106M5801K Diagramas de Conexionado 2300
106M5801K Diagramas de Conexionado 2300
REVISION
ZONE REV DESCRIPTION NAME APPROVED
D D
105 106
C 105
C
104 BASE MUST BE MOUNTED AS SHOWN RELATIVE TO GRAVITY. NO CHANGES TO THIS DRAWING WITHOUT
APPROVAL OF THE APPROVALS AGENCIES.
103. MECHANICAL VIBRATION SHALL NOT EXCEED 5g @ 57-500Hz. UNCONTROLLED WHEN PRINTED OR TRANSMITTED ELECTRONICALLY.
ANGULAR ±
2300 VIBRATION MONITOR
FRACTIONAL ± FIELD WIRING DIAGRAM
101. DIAGRAM IS FOR THE 2300 MONITOR SYSTEMS. DECIMAL .XX= ±
.XXX= ±
0.02
0.010
SEE SHEET 1
TABLE 2A
RELAY OUTPUT WIRING CHART
2300 CONTACT DESCRIPTION
NO1 RELAY 1 - NORMALLY OPEN
ARM RELAY 1 - COM
D NC1 RELAY 1 - NORMALLY CLOSE D
NO2 RELAY 2 - NORMALLY OPEN
ARM RELAY 2 - COM
NC2 RELAY 2 - NORMALLY CLOSE
TABLE 2B
CONTACT INPUT WIRING CHART
2300 CONTACT DESCRIPTION
1S CONFIG LOCK
1C COM
CHASSIS
3S ALARM INHIBIT
3C COM
2S ALARM RESET
2C COM
C CHASSIS
CHASSIS
C
CHASSIS
TABLE 2C
POWER INPUT WIRING CHART
2300 CONTACT DESCRIPTION
+ DC 24V +
- DC 24V COM
CHASSIS
TABLE 2D (2300/20)
ANALOG OUTPUT WIRING CHART
B 2300 CONTACT DESCRIPTION
SHD SHIELD
B
R1+ RECORDER 1
R1- RECORDER 1 - COM
R2+ RECORDER 2
R2- RECORDER 2 - COM
SHD SHIELD
TABLE 2D (2300/25)
SPA CONNECTION WIRING CHART
2300 CONTACT DESCRIPTION
S SHIELD
R POWER
B COM
W SIGNAL -
A G SIGNAL + A
S SHIELD
R POWER
B COM
W SIGNAL -
G SIGNAL + CAGE CODE SIZE DWG NO.
201. TERMINAL DEFINITION
3WAP1 D 106M5801
NOTES: SEE SHEET 1 (UNLESS OTHERWISE SPECIFIED) PLOT SCALE NONE SHEET 2 OF 11
8 7 6 5 4 3
CDA/106M5801/000/09
2 1
8 7 6 5 4 3 2 1
REVISION
SEE SHEET 1
D TABLE 3E D
INPUT CHANNEL WIRING CHART
2300 CONTACT DESCRIPTION
CHASSIS
COM CHANNEL 1 COM
SIG CHANNEL 1 SIGNAL
PWR CHANNEL 1 POWER
+ CHANNEL 1 A/+
- CHANNEL 1 B/-
CHASSIS
COM CHANNEL 2 COM
SIG CHANNEL 2 SIGNAL
PWR CHANNEL 2 POWER
+ CHANNEL 2 A/+
- CHANNEL 2 B/-
CHASSIS
KCM KPH COM
C KSG KPH SIGNAL
C
KPW KPH POWER
B B
0.25
NOT TO EXCEED
2 INCHES
A A
8 7 6 5 4 3
CDA/106M5801/000/09
2 1
8 7 6 5 4 3 2 1
REVISION
SEE SHEET 1
SAFE AREA
OR ZONE 2 ZONE 0
D OR CLASS I DIV 2 OR CLASS 1, DIV I D
OR CLASS I ZONE2 OR CLASS1, ZONE 0
VT (-24 Vdc)
COM
OUT
CUST ID:
MADE IN U.S.A.
C WARNING!
C
IMPROPER GROUNDING OF SIGNAL COMMON 3300XL 8mm PROXIMITOR SHOWN.
