IndustrialIT
800xA - Information Management
             System Version 5.0 SP1
                Release Notes
                    IndustrialIT
800xA - Information Management
             System Version 5.0 SP1
                Release Notes
NOTICE
         This document contains information about one or more ABB products and may include a
         description of or a reference to one or more standards that may be generally relevant to
         the ABB products. The presence of any such description of a standard or reference to a
         standard is not a representation that all of the ABB products referenced in this document
         support all of the features of the described or referenced standard. In order to determine
         the specific features supported by a particular ABB product, the reader should consult the
         product specifications for the particular ABB product.
         The information in this document is subject to change without notice and should not be
         construed as a commitment by ABB. ABB assumes no responsibility for any errors that
         may appear in this document.
         In no event shall ABB be liable for direct, indirect, special, incidental or consequential
         damages of any nature or kind arising from the use of this document, nor shall ABB be
         liable for incidental or consequential damages arising from use of any software or hard-
         ware described in this document.
         This document and parts thereof must not be reproduced or copied without written per-
         mission from ABB, and the contents thereof must not be imparted to a third party nor used
         for any unauthorized purpose.
         The software or hardware described in this document is furnished under a license and
         may be used, copied, or disclosed only in accordance with the terms of such license.
         This product meets the requirements specified in EMC Directive 89/336/EEC and in Low
         Voltage Directive 72/23/EEC.
TRADEMARKS
         All rights to copyrights, registered trademarks, and trademarks reside with their respec-
         tive owners.
         Copyright © 2003-2007 by ABB.
         All rights reserved.
         Release:                 June 2007
         Document number:         3BUF001135R5011
                                                                                        Table of Contents
            Section 1 - Release Notes
            Introduction .......................................................................................................................7
            Functionality Changes .......................................................................................................8
            Product Support .................................................................................................................8
            Backups .............................................................................................................................8
            Licensing ...........................................................................................................................8
                      Server Software ......................................................................................................8
                      History Logs...........................................................................................................8
                      Desktop Client Software ........................................................................................9
            Components Supported .....................................................................................................9
                      History Services ...................................................................................................10
                      Softpoint Services ................................................................................................10
                      Calculations..........................................................................................................10
                      Application Scheduler ..........................................................................................11
                      Open Data Access ................................................................................................11
                      Data Direct ...........................................................................................................12
                      Desktop Trends.....................................................................................................12
                      Display Services...................................................................................................13
            Section 2 - History Services
            Changed Functionality.....................................................................................................15
            Fixed Problems ................................................................................................................15
            Known Problems and Workarounds ................................................................................24
            Section 3 - Calculations
            Changed Functionality.....................................................................................................31
3BUF001135R5011                                                                                                                                      5
Table of Contents
               Fixed Problems................................................................................................................ 31
               Known Problems and Workarounds................................................................................ 32
               Section 4 - Application Scheduler
               Changed Functionality .................................................................................................... 37
               Fixed Problems................................................................................................................ 37
               Known Problems and Workarounds................................................................................ 37
               Section 5 - Open Data Access
               Changed Functionality .................................................................................................... 41
               Known Problems and Workarounds................................................................................ 41
               Section 6 - Desktop Applications
               Changed Functionality .................................................................................................... 43
               Fixed Problems................................................................................................................ 43
               Known Problems and Workarounds................................................................................ 46
6                                                                                                                    3BUF001135R5011
                                            Section 1 Release Notes
Introduction
            This document presents release information for Industrial IT Information
            Management Version 5.0 Service Pack 1 for use in the Industrial IT 800xA System
            Version 5.0 Service Pack 1. This includes:
            •     A brief overview of new and modified functionality since the last release.
            •     A listing of problems fixed since the last release (SV 5.0) that are fixed by this
                  release (SV5.0 SP1). This includes problems fixed in roll ups since SV 5.0.
            •     A listing of known problems that exist in the current release after final testing
                  with workarounds that help overcome the problem.
            The document contains additional notes that may be valuable to customers and
            service personnel working with the product. It replaces release notes for prior
            releases and is included on the product media.
            The release information is organized by software component as follows:
            •     Section 2, History Services.
            •     Section 3, Calculations.
            •     Section 4, Application Scheduler.
            •     Section 5, Open Data Access.
            •     Section 6, Desktop Applications.
            Upgrades are supported from previous system versions as described in the system
            instructions. Information Management application servers use Windows Server
            2003 with SP1. Information Management clients can be loaded on Windows XP
            Professional with SP2.
3BUF001135R5011                                                                                       7
Functionality Changes                                                     Section 1   Release Notes
Functionality Changes
               New functionality and features added since the last release and functionality and
               features that have changed or been removed are described in each of the component
               sections.
Product Support
               Contact ABB technical support for assistance in problem reporting.
Backups
               It is recommended that an image backup be made after installing the 800xA System
               software and before Information Management software is installed. Make a second
               backup after Information Management software installed.
                  Oracle for Information Management can be configured to span multiple
                  partitions. Any backup must contain all Oracle files from all partitions. Any
                  reboots between backups of partitions containing Oracle will corrupt the backup
                  (Oracle will not restart after the restore of the backup).
Licensing
               Information Management server software, history logs, and desktop client software
               must be licensed before they will function correctly.
Server Software
               Server software components are licensed on a per-server basis. This means one
               license entitles the software to be installed on one server. One base history license
               must be purchased for each server.
History Logs
               Information Management history logs are licensed on a system basis. The license
               resides on the system licensing server (Aspect Server), and the quantity of logs
               specified by that license may be distributed in any combination on the Information
8                                                                                3BUF001135R5011
Section 1   Release Notes                                                  Desktop Client Software
               Management application servers in the system. This license does not account for
               consolidating of historical data. A separate license is required for consolidation.
               Dual logs span two Information Manager servers. For example 200 dual logs allows
               a log to be created that provides a 200 log configuration spanning two servers.
Desktop Client Software
               Desktop Client software components are licensed on a concurrent-user basis. This
               means the client software can be installed on as many computers as needed. The
               server will control the number of clients that may connect to the server based on the
               number of client licenses purchased. For example, Display Client software can be
               installed on ten computers event though only two Display Client licenses were
               purchased. Only two client computers will be permitted to connect to the server at
               any one time.
               For Display Client and DataDirect, each open display and/or DataDirect window
               occupies a client license, even if the windows are open on the same computer. Thus
               one computer may occupy two or more client licenses concurrently.
               For Desktop Trends, client licenses are occupied on a per-computer basis. As many
               trend displays as needed can be open on a given computer. This would still occupy
               just one client license.
Components Supported
               The component software packages for Information Management Version 5.0 are:
               •   Systems Services 5.0.
               •   History Services 5.0.
               •   Softpoint Services 5.0.
               •   Calculations 5.0.
               •   Application Scheduler 5.0.
               •   Open Data Access 5.0.
               •   Data Direct 5.0.
               •   Desktop Trends 5.0.
               •   Display Services 5.0.
               •   Oracle 9.2.0.7.
3BUF001135R5011                                                                                    9
History Services                                                          Section 1   Release Notes
History Services
               History Services supports data collection with optional compression (polled, by
               exception, user-supplied, or manual), online storage, offline storage, and retrieval.
               History Services can collect the following types of data:
               •    Process data from aspect object properties.
               •    Manually or programmatically entered lab data.
               •    Events and messages from the 800xA system Alarm/Event server.
               •    Finished reports scheduled and executed via the Application Scheduler
               •    Production data, batch and manufacturing data.
Softpoint Services
               Refer to the PLC Connect and SoftPoint Server System Version 5.0 Release Notes
               (3BSE036375Rxxxx) for changes and fixes to softpoints.
               SoftPoint Services provides for configuration and use of internal process variables
               not connected to an external physical process signal. Once configured, the softpoints
               may be accessed by other Information Management applications as if they were
               actual process points. For example, softpoint values may be stored in property logs
               in History Services. Reporting packages such as Crystal Reports may access
               softpoints for presentation in reports. Desktop tools such as Desktop Trends and
               DataDirect can read from and write to softpoints.
               Softpoint alarms can be configured and are directly integrated with system alarms
               and events. Engineering unit definitions for softpoints include minimum/maximum
               limits and a unit descriptor.
               Softpoints is supported as a redundant service on a nonredundant Information
               Manager Server pair. The Softpoint Services software may run on any number of
               servers within a system.
               Data types supported are: Boolean, integer (32bit), single precision floating point
               (32 bit) and string. Also, double precision floating point (64 bit) is supported as an
               extended data type.
