ACS 800-01 (0.55 To 110kW) U1 (0.75 To 150HP) Drives Hardware Manual
ACS 800-01 (0.55 To 110kW) U1 (0.75 To 150HP) Drives Hardware Manual
Hardware Manual
ACS800-01 Drives (0.55 to 110 kW)
ACS800-U1 Drives (0.75 to 150 HP)
ACS 800 Single Drive Manuals
•   Safety instructions
•   Electrical installation planning
•   Mechanical and electrical installation
•   Motor control and I/O board (RMIO)
•   Maintenance
•   Technical data
•   Dimensional drawings
•   Resistor braking
Hardware Manual
Safety instructions
                                                                                Safety instructions
6
Only qualified electricians are allowed to install and maintain the drive.
                  •   Never work on the drive, the motor cable or the motor when main power is
                      applied. After switching off the input power, always wait for 5 min to let the
                      intermediate circuit capacitors discharge before you start working on the drive,
                      the motor or the motor cable.
                      Always ensure by measuring with a multimeter (impedance at least 1 Mohm)
                      that:
                      1. Voltage between drive input phases U1, V1 and W1 and the frame is close to
                         0 V.
                      2. Voltage between terminals UDC+ and UDC- and the frame is close to 0 V.
                  •   Do not work on the control cables when power is applied to the drive or to the
                      external control circuits. Externally supplied control circuits may cause
                      dangerous voltages inside the drive even when the main power on the drive is
                      switched off.
                  •   Do not make any insulation tests without disconnecting the drive from the
                      cabling.
                  •   When reconnecting the motor cable, always check that the phase order is
                      correct.
                  Note:
                  •   The motor cable terminals on the drive are at a dangerously high voltage when
                      the input power is on, regardless of whether the motor is running or not.
Safety instructions
                                                                                            7
Grounding
    These instructions are intended for all who are responsible for the grounding of the
    drive. Incorrect grounding can cause physical injury, death or equipment malfunction
    and increase electromagnetic interference.
     •   Ground the drive, the motor and adjoining equipment to ensure personnel
         safety in all circumstances, and to reduce electromagnetic emission and pick-
         up.
     •   Do not install a drive with EMC filter option +E202 or +E200 (available for
         ACS800-01 only) on an ungrounded power system or a high resistance-
         grounded (over 30 ohms) power system.
     Note:
     •   Power cable shields are suitable for equipment grounding conductors only
         when adequately sized to meet safety regulations.
    WARNING! Handle the fibre optic cables with care. When unplugging optic cables,
    always grab the connector, not the cable itself. Do not touch the ends of the fibres
    with bare hands as the fibre is extremely sensitive to dirt. The maximum allowed
    bend radius is 25 mm (1 in.).
                                                                          Safety instructions
8
Mechanical installation
                  These notes are intended for all who install the drive. Handle the unit carefully to
                  avoid damage and injury.
                      •   ACS800-01: The drive is heavy. Do not lift it alone. Do not lift the unit by the
                          front cover. Place the unit only on its back.
                          ACS800-02, ACS800-04: The drive is heavy. Lift the drive by the lifting lugs
                          only. Do not tilt the unit. The unit will overturn from a tilt of about 6 degrees.
                      •   Make sure that dust from drilling does not enter the drive when installing.
                          Electrically conductive dust inside the unit may cause damage or lead to
                          malfunction.
Operation
                  These warnings are intended for all who plan the operation of the drive or operate
                  the drive. Ignoring the instructions can cause physical injury or death or damage the
                  equipment.
                      •   Before adjusting the drive and putting it into service, make sure that the motor
                          and all driven equipment are suitable for operation throughout the speed range
                          provided by the drive. The drive can be adjusted to operate the motor at
                          speeds above and below the speed provided by connecting the motor directly
                          to the power line.
                      •   Do not control the motor with the disconnecting device (means); instead, use
                          the control panel keys    and     , or commands via the I/O board of the drive.
                          The maximum allowed number of charging cycles of the DC capacitors (i.e.
                          power-ups by applying power) is five in ten minutes.
                      Note:
                      •   If an external source for start command is selected and it is ON, the drive (with
                          Standard Application Program) will start immediately after fault reset unless the
                          drive is configured for 3-wire (a pulse) start/stop.
                      •   When the control location is not set to Local (L not shown in the status row of
                          the display), the stop key on the control panel will not stop the drive. To stop
                          the drive using the control panel, press the LOC/REM key and then the stop
                          key     .
Safety instructions
                                                                                              9
           WARNING! Do not work on the drive when the permanent magnet motor is rotating.
           Also, when the supply power is switched off and the inverter is stopped, a rotating
           permanent magnet motor feeds power to the intermediate circuit of the drive and the
           supply connections become live.
       Operation
           Do not run the motor over the rated speed. Motor overspeed leads to overvoltage
           which may explode the capacitors in the intermediate circuit of the drive.
                                                                             Safety instructions
10
Safety instructions
                                                                                                                                                        11
Table of contents
Safety instructions
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .              5
To which products this chapter applies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                    5
Use of warnings and notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .               5
Installation and maintenance work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                   6
       Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .        7
       Fibre optic cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .         7
Mechanical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .           8
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   8
Permanent magnet motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                9
       Installation and maintenance work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                    9
       Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .      9
Table of contents
The ACS800-01/U1
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                21
The ACS800-01/U1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .              21
Type code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .       22
Main circuit and control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .            23
     Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .          23
     Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .          23
     Printed circuit boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .               24
     Motor control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .            24
Mechanical installation
Unpacking the unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
    Delivery check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
                                                                                                                                  Table of contents
12
Table of contents
                                                                                                                                                   13
Electrical installation
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .           47
Checking the insulation of the assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                  48
IT (ungrounded) systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .            48
Connecting the power cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .              49
       Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   49
       Conductor stripping lengths . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .             50
       Wall installed units (European version) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                   50
             Power cable installation procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                    50
       Wall installed units (US version) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .               53
       Warning sticker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .       54
Cabinet installation (IP 21, UL type 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .              54
             Frame size R5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .           55
             Frame size R6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .           55
Connecting the control cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .            56
       Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   56
       360 degrees grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .             58
             When the outer surface of the shield is covered with non-conductive material . . . . . .                                              58
       Connecting the shield wires . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .             58
       Cabling of I/O and fieldbus modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                   59
       Pulse encoder module cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                  59
       Fastening the control cables and covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                     60
Installation of optional modules and PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                  60
       Fibre optic link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .    60
External +24 V power supply for the RMIO board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                         60
                                                                                                                             Table of contents
14
Installation checklist
Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67
Maintenance
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69
Maintenance intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69
Heatsink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69
Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70
      Fan replacement (R2, R3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70
      Fan replacement (R4) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
      Fan replacement (R5, R6) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
Additional fan in IP 55 units and certain IP 21 units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72
      Replacement (R2, R3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72
      Replacement (R4, R5) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72
      Replacement (R6) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72
Capacitors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73
      Reforming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73
LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73
Technical data
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
IEC ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
       Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76
       Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .77
       Derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .77
             Temperature derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .77
             Altitude derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .77
Mains cable fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78
Cable types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80
Cable entries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80
Dimensions, weights and noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .81
Input power connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .81
Motor connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .81
Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .82
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .82
Table of contents
                                                                                                                                                      15
Degrees of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .           82
Ambient conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .          83
Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   84
Applicable standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .          84
CE marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .      85
      Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .       85
      Compliance with the EMC Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                       85
            First environment (restricted distribution) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                         85
            Second environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                  86
      Machinery Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .             86
“C-tick” marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .        87
      Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .       87
      Compliance with IEC 61800-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                     87
            First environment (restricted distribution) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                         87
            Second environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                  88
Equipment warranty and liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                88
US tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   89
      NEMA ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .          89
      Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .       90
      Input cable fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .           90
      Cable types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .         92
      Cable Entries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .         92
      Dimensions and weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                  93
      UL/CSA markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .               93
            UL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .      93
Dimensional drawings
Frame size R2 (IP 21, UL type 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Frame size R2 (IP 55) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Frame size R3 (IP 21, UL type 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Frame size R3 (IP 55) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Frame size R4 (IP 21, UL type 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Frame size R4 (IP 55) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Frame size R5 (IP 21, UL type 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Frame size R5 (IP 55) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Frame size R6 (IP 21, UL type 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Frame size R6 (IP 55) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Frame size R2 (UL type 12) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Frame size R3 (UL type 12) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Frame size R4 (UL type 12) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Frame size R5 (UL type 12) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Frame size R6 (UL type 12) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Resistor braking
What this chapter contains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .            111
To which products this chapter applies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .                  111
Availability of brake choppers and resistors for the ACS 800 . . . . . . . . . . . . . . . . . . . . . . . . . . . .                              111
How to select the correct drive/chopper/resistor combination . . . . . . . . . . . . . . . . . . . . . . . . . . . .                              111
                                                                                                                                Table of contents
16
Table of contents
                                                                                                17
Intended audience
           This manual is intended for people who plan the installation, install, commission, use
           and service the drive. Read the manual before working on the drive. The reader is
           expected to know the fundamentals of electricity, wiring, electrical components and
           electrical schematic symbols.
           This manual is written for readers worldwide. Both SI and imperial units are shown.
           Special US instructions for installations within the United States that must be
           installed per the National Electrical Code and local codes are marked with (US).
Contents
           The chapters of this manual are briefly described below.