COULD CAUSE EXPLOSION OR FIRE IN THE DIAGRAM ALSO APPLIES TO PART
HAZARDOUS AREA, RESULTING IN PERSONAL NUMBERS AS SHOWN IN TABLE 4B.
INJURY OR DEATH.COMMON MUST BE
CONNECTED TO EARTH GROUND AT THE
BARRIER RAIL.
TABLE 4B
TABLE 4A
TRANSDUCERS AREA TYPE
PROXIMITOR MODULE WIRING CHART
3300XL 8MM PRODUCT
2300 CONTACT PROXIMITOR MODULE CONTACT CERTIFICATIONS TO BE
3300XL NSV
KPW VT VERIFIED FOR THE
B KSG OUT
3300XL 5MM
SPECIFIC LOCATION OF B
PROXPAC XL 330880 INSTALLATION
406 BARRIERS LOCATED IN DIVISION 2 OR ZONE 2 HAZARDOUS KCM COM
AREAS MUST BE INSTALLED IN IP54 APPROVED PROTECTIVE PROXPAC XL 330881
HOUSINGS AND INSTALLED IN ACCORDANCE WITH 3300XL 11MM
MANUFACTURER'S INSTRUCTIONS. FINAL INSTALLATION 3300XL 25MM
TO BE APPROVED BY LOCAL AUTHORITY HAVING JURISDICTION.
8 7 6 5 4 3
CDA/106M5801/000/09
2 1
8 7 6 5 4 3 2 1
REVISION
SEE SHEET 1
TABLE 5A
MTL 7787(-) (SHOWN HERE)
BARRIER BARRIER ACCELEROMETER R
2300 MODULE R 507
SAFE AREA HAZ AREA OR VELOMITOR
D - 1 3 B
D
+ 2 4 A
EARTH RAIL EARTH RAIL SHIELD
P&F Z887
511 BARRIER BARRIER ACCELEROMETER R
2300 MODULE SAFE AREA HAZ AREA OR VELOMITOR
R
- 8 1 B
+ 5 4 A
SHIELD/GND SHIELD/GND SHIELD
SAFE AREA
OR ZONE 2 ZONE 0
OR CLASS I DIV 2 OR CLASS 1, DIV I
OR CLASS I ZONE2 OR CLASS1, ZONE 0
C C
MTL 7787(-) (SHOWN HERE)
506 507
2 4
1 3
505 504
CHANNEL 1
B ACCELEROMETER
R B
505 510
ACCELEROMETER
507 BARRIER RECOMMENDATION: MTL 787(-) (BNC P/N 02204023), P&F Z887, OR EQUIVALENT.
SEE TABLE FOR INFORMATION REGARDING WIRING TO THE BARRIERS. BN PART NUMBER 200350 SHOWN.
THIS DRAWING IS ALSO APPLICABLE
506 BARRIERS LOCATED IN DIVISION 2 OR ZONE 2 HAZARDOUS AREAS MUST BE INSTALLED TO PART NUMBERS AS SHOWN IN T
IN IP54 APPROVED PROTECTIVE HOUSINGS AND INSTALLED IN ACCORDANCE WITH ABLE 5B.
MANUFACTURER'S INSTRUCTIONS. FINAL INSTALLATION TO BE APPROVED BY
LOCAL AUTHORITY HAVING JURISDICTION.
505 BARRIERS ARE MOUNTED TO BARRIER RAIL, WHICH IS THE POTENTIAL EQUALIZATION
BUS BETWEEN SYSTEM GROUND AND EARTH GROUND. TO MINIMIZE GROUND LOOP TABLE 5B
PROBLEMS, A SINGLE POINT EARTH GROUND TO SYSTEM COMMON IS REQUIRED AT
THE BARRIER RAIL. TOTAL EARTH LOOP IMPEDANCE MUST BE LESS THAN 1 OHM. TRANSDUCERS AREA TYPE
OPEN THE JUMPER ON THE GROUND/CHASSIS CONNECTION. (REFER TO PAGE 1, 200350 PRODUCT CERTIFICATIONS TO
NOTE 105). BE VERIFIED FOR THE SPECIFIC
AP3500T2-Z1
504 TRANSDUCER SHIELDS ARE JOINED AS SHOWN TERMINATING AT BARRIER GROUND. LOCATION OF INSTALLATION
190501
SHIELDS SHOULD BE INSULATED. MAXIMUM CHASSIS PIGTAIL MUST NOT
EXCEED 2 INCHES (50.8 MM). 330500
R
511 DELETE. 330505 ACCELEROMETER
503. WHEN INTERFACING TO INTRINSICALLY SAFE APPARATUSES LOCATED
A IN A CLASS I, ZONE2/DIV2 LOCATION, REFER TO THE SAFE
PARAMETERS IN PAGE 11. 510 CONNECT THE GROUND/CHASSIS TERMINAL TO THE BARRIER RAIL.