Calculations
               Calculations services provides configuration and scheduling of calculations for
               aspect objects. Like softpoints, calculations is supported as a redundant service.
10                                                                               3BUF001135R5011
Section 1   Release Notes                                                     Application Scheduler
               Typically calculations are applied to real-time database objects, including both
               softpoints and actual process points. Calculations may also be applied to object
               types. This allows re-use of the calculation each time a new object is instantiated
               from the object type.
               Calculations can be triggered by changes to the inputs, or be scheduled to execute
               cyclically or at a given date and time. A calculation aspect may be applied to any
               aspect object such as a unit, vessel, pump, or softpoint. Inputs can be any aspect
               object property, and outputs can be any writable point in the system. Input and
               output definitions can be made relative to the object for which the calculation is
               defined. Data quality and alarm generation are supported. Calculation logic is
               written in VBScript.
Application Scheduler
               The Application Scheduler provides for the scheduling and running of jobs for
               Industrial IT applications. For example, jobs can be run related to Information
               Management applications including archival reports, event-driven data collection,
               and consolidation of Production Data Logs (PDLs) and message logs. Jobs can be
               scheduled and run at different times and under different conditions as specified
               through aspects related to a job definition object.
               The Report plug-in for the Application Scheduler is compatible with Crystal
               Reports Professional and Developer.
Open Data Access
               ODA supports client applications that use either an ODBC or OLE DB data source,
               for example: Crystal Reports and Microsoft Excel. Virtual database tables in the
               ODA Server map Information Management data types to OLE DB and ODBC data
               types. A predefined numericlog table supports access to historical process data.
               For real-time data access, configure custom tables that expose specifically those
               aspect objects and properties needed for access. These tables are then combined to
               form one or more virtual real-time databases. These real-time databases support
               read and write access. The custom views make it easier to access real-time data, and
               help impose restrictions on data access for certain users. One predefined table
               named generic_da also supports real-time data access. This is a read-only table that
               exposes all properties for all real-time objects.
3BUF001135R5011                                                                                      11
Data Direct                                                            Section 1    Release Notes
              The client application may run locally on the Information Management server
              where the ODA Server is installed, or it may run on a remote client computer.
              Remote clients require the ODA client software to be installed.
Data Direct
              DataDirect is an add-in program for Microsoft Excel that gives access to data from
              Information Management applications, ABB OCS applications, as well as Oracle
              and OPC data sources. With the proper authority, updating process values and
              add/modify entries in lab data logs is possible. DataDirect uses industry-standard
              tools and familiar techniques common to other Microsoft Office products.
              Specifically, DataDirect supports access to:
              •   Process, historical, and softpoint data from 800xA system aspect objects.
              •   Process values from ABB OCS databases.
              •   Alarm and event messages stored in historical message logs.
              •   Ad-hoc SQL queries without the use of SQL*NET or ODBC drivers.
              •   Production Data Logs (PDLs) for TCL, Batch 300, Batch Management, and
                  Profile Historian applications.
Desktop Trends
              Desktop Trends provides real time views for trend, production, and event data on
              Information Management display clients using these ActiveX controls. Each of
              these display clients includes easy access to the User Tag Management application.
              •   Trend display - Shows graphical representations of values for up to eight tags.
                  The Trend Display supports common trend display tools including, zoom,
                  ruler, filtering, and time offset.
              •   Ticker - Shows a repeating stream of real time data for selected tags, similar to
                  a stock market ticker.
              •   Tag explorer - Provides data for selected tags in tabular format. The
                  presentation and mode of operation resembles the Windows Explorer.
              •   PDL browser - Accesses production data from Production Data Logs for Batch
                  Management, Batch 300, TCL Batches, and Profile Historian.
12                                                                             3BUF001135R5011
Section 1   Release Notes                                                           Display Services
               •   Batch to batch display - Combines the functionality of the Trend Display with
                   the PDL Browser. It allows easy navigation of the PDL structure to find and
                   display historical trends for different batches.
               •   Event browser - Retrieves the time stamp, source, and message from OPC and
                   Audit Trail message logs configured in Information Management - History
                   Services.
               •   SQL browser - Runs ad-hoc SQL queries. A query can be saved after it is run.
                   The query can then be reopened for viewing at some time in the future. Saved
                   queries can also be deleted.
Display Services
               Display Services is used to build and view dynamic runtime displays on desktop
               client nodes connected to a Display server. This is an efficient and cost-effective
               method for building and distributing process monitoring capability throughout a
               plant.
               Custom-built displays can be connected to a variety of data sources. For example,
               use Display Services to build and run a display for viewing trend data collected by
               History Services. Also, use it to connect the same display to a third-party database,
               for instance an Oracle database on a remote Information Management node.
3BUF001135R5011                                                                                      13
Display Services   Section 1   Release Notes
14                       3BUF001135R5011
                                        Section 2 History Services
Changed Functionality
            The following new functionality is introduced in this release of History Services:
            •     Offline configuration - It is now possible to create all Oracle information, logs,
                  tables and History flat files with just the History Service running. All PAS
                  processes can be stopped.
            •     Two buttons have been added to the Inform IT History Control aspect (Node
                  Administration Structure/Inform IT History Service Provider/Inform IT
                  History object). The Check Names button produces a report of the object
                  names, log names, and object locations in the aspect directory that are different
                  or not in the Oracle database. The Check Synchronization button produces a
                  report of all the configuration attributes in all the objects in the aspect directory
                  that are different or are not in the Oracle database.
            •     Migration of Enterprise Historian online database to the System Version 5.0
                  Service Pack 1 800xA systems is supported.A new database view (logattrs) has
                  been added to provide simplified access to the presentation attributes for the
                  engineering units, minimums, and maximums. This view can be referenced by
                  log name or object name. In the past, it would have been necessary to get the
                  values directly from the controllers using the generic_da view.
Fixed Problems
            Fixed problems that are related to History Services are described in Table 1.
3BUF001135R5011                                                                                     15
Fixed Problems                                                           Section 2   History Services
                 Table 1. Fixed History Services Problems
                      Issue                                        Correction or Fix
Users should be allowed to select the drive on     Users can now choose the drive on which to
which to place Oracle files during the creation of place the system, temp, undo, and redo files
an Oracle database instance.                       while creating an Oracle database instance.
                         800xAINM-OL-5010-057
Changes made in the Maintenance view of the   The Maintenance view of the Oracle Instance
Oracle Instance Wizard are not reflected in the
                                              Wizard now contains a Refresh button. Use this
displayed values.                             button to update the values shown in the
                         800xAINM-CN-5010-059 Maintenance view.
An AdeRuntime Fail error is generated in the        The Ade Runtime function has been corrected
alarm event list when a message log is created.     to prevent the generation of this error.
                         800xAINM-CN-5010-001
Inform IT History View Display does not show the The end time is now blank until the log has
correct time for incomplete batches.             completed.
                         800xAINM-CN-5010-002
Archive data cannot be retrieved from CDs.    A software pointer has been corrected so that
                         800xAINM-CN-5010-003 archive data can now be recovered from CDs.
The status of API logs is not consistent (after a   Status bits are now correctly interpreted so that
forced resynchronization) when translating and      states and log counts are represented correctly
pending logs exist at the same time.                in the History aspect and log list.
                         800xAINM-CN-5010-004
Archived MODMSGLOG logs cannot be restored A utility has been corrected to look in the proper
(from backup (ISO) images) to workstations  place for the name of the log allowing the
other than the one on which the archive was archived logs to be found.
performed.
                         800xAINM-CN-5010-005
16                                                                                3BUF001135R5011
Section 2   History Services                                                            Fixed Problems
                 Table 1. Fixed History Services Problems (Continued)
                       Issue                                          Correction or Fix
An invalid user event (Invalid user           Logic within the History Client has been
workstation_name\Administrator for            corrected to prevent this error from being
node node_name[hsHistoryIcon,                 generated.
nn.nnn.n.nn] for example) is logged every few
seconds after a non-800xA user is logged into
the Information Management workstation.
                          800xAINM-CN-5010-006
Event triggered data collection action of a             A missing connection to the history service was
scheduler object can cause the job to end in a          corrected and now event-triggered data is
catastrophic error.                                     collected.
                          800xAINM-CN-5010-007
Backsync does not synchronize the PDL Auto              Backsync of the PDL Auto Archive aspect has
Archive aspect settings to those in the Oracle          been corrected to ensure the Oracle database
database.                                               and the aspect directory are correct.
                          800xAINM-CN-5010-008
No indication event is logged to the 800xA              The error OPC Log Consolidation: Error
system when a consolidation job fails. An error is      connecting to the remote node (...)
logged to the history log files but this error can be   is now found in the alarm and event list when a
difficult to find. The log file                         consolidation job fails.
