5006162-YTG-G-0717

DESCRIPTION
This fan coil line offers the ultimate in application flexibility. This
unit may be used for upflow, downflow, horizontal right, or
horizontal left applications.
All JCI Unitary Products air handlers and coils can use a TXV to
provide our customers with the optimum performance and
refrigerant control. Single piece air handlers are available with
“Flex-coils” (without a factory installed metering device). For
TECHNICAL GUIDE added flexibility, an R-22 or R-410A TXV or piston must be field
installed to meet the requirement of the desired refrigerant.
SINGLE PIECE PSC AIR HANDLERS Some models available +with factory installed TXV.
FOR USE WITH SPLIT-SYSTEM
FEATURES
COOLING & HEAT PUMPS
RC2 - Rigid Case Construction interior endoskeleton for
MODELS: AP SERIES structural support, smooth side, and locks in insulation.
Powder-painted - G30 galvanized steel case provide a coated
edge that resists corrosion and rust creep.
MaxAlloyTM Coil - Long life aluminum coils built to deliver
lasting performance, efficiency and reliability.
Quality Construction - Structural components are made of
Aluminum or G90 galvanized steel to prevent corrosion.
Improved Insulation Design - Single piece with no external
screws to reduce thermal transmission paths to prevent
sweating. Foil faced insulation for ease of cleaning.
Thermostatic Expansion Valve - The accessory chatleff style
TXV provides easy installation to convert the indoor coil to the
required refrigerant that does not require brazing to replace or
install. Some models are available with factory installed TXV.
Case Depth - These models have 20.5” casing which provide
ease of attic access and tight applications.
Thermoset Drain Pan - Positive slope for drainage to reduce
cause for potential mold or contaminants.
Factory Sealed - Achieves 2% or less total airflow leakage rate
® at duct leakage test conditions in positive and negative
pressure for system airflow verification.
Enhanced Filter Rack - All models have integrated internal
filter racks provided for use with 1” thick standard size filters.
Electric Heat Kits - 6HK series of field installed electric heat
kits are available for installation-friendly and easy service
applications.
Blowers - All models use direct-drive, multi-speed PSC motors.
Due to continuous product improvement,
specifications are subject to change without notice.
Visit us on the web at:
www.upgnet.com and www.york.com
Additional rating information can be found at:
www.ahridirectory.org
WARRANTY SUMMARY
Standard 5-year limited parts warranty.
Extended 10-year limited parts warranty when product is
registered online within 90 days of purchase for replacement
or closing for new home construction.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE


5006162-YTG-G-0717

LIST OF SECTIONS NOMENCLATURE


DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
PRODUCT TYPE A A = Single Piece Air Handler

NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 P = Multi PSC


DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 POSITION E = Multi Std ECM
MOTOR TYPE P
COIL TECHNICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 V = Multi VS ECM
COOLING CAPACITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Z = Compact Up Std ECM
PHYSICAL & ELECTRICAL DATA - COOLING ONLY . . . . . . . . . . 5 C = Communications Ready
ELECTRICAL DATA - COOLING ONLY . . . . . . . . . . . . . . . . . . . . . . 5 OPTIONS -
- = Standard (No Options)
ELECTRICAL HEAT - MINIMUM FAN SPEED . . . . . . . . . . . . . . . . . 6 18 = 1.5 Ton 42 = 3.5 Ton
ELECTRIC HEAT PERFORMANCE DATA:
208/230-1-60 & 208/230-3-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 NOMINAL 24 = 2 Ton 48 = 4-Ton
UNIT CAPACITY 36
ELECTRICAL DATA FOR SINGLE SOURCE 30 = 2.5 Ton 60 = 5-Ton
POWER SUPPLY: 208/230-1-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 36 = 3 Ton
ELECTRICAL DATA FOR MULTI-SOURCE A = 14.5"
POWER SUPPLY: 208/230-1-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
B = 17.5"
ELECTRICAL DATA FOR SINGLE SOURCE CABINET WIDTH B
POWER SUPPLY: 208/230-3-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 C = 21.0"
ELECTRICAL DATA FOR MULTI-SOURCE D = 24.5"
POWER SUPPLY: 208/230-3-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 BA-BF = Valve Size
AIR FLOW DATA (CFM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 TXV INDICATOR X
X = no valve
kW & MBH CONVERSIONS - FOR TOTAL VOLTAGE
POWER INPUT REQUIREMENT . . . . . . . . . . . . . . . . . . . . . . . . . . 12 (Voltage-Phase-Hertz) 2 2 = 208/230-1-60
APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM . . . . 12 1 = 1st Gen
BLOWER SPEED CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . 13 GENERATION
(MAJOR REVISION) 1 2 = 2nd Gen
ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
etc.
POWER WIRING - LINE CONNECTIONS . . . . . . . . . . . . . . . . . . . 13
STYLE LETTER A = Style A
TYPICAL THERMOSTAT CONNECTION . . . . . . . . . . . . . . . . . . . . 14 (MINOR REVISION)
COMBUSTIBLE FLOOR BASE ACCESSORY . . . . . . . . . . . . . . . . 15 NOT USED FOR A B = Style B
LIMITATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 ORDERING etc.
TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

2 Johnson Controls Unitary Products


5006162-YTG-G-0717
DIMENSIONS & DUCT CONNECTION DIMENSIONS

F REFRIGERANT CONNECTIONS
DRAIN CONNECTIONS TOP OUTLET
FOR UPFLOW APPLICATIONS DIMENSIONS
BLOWER
12-3/16”
COMPARTMENT
E

COIL
COMPARTMENT G

A
SERVICE
C DISCONNECT
PANEL

7-11/32
18-5/8”
D
1-1/2”