           Safety instructions give safety instructions for the installation, commissioning,
           operation and maintenance of the drive.
           About this manual lists the steps in checking the delivery and installing and
           commissioning the drive and refers to chapters/sections in this manual and other
           manuals for particular tasks.
Task See
                Unpack and check the units.                          Mechanical installation: Unpacking the unit.
                Check that all necessary optional modules and        If the converter has been non-operational for
                equipment are present and correct.                   more than one year, the converter DC link
                Only intact units may be started up.                 capacitors need to be reformed. Ask ABB for
                                                                     instructions.
Task See
            Check the insulation of the motor and the motor         Electrical installation: Checking the insulation of
            cable.                                                  the assembly
            Connect the control and the auxiliary control cables.   Electrical installation, Motor control and I/O
                                                                    board (RMIO), and the optional module manual
                                                                    delivered with the module.
Inquiries
            Address any inquiries about the product to the local ABB representative, quoting the
            type code and the serial number of the unit. If the local ABB representative cannot
            be contacted, address inquiries to the manufacturing facility (addresses and phone
            numbers are on the back cover of this manual).
The ACS800-01/U1
The ACS800-01/U1
             The ACS800-01/U1 is a wall mountable drive for controlling AC motors.
Front cover
Connection box
IP 21 (UL type 1)
                                                                                    The ACS800-01/U1
22
Type code
                The type code contains information on the specifications and configuration of the
                drive. The first digits from left express the basic configuration (e.g. ACS800-01-
                0006-5). The optional selections are given thereafter, separated by + signs (e.g.
                +E202). The main selections are described below. Not all selections are available for
                all types. For more information, refer to ACS 800 Ordering Information (EN code:
                64556568, available on request).
         Selection                  Alternatives
         Product series             ACS800 product series
         Type                       01      wall mounted. When no options are selected: IP 21, Control Panel
                                            CDP312R, no EMC filter, Standard Application Program, cable
                                            connection box (cabling from below), brake chopper in frame sizes R2
                                            and R3, boards without coating, one set of manuals
                                    U1      wall mounted (USA). When no options are selected: UL type 1, Control
                                            Panel CDP312R, no EMC filter, US version of the Standard Application
                                            Program (three-wire start/stop as default setting), US gland/conduit box,
                                            brake chopper in frame sizes R2 and R3, boards without coating, one set
                                            of English manuals.
         Size                       Refer to Technical data: IEC ratings.
         Voltage range              2       208/220/230/240 VAC
         (nominal rating in bold)   3       380/400/415 VAC
                                    5       380/400/415/440/460/480/500 VAC
                                    7       525/575/600/690 VAC
         + options
         Degree of protection       B056  IP 55 / UL type 12
         Resistor braking           D150  brake chopper
         Filter                     E200  EMC/RFI filter for second environment TN (grounded) system,
                                          unrestricted distribution
                                    E202 EMC/RFI filter for first environment TN (grounded) system, restricted
                                          distribution (the A limits)
         Cabling                    H358 US/UK gland/conduit box
         Control panel              0J400 no control panel
         Fieldbus                   K...  Refer to ACS 800 Ordering Information (EN code: 64556568).
         I/O                        L...
         Application program        N...
         Manual language            R...
         Specialities                     P901 = coated boards
The ACS800-01/U1
                                                                                                              23
        Diagram
            This diagram shows the control interfaces and the main circuit of the drive.
                                          Motor
                                          control and               Optional module 1: RMBA, RAIO,
                                          I/O board                 RDIO, RDNA, RLON, RIBA, RPBA,
                                          (RMIO)                    RCAN, RCNA, RMBP, RETA or RTAC
               Input power
                                        =                               ~            Output power
                                    ~                               =
                                                   R- UDC+ UDC-
                                                        R+
        Operation
            This table describes the operation of the main circuit in short.
Component Description
capacitor bank energy storage which stabilizes the intermediate circuit DC voltage
              six-pulse IGBT inverter   converts the DC voltage to AC voltage and vice versa. The motor
                                        operation is controlled by switching the IGBTs.
                                                                                            The ACS800-01/U1
24
          Motor control
              The motor control is based on the Direct Torque Control (DTC) method. Two phase
              currents and DC link voltage are measured and used for the control. The third phase
              current is measured for earth fault protection.
The ACS800-01/U1
                                                                                                 25
Mechanical installation
Tear
                                                                        Mechanical installation
26
            Delivery check
                   Check that there are no signs of damage. Before attempting installation and
                   operation, check the information on the type designation label of the drive to verify
                   that the unit is of the correct type. The label includes an IEC and NEMA rating, UL,
                   C-UL, CSA and CE markings, a type code and a serial number, which allow
                   individual recognition of each unit. The first digit of the serial number refers to the
                   manufacturing plant. The next four digits refer to the unit’s manufacturing year and
                   week, respectively. The remaining digits complete the serial number so that there
                   are no two units with the same serial number.
                   The type designation label is attached to the heat sink and the serial number label to
                   the upper part of the back plate of the unit. Example labels are shown below.
Before installation
                   The drive must be installed in an upright position with the cooling section facing a
                   wall. Check the installation site according to the requirements below. Refer to
                   Dimensional drawings for frame details.
Mechanical installation
                                                                                               27
                                                                       50 [2.0]
                      200 [7.9]
      300 [12]
                                                                       50 [2.0]
                                                                          Mechanical installation
28
IP 55 (UL 12)
              UL 12 units
                     Install the hood delivered with the drive 50 mm (2.0 in.) above the top of unit.
Mechanical installation
                                                                                                    29
Cabinet installation
            The required distance between parallel units is five millimetres (0.2 in.) in
            installations without the front cover. The cooling air entering the unit must not exceed
            +40 °C (+104 °F).
                                                HOT
                  Main air flow out             AREA
COOL AREA
                                                                                Mechanical installation
30
Mechanical installation
                                                                                                    31
            WARNING! Operation is not allowed if the motor nominal voltage is less than 1/2 of
            the drive nominal input voltage. The allowed range of the motor nominal current is
            1/6 ... 2 · I2hd of the drive in DTC control and 0 ... 2 · I2hd in scalar control. The
            control mode is selected by a drive parameter.
                              To avoid damage to motor bearings, insulated N-end (non-driven end) bearings and
                              output filters from ABB must be used according to the following table. In addition, the
                              cables must be selected and installed according to the instructions given in this
                              manual. Three types of filters are used individually or in combinations:
                              • optional du/dt filter (protects motor insulation system and reduces bearing
                                currents).
                              • common mode filter (mainly reduces bearing currents)
                              • light common mode filter (mainly reduces bearing currents).
                              The common mode filter is composed of toroidal cores installed onto the output
                              busbars inside the drive at the factory.
                        Requirements table
                              The following table shows how to select the motor insulation system and when optional ABB du/dt filter,
                              insulated N-end (non-driven end) motor bearings and ABB common mode filters are required. The
                              motor manufacturer should be consulted regarding the construction of the motor insulation and
                              additional requirements for explosion-safe (EX) motors. Failure of the motor to fulfil the following
                              requirements or improper installation may shorten motor life or damage the motor bearings.
                                                      system                                             filter
                                                                            PN < 100 kW         100 kW < PN < 350 kW         PN > 350 kW
                                                                                 and                     or                       or
                                                                         frame size < IEC 315    frame size > IEC 315    frame size > IEC 400
                                                                             PN < 134 HP        134 HP < PN < 469 HP        PN > 469 HP
                                                                           and frame size <          or frame size >
                                                                             NEMA 500                  NEMA 500
 A             Random-        UN < 500 V          Standard           -                          +N                      + N + CMF
 B             wound M2_      500 V < UN < 600 V Standard            + du/dt                    + du/dt + N             + du/dt + N + LCMF
               and M3_
 B                                                or
                                                  Reinforced         -                          +N                      + N + CMF
                              600 V < UN < 690 V Reinforced          + du/dt                    + du/dt + N             + du/dt + N + LCMF
               Form-wound     380 V < UN < 690 V Standard            n.a.                       + N + CMF               + N + CMF
               HXR and AM_
               Old* form-     380 V < UN < 690 V Check with the      + du/dt with voltages over 500 V + N + CMF
               wound HX_                         motor
               and modular                       manufacturer.
               Random-        380 V < UN < 690 V Check with the      + du/dt with voltages over 500 V + N + CMF
               wound HXR                         motor
               and AM_                           manufacturer.