%HS_LOG%/HS_CONSOLIDATE is the only
source of pertinent information.
                          800xAINM-CN-3500-010
If a log is selected using the Retrieve tab of the The History function has been corrected so that
Inform IT History View PDL aspect, the keyboard up and down keys function normally.
up and down keys have no effect (task, start
time, and end time do not change) in the Task,
Start Time, and End Time windows.
                          800xAINM-CN-5010-009
3BUF001135R5011                                                                                      17
Fixed Problems                                                          Section 2    History Services
                 Table 1. Fixed History Services Problems (Continued)
                      Issue                                        Correction or Fix
Migrating Enterprise Historian 2.2 (History         Migration of Enterprise Historian information to
Component Version 2.4) to Information               the System Version 5.0 Service Pack 1 800xA
Management SV 5.0 fails during the creation of      systems is supported.
log configuration aspects in the 800xA system.
                         800xAINM-CN-5010-010
Information Management 3.5 (SB 2) without a         The function that reads the database tables has
PDL license will not upgrade to Information         been corrected to create default PDL tables if
Management 3.6 (SV 3.1 SP3) or later because        none exist allowing the upgrade to proceed
IM 3.5 does not contain the PDL tables needed       without error.
by IM 3.6 and newer versions.
                         800xAINM-CN-5010-011
Creating a large database using the Oracle          The wizard has been corrected to allow creation
Instance Wizard fails when the SB 2 upgrade         of large databases.
option is selected.
                         800xAINM-CN-5000-043
When viewing a LogSet aspect, if you change         The majority of all logs are now shown as
the state of a numeric log to activate, the state   passing through the pending state before
skips the pending state and shows only the          entering the active state.
active state even though the actual state is
pending.
                         800xAINM-CN-5010-012
The selection in the Second Logset field on the     The property page has been corrected to
property page is not remembered when another        remember its selections when other pages are
page is selected and then the original property     selected.
page is selected.
                         800xAINM-CN-5010-013
18                                                                               3BUF001135R5011
Section 2   History Services                                                           Fixed Problems
                Table 1. Fixed History Services Problems (Continued)
                       Issue                                          Correction or Fix
When upgrading from SB 2 (IM 3.5/0), the AC800          The History function now updates the Oracle
upgrade deletes and recreates the control               database with the new GUIDs and dual logs that
module aspects which results in them having             are not identical are synchronized during the
new GUIDs. Information Management does not              upgrade process.
account for this and the Oracle database points
to missing control module aspects.
                          800xAINM-CN-5010-014
The Archive Import function creates a new      The Match Existing Objects feature of the
archive (RST) log instead of using the existingArchive Importer function now matches existing
one.                                           objects and archive links eliminating the
                          800xAINM-CN-5010-015 creation of another archive log.
Authentication or double authentication does not
                                              Audit trail messages are now generated for
generate audit trail messages for IM Aspects. messages logs. For numeric logs, add Inform IT
When performing an operation or configuration Authentication Category aspect to the log
change to an IM Aspect, audit trail messages are
                                              configuration object of the Aspect System
only generated for that change, not for the   Structure. From their follow the documentation
authentication or double authentication       (Configuring Authentication in 800xA -
performed to allow the change.                Information Management Configuration,
                        800xAINM-CN-3620-0008 3BUF001092Rxxxx) and this will ask for the
                                              double authentication and also report it in the
                                              alarm and event list.
When importing an archive that contains objects         The fix to 800xAINM-CN-4106-0010 makes the
that do not exist in the target system and you          Archive Importer run properly and the Match
choose to match existing objects, the import will       Existing Object feature skips rows where the
fail. Filtering out the objects with undefined object   matching object does not exists.
paths, or deleting those rows in the spreadsheet
does not fix the problem.
                        800xAINM-CN-4000-0012
Unable to associate Profile Logs to a Batch    Batch PDL has been corrected to allow a batch
recipe.                                        that is associated with a profile log to be run.
                          800xAINM-CN-5010-016 The profile log gets a taskid and shows up in the
                                               association start and end tables.
3BUF001135R5011                                                                                     19
Fixed Problems                                                           Section 2    History Services
                 Table 1. Fixed History Services Problems (Continued)
                      Issue                                        Correction or Fix
The Inform IT History Profile Log object gets an
                                              In the system extension, the aspect type was
AspectHook error on upgrade                   being deleted before the aspect category. The
(AfwConfigWizard.log).                        upgrade process no longer produces this error
                        800xAINM-CN-5000-0029 message.
Data types VT_I8 and VT_UI8 are not supported Filtering for data types VT_I8 and VT_UI8 is
in attribute filtering.                       now supported.
                         800xAINM-CN-5010-017
An event is not reported to the 800xA system if     The software (hsEventLogCollector) has been
an event category is not successfully defined       corrected to send a message to the 800xA
during 800xA system startup. In this case, events   system when an event category is not
of this category are not stored in Oracle and the   successfully defined. The message indicates
user is not notified.                               that event of the category will not be collected.
                         800xAINM-CN-5010-018
The retrieval function (Archive Service) may use The retrieval function has been corrected to use
the wrong time range when retrieving messages the Filetime value for all time ranges. The
for small retrieval windows due to a rounding    correct range of events are now returned.
problem.
                         800xAINM-CN-5010-019
When upgrading, there is a small chance that the The Information Management software has
Restore will hang when it gets to the conversion been corrected to restore without a problem.
of the database. The window status says it has
run to completion but the Next button is still
grayed out.
                        800xAINM-CN-5000-0045
The DataDirect AE plug-in doesn’t display the Information Management has been corrected by
ActorID value in the Actor column of an alarm changing the attribute name from Actor to the
and event list.                               constant ActorID. The Actor column now
                         800xAINM-CN-5010-020 displays the correct information.
20                                                                                3BUF001135R5011
Section 2   History Services                                                         Fixed Problems
                Table 1. Fixed History Services Problems (Continued)
                      Issue                                        Correction or Fix
A problem has been found in the history              The correct UTC timestamp value is now used.
BackSync utility which updates the First
Activation Time field of the report, message, and
profile logs. Under a forced synchronization, the
First Activation Time field will be modified with an
incorrect timestamp value based on local time
instead of UTC (coordinated universal time).
                         800xAINM-OP-5010-021
During an upgrade, if the nodes names in the    The HistoryContext function is now used
node structure have been modified as part of an (instead of an older conversion program) to
upgrade, the history upgrade could fail. This   handle irregularities in user configuration.
could occur when upgrade from SV 3.1 SP 3 and
SV 4.1 systems to SV 5.0 SP 1.
                         800xAINM-OL-5010-022
Environment support is disabled after upgrading The Information Management system extension
from System Version 4.1 to System Version 5.0 now removes the Inform IT History Admin
because the restored SV 4.1 information          aspect type.
contains the Inform IT History Admin aspect type
(in Aspect System Structure\Aspect System
Structure, Aspect Category\Inform IT Historian,
Aspect System). This aspect type must be
deleted.
                         800xAINM-CN-5010-023
Resizing a profile log causes all original data to   The copying phase of the resizing operation has
be lost. Resizing a profile log is supposed to       been corrected to copy the original data to the
cause a new log with the same name to be             new profile log.
created, all data from the old log to be copied to
the new log, and the old log to be deleted. The
copy phase of the resizing operation is not
functioning correctly.
                         800xAINM-CN-5010-024
3BUF001135R5011                                                                                   21
Fixed Problems                                                            Section 2   History Services
                 Table 1. Fixed History Services Problems (Continued)
                      Issue                                         Correction or Fix
Unable to recover archive data from CDs. The  There were 2 errors: a typo in the Visual Basic
Archive Import Tool does not work.            code in the Excel spreadsheet and some
                        800xAINM-CN-4106-0010 improper pointer manipulation in a 800xA
                                              Archive Import library which is used by the excel
                                              spreadsheet. Both have been corrected.
Restoring an Oracle-only backup fails because it      The restore function has been corrected to
executes the hsDBMaint -restore command               place double quotes around the hsDBMaint -
incorrectly (no double quotes around the              restore command allowing the flat files to be
command).                                             created.
                         800xAINM-CN-5010-025
Catchup data for profile log consolidation (the
                                              A software overwrite problem was detected in
data read from disk during the period right after a
                                              monitoring the data quality of the profile log,
distributed log is activated) always has a badcausing the data not to be consolidated.
data quality and as a result is not consolidated.