FILTER ACCESS BOTTOM INLET


B 20-1/2”
DIMENSIONS
21-7/16”
A0329-001

DIMENSIONS
Dimensions1 Wiring Knockouts2 Refrigerant
Connections
Models A B F G Line Size
C D E Control
Height Width Power (Conduit) Liquid Vapor
(Conduit)
AP18BX21 41 17-1/2 12-7/8 14-1/4 16-1/2
AP24BX21 41 17-1/2 12-7/8 14-1/4 16-1/2
AP30BX21 47-1/2 17-1/2 19-1/2 14-1/4 16-1/2
3/4
AP36BX21 47-1/2 17-1/2 19-1/2 14-1/4 16-1/2
AP36CX21 51-1/2 21 22-5/8 17-3/4 20 7/8 (1/2)
AP37CX21 51-1/2 21 22-5/8 17-3/4 20 1-3/8 (1) 7/8 (1/2) 3/8
AP42CX21 51-1/2 21 22-5/8 17-3/4 20 1-23/32 (1-1/4)
AP48CX21 51-1/2 21 22-5/8 17-3/4 20
AP48DX21 55-1/2 24-1/2 26-5/8 21-1/4 23-1/2 7/8
AP60CX21 55-3/4 21 26-7/8 17-3/4 20
AP60DX22 55-1/2 24-1/2 26-5/8 21-1/4 23-1/2
1. All dimensions are in inches.
2. Knockout size (conduit size in parentheses).

COIL TECHNICAL DATA


Refrig. Face Area Rows Fins Tube Tube Fin
Models1 Application Coil Size
Conn. Types (Sq. Ft.) Deep Per In. Geometry Dia. Type
AP18BX21 Cooling /Heat Pump Sweat 4.3 2 14 (3) 12 x 17.1 1 x 0.866 3/8 Sine Wave
AP18BBA21* Cooling /Heat Pump Sweat 4.3 2 14 (3) 12 x 17.1 1 x 0.866 3/8 Sine Wave
AP24BX21 Cooling /Heat Pump Sweat 5.0 2 14 (3) 14 x 17.1 1 x 0.866 3/8 Sine Wave
AP24BBA21* Cooling /Heat Pump Sweat 5.0 2 14 (3) 14 x 17.1 1 x 0.866 3/8 Sine Wave
AP30BX21 Cooling /Heat Pump Sweat 7.1 2 14 (3) 20 x 17.1 1 x 0.866 3/8 Sine Wave
AP30BBB21* Cooling /Heat Pump Sweat 7.1 2 14 (3) 20 x 17.1 1 x 0.866 3/8 Sine Wave
AP36BX21 Cooling /Heat Pump Sweat 7.1 2 14 (3) 20 x 17.1 1 x 0.866 3/8 Sine Wave
AP36CX21 Cooling /Heat Pump Sweat 7.8 2 14 (3) 22 x 17.1 1 x 0.866 3/8 Sine Wave
AP37CX21 Cooling /Heat Pump Sweat 8.6 2 14 (3) 24 x 17.1 1 x 0.866 3/8 Sine Wave
AP37CBF21* Cooling /Heat Pump Sweat 8.6 2 14 (3) 24 x 17.1 1 x 0.866 3/8 Sine Wave
AP42CX21 Cooling /Heat Pump Sweat 7.8 2 14 (3) 22 x 17.1 1 x 0.866 3/8 Sine Wave
AP48CX21 Cooling /Heat Pump Sweat 8.6 2 14 (3) 24 x 17.1 1 x 0.866 3/8 Sine Wave
AP48DX21 Cooling /Heat Pump Sweat 8.6 2 14 (3) 24 x 17.1 1 x 0.866 3/8 Sine Wave
AP60CX21 Cooling /Heat Pump Sweat 10.0 2 14 (3) 28 x 17.1 1 x 0.866 3/8 Sine Wave
AP60DX22 Cooling /Heat Pump Sweat 10.0 2 14 (3) 28 x 17.1 1 x 0.866 3/8 Sine Wave
1. Asterisk denotes Factory-Installed TXV option.

Johnson Controls Unitary Products 3


5006162-YTG-G-0717

COOLING CAPACITY1
Entering Air MBH@ Evap. Temp. and Corresponding R-410A Pressure (°F/PSIG)
Models Rated CFM2 Dry/Wet Bulb (°F) 35/107.9 40/118.9 45/130.7 50/143.3
85/72 45.7 41.6 36.8 30.5
80/67 38.5 33.9 28.5 22.3
18B 600
75/62 31.5 26.5 20.5 15.9
70/57 24.4 19.5 15.2 11.5
85/72 52.2 47.5 41.8 35.0
80/67 43.6 38.3 31.9 24.5
24B 800
75/62 35.2 29.5 22.7 16.2
70/57 27.1 20.7 15.5 11.4
85/72 82.1 73.7 64.1 54.4
80/67 68.6 60.1 50.5 39.5
30B 1000
75/62 56.3 47.0 37.3 29.2
70/57 43.5 36.0 28.3 21.6
85/72 91.6 82.4 71.3 59.4
80/67 76.5 65.4 54.6 42.8
36B 1200
75/62 61.3 51.2 40.0 30.5
70/57 47.5 38.1 28.7 22.3
85/72 98.0 88.6 77.4 66.4
80/67 82.6 72.6 61.7 50.6
36C 1200
75/62 68.5 57.6 47.5 36.6
70/57 53.9 44.8 35.0 28.4
85/72 90.8 82.1 73.1 62.5
80/67 76.1 67.4 57.0 44.8
37C 1200
75/62 62.2 53.0 42.3 30.6
70/57 49.3 39.2 29.0 22.6
85/72 100.6 89.8 78.2 64.7
80/67 83.5 73.7 59.8 48.0
42C 1400
75/62 67.8 55.8 44.7 32.5
70/57 52.3 41.5 30.7 23.7
85/72 115.2 105.0 93.9 79.0
80/67 88.3 78.2 65.5 52.6
48C 1600
75/62 72.7 60.8 50.1 37.6
70/57 57.7 46.9 36.6 29.7
85/72 115.2 105.0 93.9 79.0
80/67 88.3 78.2 65.5 52.6
48D 1600
75/62 72.7 60.8 50.1 37.6
70/57 57.7 46.9 36.6 29.7
85/72 115.1 103.0 91.7 78.6
80/67 96.8 85.9 73.7 60.5
60C 1800
75/62 80.7 69.4 57.5 43.5
70/57 58.7 48.9 37.7 32.7
85/72 115.1 103.0 91.7 78.6
80/67 96.8 85.9 73.7 60.5
60D 1800
75/62 80.7 69.4 57.5 43.5
70/57 58.7 48.9 37.7 32.7
1. Actual capacity varies with the outdoor AC or HP that is used with the system.
2. Airflow is calculated for each system tonnage.

