5 2.5 BED RM 1 & BATH & BALCONY 1\4\1\2 1 50\35\100 395

6 B2 10 2.5 2.5 BED RM 2 & BATH & BALCONY 1\3\1\1 1 50\35\100 325

7 R3 10 2.5 2.5 TV RM 1 300 300


63A
100mA 4P 8 Y3 10 2.5 2.5 KITCHEN 1 200 200 GAS DETECTOR
ELCB
SEC. 3 1 300
9 B3 20 4.0 4.0 T-01 A FCU( LIVING&KIT&LOBBY) 300

10 R4 16 4.0 4.0 LOBBY 1 400 400 12U CABINET

11 Y4 16 4.0 4.0 KITCHEN 2 200 400


63A 30mA
4P 12 B4 16 4.0 4.0 LIVING RM 2 200 400
ELCB
63 A TPN ISOLATOR

13 R5 16 4.0 4.0 MAID RM & BATH 1 200 200


SEC. 4
14 Y5 16 4.0 4.0 BED RM 1 & BATH 1 200 200

15 B5 16 4.0 4.0 BED RM 2 & BATH 1 200 200

16 R6 16 4.0 4.0 TV RM 1 200 200

17 Y6 20 4.0 4.0 BED RM 1 BATH 1 1500 1500 WATER HEATER


63A 30mA
4P 18 B6 20 4.0 4.0 BED RM 2 BATH 1 1500 1500 WATER HEATER
ELCB
19 R7 20 4.0 4.0 LAUNDRY 1 500 1500
SEC. 5
20 Y7 SPACE

21 B7 20 4.0 4.0 KITCHEN 1 1500 1500 FRIDGE

63A 30mA 22 R8 20 4.0 4.0 MAID RM BATH 1 1500 1500 WATER HEATER
4P
ELCB 23 Y8 SPACE
SEC. 8
24 B8 SPACE

63A 25 R9 32 6.0 6.0 T-01 A ( LIVING&KIT&LOBBY) 1 3000 3000 UVR+TIMER


100mA 4P
26 Y9 SPACE
ELCB
SEC. 9
27 B9 32 6.0 6.0 T-01C (TV&MAID&LAN) 1 3000 3000 UVR+TIMER

63A 28 R10 20 4.0 4.0 T-01B FCU (BED RM 1&BED RM 2) 1 300 300
100mA 4P
ELCB 29 Y10 32 6.0 6.0 T-01B(BED RM 1&BED RM 2) 1 3000 3000 UVR+TIMER
SEC. 10
30 B10 20 4.0 4.0 T-01 C FCU (TV&MAID&LAN) 1 300 300
1 X 4/C- 25 mm2 XLPE/SWA/PVC + CL / Ø 8065 6095 7825 WATTS
CABLE SIZE
1 X 1 /C- 16 mm2 CU. GY, ECC TCL / Ø 8.065 6.095 7.825 kW

LTG = Lighting, Sh. S/O = Shaver Socket Outlet, S/O (1) = Single Socket Outlet, S/O (2 )= Double Socket Outlet, W/M=washing machne, W/H = Water Heater, PUMP, FCU = Fan Coil Unit, ISOL = Isolator Switch For Equipment,MSFD= Motorized Smoke Fire Damper,FLEX OUT= For systems modules. TCL 21.985 kW
PROPOSED G + 7 + PH
PLOT NO.: 6/B
PROJECT: RESIDENTIAL / COMMERCIAL DETAIL OF CONNECTED LOAD/MAX. DEMAND

OWNER: H.H. SHEIKH FAISAL BIN LOCATION :AL MDR 2


DB REF. DB-LL-1
ABDULLA AHMED AL MULLA

FED FROM: SMDB-SR CONSULTANT: MODULE ENGINEERING CONSULTANTS DB Location: 1ST FLOOR - ELECTIRCAL RM

LOAD PER CIRCUIT-


CCT. ECC CONNECTED LOADS/POINTS
WATTS
Rating Of Rating CCT MCB RTG. Wire Wire
SL No. Room / Area Watts/ Unit REMARKS
Incomer Of ELCB No. In A Size Size
mm2 mm2 CALLBEL 13A S/O 13A S/O 15A
LTG SHA.S/O COVELTG EX. FAN C/K HD D/W W/H A/C FCU ISO R Y B
L single twin S/O