                                              Software that was overwriting the correct quality
                         800xAINM-OL-5010-026 with bad quality has been corrected.
Logs created on objects whose name contains           The Archive Importer now reads the log names,
spaces are stored in Information Management           creates a listing of the log names (with all
with the spaces replaced with underscores.            spaces converted to underscores), and then
Using the Archive Importer to restore a log, the      compares the archive and aspect directory log
import will not happen because the name of the        names. Matches are now found and logs are
log in the archive will not match what is in the      imported successfully.
aspect directory.
                         800xAINM-OL-5010-027
22                                                                                 3BUF001135R5011
Section 2   History Services                                                          Fixed Problems
                Table 1. Fixed History Services Problems (Continued)
                      Issue                                         Correction or Fix
Oracle connection error (ORA-03114: not             The software (hsMsgServer) now detects
connected to ORACLE) does not cause A/E             Oracle errors 3114 (Not Connected to Oracle)
collection to stop.                                 and -1012 (Not Logged on to Oracle) and
The error code is not passed back to the Event      generates the
Log Collector. A/E collection continues and event HSMSG_ORACLE_CONNECT_ERROR. The
messages are discarded. The Event Log               hsEventLogCollector application detects this
Collector should detect this problem, stop          error and stops event collection. Collection will
collection, wait 30 seconds and try again until the not resume until the Oracle problem is fixed.
problem is fixed.
                       800xAINM-CN-5000-0030
The Archive Importer function cannot import from The Archive Importer has been changed to look
an SV 5.0 Information Management archive that to the data source for the property name in
contains a log that does not contain a property  these cases.
name.
                         800xAINM-CN-5010-029
The following invalid diagnostic message is         Information Management no longer generates
generated yet the file exists.                      this invalid error message.
Could not find
C:\temp\IM_Backup_254\HistDB*.zip
                       800xAINM-CN-5000-0034
When hsDBMaint -checkDB and -clean are used, The auto archive/delete configuration is
the $HSSERVER_CONFIG object is marked for retained and growth of PDL is kept in check.
deletion or is deleted because the aspect
information does not match after a node
structure is rebuilt. This causes the PDL auto
archive/delete configuration to be lost. Without
the archive/delete, Online PDL can grow
unchecked.
                       800xAINM-CN-5000-0041
3BUF001135R5011                                                                                     23
Known Problems and Workarounds                                            Section 2   History Services
                 Table 1. Fixed History Services Problems (Continued)
                       Issue                                         Correction or Fix
If the hsEventLogCollector (history event log          Information Management has been corrected to
collector) process is collecting events, it will not   automatically detect the creation of a new
automatically detect the creation of a new             IMMSGLOG or PDLMSGLOG in the Oracle
IMMSGLOG or PDLMSGLOG in the oracle                    database.
database. Automatic detection was found to not
work in the system 4.0 release and later.
                         800xAINM-CN-5000-0042
The OCSHIS Windows user was removed from               The OCSHIS User and Changing Passwords for
the installation but not from the documentation.       Windows Users topics have been removed from
The Oracle OCSHIS user still exists to support         Section 17 of the Information Management
IM History Objects.                                    Configuration instruction (3BUF001092Rxxxx).
                         800xAINM-CN-5000-0031
Known Problems and Workarounds
                 Known problems and workarounds for History Services are described in Table 2.
                 Table 2. Known History Services Problems and Workarounds
                                                                Workarounds, Clarifications, and
                           Issue
                                                                        Helpful Hints
 When using the Engineering in Environments function         Run hsDBMaint -checkDB to verify that
 with a separate Engineering system, it is possible that     incorrect ITEM IDs are present.
 the ITEM ID can be incorrect for Information                Run hsDBMaint -clean to correct the
 Management logs moved from the Engineering                  ITEM IDs.
 System to the Production System. One indication of
 this problem is the IM log returning the
 E_INVALID_ITEM_ID error code on the Status tab.
                                 800xAINM-OL-5010-077
 The archiving of a PDL log will fail at the first history   Call ABB Technical Support for
 association to a log that does not exist.                   assistance.
                                 800xAINM-OL-5010-076
24                                                                                 3BUF001135R5011
Section 2   History Services                                     Known Problems and Workarounds
                Table 2. Known History Services Problems and Workarounds (Continued)
                                                           Workarounds, Clarifications, and
                         Issue
                                                                   Helpful Hints
 Consolidating numeric log data from one InformationUse the same naming convention for the
 Management workstation to another causes the data  numeric log template on both the source
 to be consolidated into a new log with a new name. and consolidation Information
 Because of this name change, PDL log associations  Management workstations. Keeping the
 that store the log name are no longer valid when used
                                                    name the same ensures that the PDL
 on the consolidation workstation.                  data associations will work on both
                               800xAINM-OL-5010-073 workstations.
 Information Management only supports batch              None.
 procedure paths of 40 characters or less.
                               800xAINM-CN-5010-071
 Using the Express option in the Set Archive Group Do not use the Express option.
 Rates window while importing an archive volume
 generates a Compile Error in Hidden Module
 error.
                               800xAINM-OL-5010-065
 The error code NO_DATA is returned when trying to  None.
 restore an Information Management system backup if
 the backup contains no flat files AND a new path
 (drive:\directory) is chosen during the restore.
                               800xAINM-OL-5010-063
 Condition events are stored in the IMMSGLOG log         None.
 with an incorrect active time.
                               800xAINM-OL-5010-056
 High and low limit values (listed below) are       If the resynch report is executed, you may
 inconsistently stored in the Oracle database.      notice inconsistencies as noted for the
                               800xAINM-OL-5010-051 specified attributes between what is
                                                    stored in Oracle and what is reported in
                                                    the aspect directory. The issue is related
                                                    to the various sources for these attributes
                                                    in the 800xA system.
3BUF001135R5011                                                                               25
Known Problems and Workarounds                                            Section 2   History Services
                Table 2. Known History Services Problems and Workarounds (Continued)
                                                               Workarounds, Clarifications, and
                          Issue
                                                                       Helpful Hints
 The For DataDirect and Microsoft Excel topic on page Add the following informational note at the
 423 of the Information Management Configuration        end of the For DataDirect and Microsoft
 instruction (3BUF001092Rxxxx) needs to state that it Excel topic:
 is not possible to output Excel reports in HTML format     An Excel report cannot be output in
 to the aspect directory (object path).                     HTML format to the aspect directory
                               800xAINM-MC-5010-030         (object path).
 The synchronization operation is now automatically         Step 8 through Step 14 and Figure 315
 started and completed as part of the history database      through Figure 320 need to be moved to
 restoration process. Procedure documented on page          just after the last paragraph of the
 417 through page 421 (Step 8 through Step 14) of the       Synchronizing the Aspect Directory with
 Information Management Configuration instruction           the History Database topic on page 423.
 (3BUF001092Rxxxx) is incorrect for normal          Replace the last paragraph of the
 configuration and an example manual configuration  Synchronizing the Aspect Directory with
 procedure needs to be documented.                  the History Database topic on page 423
                               800xAINM-MC-5010-031 with:
                                                                An example synchronization
                                                                operation is demonstrated in the
                                                                following steps:
                                                            The following step (Step 8) needs to be
                                                            added to replace the steps that were
                                                            moved (page 417):
                                                                8. When the Click Finish to Exit the
                                                                Application message is displayed,
                                                                click Finish.
 The second sentence in the last paragraph on page          Replace the second sentence in the last
 331 dealing with Configuring Archive Backup needs to       paragraph with:
 be clarified to remind the user that the write privilege
                                                    The directory on the remote node must be
 must be one of the privileges added to the directory on
                                                    shared folder with the correct privileges
 the remote node.                                   (the write privilege must be one of the
                               800xAINM-MC-5010-032 privileges).
26                                                                                3BUF001135R5011
Section 2   History Services                                    Known Problems and Workarounds
                Table 2. Known History Services Problems and Workarounds (Continued)
                                                            Workarounds, Clarifications, and
                         Issue
                                                                    Helpful Hints
 When the archive device is configured to backup fullExclude the mkisofs.exe application
 archive volumes to an ISO image of the archive      (located in the C:\Program Files\ABB
 volume directory, the mkisofs.exe application crashes
                                                     Industrial IT\Inform IT\history\bin
 causing the archive job to fail.                    directory) from Data Execution Prevention
                                800xAINM-CN-5010-078 (DEP) using one of the methods
                                                     described in the MSDN knowledge base
                                                     article 875352.
 When an Information Management server object is         Delete the objects manually. They will be
 deleted from the Node Administration structure, the     located at the top of the Plant Explorer.
 corresponding Inform IT History Objects are not
 deleted from the Node Administration structure.