4 Johnson Controls Unitary Products


5006162-YTG-G-0717
PHYSICAL & ELECTRICAL DATA - COOLING ONLY
Models 18B 24B 30B 36B 36C 37C
Blower - Diameter x Width 10 x 8 10 x 8 10 x 8 10 x 8 10 x 10 10 x 10
HP 1/8 HP 1/4 HP 1/3 HP 1/2 HP 1/2 HP 1/2 HP
Motor
Nominal RPM 867 850 950 1085 1050 1050
Voltage 208/230 208/230 208/230 208/230 208/230 208/230
Full Load Amps @230V 1.0 1.4 2.3 2.6 2.2 2.2
Type DISPOSABLE OR PERMANENT
Filter1 Size 16 x 20 x 1 16 x 20 x 1 16 x 20 x 1 16 x 20 x 1 20 x 20 x 1 20 x 20 x 1
Permanent Type Kit 1PF0601 1PF0601 1PF0601 1PF0601 1PF0602 1PF0602
Shipping/Operating Weight (lbs.) 91/85 93/87 119/113 119/113 120/114 158/150

Models 42C 48C 48D 60C 60D


Blower - Diameter x Width 10 x 10 10 x 10 10 x 10 10 x 10 10 x 10
HP 1/2 HP 1/2 HP 1/2 HP 1 HP 1 HP
Motor
Nominal RPM 1085 1040 1040 1007 1007
Voltage 208/230 208/230 208/230 208/230 208/230
Full Load Amps @230V 2.8 2.9 2.9 4.1 4.4
Type DISPOSABLE OR PERMANENT
Filter1 Size 20 x 20 x 1 20 x 20 x 1 22 x 20 x 1 20 x 20 x 1 22 x 20 x 1
Permanent Type Kit 1PF0602 1PF0602 1PF0603 1PF0602 1PF0603
Shipping/Operating Weight (lbs.) 144/136 158/150 163/153 156/146 180/170
1. Field supplied.

ELECTRICAL DATA - COOLING ONLY


Models Motor FLA1 Minimum Circuit Ampacity MOP2
18B 1.1 1.4 15
24B 1.4 1.8 15
30B 2.3 2.9 15
36B 2.6 3.3 15
36C/37C 2.2 2.8 15
42C 2.8 3.5 15
48C/48D 2.9 3.6 15
60C 4.1 5.1 15
60D 4.4 5.5 15
1. FLA = Full Load Amps
2. MOP = Maximum Overcurrent Protection device; must be HACR type service disconnect or time delay fuse. Refer to the latest
edition of the National Electric Code or in Canada the Canadian electrical Code and local codes to determine correct wire sizing.

Johnson Controls Unitary Products 5


5006162-YTG-G-0717

ELECTRICAL HEAT - MINIMUM FAN SPEED


Heater Kit Nom. Air Handler Models
Models1,2,3 kW@240V 18B 24B 30B 36B 36C 37C 42C 48C 48D 60C 60D
6HK(0,1)6500206 2.4kW Med Low Low Low Low Low Low Low Low Low Low
6HK(0,1)6500506 4.8kW Med Low Low Low Low Low Low Low Low Low Low
6HK(0,1)6500806 7.7kW High High Med Low Low Low Low Low Low Low Low
6HK(0,1)6501006
9.6kW High High Med Low Low Low Low Low Low Low Low
6HK36501025
6HK(1,2)6501306 12.5kW – High Med Low Med Med Low Low Low Low Med
6HK(1,2)6501506
14.4kW – – Med Low Med Med Med Low Low Low Med
6HK36501525
6HK(1,2)6501806
17.3kW – – – Low Med Med Med Low Low Low High
6HK36501825
6HK(1,2)6502006
19.2kW – – – Low High High Med Med Med High High
6HK46502025
6HK(1,2)6502506
24kW – – – – – – – – Med - High
6HK46502525
1. (0,1) - 0 = no service disconnect OR 1 = with service disconnect.
2. (1,2) - 1 = with service disconnect, no breaker jumper bar OR 2 = with service disconnect & breaker jumper bar.
3. 6HK3 = 3-Phase with terminal block connectors only, 6HK4 = 3-Phase with service disconnect.