                                                          system                                             filter
                                                                                PN < 100 kW         100 kW < PN < 350 kW         PN > 350 kW
                                                                                     and                     or                       or
                                                                             frame size < IEC 315    frame size > IEC 315    frame size > IEC 400
                                                                                 PN < 134 HP        134 HP < PN < 469 HP        PN > 469 HP
                                                                               and frame size <          or frame size >
                                                                                 NEMA 500                  NEMA 500
 N             Random-        UN < 420 V              Standard: ÛLL =    -                          + N or CMF              + N + CMF
 O             wound and                              1300 V
               form-wound
 N                            420 V < UN < 500 V Standard: ÛLL =         + du/dt                    + du/dt + N             + du/dt + N + CMF
 -                                               1300 V
                                                                                                    or
 A
                                                                                                    + du/dt + CMF
 B
                                                      or
 B
                                                      Reinforced: ÛLL = -                           + N or CMF              + N + CMF
                                                      1600 V, 0.2
                                                      microsecond rise
                                                      time
                              500 V < UN < 600 V Reinforced: ÛLL = + du/dt                          + du/dt + N             + du/dt + N + LCMF
                                                 1600 V                                             or
                                                                                                    + du/dt + CMF
                                                      or
                                                      Reinforced: ÛLL = -                           + N or CMF              + N + CMF
                                                      1800 V
                              600 V < UN < 690 V Reinforced: ÛLL = + du/dt                          + du/dt + N             + du/dt + N + LCMF
                                                 1800 V
               Form-wound     600 V < UN < 690 V Reinforced: ÛLL = n.a.                             N + CMF                 N + CMF
                                                 2000 V, 0.3
                                                 microsecond rise
                                                 time
  Abbreviation                Definition
  UN                          nominal voltage of the supply network
  ÛLL                         peak line-to-line voltage at motor terminals which the motor insulation must withstand
  PN                          motor nominal power
  du/dt                       du/dt filter at the output of the drive
  CMF                         common mode filter +E208 (3 toroidal cores)
  LCMF                        light common mode filter +E209 (1 toroidal core)
  N                           N-end bearing: insulated motor non-driven end bearing
  n.a.                        Motors of this power range are not available as standard units. Consult the motor manufacturer.
Supply connection
       EU
            To meet the European Union Directives, according to standard EN 60204-1, Safety
            of Machinery, the disconnecting device must be one of the following types:
            • a switch-disconnector of utilization category AC-23B (EN 60947-3)
            • a disconnector that has an auxiliary contact that in all cases causes switching
              devices to break the load circuit before the opening of the main contacts of the
              disconnector (EN 60947-3)
            • a circuit breaker suitable for isolation in accordance with EN 60947-2.
       US
            The disconnecting means must conform to the applicable safety regulations.
       Fuses
            See section Thermal overload and short-circuit protection.
            The drive protects the motor cable and the motor in a short-circuit situation when the
            motor cable is dimensioned according to the nominal current of the drive.
             ACS800-07/U7
                   An emergency stop function is optionally available for stopping and switching off the
                   whole drive. Two stop categories according to IEC/EN 60204-1 (1997) are available:
                   immediate removal of power (Category 0) and controlled emergency stop
                   (Category 1).
            WARNING! The Prevention of Unexpected Start function does not disconnect the
            voltage of the main and auxiliary circuits from the drive. Therefore maintenance work
            on electrical parts of the drive or the motor can only be carried out after isolating the
            drive system from the main supply.
             General rules
                   Dimension the mains (input power) and motor cables according to local
                   regulations:
                   • The cable must be able to carry the drive load current. See chapter Technical
                     data for the rated currents.
                   • The cable must be rated for at least 70 °C maximum permissible temperature of
                     conductor in continuous use. For US, see Additional US requirements.
                   • The inductance and impedance of the PE conductor/cable (grounding wire) must
                     be rated according to permissible touch voltage appearing under fault conditions
                     (so that the fault point voltage will not rise excessively when an ground fault
                     occurs).
                   • 600 VAC cable is accepted for up to 500 VAC. For 690 VAC rated equipment, the
                     rated voltage between the conductors of the cable should be minimum 1 kV.
                   For drive frame size R5 and larger, or motors larger than 30 kW (40 HP),
                   symmetrical shielded motor cable must be used (figure below). A four-conductor
                   system can be used up to frame size R4 with up to 30 kW (40 HP) motors, but
                   shielded symmetrical motor cable is recommended.
                   A four-conductor system is allowed for input cabling, but shielded symmetrical cable
                   is recommended. To operate as a protective conductor, the shield conductivity must
                   be as follows when the protective conductor is made of the same metal as the phase
                   conductors:
                   Cross-sectional area of the phase   Minimum cross-sectional area of the
                   conductors                          corresponding protective conductor
                                   S (mm2)                          Sp (mm2)
                                    S < 16                              S
                                  16 < S < 36                           16
                                    35 < S                             S/2
              The motor cable and its PE pigtail (twisted shield) should be kept as short as
              possible in order to reduce electromagnetic emission as well as capacitive current.
                Recommended
Symmetrical shielded cable: three phase conductors           A separate PE conductor is required if the conductivity
and a concentric or otherwise symmetrically                  of the cable shield is < 50 % of the conductivity of the
constructed PE conductor, and a shield                       phase conductor.
             PE conductor                      Shield
             and shield                                                                   Shield
                                                                                               PE
                                               PE
                                           PE                                                      Shield
A four-conductor system:
three phase conductors
and a protective
conductor.
                                 Not allowed for motor cables        Not allowed for motor cables with phase
                                                                     conductor cross section larger than 10 mm2
                                                                     [motors > 30 kW (40 HP)].
Cable core
             Additional US requirements
                   Type MC continuous corrugated aluminum armor cable with symmetrical grounds or
                   shielded power cable must be used for the motor cables if metallic conduit is not
                   used. For the North American market, 600 VAC cable is accepted for up to 500 VAC.
                   1000 VAC cable is required above 500 VAC (below 600 VAC). For drives rated over
                   100 amperes, the power cables must be rated for 75 °C (167 °F).
             Conduit
                   Where conduits must be coupled together, bridge the joint with a ground conductor
                   bonded to the conduit on each side of the joint. Bond the conduits also to the drive
                   enclosure. Use separate conduits for input power, motor, brake resistors, and control
                   wiring. Do not run motor wiring from more than one drive in the same conduit.
             Armored cable / shielded power cable
                   The motor cables can be run in the same cable tray as other 460 V or 600 V power
                   wiring. Control and signal cables must not be run in the same tray as power cables.
                   Six conductor (3 phases and 3 ground) type MC continuous corrugated aluminum
                   armor cable with symmetrical grounds is available from the following suppliers (trade
                   names in parentheses):
                   • Anixter Wire & Cable (Philsheath)
                   • BICC General Corp (Philsheath)
                   • Rockbestos Co. (Gardex)
                   • Oaknite (CLX).
                   Shielded power cables are available from Belden, LAPPKABEL (ÖLFLEX) and
                   Pirelli.
           WARNING! Never connect the supply power to the drive output terminals U2, V2
           and W2. If frequent bypassing is required, employ mechanically connected switches
           or contactors. Mains (line) voltage applied to the output can result in permanent
           damage to the unit.
                                                                      RMIO
                                                      Relay outputs
                                        Varistor      X25
                                                       1    RO1
                                                       2    RO1
                             230 VAC
                                                       3    RO1
                                        RC filter     X26
                                                       1    RO2
                                                       2    RO2
                              230 VAC
                                                       3    RO2
                                         Diode        X27
                                                       1    RO3
                                                       2    RO3
                              24 VDC
                                                       3    RO3
                             a                                    b
                 A double shielded twisted           A single shielded twisted
                 pair cable                          multipair cable
        Relay cable
            The cable type with braided metallic screen (e.g. ÖLFLEX by LAPPKABEL,
            Germany) has been tested and approved by ABB.
                   WARNING! IEC 60664 requires double or reinforced insulation between live parts
                   and the surface of accessible parts of electrical equipment which are either non-
                   conductive or conductive but not connected to the protective earth.
                   To fulfil this requirement, the connection of a thermistor (and other similar
                   components) to the digital inputs of the drive can be implemented in three alternate
                   ways:
                   1. There is double or reinforced insulation between the thermistor and live parts of
                      the motor.
                   2. Circuits connected to all digital and analogue inputs of the drive are protected
                      against contact and insulated with basic insulation (the same voltage level as the
                      drive main circuit) from other low voltage circuits.
                   3. An external thermistor relay is used. The insulation of the relay must be rated for
                      the same voltage level as the main circuit of the drive. For connection, see
                      ACS 800 Firmware Manual.
                                                    Motor cable
                                       Drive
                                                                         min 300 mm (12 in.)
                                                   Power cable
Control cables
Electrical installation
           WARNING! The work described in this chapter may only be carried out by a qualified
           electrician. Follow the Safety instructions on the first pages of this manual. Ignoring
           the safety instructions can cause injury or death.
           Make sure that the drive is disconnected from the mains (input power) during
           installation. If the drive is already connected to the mains, wait for 5 min after
           disconnecting mains power.
                                                                               Electrical installation
48
                    WARNING! Check the insulation before connecting the drive to the mains. Make
                    sure that the drive is disconnected from the mains (input power).
                    1. Check that the motor cable is disconnected from the drive output terminals U2,
                       V2 and W2.
              M     2. Measure the insulation resistances of the motor cable and the motor between
 ohm                   each phase and the Protective Earth by using a measuring voltage of 1 kV DC.
       PE
                       The insulation resistance must be higher than 1 Mohm.
IT (ungrounded) systems
                    Disconnect the EMC filter capacitors of selections +E202 and +E200 before
                    connecting the drive to an ungrounded system. For detailed instructions on how to
                    do this, please contact your local ABB distributor.
Electrical installation
                                                                                                                                 49
Diagram
                                                                    Drive
                                             INPUT                       UDC+ UDC-         OUTPUT
                                 PE        U1 V1 W1                 R-    R+             U2       V2    W2
                            1)        2)
3) 4) 4)
                          (PE) PE (PE)
                                                                                                                   5)
                                                                                                  V1    W1
                                                                                          U1
                                                                  Optional brake
For alternatives, see
Planning the electrical
                                                                  resistor                    3   ~
installation:                                                                                 Motor
Disconnecting device
(means)                                    L1   L2        L3
                                                                                                  b > 1/5 · a
5) Use a separate grounding cable if the conductivity of
   the cable shield is < 50 % of the conductivity of the                                   b
                                                                              a
   phase conductor and there is no symmetrically
   constructed grounding conductor in the cable (see
   Planning the electrical installation / Selecting the
   power cables).