                               800xAINM-CN-3500-0004
 When using the Bulk Configuration tool in Microsoft     If new logs do not start automatically, they
 Excel to create a large number of property logs, the    must be started manually. If existing logs
 logs will not activate automatically, even if the       go inactive, they must be restarted.
 Activation Command is set to Activate. Also some    Use the Inform IT History Log List display
 existing logs may be deactivated inadvertently.     as part of the Node Administration
                               800xAINM-CN-3500-0005 Structure to check the status after bulk
                                                     configuration.
 Changes not propagated from History template to         Modify the corresponding logs that were
 actual log. Currently, if changes are made to the log   created by the template to resemble the
 template that a log uses, the modifications do not flow template.
 down to the logs created by the template.
                               800xAINM-CN-3600-0001
 The current architecture of Batch Management            If trying to extract a PFC from a PDL on a
 interfacing to the Information Management does not      certain Information Management node,
 support the recording of the Batch Recipes (PFCs) to    results in one not being found, look for the
 more than one Information Management PDL. The           PFC on another Information Management
 PFC is guaranteed to be on one of the Information       node.
 Management nodes.
                               800xAINM-CN-3510-0011
3BUF001135R5011                                                                                    27
Known Problems and Workarounds                                           Section 2   History Services
                Table 2. Known History Services Problems and Workarounds (Continued)
                                                              Workarounds, Clarifications, and
                           Issue
                                                                      Helpful Hints
 PDL Extractor used for viewing Batch Management     None. The PDL extractor can only be
 Recipes doesn’t support restored PDLs.              used for recipes from PDL that has not
                               800xAINM-CN-3510-0012 been archived.
 When forgetting to configure a PDL Message Log on   Configure the PDL Message Log on the
 the Information Management Consolidation node, or   Consolidation node and then use
 when configuring the log wrong, PDLs created by     SQLPLUS on the target node to set the
 Produce IT Batch will still be consolidated from theArchive Status to 0 for all tasks in the task
 target node but will not contain any messages for any
                                                     table. This forces the PDLs to be
 of the tasks when viewed on the Consolidation node. reconsolidated at which time the
                               800xAINM-CN-3520-0014 messages will be consolidated.
                                                     If a PDL Message Log does not exist on
                                                     the Consolidation node, avoid
                                                     consolidating Batch created PDLs.
                                                     Object under the node object needs to be
 It is difficult to recover an IM node when it is deleted
 from the system because objects under the node      deleted and recreated when the IM is
 object are not deleted.                             added back into the system, including
                               800xAINM-CN-3600-0004 fixing the GUID for the PPA basic history.
 The Vendor/Categories list of the OPC/Audit Trail tab
                                                     DataDirect simply reports the category
 on the DataDirect Message Log dialog displays       names and numbers as found in the
 different Categories/Category numbers depending on  database. The numbers can be different
 the IM at which its viewed.                         at different times causing two IMs to use
                               800xAINM-CN-3620-0009 different numbers to refer to the same
                                                     category.
                                                            Use category names instead of category
                                                            numbers.
 License count for dual logs is incorrect for history logs. None.
 Distributed and regular logs are counted correctly.
                               800xAINM-CN-4000-0010
28                                                                               3BUF001135R5011
Section 2   History Services                                      Known Problems and Workarounds
                Table 2. Known History Services Problems and Workarounds (Continued)
                                                              Workarounds, Clarifications, and
                         Issue
                                                                      Helpful Hints
 Information Management Performance Counters               Refer to Appendix D of the Information
 operate as expected when current values are being         Management Data Access Reports
 displayed. However, when counters are added to a log      instruction (3BUF001094Rxxxx) for
 file for longer term monitoring, attempting to activate   information on how to add performance
 the log file returns a fatal error.                       counters.
                               800xAINM-CN-4000-0005
 The History Access Importer can create multiple           When the Bulk Importer is used to create
 objects with the same name. This happens when             actual consolidation logs, they fail
 consolidating from a node that has logs using the         because the same object exists twice.
 object.0000n notation and more then one property of       This requires redoing the control
 that object is being logged. For example: two logs        application and IM configuration to get rid
 tag1.00001:Level1 and tag1.00001:Level2 end up            of the multiple objects sharing the same
 creating two objects with the same name, tag1.00001,      name.
 with one property assigned to each log.
                               800xAINM-CN-3621-0010
 Excel sheet columns A through E may disappear             This can be corrected by unfreezing
 when using the Bulk Import > Initialize Sheet to          panes and refreezing panes.
 initialize a workbook. No log names are shown.
                               800xAINM-CN-3621-0011
 The Information Manager authentication aspect is not Add the authentication aspect manually.
 created on the new history control or PDL control    Refer to the Information Management
 aspects.                                             Configuration instruction
                             800xAINM-CN-5000-0032 (3BUF001092Rxxxx) for information on
                                                      configuring authentication.
3BUF001135R5011                                                                                     29
Known Problems and Workarounds   Section 2   History Services
30                                       3BUF001135R5011
                                                   Section 3 Calculations
Changed Functionality
                No new functionality is introduced in this release of Calculations.
Fixed Problems
                The problems related to Calculations that are fixed are described in Table 3.
                Table 3. Fixed Calculation Services Problems
                      Issue                                        Correction or Fix
The calculation status in the Calculation Status    Added logic that detects removal of input and
view and Calculation aspect are not updated         output signals and causes:
when inputs or output are removed from the          •    The error status icon in the Calculation
system.                                                  Status view will change to red indicating
                        800xAINM-CN-5010-033             the calculation is not executing.
                                                    •    An error message stating why the
                                                         calculation is not executing will be
                                                         displayed on the Calculation Status view
                                                         and Calculation aspect.
                                                    •    The Calculation aspect icon will change to
                                                         red indicating the calculation is not
                                                         executing.
The Timeout property of calculations is not         Internal utilities have been corrected to use the
functioning correctly. It is not being used and the timeout period and allow the period value to be
value cannot be changed.                            changed.
                        800xAINM-CN-5010-034
3BUF001135R5011                                                                                      31
Known Problems and Workarounds                                            Section 3   Calculations
               Table 3. Fixed Calculation Services Problems (Continued)
                     Issue                                      Correction or Fix
The 800xA workplace closes when an object is   The workplace does not close when dragging
dragged from the Control Structure and dropped and dropping objects.
on a Calculation aspect.
                       800xAINM-CN-5010-035
The Calculation Status Viewer does not display a The status is now updated anytime the status of
message when the OPC connection is lost from the Calculation aspect changes.
calculations.
                       800xAINM-CN-5010-036
Deleting Softpoint instances that have enabled   A time delay was added to allow the Calculation
Calculation aspects on them does not stop the    Service to delete the calculation before the
calculation from executing the calculation.      aspect is deleted.
                       800xAINM-CN-4100-004
Calculations system extension (CAS.afw) fails to The methods used to modify the Calculation
load in systems where environments are           Status Viewer aspect during the loading of the
enabled.                                         system extension have been changed so that
                       800xAINM-CN-5010-037 the extension successfully loads in systems
                                                 where environments are enabled.
Known Problems and Workarounds
               Known problems and workarounds for Calculation Services are described in
               Table 4.
32                                                                            3BUF001135R5011
Section 3   Calculations                                            Known Problems and Workarounds
                Table 4. Known Calculation Services Problems and Workarounds
                                                                Workarounds, Clarifications, and
                           Issue
                                                                        Helpful Hints
 When a calculation is enabled, or when configuration        Copy/paste the aspect and enable the
 of a calculation is protected by a Security aspect it is    copy. This will enable the scroll bar for
 expected that modifications to the variable grid will not   viewing the calculation. Delete the copy
 be allowed. However, the scroll bar is rendered             when finished.
 inoperable which may make it difficult to view the
 entire grid when the grid is large.
                              800xAINM-CN-3500-0008
 After running a calculation in a test mode with update      When running the calculation online, use
 status setting = TRUE (On), when the update status is       a script in the calculation logic to
 turned off (FALSE), the status viewer shows                 periodically turn the update status on to
 misleading information. It maintains the data from the      refresh the data.
 last time the calculation executed.
                              800xAINM-CN-3600-0002
 Following an upgrade from System Baseline 2,          Delete and then recreate the Calculation
 calculation aspects that existed in the pre-upgrade   Status Viewer aspect.
 system may not be viewable via the Calculation Status
 Viewer.