330525 TOP VIEW A
502. WIRING RECOMMENDATIONS: 509. WIRING SHIELDS ARE TERMINATED AT THE 2300 TERMINAL
R
2300 TO BARRIERS - BARRIERS TO ACCELEROMETER : 16AWG TO 18AWG BLOCK CONTACT MARKED " ". SHIELDS SHOULD BE INSULATED
STRANDED 2-WIRE SHIELDED WITH INSULATING SHEATH. UP TO THE POINT OF CONNECTION.
501. WIRING SHOWN WITH BARRIERS. 508. STRIP WIRE ENDS 0.25 INCH (6.35 MM). MAXIMUM CHASSIS PIGTAIL CAGE CODE SIZE DWG NO.
CONSULT PAGE 7 FOR WIRING WITHOUT BARRIERS. MUST NOT EXCEED 2 INCHES (50.8 MM). SEE PAGE 3. 3WAP1 D 106M5801
NOTES: SEE SHEET 1 (UNLESS OTHERWISE SPECIFIED) PLOT SCALE NONE SHEET 5 OF 11
8 7 6 5 4 3
CDA/106M5801/000/09
2 1
8 7 6 5 4 3 2 1
REVISION
SEE SHEET 1
SAFE AREA
D OR ZONE 2 D
OR CLASS I DIV 2
OR CLASS I ZONE2
C C
VT (-24 Vdc)
COM
OUT
CUST ID:
MADE IN U.S.A.
TABLE 6A TABLE 6B
PROXIMITOR MODULE WIRING CHART TRANSDUCERS AREA TYPE
2300 CONTACT PROXIMITOR MODULE CONTACT 3300XL 8MM PRODUCT
KPW VT 3300XL NSV CERTIFICATIONS TO BE
KSG OUT VERIFIED FOR THE
3300XL 5MM
SPECIFIC LOCATION OF
B KCM COM PROXPAC XL 330880 INSTALLATION B
PROXPAC XL 330881
3300XL 11MM
3300XL 25MM
608 DELETE.
607. STRIP WIRE ENDS 0.25 INCH (6.35 MM). MAXIMUM CHASSIS PIGTAIL
MUST NOT EXCEED 2 INCHES (50.8 MM). SEE PAGE 3.
606. TO MINIMIZE GROUND LOOP NOISE PROBLEMS, A SINGLE POINT
EARTH GROUND TO SYSTEM COMMON IS RECOMMENDED.
CONNECTION IS MADE AT THE TERMINAL BASE, SEE PAGE 1,
NOTE 105.
605 3300XL PROXIMITOR CASE HAS BUILT-IN CASE ISOLATION, AND IS
ELECTRICALLY ISOLATED FROM EARTH GROUND.
604 WIRING SHIELDS ARE TERMINATED AT THE 2300 TERMINAL BLOCK CONTACT
MARKED " " ONLY AND LEFT FLOATING AT THE PROXIMITOR/PROXPAC
END. SHIELDS SHOULD BE INSULATED UP TO THE POINT OF CONNECTION.
603. MAXIMUM CABLE LENGTH BETWEEN 2300 AND PROXPAC MUST
A NOT EXCEED 1000 FEET (305 METERS). A
602. WIRING RECOMMENDATIONS: 610. REFER TO THE ENTITY PARAMETERS ON PAGE 11.
SINGLE CABLE ASSEMBLY, STRANDED 3-WIRE 16 TO 24 AWG
WITH 100% SHIELD COVERAGE AND INSULATING SHEATH.