Note:
If there is a symmetrically constructed grounding
conductor in the motor cable in addition to the
conductive shield, connect the grounding conductor to
the grounding terminal at the drive and motor ends.
Do not use an asymmetrically constructed motor cable.
Connecting its fourth conductor at the motor end
increases bearing currents and causes extra wear.
                                                                                                             Electrical installation
50
Electrical installation
                                                                                                                         51
                                   8
          1
Bottom plate
Fasten the
control
cables
between
these plates
with cable
                                                 Cover
ties
          U1       V1    W1           UDC+
                                               U2      V2       W2
                                 R-    R+ UDC-
    PE
                                                                                                             6
               6                                                     6
5 5
                                                                                                 Electrical installation
52
Frame size R6: Cable lug installation [16 to 70 mm2 (6 to 4/0 AWG) cables]
                                                                                                  a
                                                                    Isolate the ends of          Connection plate
                                          a                         the cable lugs with          fastening screws
                  PE 6
                                                                    insulating tape or
                                                                    shrink tubing.
3 3
5 5
Frame size R6: Cable terminal installation (95 to 185 mm2 cables)
PE 6
                                                                             a
                                                                    a. Connect the cable to the terminal.
5 5
Electrical installation
                                                                                              53
Frame sizes R2 to R4
                                                               UDC+
                                            U1 V1 W1        R- R+ UDC- U2 V2 W2
                                      4                                                 4
                                            PE
3 3
    5. Lead the cables through the glands to the inside of the gland box.
    6. Connect the PE conductors of the input and motor cables to the grounding
       terminal. Note: cable lugs are needed in frame sizes R2 and R3. Connect the
       separate PE conductor (if used) to the grounding terminal.
    7. Connect the phase conductors of the input cable to the U1, V1 and W1 terminals
       and the phase conductors of the motor cable to the U2, V2 and W2 terminals.
       For frame size R6, see Wall installed units (European version) / figure Frame size
       R6: Cable lug installation [16 to 70 mm2 (6 to 4/0 AWG) cables]. To meet UL
       requirements, use UL listed cable lugs and tools given below or corresponding.
                                                                          Electrical installation
54
              Warning sticker
                    There are warning stickers in different languages inside the packing box of the drive.
                    Attach a warning sticker in the language of your choice onto the plastic skeleton
                    above the power cable terminals.
Electrical installation
                                                                                                 55
      Protect the RMIO board terminals X25 to X27 against contact when input voltage
      exceeds 50 VAC.
Frame size R5
      Cover the power cable terminals as follows:
      1. Cut holes for the installed cables into the clear plastic shroud.
      2. Press the shroud onto the terminals.
1 2
Frame size R6
      Cover the power cable terminals as follows:
      1. Cut holes for the installed cables into the clear plastic shroud in cable lug
         installations.
      2. Press the shroud onto the terminals.
Removal of the shroud by lifting up with a screw driver from the corner:
                                                                             Electrical installation
56
Terminals
  Frame sizes R2 to R4
  The control cable connection terminals are
  exposed when the control panel mounting platform
  is turned aside by pulling this knob. Be careful, do        Detachable connection terminals (pull up)
  not use excess force when pulling.
                                                                        X39 for control panel cable
Optional module 1
Optional module 2
Electrical installation
                                                                              57
Control panel
Optional module 2
                                                          Electrical installation
58
Insulation
                                     4
                                    3
                                2
                            1
              When the outer surface of the shield is covered with non-conductive material
                    • Strip the cable carefully (do not cut the grounding wire and the shield)
                    • Turn the shield inside out to expose the conductive surface.
                    • Wrap the grounding wire around the conductive surface.
                    • Slide a conductive clamp onto the conductive part.
                    • Fasten the clamp to the grounding plate with a screw as close as possible to the
                      terminals where the wires are about to be connected.
Electrical installation
                                                                                                                   59
                                                      Module
  As short as possible
Shield
                                           4
                                          3
                                      2
                                  1
                                      As short as
                                      possible
                                                                 Note1: If the encoder is of
                         1
                             2                                   unisolated type, ground the encoder
                                                                 cable at the drive end only. If the
                                 3
                                  4
                                                                                               Electrical installation
60
US cover
Electrical installation
                                                                                               61
Note for the ACS800-02 with enclosure extension and the ACS800-07
           The connections for the RMIO board shown below apply also to optional terminal
           block X2. The terminals of the RMIO board are wired to terminal block X2 internally.
           Terminals of X2 accept cables from 0.5 to 4.0 mm2 (22 to 12 AWG). Tightening
           torque: 0.4 to 0.8 Nm (0.3 to 0.6 lbf ft)
Analogue outputs
                              Two programmable current outputs: 0 (4) to 20 mA, RL < 700 ohm
Resolution                    0.1 % (10 bit)
Inaccuracy                    ± 1 % (Full Scale Range) at 25 °C (77 °F). Temperature coefficient: ± 200 ppm/°C
                              (± 111 ppm/°F) max.
Digital inputs
                              With Standard Application Program six programmable digital inputs (common ground:
                              24 VDC, -15 % to +20 %) and a start interlock input. Group isolated, can be divided in
                              two isolated groups (see Isolation and grounding diagram below).
                              Thermistor input: 5 mA, < 1.5 kohm     “1” (normal temperature), > 4 kohm           “0”
                              (high temperature), open circuit  “0” (high temperature).
                              Internal supply for digital inputs (+24 VDC): short circuit proof. An external 24 VDC
                              supply can be used instead of the internal supply.
Isolation test voltage        500 VAC, 1 min
Logical thresholds            < 8 VDC      “0”, > 12 VDC       “1”
Input current                 DI1 to DI 5: 10 mA, DI6: 5 mA
Filtering time constant       1 ms
Relay outputs
                                  Three programmable relay outputs
Switching capacity                8 A at 24 VDC or 250 VAC, 0.4 A at 120 VDC
Minimum continuous current        5 mA rms at 24 VDC
Maximum continuous current        2 A rms
Contact material                  Silver Cadmium Oxide (AgCdO)
Isolation test voltage            4 kVAC, 1 minute
The terminals on the RMIO board as well as on the optional modules attachable to the board fulfil the Protective Extra
Low Voltage (PELV) requirements stated in EN 50178 provided that the external circuits connected to the terminals also
fulfil the requirements.
                9     AO1+
                10    AO1-
                11    AO2+
                12    AO2-
                X22
                1     DI1
                2     DI2
                3     DI3
                4     DI4
                                                                     Jumper J1 settings:
                9     DGND1
Installation checklist
Checklist
                Check the mechanical and electrical installation of the drive before start-up. Go
                through the checklist below together with another person. Read the Safety
                instructions on the first pages of this manual before you work on the unit.
      Check
MECHANICAL INSTALLATION
      The ambient operating conditions are allowed. (See Mechanical installation, Technical data:
      IEC ratings or US tables / NEMA ratings, Ambient conditions.)
      The unit is fixed properly on a vertical non-flammable wall. (See Mechanical installation.)
      The cooling air will flow freely.
      The motor and the driven equipment are ready for start. (See Planning the electrical
      installation: Checking the compatibility of the motor, Technical data: Motor connection.)
ELECTRICAL INSTALLATION (See Planning the electrical installation, Electrical installation.)
      The +E202 and +E200 EMC filter capacitors are disconnected if the drive is connected to an
      IT (ungrounded) system.
      The capacitors are reformed if stored over one year (refer to ACS 600/800 Capacitor
      Reforming Guide [64059629 (English)].
      The drive is grounded properly.
      The mains (input power) voltage matches the drive nominal input voltage.
      The mains (input power) connections at U1, V1 and W1 and their tightening torques are OK.
      Appropriate mains (input power) fuses and disconnector are installed.
      The motor connections at U2, V2 and W2 and their tightening torques are OK.
      The motor cable is routed away from other cables.
      There are no power factor compensation capacitors in the motor cable.
      The external control connections inside the drive are OK.
      There are no tools, foreign objects or dust from drilling inside the drive.
      Mains (input power) voltage cannot be applied to the output of the drive (with bypass
      connection).
      Drive, motor connection box and other covers are in place.
                                                                                    Installation checklist
68
Installation checklist
                                                                                                               69
Maintenance
Safety
           WARNING! Read the Safety instructions on the first pages of this manual before
           performing any maintenance on the equipment. Ignoring the safety instructions can
           cause injury or death.
Maintenance intervals
           If installed in an appropriate environment, the drive requires very little maintenance.
           This table lists the routine maintenance intervals recommended by ABB.
Heatsink
           The heatsink fins pick up dust from the cooling air. The drive runs into
           overtemperature warnings and faults if the heatsink is not clean. In a “normal”
           environment (not dusty, not clean) the heatsink should be checked annually, in a
           dusty environment more often.
           Clean the heatsink as follows (when necessary):
           1. Remove the cooling fan (see section Fan).
           2. Blow clean compressed air (not humid) from bottom to top and simultaneously
              use a vacuum cleaner at the air outlet to trap the dust. Note: If there is a risk of
              the dust entering adjoining equipment, perform the cleaning in another room.