                              800xAINM-CN-3610-0006
3BUF001135R5011                                                                                          33
Known Problems and Workarounds                                               Section 3   Calculations
                Table 4. Known Calculation Services Problems and Workarounds (Continued)
                                                               Workarounds, Clarifications, and
                          Issue
                                                                       Helpful Hints
 Calculations don’t always update the signals under the Do not try to enable a calculation if the
 following conditions.                                  Calculation Service is stopped.
 •    When the Calculation Service is Stopped
      {undefined}, and an attempt is made to enable
      some calculations to run from the Calculation
      Status Viewer. This returns error # -1067456246
      error occurred accessing Calculation
      Services.
 •    Start the Calculations service [service} then
      enable calculations from the Calculation Status
      Viewer.They should appear enabled. Viewing the
      values from the object dialog aspect for one of
      the objects to verify if the values are updating,
      some will and some won't. Also note that the
      calculations appear to be enabled inside of the
      workplace, but in some cases when the
      calculation aspect is opened outside it is different
      than the one in the workplace.
                              800xAINM-CN-4000-0003
 VB Script for Calculations cannot interpret comma in        None. Do not use comma in foreign
 foreign language.                                           language.
                              800xAINM-CN-4000-0004
 After deleting an object that has a calculation aspect,
                                                    The Alarm and Event List aspect gets
 the calculation continues to run.                  Calculation error messages for writing
                              800xAINM-CN-3610-0007 OPC value to non existent object.
 The Calculation Service sends out at least one        Stop the Calculation Service and reduce
 diagnostic each time the calculation executes and can the event load before starting.
 not write to one of the output variables.
                              800xAINM-CN-4100-0005
34                                                                                3BUF001135R5011
Section 3   Calculations                                       Known Problems and Workarounds
               Table 4. Known Calculation Services Problems and Workarounds (Continued)
                                                            Workarounds, Clarifications, and
                           Issue
                                                                    Helpful Hints
 Calculations Service takes excessive time to restart    After the 800xA system has been started,
 after reboot (45 minutes or more) on certain nodes      stop and then start the Calculation
 that have calculations. On these nodes, the service     Service and it will be faster.
 goes to initializing state and appears stuck on every
 reboot. It will go to the service state.
                              800xAINM-CN-4100-0006
3BUF001135R5011                                                                                35
Known Problems and Workarounds   Section 3   Calculations
36                                   3BUF001135R5011
                             Section 4 Application Scheduler
Changed Functionality
               No new functionality is introduced in this release of the Application Scheduler.
                 Data Execution Prevention (DEP) enabled hardware and software with Windows
                 XP SP2 (or later) and Windows 2003 SP1 (or later) will not open Crystal Reports
                 11 Developer Edition. The Crystal Reports application must be excluded from
                 Data Execution Prevention (DEP) using one of the methods described in the
                 MSDN knowledge base article 875352.
Fixed Problems
               The problems related to Application Scheduler that are fixed are described in
               Table 5.
               Table 5. Fixed Application Scheduler Problems
                     Issue                                       Correction or Fix
Job Description objects not placed in the Job
                                            The Scheduler function now presents the error
Descriptions Job Folder (Scheduling Structure)
                                            job_name will never be scheduled.
are not scheduled and no error is presented to
                                            It must be a descendant of the Job
describe why.                               Descriptions Job Folder in the
                       800xAINM-CN-5010-038 Scheduling Structure in the
                                            ABBScheduler.log file.
Known Problems and Workarounds
               The known problems and workarounds for the Application Scheduler are described
               in Table 6.
3BUF001135R5011                                                                                   37
Known Problems and Workarounds                                    Section 4    Application Scheduler
               Table 6. Known Application Scheduler Problems and Workarounds
                                                            Workarounds, Clarifications, and
                         Issue
                                                                    Helpful Hints
 The scheduler failed because the Microsoft Excel        Turn off the compatibility check in each
 compatibility checker for Office 2007 found a problem   report template:
 while running a report created from a report template   1. Open the report template.
 that was created in the Excel component of Microsoft
                                                         2. Click the Microsoft Office button in the
 Office 2007.
                                                         upper left corner.
                              800xAINM-OL-5010-074
                                                         3. Hover over Prepare.
                                                         4. Select Run Compatibility Checker.
                                                         5. Disable the Check compatibility when
                                                         saving this workbook option and click OK.
                                                         6. Save the template.
 The scheduler failed because the Microsoft Excel        Turn off the compatibility check in each
 compatibility checker for Office 2007 found a problem   predefined report template:
 while running a report created from a predefined        1. Locate the predefined report template
 report template supplied by ABB.                        in the Scheduling Structure.
                              800xAINM-OL-5010-075 2. Right click the Report Template aspect
                                                   and select Config View.
                                                         3. Click Edit.
                                                         4. Click the Microsoft Office button in the
                                                         upper left corner.
                                                         5. Hover over Prepare.
                                                         6. Select Run Compatibility Checker.
                                                         7. Disable the Check compatibility when
                                                         saving this workbook option and click OK.
                                                         8. Save the report or template.
                                                         9. Close the template and Excel.
                                                         10. Click Check In.
38                                                                               3BUF001135R5011
Section 4   Application Scheduler                                 Known Problems and Workarounds
                Table 6. Known Application Scheduler Problems and Workarounds
                                                             Workarounds, Clarifications, and
                          Issue
                                                                     Helpful Hints
 The Scheduler component (and others) of the              None.
 Information Management does not properly install on
 disk drives other than C:.
                                  800xAINM-IN-5010-052
 Data Execution Prevention (DEP) enabled hardware         The Crystal Reports application must be
 and software with Windows XP SP2 (or later) and          excluded from Data Execution Prevention
 Windows 2003 SP1 (or later) will not open Crystal        (DEP) using one of the methods
 Reports 11 Developer Edition. The Event Viewer           described in the MSDN knowledge base
 shows the Dr. Watson error Application error             article 875352.
 C0000005 at address 7FF2FBFC.
                               800xAINM-CN-5010-039
 When report log is made inactive and the action           None. Inactive state is only used to allow
 aspect is configured to output the report to a report log editing of report log fields.
 in History Services, the reports get updated in history
 even though the state indicated is inactive.
                              800xAINM-CN-3500-0006
 The Abort and Pause buttons on the Scheduled Job None. A timeout is built-in or the job could
 aspect for a running job are not enabled when a job is be deleted.
 running. Buttons need to be removed.
                              800xAINM-CN-3600-0003
 Reports can be deleted before they are digitally         Make sure reports are digitally signed. Do
 signed and archived. There is no tie between the         not let the archive utility build up to the
 reporting scheduler and the archive on how the files     maximum number of reports before
 are managed.                                             unsigned reports are deleted.
                              800xAINM-CN-3622-0012
3BUF001135R5011                                                                                     39
Known Problems and Workarounds                                 Section 4   Application Scheduler
                Table 6. Known Application Scheduler Problems and Workarounds
                                                           Workarounds, Clarifications, and
                          Issue
                                                                   Helpful Hints
 Reading Excel Reports produced using ODBC queries Microsoft has documentation on the
 produced the following modal error message on     causes of this error, and possible
 opening the file:                                 programmatic workarounds (Excel 2002).
     Cannot find XLQuery.XLA!Register.DClick, which Refer to http://support.microsoft.com/
     has been assigned to run each time               default.aspx?scid=kb;en-us;277620
     [filename.xls]Sheet1 is opened. Continuing could
     cause errors. Cancel opening
     [filename.xls]Sheet1?
 The Scheduler has no problem executing reports.
                             800xAINM-CN-4000-0002
 Scheduled 800xA System backups cannot be aborted None.
 from the scheduler.
                             800xAINM-CN-4100-0032
 Reports saved in HTML format in the Object Store  HTML format being saved in the Aspect
 (Aspect Directory) do not display multi-file formats.
                                                   Directory is intended for a single file
 The file viewer aspect only accepts one file, while the
                                                   format to display data. Do not use this
 HTML conversion generates several.                location to store multi-file HTML reports
                             800xAINM-CN-5000-0033 that reference graphics or other
                                                   information. Store to disk instead.
40                                                                           3BUF001135R5011
                                   Section 5 Open Data Access
Changed Functionality
               No new functionality is introduced in this release of Open Data Access.
Known Problems and Workarounds
               The known problems and workarounds for ODA are described in Table 7.
               Table 7. Known Open Data Access Problems and Workarounds
                                                          Workarounds, Clarifications, and
                        Issue
                                                                  Helpful Hints
 Open Data Access cannot use ACCESS NAME to            Use the full log name.
 access numeric logs in a hierarchy by methods for
 mean, max, min etc.