609. WHEN INTERFACING TO INTRINSICALLY SAFE
601. WIRING SHOWN WITHOUT BARRIERS. APPARATUSES LOCATED IN A CLASS I, ZONE2/DIV2
CONSULT PAGE 4 FOR WIRING WITH BARRIERS. LOCATION, REFER TO THE SAFE PARAMETERS IN PAGE 11. CAGE CODE SIZE DWG NO.
3WAP1 D 106M5801
NOTES: SEE SHEET 1 (UNLESS OTHERWISE SPECIFIED) PLOT SCALE NONE SHEET 6 OF 11
8 7 6 5 4 CDA/106M5801/000/09
3 2 1
8 7 6 5 4 3 2 1
REVISION
SEE SHEET 1
SAFE AREA
OR ZONE 2
D OR CLASS I DIV 2 D
OR CLASS I ZONE2
TABLE 7A TABLE 7B
ACCELEROMETER OR VELOMITOR TRANSDUCERS AREA TYPE
AM3100T2-Z2 PRODUCT
WIRING CHART CERTIFICATIONS TO BE
TP100
R R VERIFIED FOR THE
2300 MODULE ACCELEROMETER OR VELOMITOR TP500
SPECIFIC LOCATION OF
703 200350 INSTALLATION
- B
AP3500T2-Z1
+ A
AS3100S2-Z2
SHIELD 190501
330500
C 330505 C
330525
B CHANNEL 1 B
ACCELEROMETER R
705. STRIP WIRE ENDS 0.25 INCH (6.35 MM). MAXIMUM CHASSIS PIGTAIL
MUST NOT EXCEED 2 INCHES (50.8 MM). SEE PAGE 3.
704. TO MINIMIZE GROUND LOOP NOISE PROBLEMS, A SINGLE POINT
EARTH GROUND TO SYSTEM COMMON IS RECOMMENDED.
CONNECTION IS MADE AT THE CHASSIS, SEE PAGE 1, NOTE 105.
703 WIRING SHIELDS ARE TERMINATED AT THE 2300 TERMINAL
BLOCK CONTACT MARKED " ". SHIELDS SHOULD BE INSULATED A B
A UP TO THE POINT OF CONNECTION. MAXIMUM CHASSIS PIGTAIL
MUST NOT EXCEED 2 INCHES (50.8 MM).
A
702. WIRING RECOMMENDATIONS:
SINGLE CABLE ASSEMBLY, STRANDED 2-WIRE 16 TO 24 AWG
WITH 100% SHIELD COVERAGE AND INSULATING SHEATH. ACCELEROMETER R
TOP VIEW
701. WIRING SHOWN WITHOUT BARRIERS. CAGE CODE SIZE DWG NO.
CONSULT PAGE 5 FOR WIRING WITH BARRIERS. 3WAP1 D 106M5801
NOTES: SEE SHEET 1 (UNLESS OTHERWISE SPECIFIED) PLOT SCALE NONE SHEET 7 OF 11
8 7 6 5 4 3
CDA/106M5801/000/09
2 1
8 7 6 5 4 3 2 1
REVISION
SEE SHEET 1
SAFE AREA
OR ZONE 2
OR CLASS I DIV 2
D OR CLASS I ZONE2 D
803
C C
804
B B
3WAP1 D 106M5801
NOTES: SEE SHEET 1 (UNLESS OTHERWISE SPECIFIED) PLOT SCALE NONE SHEET 8 OF 11
8 7 6 5 4 3
CDA/106M5801/000/09
2 1
8 7 6 5 4 3 2 1
REVISION
SEE SHEET 1
SAFE AREA
OR ZONE 2
D OR CLASS I DIV 2 D
OR CLASS I ZONE2
C PROXIMITY SWITCH C
BN PART NUMBER 100M0741 SHOWN
B B
906 DELETE.
905. STRIP WIRE ENDS 0.25 INCH (6.35 MM). MAXIMUM CHASSIS PIGTAIL
MUST NOT EXCEED 2 INCHES (50.8 MM). SEE PAGE 3. TABLE 9A
904. TO MINIMIZE GROUND LOOP NOISE PROBLEMS, A SINGLE POINT PROXIMITY SWITCH WIRING CHART
EARTH GROUND TO SYSTEM COMMON IS RECOMMENDED. PROXIMITY SWITCH LEAD COLOR
CONNECTION IS MADE AT THE CHASSIS, SEE PAGE 1, NOTE 105. 2300 CONTACT
KCM BROWN
903. WIRING SHIELDS ARE TERMINATED AT THE 2300 TERMINAL KSG BLACK
BLOCK CONTACT MARKED " ". SHIELDS SHOULD BE INSULATED
A UP TO THE POINT OF CONNECTION.MAXIMUM CHASSIS PIGTAIL KPW BLUE A
MUST NOT EXCEED 2 INCHES (50.8 MM).