           3. Replace the cooling fan.
                                                                                                 Maintenance
70
Fan
              The cooling fan lifespan of the drive is about 60 000 operating hours. The actual
              lifespan depends on the drive usage and ambient temperature. See the appropriate
              ACS 800 firmware manual for an actual signal which indicates the hours of usage of
              the fan.
              Fan failure can be predicted by the increasing noise from fan bearings and the
              gradual rise in the heatsink temperature in spite of heatsink cleaning. If the drive is
              operated in a critical part of a process, fan replacement is recommended once these
              symptoms start appearing. Replacement fans are available from ABB. Do not use
              other than ABB specified spare parts.
Bottom view
Maintenance
                                                                                            71
             1                             1         Bottom view
  2
                                      3
                                                         View from above fan
                                                         plate pulled out
4 4
4 4
                                                                                  Maintenance
72
                                     1
                                                           2
          Replacement (R6)
              Remove the top cover by lifting it by the rear edge. To remove the fan, release the
              retaining clips by pulling the back edge (1) of the fan upwards. Disconnect the cable
              (2, detachable terminal). Install the fan in reverse order.
Maintenance
                                                                                                                     73
Capacitors
                   The drive intermediate circuit employs several electrolytic capacitors. Their lifespan
                   is from 45 000 to 90 000 hours depending on drive loading and ambient
                   temperature. Capacitor life can be prolonged by lowering the ambient temperature.
                   It is not possible to predict a capacitor failure. Capacitor failure is usually followed by
                   a mains fuse failure or a fault trip. Contact ABB if capacitor failure is suspected.
                   Replacements for frame size R4 and up are available from ABB. Do not use other
                   than ABB specified spare parts.
               Reforming
                   Reform (re-age) spare part capacitors once a year according to ACS 600/800
                   Capacitor Reforming Guide (code: 64059629).
LEDs
                   This table describes LEDs of the drive.
                                                                                                         Maintenance
74
Maintenance
                                                                                                                 75
Technical data
IEC ratings
                  The IEC ratings for the ACS800-01 with 50 Hz and 60 Hz supplies are given below.
                  The symbols are described below the table.
 ACS800-01 size       Nominal        No-          Light-overload   Heavy-duty use    Frame   Air flow      Heat
                                     overload
                      ratings        use
                                                  use                                size               dissipation
                  Icont.max   Imax    Pcont.max     I2N       PN     I2hd      Phd
                     A        A         kW        A       kW             A      kW            m3/h          W
 Three-phase supply voltage 208 V, 220 V, 230 V or 240 V
 -0001-2          5.1      6.5      1.1       4.7      0.75        3.4       0.55     R2        35         100
 -0002-2          6.5      8.2      1.5       6.0      1.1         4.3       0.75     R2        35         100
 -0003-2          8.5      10.8     1.5      7.7       1.5         5.7       1.1      R2        35         100
 -0004-2          10.9     13.8     2.2       10.2     2.2         7.5       1.5      R2        35         120
 -0005-2          13.9     17.6     3         12.7     3           9.3       2.2      R2        35         140
 -0006-2          19       24       4         18       4           14        3        R3        69         160
 -0009-2          25       32       5.5       24       5,5         19        4        R3        69         200
 -0011-2          34       46       7.5       31       7.5         23        5.5      R3        69         250
 -0016-2          44       62       11        42       11          32        7.5      R4       103         340
 -0020-2          55       72       15        50       11          37        7.5      R4       103         440
 -0025-2          72       86       18.5      69       18.5        49        11       R5       168         530
 -0030-2          86       112      22        80       22          60        15       R5       168         610
 -0040-2          103      138      30       94        22          69        18.5     R5       168         810
 -0050-2          141      164      37        132      37          97        30       R6       405        1190
 -0060-2          166      202      45        155      45          115       30       R6       405        1190
 -0070-2          202      282      55        184      55          141       37       R6       405        1440
 Three-phase supply voltage 380 V, 400 V or 415 V
 -0003-3          5.1      6.5      1.5       4.7      1.5         3.4       1.1      R2        35         100
 -0004-3          6.5      8.2      2.2       5.9      2.2         4.3       1.5      R2        35         120
 -0005-3          8.5      10.8     3         7.7      3           5.7       2.2      R2        35         140
 -0006-3          10.9     13.8     4         10.2     4           7.5       3        R2        35         160
 -0009-3          13.9     17.6     5.5       12.7     5.5         9.3       4        R2        35         200
 -0011-3          19       24       7.5       18       7.5         14        5.5      R3        69         250
 -0016-3          25       32       11        24       11          19        7.5      R3        69         340
 -0020-3          34       46       15        31       15          23        11       R3        69         440
 -0025-3          44       62       22        41       18.5        32        15       R4       103         530
 -0030-3          55       72       30        50       22          37        18.5     R4       103         610
 -0040-3          72       86       37        69       30          49        22       R5       168         810
 -0050-3          86       112      45        80       37          60        30       R5       168         990
 -0060-3          103      138      55        94       45          69        37       R5       168        1190
 -0070-3          141      164      75        132      55          97        45       R6       405        1440
 -0100-3          166      202      90        155      75          115       55       R6       405        1940
 -0120-3          202      282      110       184      90          141       75       R6       405        2310
                                                                                                     Technical data
76
 ACS800-01 size        Nominal        No-          Light-overload   Heavy-duty use      Frame    Air flow        Heat
                                      overload
                       ratings        use
                                                   use                                  size                  dissipation
                   Icont.max   Imax    Pcont.max  I2N       PN       I2hd      Phd
                      A       A        kW          A       kW          A        kW                 m3/h             W
 Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
 -0004-5          4.9      6.5      2.2       4.5       2.2       3.4       1.5           R2         35           120
 -0005-5          6.2      8.2      3         5.6       3         4.2       2.2           R2         35           140
 -0006-5          8.1      10.8     4         7.7       4         5.6       3             R2         35           160
 -0009-5          10.5     13.8     5.5       10        5.5       7.5       4             R2         35           200
 -0011-5          13.2     17.6     7.5       12        7.5       9.2       5.5           R2         35           250
 -0016-5          19       24       11        18        11        13        7.5           R3         69           340
 -0020-5          25       32       15        23        15        18        11            R3         69           440
 -0025-5          34       46       18.5      31        18.5      23        15            R3         69           530
 -0030-5          42       62       22        39        22        32        18.5          R4        103           610
 -0040-5          48       72       30        44        30        36        22            R4        103           810
 -0050-5          65       86       37        61        37        50        30            R5        168           990
 -0060-5          79       112      45        75        45        60        37            R5        168          1190
 -0070-5          96       138      55        88        55        69        45            R5        168          1440
 -0100-5          124      164      75        115       75        88        55            R6        405          1940
 -0120-5          157      202      90        145       90        113       75            R6        405          2310
 -0140-5          180      282      110       163       110       141       90            R6        405          2810
 Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V or 690 V
 -0011-7          13       14       11        11.5      7.5       8.5       5.5           R4        103           300
 -0016-7          17       19       15        15        11        11        7.5           R4        103           340
 -0020-7          22       28       18.5      20        15        15        11            R4        103           440
 -0025-7          25       38       22        23        18.5      19        15            R4        103           530
 -0030-7          33       44       30        30        22        22        18.5          R4        103           610
 -0040-7          36       54       30        34        30        27        22            R4        103           690
 -0050-7          51       68       45        46        37        34        30            R5        168           840
 -0060-7          57       84       55        52        45        42        37            R5        168          1010
 -0070-7          79       104      75        73        55        54        45            R6        405          1220
 -0100-7          93       124      90        86        75        62        55            R6        405          1650
 -0120-7          113      172      110       108       90        86        75            R6        405          1960
                                                                                                          PDM code: 00096931-C
             Symbols
                   Nominal ratings
                   Icont.max continuous rms output current. No overload capability at 40 °C.
                   Imax       maximum output current. Available for 10 s at start, otherwise as long as allowed by drive
                              temperature.
                   Typical ratings:
                   No-overload use
                   Pcont.max typical motor power. The power ratings apply to most IEC 34 motors at the nominal voltage,
                              230 V, 400 V, 500 V or 690 V.
                   Light-overload use (10 % overload capability)
                   I2N        continuous rms current. 10 % overload is allowed for one minute every 5 minutes.
                   PN         typical motor power. The power ratings apply to most IEC 34 motors at the nominal voltage,
                              230 V, 400 V, 500 V or 690 V.
                   Heavy-duty use (50 % overload capability)
                   I2hd       continuous rms current. 50 % overload is allowed for one minute every 5 minutes.
                   Phd        typical motor power. The power ratings apply to most IEC 34 motors at the nominal voltage,
                              230 V, 400 V, 500 V or 690 V.
Technical data
                                                                                                            77
Sizing
     The current ratings are the same regardless of the supply voltage within one voltage range. To achieve
     the rated motor power given in the table, the rated current of the drive must be higher than or equal to
     the rated motor current.
     Note 1: The maximum allowed motor shaft power is limited to 1.5 · Phd. If the limit is exceeded, motor
     torque and current are automatically restricted. The function protects the input bridge of the drive
     against overload.
     Note 2: The ratings apply in ambient temperature of 40 °C (104 °F). In lower temperatures the ratings
     are higher (except Imax).
     Note 3: Use the DriveSize PC tool for a more accurate dimensioning if the ambient temperature is
     below 40 °C (104 °F) or the drive is loaded cyclically.