ELECTRIC HEAT PERFORMANCE DATA: 208/230-1-60 & 208/230-3-60


Total Heat4 kW Staging
Heater Nominal kW
kW MBH W1 Only W1 + W2
Models1,2,3 @240V
208V 230V 208V 230V 208V 230V 208V 230V
6HK(0,1)6500206 2.4 1.8 2.2 6.2 7.5 1.8 2.2 1.8 2.2
6HK(0,1)6500506 4.8 3.6 4.4 12.3 15 3.6 4.4 3.6 4.4
6HK(0,1)6500806 7.7 5.8 7.1 19.7 24.1 5.8 7.1 5.8 7.1
6HK(0,1)6501006 9.6 7.2 8.8 24.6 30.1 7.2 8.8 7.2 8.8
1PH 6HK(1,2)6501306 12.5 9.4 11.5 32 39.2 3.1 3.8 9.4 11.5
6HK(1,2)6501506 14.4 10.8 13.2 36.9 45.1 3.6 4.4 10.8 13.2
6HK(1,2)6501806 17.3 13 15.9 44.3 54.2 6.5 7.9 13 15.9
6HK(1,2)6502006 19.2 14.4 17.6 49.2 60.2 7.2 8.8 14.4 17.6
6HK(1,2)6502506 24 18 22 61.5 75.2 7.2 8.8 18 22
6HK36501025 9.6 7.2 8.8 24.6 30.1 7.2 8.8 7.2 8.8
6HK36501525 14.4 10.8 13.2 36.9 45.1 10.8 13.2 10.8 13.2
3PH 6HK36501825 17.3 13 15.9 44.3 54.2 13 15.9 13 15.9
6HK46502025 19.2 14.4 17.6 49.2 60.2 7.2 8.8 14.4 17.6
6HK46502525 24 18 22 61.5 75.2 9 11 18 22
1. (0,1) - 0 = no service disconnect OR 1 = with service disconnect.
2. (1,2) - 1 = with service disconnect, no breaker jumper bar OR 2 = with service disconnect & breaker jumper bar.
3. 6HK3 = 3-Phase with terminal block connectors only, 6HK4 = 3-Phase with service disconnect.
4. For different power distributions, see conversion table on Page 11.

6 Johnson Controls Unitary Products


5006162-YTG-G-0717

ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY: 208/230-1-60


Heater Field Wiring
Heater
Air Handler Models Amps Min. Circuit Ampacity MOP.3
Models1,2 @240V 208V 230V 208V 230V
6HK(0,1)6500206 10 12.2 13.3 15 15
6HK(0,1)6500506 20 23.0 25.3 25 30
18B
6HK(0,1)6500806 32 36.2 40.0 40 40
6HK(0,1)6501006 40 44.6 49.2 45 50
6HK(0,1)6500206 10 12.6 13.7 15 15
6HK(0,1)6500506 20 23.4 25.7 25 30
24B 6HK(0,1)6500806 32 36.6 40.3 40 45
6HK(0,1)6501006 40 45.0 49.6 45 50
6HK(1,2)6501306 52 58.2 64.3 60 70
6HK(0,1)6500206 10 13.7 14.8 15 15
6HK(0,1)6500506 20 24.5 26.8 25 30
6HK(0,1)6500806 32 37.7 41.5 40 45
30B
6HK(0,1)6501006 40 46.1 50.7 50 60
6HK(1,2)6501306 52 59.4 65.4 60 70
6HK(1,2)6501506 60 67.8 74.6 70 80
6HK(0,1)6500206 10 14.1 15.2 15 20
6HK(0,1)6500506 20 24.9 27.2 25 30
6HK(0,1)6500806 32 38.1 41.8 40 45
6HK(0,1)6501006 40 46.5 51.1 50 60
36B
6HK(1,2)6501306 52 59.7 65.8 60 70
6HK(1,2)6501506 60 68.2 75.0 70 80
6HK(1,2)6501806 72 81.4 89.7 90 90
6HK(1,2)6502006 80 89.8 98.9 90 100
6HK(0,1)6500206 10 13.6 14.7 15 15
6HK(0,1)6500506 20 24.4 26.7 25 30
6HK(0,1)6500806 32 37.6 41.3 40 45
6HK(0,1)6501006 40 46.0 50.6 50 60
36C
6HK(1,2)6501306 52 59.2 65.3 60 70
6HK(1,2)6501506 60 67.7 74.5 70 80
6HK(1,2)6501806 72 80.9 89.2 90 90
6HK(1,2)6502006 80 89.3 98.4 90 100
6HK(0,1)6500206 10 13.6 14.7 15 15
6HK(0,1)6500506 20 24.4 26.7 25 30
6HK(0,1)6500806 32 37.6 41.3 40 45
6HK(0,1)6501006 40 46.0 50.6 50 60
37C
6HK(1,2)6501306 52 59.2 65.3 60 70
6HK(1,2)6501506 60 67.7 74.5 70 80
6HK(1,2)6501806 72 80.9 89.2 90 90
6HK(1,2)6502006 80 89.3 98.4 90 100
6HK(0,1)6500206 10 14.3 15.5 15 20
6HK(0,1)6500506 20 25.1 27.4 30 30
6HK(0,1)6500806 32 38.4 42.1 40 45
6HK(0,1)6501006 40 46.8 51.3 50 60
42C
6HK(1,2)6501306 52 60.0 66.0 60 70
6HK(1,2)6501506 60 68.4 75.2 70 80
6HK(1,2)6501806 72 81.6 89.9 90 90
6HK(1,2)6502006 80 90.0 99.2 90 100
Continued on next page.