                            800xAINM-CN-3200-0001
 When using QURYDemo or Microsoft Excel to update None.
 property values that are aspects of objects
 instantiated in the control structure, the response time
 is very slow - on the order of a minute or more when
 the objects in question are associated with a
 controller. When objects are local, access is
 reasonably fast. The slowness affects not only Update
 but also Select commands in SQL.
                            800xAINM-CN-3500-0007
3BUF001135R5011                                                                              41
Known Problems and Workarounds   Section 5   Open Data Access
42                                           3BUF001135R5011
                              Section 6 Desktop Applications
Changed Functionality
               The following new functionality is introduced in this release of Desktop
               Applications:
               •    The scan and clear functions now log their start times, end times, and a brief
                    description of the outcome (success or a description of the error) into the
                    Oracle database. The History Control aspect can be used to view a log of these
                    operations.
Fixed Problems
               The problems related to DataDirect, Desktop Trends and Display Services that are
               fixed are described in Table 8.
               Table 8. Fixed Desktop Application Problems
                    Problem                                       Correction or Fix
When a timeout occurs while using the               The History Server has been changed to return
ABBAERetrival function of DataDirect, it returns    the transaction code EVENT_REQUEST_
the transaction code EVENT_MESSAGES_                TIMEOUT. DataDirect will now display a
COMPLETE. The message ABBAERetrieval: No            message that tells the user to increase the
messages found fitting this criteria is displayed   Timeout value in the Options display.
by the DataDirect AE plug-in.
                        800xAINM-CN-5010-040
3BUF001135R5011                                                                                 43
Fixed Problems                                                    Section 6   Desktop Applications
                 Table 8. Fixed Desktop Application Problems (Continued)
                     Problem                                     Correction or Fix
DataDirect is not finding the correct beginning to A software module (Timeprocedures.bas) has
daylight savings time (DST). DataDirect thinks     been corrected to properly determine the start
DST started on the first week of March instead of of DST
the second week.
                         800xAINM-CN-5010-041
DataDirect does not display all the events        The DataDirect A/E plug-in has been corrected
requested. It displays the requested number of    to not count the header lines as events and
events minus two (it counts the header lines as   display the correct number of events.
events).
                         800xAINM-CN-5010-042
The UTM display will only list the first 65,000     The UTM function has been corrected to handle
objects (total of tags and groups) as counted by more than 65,000 objects and display all groups
UTM (total of all history logs and objects on trend in the navigation tree.
aspects and groups). Excess groups are shown
as missing branches on the tree.
                         800xAINM-CN-5010-043
Desktop trends for tags that contain Swedish  A check that only ASCII characters are allowed
letters are not displayed.                    in file names has been removed. The trends are
                         800xAINM-CN-5010-044 now displayed.
Desktop Trend’s Event Browser should have a   Added field to the options window to limit the
way to control memory usage. Otherwise, the   values that are queried to save time and lower
Internet Explorer hosting the control can     usage. The number of specified values returned
consume too much memory.                      show in descending order so the most recent
                         800xAINM-CN-5010-045 number is shown first.
The DataDirect ABBAERetrieval function cannot The DataDirect A/E plug-in can now be used to
retrieve process alarms from the 800xA System. view the alarms from the event and alarm list.
                         800xAINM-CN-5010-046
44                                                                             3BUF001135R5011
Section 6   Desktop Applications                                                   Fixed Problems
               Table 8. Fixed Desktop Application Problems (Continued)
                    Problem                                     Correction or Fix
UTM Client needs to show UTM Scan               Scan Log
Information.                                There is a new table added called
                       800xAINM-CN-5010-047 CLIENT_SCAN_LOG that keeps track of
                                            database scans on the server (times/success).
                                            The client application checks for the existence
                                            of this new table (for backwards compatibility),
                                            and if it exists, has a new menu option that
                                            brings up a dialog to show this information.
A new column, UTMPath, is needed in the     The UTM Path change allows recursive
CLIENT_GROUPS table.                        searches to take seconds instead of minutes. It
                       800xAINM-CN-5010-048 is a new column in the CLIENT_GROUPS table.
                                            The UTMPath column is a hierarchical-based
                                            string of hexidecimal values.
                                                The client currently checks to see if this column
                                                exists (for backwards compatibility), and if it
                                                does, it bases it’s searches on it. It also handles
                                                the addition of new groups to the table if one is
                                                saved.
                                                If the column does not exist, and a recursive
                                                search is attempted, a Database Not Updated
                                                warning is displayed indicating that the search
                                                may be slow and to convert to the current
                                                version.
3BUF001135R5011                                                                                  45
Known Problems and Workarounds                                       Section 6   Desktop Applications
                Table 8. Fixed Desktop Application Problems (Continued)
                    Problem                                         Correction or Fix
User interface improvements needed.          In the tag (list) view, all items now get an icon.
                        800xAINM-CN-5010-049 Previously, there was only an icon for actual
                                             tags (one for log config tags, another for trend
                                             tags). The new icons include one for offline and
                                             for info (i.e. no tags exist in this group). This
                                             makes for a cleaner display, and overcomes a
                                             .NET (or WinAPI) shortcoming that prevents the
                                             columns of the list from resizing properly if an
                                             icon is used for one item, and not another.
                                                     When searching, a progress bar is now shown
                                                     while adding tags to the search results list. The
                                                     label is also more descriptive, and updates with
                                                     information as the search progresses.
The following dialogs may fail to open when          The dialogs now open correctly when running
running DataDirect (Windows 2003 only):              DataDirect on Windows 2003 workstations.
•    Classic (Inform IT) version of History Values
•    Classic (Inform IT) version of Process
     Values
•    Industrial IT Batch Data.
Microsoft Visual Basic Error message is: Run-
time error 459.
                       800xAINM-CN-5000-0025
Known Problems and Workarounds
                Known problems and workarounds are described in Table 9.
46                                                                                3BUF001135R5011
Section 6   Desktop Applications                                Known Problems and Workarounds
               Table 9. Known Desktop Application Problems and Workarounds
                                                           Workarounds, Clarifications, and
                         Issue
                                                                   Helpful Hints
 Vendor attributes configured in the Vendor and         None.
 Category Filter window are not displayed as columns
 in the Excel workbook. OPC attributes are displayed
 correctly.
                              800xAINM-CN-5010-072
 The ACC setup program does not run from accounts  Run the ACC setup from the Admin
 having only operator access privileges.           account to set the user/password and
                              800xAINM-CN-5010-070 server location. Desktop trends will work
                                                   correctly.
 Using the log calculation algorithm (aggregate) called The Dynamics log calculation algorithm is
 Dynamics causes an overflow error. Log calculation      not supported in this release.
 algorithms are applied to data retrieved by DataDirect.
                              800xAINM-OL-5010-069
 Clients using cyclic rates other than the approved     Use only the approved cyclic rates.
 ones (dcs_9s, dcs_3s, and dcs_1s) cause the OPC
 data provider to fail.
                              800xAINM-OL-5010-068
 After upgrading from SV 5.0 to SV 5.0 SP 1, the User Execute the UTM scan to recreate the
 Tag Management tool does not function correctly.     missing tables and initialize the UTM data
 Database tables are missing after the upgrade.       browser.
                                 800xAINM-IN-5010-067
 Crystal Reports does not work following the            Delete and recreate the ODBC
 installation of an Information Management rollup or    connection.
 service pack.
                                 800xAINM-IN-5010-066
3BUF001135R5011                                                                                47
Known Problems and Workarounds                                    Section 6   Desktop Applications
               Table 9. Known Desktop Application Problems and Workarounds (Continued)
                                                            Workarounds, Clarifications, and
                         Issue
                                                                    Helpful Hints
 During the manual installation of Information           Ignore this prerequisite and continue the
 Management SV 5.0 SP 1, a window listing                installation.
 prerequisites states that Internet Explorer Version 6.0
 SP 1 is required. This is incorrect. Internet Explorer
 Version 7.0 is the correct prerequisite.
                                 800xAINM-IN-5010-058
 The UTM scan run on an Information Management           None.
 node in a Multisystem Integration subscriber system
 does not retrieve tags and groups for log configuration
 and trend display aspects found in the provider
 system.
                              800xAINM-OL-5010-064
 Dragging a group from one parent group to another in Restart the UTM client and the original
 the group hierarchy tree does not move the group as it group will contain all the tags it should.
 should. Instead, the new group having the same name The new group will not contain any tags.
 but different group ID is created in the destination
 location. The original group a still exists and UTM
 temporarily get confused as to which group to use.
 Both groups seem to contain no tags.