Derating
     The load capacity (current and power) decreases if the installation site altitude exceeds 1000 metres
     (3300 ft), or if the ambient temperature exceeds 40 °C (104 °F).
Temperature derating
     In the temperature range +40 °C (+104 °F) to +50 °C (+122 °F) the rated output current is decreased
     1 % for every additional 1 °C (1.8 °F). The output current is calculated by multiplying the current given
     in the rating table by the derating factor.
     Example If the ambient temperature is 50 °C (+122 °F) the derating factor is 100 % - 1 % · 10 °C =
     90 % or 0.90. The output current is then 0.90 · I or 0.90 · I .                            °C
                                                      2N           2hd
Altitude derating
     In altitudes from 1000 to 4000 m (3300 to 13123 ft) above sea level, the derating is 1 % for every 100 m
     (328 ft). For a more accurate derating, use the DriveSize PC tool. If the installation site is higher than
     2000 m (6600 ft) above sea level, please contact your local ABB distributor or office for further
     information.
                                                                                              Technical data
78
Technical data
                                                                                                          79
                                                                                           Technical data
80
Cable types
                  The table below gives copper and aluminium cable types for different load currents.
                  Cable sizing is based on max. 9 cables laid on a cable ladder side by side, ambient
                  temperature 30 °C, PVC insulation, surface temperature 70 °C (EN 60204-1 and
                  IEC 60364-5-2/2001). For other conditions, size the cables according to local safety
                  regulations, appropriate input voltage and the load current of the drive.
                       Copper cables with concentric   Aluminium cables with concentric
                              copper shield                     copper shield
                        Max. load       Cable type        Max. load       Cable type
                         current                           current
                            A               mm2               A               mm2
                            14              3x1.5            61               3x25
                            20              3x2.5            75               3x35
                            27               3x4             91               3x50
                            34               3x6             117              3x70
                            47              3x10            143               3x95
                            62              3x16            165              3x120
                            79              3x25            191              3x150
                            98              3x35            218              3x185
                           119              3x50            257              3x240
                           153              3x70            274            3 x (3x50)
                           186              3x95            285            2 x (3x95)
                           215              3x120
                           249              3x150
                           284              3x185
                                                                       PDM code: 00096931-C
Cable entries
                  Brake resistor, mains and motor cable terminal sizes (per phase), accepted cable
                  diameters and tightening torques are given below.
Frame                            U1, V1, W1, U2, V2, W2, R+, R-                                       Earthing PE
size      Maximum wire           Max. cable Ø        Cable Ø            Tightening            Maximum         Tightening
              size                  IP 21               IP 55             torque              wire size         torque
                 mm2                 mm                  mm                  Nm                 mm2              Nm
R2               16*                 21                14...20            1.2...1.5              10              1.5
R3               16*                 21                14...20            1.2...1.5              10              1.5
R4                25                 29                23...35              2…4                  16              3.0
R5                70                 35                23...35               15                  70              15
R6               185                 53                30...45            20...40                95               8
Technical data
                                                                                                                       81
Motor connection
Voltage (U2)                   0 to U1, 3-phase symmetrical, Umax at the field weakening point
Frequency                      DTC mode: 0 to 3.2 · fFWP. Maximum frequency 300 Hz.
                                        UNmains
                               fFWP =             · fNmotor
                                        UNmotor
                               fFWP: frequency at field weakening point; UNmains: mains (input power) voltage;
                               UNmotor: rated motor voltage; fNmotor: rated motor frequency
Frequency resolution           0.01 Hz
Current                        See section IEC ratings.
Power limit                    1.5 · Phd
Field weakening point          8 to 300 Hz
Switching frequency            3 kHz (average). In 690 V units 2 kHz (average).
                                                                                                         Technical data
82
Efficiency
                             Approximately 98 % at nominal power level
Cooling
Method                       Internal fan, flow direction from bottom to top.
Free space around the unit   See chapter Mechanical installation.
Degrees of protection
                             IP 21 (UL type 1) and IP 55 (UL type 12). Without connection box and front cover, the unit
                             must be protected against contact according to IP 2x [see chapter Electrical installation:
                             Cabinet installation (IP 21, UL type 1)].
Technical data
                                                                                                                      83
Ambient conditions
                             Environmental limits for the drive are given below. The drive is to be used in a heated,
                             indoor, controlled environment.
                                       Operation                        Storage                    Transportation
                               installed for stationary use    in the protective package      in the protective package
Installation site altitude   0 to 4000 m (13123 ft) above -                                -
                             sea level [above 1000 m
                             (3281 ft), see section
                             Derating]
Air temperature              -15 to +50 °C (5 to 122 °F). -40 to +70 °C (-40 to            -40 to +70 °C (-40 to
                             No frost allowed. See section +158 °F)                        +158 °F)
                             Derating.
Relative humidity            5 to 95%                        Max. 95%                      Max. 95%
                             No condensation allowed. Maximum allowed relative humidity is 60% in the presence of
                             corrosive gases.
Contamination levels         No conductive dust allowed.
(IEC 60721-3-3, IEC 60721-3- Boards without coating:         Boards without coating:       Boards without coating:
2, IEC 60721-3-1)            Chemical gases: Class 3C1 Chemical gases: Class 1C2 Chemical gases: Class 2C2
                             Solid particles: Class 3S2      Solid particles: Class 1S3    Solid particles: Class 2S2
                               Boards with coating:          Boards with coating:          Boards with coating:
                               Chemical gases: Class 3C2     Chemical gases: Class 1C2     Chemical gases: Class 2C2
                               Solid particles: Class 3S2    Solid particles: Class 1S3    Solid particles: Class 2S2
Atmospheric pressure           70 to 106 kPa                 70 to 106 kPa                 60 to 106 kPa
                               0.7 to 1.05 atmospheres       0.7 to 1.05 atmospheres       0.6 to 1.05 atmospheres
Vibration (IEC 60068-2)        Max. 1 mm (0.04 in.)          Max. 1 mm (0.04 in.)          Max. 3.5 mm (0.14 in.)
                               (5 to 13.2 Hz),               (5 to 13.2 Hz),               (2 to 9 Hz),
                               max. 7 m/s2 (23 ft/s2)        max. 7 m/s2 (23 ft/s2)        max. 15 m/s2 (49 ft/s2)
                               (13.2 to 100 Hz) sinusoidal   (13.2 to 100 Hz) sinusoidal   (9 to 200 Hz) sinusoidal
Shock (IEC 60068-2-29)         Not allowed                   Max. 100 m/s2 (330 ft./s2),   Max. 100 m/s2 (330 ft./s2),
                                                             11 ms                         11 ms
Free fall                      Not allowed                   250 mm (10 in.) for weight    250 mm (10 in.) for weight
                                                             under 100 kg (220 lb)         under 100 kg (220 lb)
                                                             100 mm (4 in.) for weight     100 mm (4 in.) for weight
                                                             over 100 kg (220 lb)          over 100 kg (220 lb)
                                                                                                        Technical data
84
Materials
Drive enclosure          • PC/ABS 2.5 mm, colour NCS 1502-Y (RAL 90021 / PMS 420 C)
                         • hot-dip zinc coated steel sheet 1.5 to 2 mm, thickness of coating 100 micrometres
                         • cast aluminium AlSi (R2 and R3)
                         • extruded aluminium AlSi (R4 to R6)
Package                  Corrugated cardboard (frames R2 to R6 and option modules), expanded polystyrene.
                         Plastic covering of the package: PE-LD, bands PP or steel.
Disposal                 The drive contains raw materials that should be recycled to preserve energy and natural
                         resources. The package materials are environmentally compatible and recyclable. All
                         metal parts can be recycled. The plastic parts can either be recycled or burned under
                         controlled circumstances, according to local regulations. Most recyclable parts are marked
                         with recycling marks.
                         If recycling is not feasible, all parts excluding electrolytic capacitors and printed circuit
                         boards can be landfilled. The DC capacitors (C1-1 to C1-x) contain electrolyte and the
                         printed circuit boards contain lead, both of which will be classified as hazardous waste
                         within the EU. They must be removed and handled according to local regulations.
                         For further information on environmental aspects and more detailed recycling instructions,
                         please contact your local ABB distributor.
Applicable standards
                         The drive complies with the following standards. The compliance with the European Low
                         Voltage Directive is verified according to standards EN 50178 and EN 60204-1.
• EN 50178 (1997)        Electronic equipment for use in power installations
• EN 60204-1 (1997)      Safety of machinery. Electrical equipment of machines. Part 1: General requirements.
                         Provisions for compliance: The final assembler of the machine is responsible for installing
                         - an emergency-stop device
                         - a supply disconnecting device.
• EN 60529: 1991         Degrees of protection provided by enclosures (IP code)
  (IEC 60529)
• IEC 60664-1 (1992)     Insulation coordination for equipment within low-voltage systems. Part 1: Principles,
                         requirements and tests.
• EN 61800-3 (1996) +    EMC product standard including specific test methods
  Amendment A11 (2000)
• UL 508C                UL Standard for Safety, Power Conversion Equipment, second edition
• CSA C22.2 No. 14-95    Industrial control equipment
Technical data
                                                                                                                     85
CE marking
             A CE mark is attached to the drive to verify that the unit follows the provisions of the European Low
             Voltage and EMC Directives (Directive 73/23/EEC, as amended by 93/68/EEC and Directive 89/336/
             EEC, as amended by 93/68/EEC).