902. WHEN INTERFACING TO INTRINSICALLY SAFE APPARATUSES
LOCATED IN A CLASS I, DIV2 LOCATION, REFER TO THE
SAFE PARAMETERS IN PAGE 11.
901. WIRING SHOWN WITHOUT BARRIERS. CAGE CODE SIZE DWG NO.
3WAP1 D 106M5801
NOTES: SEE SHEET 1 (UNLESS OTHERWISE SPECIFIED) PLOT SCALE NONE SHEET 9 OF 11
8 7 6 5 4 3
CDA/106M5801/000/09
2 1
8 7 6 5 4 3 2 1
REVISION
SEE SHEET 1
SAFE AREA
OR ZONE 2
OR CLASS I DIV 2
D OR CLASS I ZONE2 D
1003
TABLE 10A (2300/20) TABLE 10B (2300/25)
1003
ANALOG OUTPUT WIRING CHART SPA LINE CONNECTION WIRING CHART
2300 CONTACT DESCRIPTION 2300 CONTACT WIRE (P/N 85033) DESCRIPTION
SHD SHIELD S SHLD SHIELD
R1+ RECORDER 1 R RED POWER
R1- RECORDER 1 - COM B BLACK COM
W WHITE SIGNAL -
C R2+
R2-
RECORDER 2
RECORDER 2 - COM G GREEN SIGNAL +
C
SHD SHIELD 1004 S SHLD SHIELD
R RED POWER
B BLACK COM
W WHITE SIGNAL -
1004
G GREEN SIGNAL +
1004 1004
1001
B 1005
B
3WAP1 D 106M5801
NOTES: SEE SHEET 1 (UNLESS OTHERWISE SPECIFIED) PLOT SCALE NONE SHEET 10 OF 11
8 7 6 5 4 3
CDA/106M5801/000/09
2 1
8 7 6 5 4 3 2 1
REVISION
SEE SHEET 1
1. THE SYSTEM COULD BE INSTALLED IN A SAFE AREA (UNCLASSIFIED) AND THIS WOULD STILL BE APPLICABLE TO INTERFACING WITH EQUIPMENT
IN DIV. 2 / ZONE 2 AREA.
THE FIELD WIRING MUST MEET THE FOLLOWING INTRINSICALLY SAFE PARAMETERS
2. WARNING
WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON-HAZARDOUS;
and
AVERTISSEMENT-RISQUE D'EXPLOSION-AVANT DE DÉCONNECTER L'EQUIPEMENT, COUPER LE COURANT OU S'ASSURER QUE L'EMPLACEMENT EST DÉSIGNÉ NON DAN-GEREUX.
WARNING - EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2;
and
AVERTISSEMENT-RISQUE D'EXPLOSION-LA SUBSTITUTION DECOMPOSANTS PEUT RENDRE CE MATÉRIEL INACCEPTABLE POUR LES EMPLACEMENTS DE CLASSE I, DIVISION 2.
B B
WARNING -HAZARDOUS VOLTAGE MAY BE PRESENT ON RELAY CONTACT WIRING. DO NOT SERVICE UNLESS RELAY CONNECTION WIRING IS DE-ENERGIZED.
AND
AVERTISSEMENT-DES TENSIONS ÉLEVÉES PEUVENT ÊTRE PRÉSENTES SUR LE CÂBLAGE DU RELAIS À CONTACT. NE PAS FAIRE DE MAINTENANCE SAUF SI LE CÂBLAGE DE CONNEXION
DU RELAIS EST HORS TENSION.
3WAP1 D 106M5801
NOTES: SEE SHEET 1 (UNLESS OTHERWISE SPECIFIED) PLOT SCALE NONE SHEET 11 OF 11
8 7 6 5 4 3
CDA/106M5801/000/09