Johnson Controls Unitary Products 7


5006162-YTG-G-0717

ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY: 208/230-1-60 (Continued)


Heater Field Wiring
Heater
Air Handler Models Amps Min. Circuit Ampacity MOP.3
Models1,2 @240V 208V 230V 208V 230V
6HK(0,1)6500206 10 14.4 15.6 15 20
6HK(0,1)6500506 20 25.3 27.5 30 30
6HK(0,1)6500806 32 38.5 42.2 40 45
6HK(0,1)6501006 40 46.9 51.5 50 60
48C
6HK(1,2)6501306 52 60.1 66.1 70 70
6HK(1,2)6501506 60 68.5 75.4 70 80
6HK(1,2)6501806 72 81.8 90.0 90 90
6HK(1,2)6502006 80 90.2 99.3 90 100
6HK(0,1)6500206 10 14.4 15.6 15 20
6HK(0,1)6500506 20 25.3 27.5 30 30
6HK(0,1)6500806 32 38.5 42.2 40 45
6HK(0,1)6501006 40 46.9 51.5 50 60
48D 6HK(1,2)6501306 52 60.1 66.1 70 70
6HK(1,2)6501506 60 68.5 75.4 70 80
6HK(1,2)6501806 72 81.8 90.0 90 90
6HK(1,2)6502006 80 90.2 99.3 100 100
6HK(1,2)6502506 100 111.8 123.2 125 125
6HK(0,1)6500206 10 15.9 17.1 20 20
6HK(0,1)6500506 20 26.8 29.0 30 30
6HK(0,1)6500806 32 40.0 43.7 40 45
6HK(0,1)6501006 40 48.4 53.0 50 60
60C
6HK(1,2)6501306 52 61.6 67.6 70 70
6HK(1,2)6501506 60 70.0 76.9 70 80
6HK(1,2)6501806 72 83.3 91.5 90 100
6HK(1,2)6502006 80 91.7 100.8 100 110
6HK(0,1)6500206 10 16.3 17.5 20 20
6HK(0,1)6500506 20 27.1 29.4 30 30
6HK(0,1)6500806 32 40.4 44.1 45 45
6HK(0,1)6501006 40 48.8 53.3 50 60
60D 6HK(1,2)6501306 52 62.0 68.0 70 70
6HK(1,2)6501506 60 70.4 77.2 80 80
6HK(1,2)6501806 72 83.6 91.9 90 100
6HK(1,2)6502006 80 92.0 101.2 100 110
6HK(1,2)6502506 100 113.7 125.1 125 150
1. (0,1) - maybe 0 (no service disconnect) or 1 (with service disconnect).
2. (1,2) maybe 1 (with service disconnect, no breaker jumper bar) or 2 (with service disconnect & breaker jumper bar).
3. MOP = Maximum Overcurrent Protection device; must be HACR type service disconnect or time delay fuse. Refer to the latest edition of the National Electric Code or in
Canada the Canadian electrical Code and local codes to determine correct wire sizing.

8 Johnson Controls Unitary Products


5006162-YTG-G-0717
d

ELECTRICAL DATA FOR MULTI-SOURCE POWER SUPPLY: 208/230-1-60


Min. Circuit Ampacity MOP1
Total
Air Handlers Heater Heater 208V 230V 208V 230V
Models Models Amp@ Circuit Circuit
240V
1st3 2nd 3rd 1st3 2nd 3rd 1st3 2nd 3rd 1st3 2nd 3rd
24B 6HK16501306 52 20.5 37.6 – 22.5 41.5 – 25 40 – 25 45 –
6HK16501306 52 21.7 37.6 – 23.6 41.5 – 25 40 – 25 45 –
30B
6HK16501506 60 24.5 43.3 – 26.8 47.9 – 25 45 – 30 50 –
6HK16501306 52 22.0 37.6 – 24.0 41.5 – 25 40 – 25 45 –
6HK16501506 60 24.9 43.3 – 27.2 47.9 – 25 45 – 30 50 –
36B
6HK16501806 72 42.3 39.0 – 46.4 43.1 – 45 40 – 50 45 –
6HK16502006 80 46.6 43.3 – 51.2 47.9 – 50 45 – 60 50 –
6HK16501306 52 21.5 37.6 – 23.5 41.5 – 25 40 – 25 45 –
6HK16501506 60 24.4 43.3 – 26.7 47.9 – 25 45 – 30 50 –
36C
6HK16501806 72 41.8 39.0 – 45.9 43.1 – 45 40 – 50 45 –
6HK16502006 80 46.1 43.3 – 50.7 47.9 – 50 45 – 60 50 –
6HK16501306 52 21.5 37.6 – 23.5 41.5 – 25 40 – 25 45 –
6HK16501506 60 24.4 43.3 – 26.7 47.9 – 25 45 – 30 50 –
37C
6HK16501806 72 41.8 39.0 – 45.9 43.1 – 45 40 – 50 45 –
6HK16502006 80 46.1 43.3 – 50.7 47.9 – 50 45 – 60 50 –
6HK16501306 52 22.3 37.6 – 24.3 41.5 – 25 40 – 25 45 –
6HK16501506 60 25.2 43.3 – 27.5 47.9 – 30 45 – 30 50 –
42C
6HK16501806 72 34.7 39.0 – 46.6 43.1 – 40 40 – 50 45 –
6HK16502006 80 38.2 43.3 – 51.4 47.9 – 40 45 – 60 50 –
6HK16501306 52 22.4 37.6 – 24.4 41.5 – 25 40 – 25 45 –
6HK16501506 60 25.3 43.3 – 27.6 47.9 – 30 45 – 30 50 –
48C
6HK16501806 72 42.6 39.0 – 46.8 43.1 – 45 40 – 50 45 –
6HK16502006 80 47.0 43.3 – 51.5 47.9 – 50 45 – 60 50 –
6HK16501306 52 22.4 37.6 – 24.4 41.5 – 25 40 – 25 45 –
6HK16501506 60 25.3 43.3 – 27.6 47.9 – 30 45 – 30 50 –
48D 6HK16501806 72 42.6 39.0 – 46.8 43.1 – 45 40 – 50 45 –
6HK16502006 80 47.0 43.3 – 51.5 47.9 – 50 45 – 60 50 –
6HK16502506 100 47.0 43.3 21.7 51.5 59.9 24.0 50 45 25 60 60 25
6HK16501306 52 23.9 37.6 – 25.9 41.5 – 25 40 – 30 45 –
6HK16501506 60 26.8 43.3 – 29.1 47.9 – 30 45 – 30 50 –
60C
6HK16501806 72 44.1 39.0 – 48.3 43.1 – 45 40 – 50 45 –
6HK16502006 80 48.5 43.3 – 53.0 47.9 – 50 45 – 60 50 –
6HK16501306 52 24.3 37.6 – 26.3 41.5 – 25 40 – 30 45 –
6HK16501506 60 27.2 43.3 – 29.5 47.9 – 30 45 – 30 50 –
60D 6HK16501806 72 44.5 39.0 – 48.6 43.1 – 45 40 – 50 45 –
6HK16502006 80 48.8 43.3 – 53.4 47.9 – 50 45 – 60 50 –
6HK16502506 100 48.8 43.3 21.7 53.4 59.9 24.0 50 45 25 60 60 25
1. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. The 1st circuit includes blower motor amps. Refer to the
latest edition of the National Electric Code or in Canada the Canadian electrical Code and local codes to determine correct wire sizing.