       Definitions
             EMC stands for Electromagnetic Compatibility. It is the ability of electrical/electronic equipment to
             operate without problems within an electromagnetic environment. Likewise, the equipment must not
             disturb or interfere with any other product or system within its locality.
             The EMC Directive defines the requirements for immunity and emissions of electrical equipment used
             within the European Union. The EMC product standard [EN 61800-3 + Amendment A11 (2000)] covers
             requirements stated for drives.
             First environment includes establishments connected to a low-voltage network which supplies buildings
             used for domestic purposes.
             Second environment includes establishments connected to a network not supplying domestic premises.
             Restricted distribution: mode of sales distribution in which the manufacturer restricts the supply of
             equipment to suppliers, customers or users who separately or jointly have technical competence in the
             EMC requirements of the application of drives.
             Unrestricted distribution: mode of sales distribution in which the supply of equipment is not dependent
             on the EMC competence of the customer or user for the application of drives.
                                                                                                     Technical data
86
            Second environment
                 The requirements of the EMC Directive can be met as follows:
                 1. The drive is equipped with EMC filter E200. The filter is suitable for TN (earthed) networks only.
                 2. The motor and control cables are selected as specified in the Hardware Manual.
                 3. The drive is installed according to the instructions given in the Hardware Manual.
                 4. Maximum cable length is 100 metres.
                 If the above listed provisions cannot be met, e.g., the drive cannot be equipped with EMC filter E200
                 when installed to an IT (unearthed) network, the requirements of the EMC Directive can be met as
                 follows for restricted distribution:
                 1. It is ensured that no excessive emission is propagated to neighbouring low-voltage networks. In
                    some cases, the natural suppression in transformers and cables is sufficient. If in doubt, a supply
                    transformer with static screening between the primary and secondary windings can be used.
                                         Neighbouring network
                                                                                          Static screen
Point of measurement
Equipment Equipment
                 2. An EMC plan for preventing disturbances is drawn up for the installation. A template is available
                    from the local ABB representative.
                 3. The motor and control cables are selected as specified in the Hardware Manual.
                 4. The drive is installed according to the instructions given in the Hardware Manual.
            Machinery Directive
                 The drive complies with the European Union Machinery Directive (98/37/EC) requirements for an
                 equipment intended to be incorporated into machinery.
Technical data
                                                                                                               87
“C-tick” marking
       “C-tick” marking is pending as follows.
       A “C-tick” mark is attached to each drive in order to verify compliance with the relevant standard
       (IEC 61800-3 (1996) – Adjustable speed electrical power drive systems – Part 3: EMC product
       standard including specific test methods), mandated by the Trans-Tasman Electromagnetic
       Compatibility Scheme.
   Definitions
       EMC stands for Electromagnetic Compatibility. It is the ability of electrical/electronic equipment to
       operate without problems within an electromagnetic environment. Likewise, the equipment must not
       disturb or interfere with any other product or system within its locality.
       The Trans-Tasman Electromagnetic Compatibility Scheme (EMCS) was introduced by the Australian
       Communication Authority (ACA) and the Radio Spectrum Management Group (RSM) of the New
       Zealand Ministry of Economic Development (NZMED) in November 2001. The aim of the scheme is to
       protect the radiofrequency spectrum by introducing technical limits for emission from electrical/
       electronic products.
       First environment includes establishments connected to a low-voltage network which supplies buildings
       used for domestic purposes.
       Second environment includes establishments connected to a network not supplying domestic premises.
       Restricted distribution: mode of sales distribution in which the manufacturer restricts the supply of
       equipment to suppliers, customers or users who separately or jointly have technical competence in the
       EMC requirements of the application of drives.
       Unrestricted distribution: mode of sales distribution in which the supply of equipment is not dependent
       on the EMC competence of the customer or user for the application of drives.
                                                                                               Technical data
88
            Second environment
                 The drive complies with the limits of IEC 61800-3 with the following provisions:
                 1. It is ensured that no excessive emission is propagated to neighbouring low-voltage networks. In
                    some cases, the natural suppression in transformers and cables is sufficient. If in doubt, the supply
                    transformer with static screening between the primary and secondary windings is strongly
                    recommended.
                                          Neighbouring network
                                                                                           Static screen
Point of measurement
Equipment Equipment
                 2. The drive is installed according to the instructions given in the Hardware Manual.
                 3. The motor and control cables used are selected as specified in the Hardware Manual.
Technical data
                                                                                                              89
US tables
        NEMA ratings
            The NEMA ratings for the ACS800-U1 with 60 Hz supplies are given below. The
            symbols are described below the table. For sizing, derating and 50 Hz supplies, see
            IEC ratings.
            ACS800-U1 size     Imax    Normal use         Heavy-duty use     Frame    Air flow       Heat
                                                                             size                 dissipation
                                          I2N       PN      I2hd      Phd
                                A          A        HP         A        HP            ft3/min       BTU/Hr
            Three-phase supply voltage 208 V, 220 V, 230 V or 240 V
            -0001-2         6.5        4.7      1          3.4       0.75        R2     21             350
            -0002-2         8.2        6.6      1.5        4.6       1           R2     21             350
            -0003-2         10.8       8.1      2          6.6       1.5         R2     21             350
            -0004-2         13.8       11       3          7.5       2           R2     21             410
            -0006-2         24         21       5          13        3           R3     41             550
            -0009-2         32         27       7.5        17        5           R3     41             680
            -0011-2         46         34       10         25        7.5         R3     41             850
            -0016-2         62         42       15         31        10          R4     61            1150
            -0020-2         72         54       20 *       42        15 **       R4     61            1490
            -0025-2         86         69       25         54        20 **       R5     99            1790
            -0030-2         112        80       30         68        25 **       R5     99            2090
            -0040-2         138        104      40 *       80        30 **       R5     99            2770
            -0050-2         164        132      50         104       40          R6    238            3370
            -0060-2         202        157      60         130       50 **       R6    238            4050
            -0070-2         282        192      75         154       60 **       R6    238            4910
            Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V or 480 V
            -0004-5         6.5        4.9      2          3.4       1.5         R2     21             410
            -0005-5         8.2        6.2      3          4.2       2           R2     21             480
            -0006-5         10.8       8.1      5          5.6       3           R2     21             550
            -0009-5         13.8       11       7.5        8.1       5           R2     21             690
            -0011-5         17.6       14       10         11        7.5         R2     21             860
            -0016-5         24         21       15         15        10          R3     41            1150
            -0020-5         32         27       20         21        15          R3     41            1490
            -0025-5         46         34       25         27        20          R3     41            1790
            -0030-5         62         42       30         34        25          R4     61            2090
            -0040-5         72         52       40         37        30 ***      R4     61            2770
            -0050-5         86         65       50         52        40          R5     99            3370
            -0060-5         112        79       60         65        50          R5     99            4050
            -0070-5         138        96       75         77        60          R5     99            4910
            -0100-5         164        124      100        96        75          R6    238            6610
            -0120-5         202        157      125        124       100         R6    238            7890
            -0140-5         282        180      150        156       125         R6    238            9600
            Three-phase supply voltage 525 V, 575 V, 600 V
            -0011-7         14         11.5     10         8.5       5           R4     61            1050
            -0016-7         19         15       10         11        10          R4     61            1200
            -0020-7         28         20       15         15        10          R4     61            1550
            -0025-7         38         23       20         19        15          R4     61            1850
            -0030-7         44         30       25         22        20          R4     61            2100
            -0040-7         54         34       30         27        25          R4     61            2400
            -0050-7         68         46       40         34        30          R5     99            2900
            -0060-7         84         52       50         42        40          R5     99            3450
            -0070-7         104        73       60         54        50          R6    238            4200
            -0100-7         124        86       75         62        60          R6    238            5650
            -0120-7         172        108      100        86        75          R6    238            6700
                                                                                             PDM code: 00096931-C
                                                                                             Technical data
90
                 *
                       Overload may be limited to 5 % at high speeds (> 90 % speed) by the internal power limit of the
                       drive. The limitation also depends on motor characteristics and network voltage.
                 **
                       Overload may be limited to 40 % at high speeds (> 90 % speed) by the internal power limit of the
                       drive. The limitation also depends on motor characteristics and network voltage.
                 ***
                       special 4-pole high-efficiency NEMA motor
            Symbols
                 Nominal ratings
                 Imax      maximum output current. Available for 10 s at start, otherwise as long as allowed by drive
                           temperature.
                 Normal use (10 % overload capability)
                 I2N       continuous rms current. 10 % overload is typically allowed for one minute every 5 minutes.
                 PN        typical motor power. The power ratings apply to most 4-pole NEMA rated motors (230 V,
                           460 V or 575 V).
                 Heavy-duty use (50 % overload capability)
                 I2hd      continuous rms current. 50 % overload is typically allowed for one minute every 5 minutes.
                 Phd       typical motor power. The power ratings apply to most 4-pole NEMA rated motors (230 V,
                           460 V or 575 V).
                 Note 1: The ratings apply in ambient temperature of 40 °C (104 °F). In lower temperatures the ratings
                 are higher (except Imax).
Technical data
                                                                                               91
                                                                                    Technical data
92
            Cable types
                 Cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire insulation at 40 °C
                 (104 °F) ambient temperature. Not more than three current-carrying conductors in raceway or cable or
                 earth (directly buried). For other conditions, dimension the cables according to local safety regulations,
                 appropriate input voltage and the load current of the drive.