1 R1 10 2.5 2.5 CORRIDOR -1ST FLOOR 7 50 350

2 Y1 10 2.5 2.5 CORRIDOR -1ST FLOOR 3 50 150


40A
100mA 3 B1 10 2.5 2.5 CORRIDOR -2ND FLOOR 7 50 350
4P
ELCB 4 R2 10 2.5 2.5 CORRIDOR -2ND FLOOR 3 50 150
SEC. 1
5 Y2 10 2.5 2.5 CORRIDOR -3RD FLOOR 7 50 350

6 B2 10 2.5 2.5 CORRIDOR -3RD FLOOR 3 50 150

40A 7 R3 10 2.5 2.5 WATER METER RM 3 50 150 1ST,2ND,3RD


40A TPN ISOLATOR

100mA
4P 8 Y3 10 2.5 2.5 ELECTRICAL RM 3 100 300 1ST,2ND,3RD
ELCB
SEC. 2 9 B3 10 2.5 2.5 GARBAGE RM 3 50 150 1ST,2ND,3RD

10 R4 20 4.0 4.0 ELECTRICAL RM 3 200 600 1ST,2ND,3RD


40A
30mA 4P
11 Y4 20 4.0 4.0 GARBAGE RM 3 200 600 1ST,2ND,3RD
ELCB
SEC. 3
12 B4 20 4.0 4.0 CORRIDOR 3 200 600 1ST,2ND,3RD

40A T-07 1ST F


13 R5 32 6.0 6.0 1 3000 3000 UVR+TIMER
100mA (CORR&ELEC&TELE)
4P T-07 FCU 1ST F
14 Y5 20 4.0 4.0 1 300 300
ELCB (CORR&ELEC&TELE)
SEC. 4 T-07 2ND F
15 B5 32 6.0 6.0 1 3000 3000 UVR+TIMER
(CORR&ELEC&TELE)
40A T-07 FCU 2ND F
16 R6 20 4.0 4.0 1 300 300
100mA (CORR&ELEC&TELE)
4P T-07 3RD F
17 Y6 32 6.0 6.0 1 3000 3000 UVR+TIMER
ELCB (CORR&ELEC&TELE)
SEC. 5 T-07 FCU 3RD F
18 B6 20 4.0 4.0 1 300 300
(CORR&ELEC&TELE)
1 X 4/C- 16 mm2 XLPE/SWA/PVC + CL / Ø 4550 4700 4550 WATTS
CABLE SIZE
1 X 1 /C- 16 mm2 CU. GY, ECC TCL / Ø 4.55 4.7 4.55 kW

LTG = Lighting, Sh. S/O = Shaver Socket Outlet, S/O (1) = Single Socket Outlet, S/O (2 )= Double Socket Outlet, W/M=washing machne, W/H = Water Heater, PUMP, FCU = Fan Coil Unit, ISOL = Isolator Switch For Equipment,MSFD= Motorized
TCL 13.800 kW
Smoke Fire Damper,FLEX OUT= For systems modules.
PROPOSED G + 7 + PH
PLOT NO.: 6/B
PROJECT: RESIDENTIAL / COMMERCIAL DETAIL OF CONNECTED LOAD/MAX. DEMAND

OWNER: H.H. SHEIKH FAISAL BIN LOCATION :AL MDR 2


DB REF. DB-LL-2 ABDULLA AHMED AL MULLA

FED FROM: SMDB-SR CONSULTANT: MODULE ENGINEERING CONSULTANTS DB Location: 4TH FLOOR - ELECTIRCAL RM

LOAD PER CIRCUIT-


CCT. ECC CONNECTED LOADS/POINTS
WATTS
Rating Of Rating CCT MCB RTG. Wire Wire
SL No. Room / Area Watts/ Unit REMARKS
Incomer Of ELCB No. In A Size Size
mm2 mm2 CALLBEL 13A S/O 13A S/O 15A
LTG SHA.S/O COVELTG EX. FAN C/K HD D/W W/H A/C FCU ISO R Y B
L single twin S/O