Johnson Controls Unitary Products 9


5006162-YTG-G-0717

ELECTRICAL DATA FOR SINGLE SOURCE POWER SUPPLY: 208/230-3-60


Heater Field Wiring
Air Handler Heater
Amps Min. Circuit Ampacity MOP.2
Models Models1 @240V 208V 230V 208V 230V
18B 6HK36501025 23.1 26.4 29.4 30 30
24B 6HK36501025 23.1 26.8 29.4 30 30
6HK36501025 23.1 27.9 30.5 30 35
30B
6HK36501525 34.6 40.4 44.3 45 45
6HK36501025 23.1 28.3 30.9 30 35
6HK36501525 34.6 40.8 44.7 45 45
36B
6HK36501825 41.6 48.4 53.2 50 55
6HK465020253 46.2 53.3 58.5 55 60
6HK36501025 23.1 27.8 30.4 30 35
6HK36501525 34.6 40.3 44.2 45 45
36C
6HK36501825 41.6 47.9 52.7 50 55
6HK465020253 46.2 52.8 58.0 55 60
6HK36501025 23.1 27.8 30.4 30 35
6HK36501525 34.6 40.3 44.2 45 45
37C
6HK36501825 41.6 47.9 52.7 50 55
6HK465020253 46.2 52.8 58.0 55 60
6HK36501025 23.1 28.5 31.1 30 35
6HK36501525 34.6 41.0 45.0 45 45
42C
6HK36501825 41.6 48.7 53.4 50 55
6HK465020253 46.2 53.5 58.8 55 60
6HK36501025 23.1 28.6 31.3 30 35
6HK36501525 34.6 41.1 45.1 45 50
48C
6HK36501825 41.6 48.8 53.6 50 55
6HK465020253 46.2 53.6 58.9 55 60
6HK36501025 23.1 28.6 31.3 30 35
6HK36501525 34.6 41.1 45.1 45 50
48D 6HK36501825 41.6 48.8 53.6 50 55
6HK465020253 46.2 53.6 58.9 55 60
3 57.7 66.2 72.7 70 80
6HK46502525
6HK36501025 23.1 30.1 32.8 35 35
6HK36501525 34.6 42.6 46.6 45 50
60C
6HK36501825 41.6 50.3 55.1 55 60
6HK465020253 46.2 55.1 60.4 60 70
6HK36501025 23.1 30.1 32.8 35 35
6HK36501525 34.6 42.6 46.6 45 50
60D 6HK36501825 41.6 50.3 55.1 55 60
6HK465020253 46.2 55.1 60.4 60 70
6HK465025253 57.7 67.7 74.2 70 80
1. Asterisk (*) denotes the 20kW and 25kW heater models (6HK46502025 and 6HK46502525) come with service disconnects standard. Single source power
MCA and MOP requirements are given here only for reference if used with field installed single point power modification (S1-32436041000).
2. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. The 1st circuit includes blower motor amps. Refer to the lat-
est edition of the National Electric Code or in Canada the Canadian electrical Code and local codes to determine correct wire sizing.
3. The 20kW and 25kW heater models (6HK46502025 and 6HK46502525) come with circuit breakers standard. Single source power MCA and MOP requirements
are given here only for reference if used with field installed single point power modification.

10 Johnson Controls Unitary Products


5006162-YTG-G-0717
d

ELECTRICAL DATA FOR MULTI-SOURCE POWER SUPPLY: 208/230-3-60


Min. Circuit Ampacity MOP2

Air Handlers Heater Total Heater 208V 230V 208V 230V


Models Models1 Amp@ 240V Circuit Circuit

1st2 2nd 1st2 2nd 1st2 2nd 1st2 2nd


36B 6HK46502025 46.2 28.3 25.0 30.9 27.6 30 25 35 30
36C 6HK46502025 46.2 27.8 25.0 30.4 27.6 30 25 35 30
37C 6HK46502025 46.2 34.0 31.3 37.3 34.6 30 25 35 30
42C 6HK46502025 46.2 28.5 25.0 31.1 27.6 30 25 35 30
48C 6HK46502025 46.2 28.6 25.0 31.3 27.6 30 25 35 30
6HK46502025 46.2 28.6 25.0 31.3 27.6 30 25 35 30
48D
6HK46502525 57.7 34.9 31.3 38.2 34.6 35 35 40 35
60C 6HK46502025 46.2 30.1 25.0 32.8 27.6 35 25 35 30
6HK46502025 46.2 30.5 25.0 33.1 27.6 35 25 35 30
60D
6HK46502525 57.7 36.8 31.3 40.1 34.6 40 35 45 35
1. The 20kW and 25kW heater models (6HK46502025 and 6HK46502525) come with service disconnects standard.
2. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse. The 1st circuit includes blower motor amps. Refer to the
latest edition of the National Electric Code or in Canada the Canadian electrical Code and local codes to determine correct wire sizing.