            Cable Entries
                 Brake resistor, input and motor cable (per phase) terminal sizes, accepted cable
                 diameters and tightening torques are given below.
                 Frame                 U1, V1, W1, U2, V2, W2, R+, R-                             Earthing PE
                 size         Maximum wire         Wire Ø          Tightening             Maximum         Tightening
                                  size          (UL type 1)          torque               wire size         torque
                                  AWG                in.               lbf ft               AWG              lbf ft
                 R2                 6                0.8            0.9…1.1                   8               1.1
                 R3                 6                0.8             0.9...1.1                8               1.1
                 R4                 4               1.14            1.5…3.0                   5               2.2
                 R5                2/0              1.39               11.1                  2/0             11.1
                 R6             350 MCM             2.09           14.8...29.5               4/0              5.9
Technical data
                                                                                                                       93
        UL/CSA markings
                Units of UL type 1 are UL and CSA marked. The UL and CSA markings are pending for units of UL type
                12.
        UL
                The drive is suitable for use on a circuit capable of delivering not more than 65 kA rms symmetrical
                amperes at the drive nominal voltage (600 V maximum for 690 V units).
                The drive provides overload protection in accordance with the National Electrical Code (US). See
                ACS 800 Firmware Manual for setting. Default setting is off, must be activated at start-up.
                The drives are to be used in a heated indoor controlled environment. See section Ambient conditions
                for specific limits.
                Brake chopper - ABB has brake choppers that, when applied with appropriately sized brake resistors,
                will allow the drive to dissipate regenerative energy (normally associated with quickly decelerating a
                motor). Proper application of the brake chopper is defined in chapter Resistor braking. This can be
                applied to a single drive or multiple drives with DC bus connected to allow a sharing of regenerative
                energy.
                                                                                                       Technical data
94
Technical data
                                                                                 95
Dimensional drawings
                                                                Dimensional drawings
96
64646117-B
Dimensional drawings
                                          97
64646150-B
                        Dimensional drawings
98
64646192-B
Dimensional drawings
                                          99
64646206-C
                        Dimensional drawings
100
64646214-B
Dimensional drawings
                                         101
64647130-B
                        Dimensional drawings
102
64646222-B
Dimensional drawings
                                         103
64647156-B
                        Dimensional drawings
104
64646231-B
Dimensional drawings
                                         105
64684957-C
                        Dimensional drawings
106
64788051-A
Dimensional drawings
                                              107
64788078-A
                             Dimensional drawings
108
64788086-A
Dimensional drawings
                                              109
64788094-A
                             Dimensional drawings
110
64788108-A
Dimensional drawings
                                                                                                                 111
Resistor braking
              where
              Pbr       denotes Pbr5, Pbr10, Pbr30, Pbr60, or Pbrcont depending on the duty cycle.
           3. Check the resistor selection. The energy generated by the motor during a 400-
              second period must not exceed the resistor heat dissipation capacity ER.
              If the ER value is not sufficient, it is possible to use a four-resistor assembly in which two standard
              resistors are connected in parallel, two in series. The ER value of the four-resistor assembly is four
              times the value specified for the standard resistor.
                                                                                                  Resistor braking
112
                    Note: A resistor other than the standard resistor can be used provided that:
                    • its resistance is not lower than the resistance of the standard resistor.
                    WARNING! Never use a brake resistor with a resistance below the value specified
                    for the particular drive / brake chopper / resistor combination. The drive and the
                    chopper are not able to handle the overcurrent caused by the low resistance.
                    • the resistance does not restrict the braking capacity needed, i.e.,
                                                 2
                                           UDC
                                 Pmax <
                                            R
                         where
                          Pmax       maximum power generated by the motor during braking
                          UDC        voltage over the resistor during braking, e.g.,
                                     1.35 · 1.2 · 415 VDC (when supply voltage is 380 to 415 VAC),
                                     1.35 · 1.2 · 500 VDC. (when supply voltage is 440 to 500 VAC) or
                                     1.35 · 1.2 · 690 VDC (when supply voltage is 525 to 690 VAC).
                          R          resistor resistance (ohm)
                    • the heat dissipation capacity (ER) is sufficient for the application (see step 3
                      above).
Resistor braking
                                                                                                                                         113
Pbrcont The drive and the chopper will withstand this continuous braking power. The braking is considered continuous if the braking time
        exceeds 30 s.
        Note: The braking energy transmitted to the specified resistor(s) in 400 seconds may not exceed ER.
R       Resistance value for the listed resistor assembly. Note: This is also the minimum allowed resistance for the braking resistor.
ER      Short energy pulse that the resistor assembly withstands every 400 seconds. This energy will heat the resistor element from 40 °C
        (104 °F) to the maximum allowable temperature.
PRcont Continuous power (heat) dissipation of the resistor when placed correctly. Energy ER dissipates in 400 seconds.
All braking resistors must be installed outside the converter module. The SACE braking resistors are built in an IP 21 metal housing. The
SAFUR braking resistors are built in an IP 00 metal frame.
                                                                                                                       Resistor braking
114
Pbr5      Maximum braking power of the drive with the specified resistor(s). The drive and the chopper will withstand this braking power for
          5 seconds per minute.
Pbr10     The drive and the chopper will withstand this braking power for 10 seconds per minute.
Pbr30     The drive and the chopper will withstand this braking power for 30 seconds per minute.
Pbrcont The drive and the chopper will withstand this continuous braking power. The braking is considered continuous if the braking time
        exceeds 30 s.
Note: Check that the braking energy transmitted to the specified resistor(s) in 400 seconds does not exceed ER.
Resistor braking
                                                                                                                                            115
R        Resistance value for the resistor assembly. Note: This is also the minimum allowed resistance for the braking resistor.
ER       Short energy pulse that the resistor assembly withstands every 400 seconds. This energy will heat the resistor element from
         40 °C (104 °F) to the maximum allowable temperature.
PRcont Continuous power (heat) dissipation of the resistor when placed correctly. Energy ER dissipates in 400 seconds.
                Pbr5 or Pbr10
                        Pbr30
Pbrcont
                   No braking                                                                                                       t
                                  min. 30 s max 30 s   min. 30 s   max 30 s               min. 30 s
• After Pbr5, Pbr10 or Pbr30 braking, the drive and the chopper will withstand Pbrcont continuously.
• Pbr5, Pbr10 or Pbr30 braking is allowed once every minute.
• After Pbrcont braking, there has to be at least 30 seconds without any braking if the subsequent braking power is greater than Pbrcont.
• After Pbr5 or Pbr10 braking, the drive and the chopper will withstand Pbr30 within a total braking time of 30 seconds.
• Pbr10 braking is not acceptable after Pbr5 braking.
Combined braking cycles for R8:
     Examples
                           Pbr                             max 5 s, 10 s or 30 s
Pbrcont
                   No braking                                                                                                           t
                                       min. 60 s                                                        min. 60 s
• After Pbr5, Pbr10 or Pbr30 braking, the drive and the chopper will withstand Pbrcont continuously. (Pbrcont is the only allowed braking power
  after Pbr5, Pbr10 or Pbr30.)
• Pbr5, Pbr10 or Pbr30 braking is allowed once every minute.
• After Pbrcont braking, there has to be at least 60 seconds without any braking if the subsequent braking power is greater than Pbrcont.
All braking resistors must be installed outside the converter module. The resistors are built in an IP 00 metal frame. The 2xSAFUR and
4xSAFUR resistors are connected in parallel.
                                                                                                                           Resistor braking
116
                   WARNING! The materials near the brake resistor must be non-flammable. The
                   surface temperature of the resistor is high. Air flowing from the resistor is of
                   hundreds of degrees Celsius. Protect the resistor against contact.
                   Use the cable type used for drive input cabling (refer to chapter Technical Data) to
                   ensure the input fuses will also protect the resistor cable. Alternatively, two-
                   conductor shielded cable with the same cross-sectional area can be used. The
                   maximum length of the resistor cable(s) is 10 m (33 ft). For the connections, see the
                   power connection diagram of the drive.
            ACS800-07/U7
                   If ordered, the resistors are factory installed in a cubicle(s) next to the drive cabinet .
L1 L2 L3
                                               OFF
                        Fuses                             2
1 3 5 13 3
                                                                   ON
                                2    4    6               14                   4
                      ACS 800
                                U1 V1 W1
K1
Resistor braking
                                                                                               117
           For other application programs, the thermal switch may be wired to a different digital
           input. Programming of the input to trip the drive by “EXTERNAL FAULT” may be
           needed. See the appropriate firmware manual.
           WARNING! If the drive is equipped with a brake chopper but the chopper is not
           enabled by parameter setting, the brake resistor must be disconnected because the
           protection against resistor overheating is then not in use.
                                                                                  Resistor braking
118
For settings of other application programs, see the appropriate firmware manual.
Resistor braking
                                                                                             119
When to use
           External +24 V power supply for the RMIO board is recommended if
           • the application requires fast start after connecting the input power supply
           • fieldbus communication is required when the input power supply is disconnected.
           For current consumption of the RMIO board, see chapter Motor Control and I/O
           Board (RMIO).
Parameter settings
           In Standard Application Program, set parameter 16.9 CTRL BOARD SUPPLY to
           EXTERNAL 24V if the RMIO board is powered from an external supply.
                                                                                         4
                                                                                              4
                                                     3
5 6 7