1 R1 10 2.5 2.5 CORRIDOR -4TH FLOOR 7 50 350

2 Y1 10 2.5 2.5 CORRIDOR -4TH FLOOR 3 50 150


40A
100mA 3 B1 10 2.5 2.5 CORRIDOR -5TH FLOOR 7 50 350
4P
ELCB 4 R2 10 2.5 2.5 CORRIDOR -5TH FLOOR 3 50 150
SEC. 1
5 Y2 10 2.5 2.5 CORRIDOR -6TH FLOOR 7 50 350

6 B2 10 2.5 2.5 CORRIDOR -6TH FLOOR 3 50 150

40A 7 R3 10 2.5 2.5 CORRIDOR -7TH FLOOR 7 50 350


100mA
4P 8 Y3 10 2.5 2.5 CORRIDOR -7TH FLOOR 3 50 150
ELCB
SEC. 2 T-07 FCU 5TH F
9 B3 20 4.0 4.0 1 240 240
(CORR&ELEC&TELE)
40A 10 R4 10 2.5 2.5 WATER METER RM 4 50 200 4TH,5TH,6TH,7TH FLOOR
100mA
4P 11 Y4 10 2.5 2.5 ELECTRICAL RM 4 100 400 4TH,5TH,6TH,7TH FLOOR
ELCB
SEC. 3 12 B4 10 2.5 2.5 GARBAGE RM 4 50 200 4TH,5TH,6TH,7TH FLOOR
40 A TPN ISOLATOR

4TH,5TH,6TH,7TH
13 R5 32 4.0 4.0 ELECTRICAL RM 4 200 800
40A FLOOR ,RING CIRCUIT
30mA 4P 4TH,5TH,6TH,7TH
14 Y5 32 4.0 4.0 GARBAGE RM 4 200 800
ELCB FLOOR ,RING CIRCUIT
SEC. 4 4TH,5TH,6TH,7TH
15 B5 32 4.0 4.0 CORRIDOR 4 200 800
FLOOR ,RING CIRCUIT
T-07 4TH F
16 R6 32 6.0 6.0 1 3000 3000 UVR+TIMER
(CORR&ELEC&TELE)
40A
100mA T-07 FCU 4TH F
4P 17 Y6 20 4.0 4.0 1 300 300
(CORR&ELEC&TELE)
ELCB
SEC. 5 T-07 5TH F
18 B6 32 6.0 6.0 1 3000 3000 UVR+TIMER
(CORR&ELEC&TELE)

19 R7 SPACE
40A
100mA T-07 6TH F
20 Y7 32 6.0 6.0 1 3000 3000 UVR+TIMER
4P (CORR&ELEC&TELE)
ELCB
SEC. 6 T-07 FCU 6TH F
21 B7 20 4.0 4.0 1 300 300
(CORR&ELEC&TELE)

T-07 7TH F
40A 22 R8 32 6.0 6.0 1 3000 3000
(CORR&ELEC&TELE)
100mA
4P T-07 FCU 7TH F
ELCB 23 Y8 20 4.0 4.0 1 300 300
(CORR&ELEC&TELE)
SEC. 7
24 B8 SPACE
1 X 4/C- 16 mm2 XLPE/SWA/PVC + CL / Ø 7850 5450 5040 WATTS
CABLE SIZE
1 X 1 /C- 16 mm2 CU. GY, ECC TCL / Ø 7.85 5.45 5.04 kW

LTG = Lighting, Sh. S/O = Shaver Socket Outlet, S/O (1) = Single Socket Outlet, S/O (2 )= Double Socket Outlet, W/M=washing machne, W/H = Water Heater, PUMP, FCU = Fan Coil Unit, ISOL = Isolator Switch For Equipment,MSFD= Motorized
TCL 18.340 kW
Smoke Fire Damper,FLEX OUT= For systems modules.