AIR FLOW DATA (CFM)1


Blower External Static Pressure (in. wc.)
Models
Motor Speed 0.10 0.20 0.30 0.40 0.50 0.60 0.70
208 Volt
High 723 702 666 576 523 373 317
18B Medium 566 543 480 382 305 183 N/A
Low 394 330 183 144 N/A N/A N/A
High 990 973 953 924 885 797 713
24B Medium 736 723 703 644 606 540 457
Low 579 562 513 463 395 287 202
High 1228 1192 1134 1078 1023 951 843
30B Medium 1023 998 958 915 859 741 677
Low 769 745 701 632 577 495 433
High 1522 1475 1416 1349 1276 1188 1108
36B Medium 1251 1217 1180 1135 1085 1042 968
Low 965 951 936 914 886 836 742
High 1539 1489 1450 1400 1283 1201 1110
36C Medium 1159 1147 1096 1042 994 943 877
Low 966 933 892 859 812 769 679
High 1508 1471 1436 1382 1217 1054 1031
37C Medium 1151 1138 1117 1053 923 837 758
Low 959 939 904 829 745 698 616
High 1827 1769 1707 1634 1545 1315 1236
42C Medium 1444 1423 1392 1348 1204 1118 1050
Low 1136 1140 1116 1041 982 893 842
High 1686 1643 1583 1507 1441 1357 1062
48C Medium 1482 1439 1392 1340 1280 1090 971
Low 1252 1222 1186 1148 987 928 810
High 1988 1931 1853 1775 1695 1606 1391
48D Medium 1672 1636 1587 1522 1439 1302 1139
Low 1376 1348 1309 1249 1138 1038 973
High 1851 1813 1757 1680 1601 1513 1262
60C Medium 1718 1687 1631 1562 1499 1417 1185
Low 1560 1546 1505 1441 1383 1258 1144
High 1971 1919 1844 1757 1664 1563 1190
60D Medium 1812 1763 1698 1639 1561 1451 1142
Low 1403 1394 1364 1327 1153 1079 968
Continued on next page.

Johnson Controls Unitary Products 11


5006162-YTG-G-0717

AIR FLOW DATA (CFM)1 (Continued)


Blower External Static Pressure (in. wc.)
Models
Motor Speed 0.10 0.20 0.30 0.40 0.50 0.60 0.70
230 Volt
High 806 780 745 687 623 508 380
18B Medium 640 614 563 500 405 284 216
Low 461 414 325 188 156 N/A N/A
High 1142 1114 1078 1051 988 931 778
24B Medium 854 840 826 800 738 688 605
Low 684 663 633 578 510 445 322
High 1261 1231 1174 1116 1051 977 891
30B Medium 1117 1091 1048 984 934 863 699
Low 864 846 795 754 663 575 488
High 1601 1552 1485 1414 1337 1258 1178
36B Medium 1385 1352 1302 1252 1193 1106 1057
Low 1117 1103 1079 1044 1001 945 889
High 1671 1636 1581 1513 1439 1330 1210
36C Medium 1326 1310 1280 1238 1162 1081 994
Low 1125 1102 1059 1014 950 894 827
High 1681 1630 1572 1493 1427 1175 1031
37C Medium 1308 1284 1250 1213 1022 951 859
Low 1109 1096 1063 964 856 807 723
High 1924 1861 1778 1707 1618 1442 1271
42C Medium 1629 1585 1541 1470 1403 1226 1073
Low 1323 1295 1271 1232 1111 1045 954
High 1775 1727 1668 1596 1513 1431 1190
48C Medium 1591 1551 1500 1447 1380 1312 1059
Low 1392 1363 1317 1267 1206 1025 924
High 2150 2069 1988 1894 1812 1690 1481
48D Medium 1878 1812 1752 1677 1604 1497 1258
Low 1583 1543 1493 1437 1332 1164 1075
High 1931 1889 1808 1739 1655 1566 1472
60C Medium 1845 1798 1731 1659 1581 1498 1249
Low 1726 1692 1640 1578 1503 1416 1174
High 2060 2006 1922 1829 1717 1613 1224
60D Medium 1949 1900 1817 1735 1640 1547 1176
Low 1600 1563 1527 1476 1400 1132 1022
1. Air handler units have been tested to UL 1995 / CSA 22.2 No. 236 standards up to 0.50" wc. external static pressure. 
Dry coil conditions only, tested without filters.
For optimal performance, external static pressures of 0.2" to 0.5" are recommended. Heating applications tested at 0.50” w.c. esp.

kW & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENT


For a power distribution voltage that is different than the provided nominal voltage, multiply the kW and MBH data from the table by
the conversion factor in the following table.
DISTRIBUTION POWER NOMINAL VOLTAGE CONVERSION FACTOR
208V 240V 0.75
220V 240V 0.84
230V 240V 0.92

APPLICATION FACTORS - RATED CFM VS. ACTUAL CFM


% Of Rated Airflow (CFM) 80% 90% 100% 110% 120%
Capacity Factor 0.96 0.98 1.00 1.02 1.03

12 Johnson Controls Unitary Products


5006162-YTG-G-0717

NOTICE
BLOWER SPEED CONNECTIONS
PSC STANDARD MOTOR PSC STANDARD MOTOR
Filter frames are orientation specific. The block-off box pro-
FACTORY WIRED TO FACTORY WIRED TO
FAN MOTOR RELAY vided with the kit is to be inserted after the air filter has been
TRANSFORMER

PUR
TERMINAL ON BLK installed.
CONTROL BOARD
CAP
FACTORY WIRED TO For upflow platform return applications, cut the hole in the

BRN
PRP PRP H M L FAN MOTOR RELAY
TERMINAL ON return air platform the same size as the filter frame opening

PUR
CAP 230 VOLT CONTROL BOARD HIGH (dimensions for E x D in Table 1). DO NOT cut an oversized
BLOWER
MOTOR
BLK MED hole.
RC LOW
230 VOLT

NOTICE
BRN BLOWER MOTOR GND.