                              800xAINM-CN-5010-062
 The group hierarchy tree control is disabled during the Restart the User Tag Management
 importing of groups and tags from an XML file. Several browser window to continue working.
 minutes after starting the import, the import completes
 but the tree control never returns.
                              800xAINM-OL-5010-060
 The UTM utility inconsistently fails (locks up) and does None.
 not recover.
                              800xAINM-OL-5010-055
48                                                                              3BUF001135R5011
Section 6   Desktop Applications                                   Known Problems and Workarounds
                Table 9. Known Desktop Application Problems and Workarounds (Continued)
                                                             Workarounds, Clarifications, and
                            Issue
                                                                     Helpful Hints
 Alarms and events from both the provider system           None.
 (multisystem integration functionality) appear in the
 800xA alarm and event list however, only the alarms
 are recorded by the DataDirect function within
 Information Management.
                                800xAINM-OL-5010-061
 The DataDirect message log does not support the           None.
 filtering of retrieved messages by category. All the
 messages for the time period specified are returned.
                                800xAINM-OL-5010-053
 An error (Error Number: 75 - Path/file                   Acknowledge the error (click OK). The
 access error) will be generated when a user              toolbar will be added.
 logged in as an operator tries to install the DataDirect
 toolbar.
                                    800xAINM-IN-5010-054
 After restoring Produce IT data, the messages for the If this problem occurs, remove the
 restored data may not be accessible via the PDL       restored message log using the History
 dialog.                                               Builder. This will make messages
 Switching back to the runtime data, messages may      accessible for all batches.
 still not be accessible.
                               800xAINM-CN-3200-0003
3BUF001135R5011                                                                                   49
Known Problems and Workarounds                                       Section 6    Desktop Applications
                Table 9. Known Desktop Application Problems and Workarounds (Continued)
                                                               Workarounds, Clarifications, and
                          Issue
                                                                       Helpful Hints
 On the History Values Form, under the Add/Modify           None.
 Tab, if the Select individual ranges from Spreadsheet      Do not select multiple single cells using
 radio button is checked, all of the ranges have been       the control key.
 chosen using the control button to add one cell at a
 time to the list instead of using the shift key, and the
 Add to List button is clicked, an error comes up that
 says:
      An unexpected error has occurred in
      procedure RemoveBlankBorderCells.
      Error Number: 1004- Unable to get
      the CountBlank property of the
      WorksheetFunction class.
 Also, if the use formatted range radio button is
 selected and the range is again picked using the
 control button to select one cell at a time, a message
 saying to pick 4 columns is shown even if four were
 already selected.
                              800xAINM-CN-3500-0001
50                                                                                 3BUF001135R5011
Section 6   Desktop Applications                             Known Problems and Workarounds
               Table 9. Known Desktop Application Problems and Workarounds (Continued)
                                                         Workarounds, Clarifications, and
                         Issue
                                                                 Helpful Hints
 The Bulk Data Export function in DataDirect is not  None. Function is not currently supported.
 supported for Information Management version 3.5 or However the functionality can be
 later (all 800xA system versions and PPA 2.1).      achieved using the hsDBMaint function.
                            800xAINM-CN-3500-0002 To use the Bulk Data Exporter, an input
                                                  file must first be generated. An
                                                  example/template may be found by
                                                  accessing the Bulk Data Exporter from
                                                  the Start > Programs > ABB Industrial
                                                  IT > Information Management > History
                                                  > Bulk Data Export. Once the window is
                                                  open, click Generate Input Example.
                                                           If the intention is to view this data in
                                                           Excel, set the
                                                           SEPERATION_STRING =’,’.
                                                      Save the file once it is configured.
                                                      Open a command window by typing cmd
                                                      in the Start > Run window.
                                                      Enter hsDBMaint -bdx -i <name and full
                                                      path to just created file> -e <name of file
                                                      to contain exported data>.
                                                           If the intention is to view this data in
                                                           Excel, make the output file have an
                                                           extension of csv. This will place the
                                                           data in the appropriate columns.
                                                           If the path of import or export files
                                                           contains spaces, place quotes
                                                           around the paths.
3BUF001135R5011                                                                                    51
Known Problems and Workarounds                                      Section 6   Desktop Applications
               Table 9. Known Desktop Application Problems and Workarounds (Continued)
                                                              Workarounds, Clarifications, and
                         Issue
                                                                      Helpful Hints
 A DataDirect Report which includes ABB function and       Change the file opening set-up for
 is stored in the Report log can not be viewed. On the     Microsoft Excel Worksheets so it does not
 first attempt to view report, an error message is         browse in same window.
 displayed. After acknowledgement, report may be           This can be found in the Control Panel
 seen. The second attempt to view report hangs             Folder Options, File Types tab. Select the
 Internet Explorer (IE is used to display report)          XLS extension and then select the
 because Excel never exited.                               Advanced button. Uncheck browse in
 Report which does not include ABB function can be         same window.
 viewed without problem.
                             800xAINM-CN-3510-0013
 Data provider will support access to a data source that   Create multiple data providers, one for
 uses a special browser separator, but will not support    each different required browser separator,
 the other data source. For example, the data provider     then in the client application select the
 will not support both a special browser separator         applicable data provider as required.
 configured for Harmony process objects and data
 sources that use the default browser separator such
 as AC 800M process objects.
                             800xAINM-CN-3600-0005
 Both Excel and Plant Explorer windows can become Change the file opening set-up for
 frozen if the Plant Explorer is opened, then Excel is   Microsoft Excel Worksheets so it does not
 opened, then a completed DataDirect report in Plant browse in same window.
 Explorer is read and then you start switching to
 different completed reports. Eventually a prompt to log
 in to DataDirect is shown.
                             800xAINM-CN-4000-0001
 The SQL Browser of Desktop Trends connects to          None.
 either the IM or EH data provider based on the node it
 is loaded on. As a result, Desktop Trends loaded on
 an IM can not browse for tags on an EH node.
                             800xAINM-CN-4100-0009
52                                                                                3BUF001135R5011
Section 6   Desktop Applications                                  Known Problems and Workarounds
               Table 9. Known Desktop Application Problems and Workarounds (Continued)
                                                              Workarounds, Clarifications, and
                         Issue
                                                                      Helpful Hints
 AID client (Display Services) displays sometimes use      Add the HKEY_CURRENT_USER\
 incorrect fonts. Due to a change in Windows               SOFTWARE\ABB\AID\Fonts\FaceName_
 functionality, AID client displays now uses font          0, ...\FaceName_1, and ...\FaceName_2
 information from registry keys instead of the             keys to the registry. Use the value names
 aidfonts.ini file.                                        and values listed below for all three keys:
                              800xAINM-OL-4100-0036 Value Name                     (Default) Font
                                                    Name                              Ariel
                                                    BaseSize_0                       11
                                                    BaseSize_1                       14
                                                    BaseSize_2                       17
                                                    BaseSize_3                       18
                                                    BaseSize_4                       23
                                                    BaseSize_5                       33
 The hsHistoryService process grows the first time the     Use the UTM scan as few times as
 UTM scan is run. The amount of memory growth is           possible. If memory usage for the
 proportional to the size of the system. The majority of   hsHistoryService process becomes too
 this growth is object manager cache and is not a leak.    large, reset the IM History service
 Each additional scan causes the hsHistoryService to       provider in the service structure.
 grow further. The amount of additional growth is much
 smaller than the growth from the first scan and is
 proportional to the amount of trend aspects in the
 system.
                             800xAINM-CN-5000-0040
3BUF001135R5011                                                                                     53
Known Problems and Workarounds                                 Section 6   Desktop Applications
               Table 9. Known Desktop Application Problems and Workarounds (Continued)
                                                         Workarounds, Clarifications, and
                        Issue
                                                                 Helpful Hints
 Trying to open UTM in Desktop trends during a scan
                                                  Do not open UTM from Desktop trends
 of the UTM database causes UTM to hang and       during a scan of the UTM database. With
 eventually generate an application error.        medium and large systems, UTM scans
                            800xAINM-CN-5000-0044 can take about 30 minutes.
 Users logged in as Operator get a Path/File access     Open the trend display from the Start
 error when trying to view a trend display from         menu. Results can also be dragged from
 DataDirect and the following ABB applications (Ticker, the History tab to the trend display.
 Tag Explorer, PDL Browser, User Tag Management,
 and Batch to Batch).
                             800xAINM-OL-5010-050
54                                                                          3BUF001135R5011
3BUF001135R5011. Printed in Sweden June 2007
Copyright © 2003-2007 by ABB. All Rights Reserved
® Registered Trademark of ABB.
™ Trademark of ABB.