FACTORY WIRED TO GND.


TRANSFORMER
When attaching return air duct system to filter frame, mount-
ALTERNATE CONNECTION ALL OTHER AIR HANDLER ing hardware should not have sharp extruding points
AP60, RFCX60, MP20 A0342-001
exposed.

ACCESSORIES Combustible Floor Base Accessory - If an electric heat


Refer to Price Manual for specific model numbers where not accessory which is rated for greater than zero clearance to
shown. combustible surfaces is installed in these air handlers in the
downflow operating positions on a combustible floor, one of the
TXV Kits - Air handlers are shipped with “Flex-coils” without a following combustible floor base accessory models is required:
factory installed metering device. For added flexibility, an R-22 S1-1FB1917, S1-1FB1921, S1-1FB1924.
or R-410A TXV or orifice can be field installed to meet your
refrigerant choice. All kits are chatleff style and require no Breaker Moisture Seal Accessory - A clear circuit breaker
brazing to install. moisture barrier seals the breakers from humidity and dust. The
flexibility of the clear cover allows circuit breakers to be turned
Electric Heaters - 6HK models shown under electrical data ON or OFF without removing the cover. The cover firmly
include sequential operation and temperature dual limit attaches to the access panel around the circuit breakers with
switches for safe, efficient operation. Service disconnects are the use of double backed adhesive tape. To ensure that
provided where shown. moisture or dust does not contaminate circuit breakers, an S1-
02435672000, Circuit Breaker, Cover Seal may be ordered.
SINGLE SOURCE POWER ACCESSORIES (SINGLE PHASE)
S1-02435670000 For heat kits with 2 service disconnects.
Thermostat - Compatible thermostat controls are available
through accessory sourcing. For optimum performance, these
S1-02435671000 For heat kits with 3 service disconnects.
outdoor units are fully compatible with our York touch screen
SINGLE SOURCE POWER ACCESSORY (THREE PHASE)
thermostat with proprietary (patent-pending) hexagon interface.
Contains a terminal block and wiring to For more information, see the thermostat section of the Product
S1-32436041000
connect service disconnects together.
Equipment Catalog.

POWER WIRING - LINE CONNECTIONS


3+$6((/(&75,&+($7237,216
6,1*/(6285&(32:(5 
08/7,6285&(32:(5 08/7,6285&(32:(5

 :,7+-803(5%$5 *1'
*1'
*1'
6' &.7 /
/ 
6'
32:(5 /
6833/< / 32:(5 / 6' 32:(5 &.7 / 6'
/ /
6833/< 6833/< 
12(/(&75,&+($7 6' &.7 / 6'
7(50,1$/%/2&.25 /
-803(5%$5 
*1' 6(59,&(',6&211(&7
&,5&8,7621N:N: &,5&8,7621N:N:
&,5&8,7621N: &,5&8,7621N:
32:(5
&1
6833/<
&1
3+$6((/(&75,&+($732:(5237,216
 
&20321(17&2'(6 6,1*/(6285&(32:(5 08/7,6285&(32:(5

*1'*5281'/8*
*1' *1'
6'6(59,&(',6&211(&7
&.7&,5&8,7
&1:,5(&211(&725187 / /
32:(5 / &.7 /
),(/'32:(5:,5,1* / / 6'
6833/< 32:(5
9  /
6833/< /
7(50,1$/%/2&.25 &.7 6'
6(59,&(',6&211(&7 / $

Johnson Controls Unitary Products 13


5006162-YTG-G-0717

TYPICAL THERMOSTAT CONNECTION

),(/'
,167$//('
-803(5,)
5(48,5('

:. :.

),(/',167$//('
-803(5,)6,1*/(
67$*(7+(50267$7
,686(' ),(/'
,167$//('
-803(5,)
5(48,5('
:

:. :.

$

14 Johnson Controls Unitary Products


5006162-YTG-G-0717

COMBUSTIBLE FLOOR BASE ACCESSORY


$,5+$1'/(5
'(37+

)5217

'2:1)/2:
$,5+$1'/(5
)/225

:$50$,53/(180 $3352;´
&/($5$1&(
ZLWK´IODQJHRXW ´
$//$5281'

RQHDFKVLGH 3/(180
 ´ ´
% )/22523(1,1*
$ ),%(5*/$66
,168/$7,21 &52666(&7,21 $$ )5206,'(

$

),%(5*/$667$3( $,5+$1'/(5
XQGHUIODQJH :,'7+
% $
&20%867,%/(
)/225%$6(
)/225
 
&20%867,%/()/225
%$6($&&(6625<


%
3/(180
$3352;´
&/($5$1&(
$//$5281'
´ & ´
)/22523(1,1*

&52666(&7,21 %% )520)5217 $

Floor Base Dimensions


Used with
Models A B C
1FB1917 18B, 24B, 30B, 36B 17.5 14.0 16.0
1FB1921 36C, 37C, 42C, 48C, 60C 21.0 17.5 19.5
1FB1924 48D, 60D 24.5 21.0 23.0

LIMITATIONS TYPICAL APPLICATIONS


These units must be wired and installed in accordance with all
national and local safety codes. UPFLOW DOWNFLOW

Voltage limits are as follows: HEAT

1Normal HEAT
Air Handler Voltage Operating Voltage
Range
208/230-1-60 187-253 HORIZONTAL RIGHT

1. Rated in accordance with ARI Standard 110, utilization range “A”.


HEAT

Airflow must be within the minimum and maximum limits


approved for electric heat, evaporator coils and outdoor units. HEAT

HORIZONTAL LEFT
A0330-001

Johnson Controls Unitary Products 15


NOTES

Subject to change without notice. Published in U.S.A. 5006162-YTG-G-0717