IEEE 1591.2-2017 Standard
IEEE 1591.2-2017 Standard
Sponsored by the
Power System Communications Committee
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2™-2017
Sponsor
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
Abstract: Hardware performance, test requirements, procedures, and acceptance criteria for an all-
dielectric self-supporting overhead cable with optical fibers are covered in this standard. Functional
requirements, such as electrical, mechanical, optical fiber, environmental and test requirements
related to design, installation, in-service, and maintenance, including routine tests, are covered.
Keywords: ADSS, all-dielectric self-supporting fiber optic cable, fiber optic cable, IEEE 1591.2™,
laboratory tests, maximum installation tension, maximum rated cable load, maximum rated design
tension
IEEE is a registered trademark in the U.S. Patent & Trademark Office, owned by the Institute of Electrical and Electronics Engineers,
Incorporated.
National Electrical Safety Code and NESC are registered trademarks and service marks of the Institute of Electrical and Electronics
Engineers, Incorporated.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
Important Notices and Disclaimers Concerning IEEE Standards Documents
IEEE documents are made available for use subject to important notices and legal disclaimers. These notices
and disclaimers, or a reference to this page, appear in all standards and may be found under the heading
“Important Notices and Disclaimers Concerning IEEE Standards Documents.” They can also be obtained on
request from IEEE or viewed at http://standards.ieee.org/IPR/disclaimers.html.
IEEE Standards do not guarantee or ensure safety, security, health, or environmental protection, or ensure
against interference with or from other devices or networks. Implementers and users of IEEE Standards
documents are responsible for determining and complying with all appropriate safety, security, environmental,
health, and interference protection practices and all applicable laws and regulations.
IEEE does not warrant or represent the accuracy or content of the material contained in its standards, and
expressly disclaims all warranties (express, implied and statutory) not included in this or any other document
relating to the standard, including, but not limited to, the warranties of: merchantability; fitness for a particular
purpose; non-infringement; and quality, accuracy, effectiveness, currency, or completeness of material. In
addition, IEEE disclaims any and all conditions relating to: results; and workmanlike effort. IEEE standards
documents are supplied “AS IS” and “WITH ALL FAULTS.”
Use of an IEEE standard is wholly voluntary. The existence of an IEEE standard does not imply that there
are no other ways to produce, test, measure, purchase, market, or provide other goods and services related to
the scope of the IEEE standard. Furthermore, the viewpoint expressed at the time a standard is approved and
issued is subject to change brought about through developments in the state of the art and comments received
from users of the standard.
In publishing and making its standards available, IEEE is not suggesting or rendering professional or other
services for, or on behalf of, any person or entity nor is IEEE undertaking to perform any duty owed by any
other person or entity to another. Any person utilizing any IEEE Standards document, should rely upon his or
her own independent judgment in the exercise of reasonable care in any given circumstances or, as appropriate,
seek the advice of a competent professional in determining the appropriateness of a given IEEE standard.
IN NO EVENT SHALL IEEE BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL,
EXEMPLARY, OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO:
PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS;
OR BUSINESS INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY,
WHETHER IN CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR
OTHERWISE) ARISING IN ANY WAY OUT OF THE PUBLICATION, USE OF, OR RELIANCE
UPON ANY STANDARD, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE AND
REGARDLESS OF WHETHER SUCH DAMAGE WAS FORESEEABLE.
3
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
Translations
The IEEE consensus development process involves the review of documents in English only. In the event that
an IEEE standard is translated, only the English version published by IEEE should be considered the approved
IEEE standard.
Official statements
A statement, written or oral, that is not processed in accordance with the IEEE-SA Standards Board Operations
Manual shall not be considered or inferred to be the official position of IEEE or any of its committees and shall
not be considered to be, or be relied upon as, a formal position of IEEE. At lectures, symposia, seminars, or
educational courses, an individual presenting information on IEEE standards shall make it clear that his or her
views should be considered the personal views of that individual rather than the formal position of IEEE.
Comments on standards
Comments for revision of IEEE Standards documents are welcome from any interested party, regardless
of membership affiliation with IEEE. However, IEEE does not provide consulting information or advice
pertaining to IEEE Standards documents. Suggestions for changes in documents should be in the form of a
proposed change of text, together with appropriate supporting comments. Since IEEE standards represent a
consensus of concerned interests, it is important that any responses to comments and questions also receive
the concurrence of a balance of interests. For this reason, IEEE and the members of its societies and Standards
Coordinating Committees are not able to provide an instant response to comments or questions except in
those cases where the matter has previously been addressed. For the same reason, IEEE does not respond to
interpretation requests. Any person who would like to participate in revisions to an IEEE standard is welcome
to join the relevant IEEE working group.
Copyrights
IEEE draft and approved standards are copyrighted by IEEE under U.S. and international copyright laws. They
are made available by IEEE and are adopted for a wide variety of both public and private uses. These include
both use, by reference, in laws and regulations, and use in private self-regulation, standardization, and the
promotion of engineering practices and methods. By making these documents available for use and adoption
by public authorities and private users, IEEE does not waive any rights in copyright to the documents.
4
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
Photocopies
Subject to payment of the appropriate fee, IEEE will grant users a limited, non-exclusive license to photocopy
portions of any individual standard for company or organizational internal use or individual, non-commercial
use only. To arrange for payment of licensing fees, please contact Copyright Clearance Center, Customer
Service, 222 Rosewood Drive, Danvers, MA 01923 USA; +1 978 750 8400. Permission to photocopy portions
of any individual standard for educational classroom use can also be obtained through the Copyright Clearance
Center.
Users of IEEE Standards documents should be aware that these documents may be superseded at any time
by the issuance of new editions or may be amended from time to time through the issuance of amendments,
corrigenda, or errata. An official IEEE document at any point in time consists of the current edition of the
document together with any amendments, corrigenda, or errata then in effect.
Every IEEE standard is subjected to review at least every ten years. When a document is more than ten years
old and has not undergone a revision process, it is reasonable to conclude that its contents, although still of
some value, do not wholly reflect the present state of the art. Users are cautioned to check to determine that
they have the latest edition of any IEEE standard.
In order to determine whether a given document is the current edition and whether it has been amended
through the issuance of amendments, corrigenda, or errata, visit the IEEE Xplore at http://ieeexplore.ieee.org/
or contact IEEE at the address listed previously. For more information about the IEEE-SA or IEEE’s standards
development process, visit the IEEE-SA Website at http://standards.ieee.org.
Errata
Errata, if any, for all IEEE standards can be accessed on the IEEE-SA Website at the following URL: http://
standards.ieee.org/findstds/errata/index.html. Users are encouraged to check this URL for errata periodically.
Patents
Attention is called to the possibility that implementation of this standard may require use of subject matter
covered by patent rights. By publication of this standard, no position is taken by the IEEE with respect to the
existence or validity of any patent rights in connection therewith. If a patent holder or patent applicant has
filed a statement of assurance via an Accepted Letter of Assurance, then the statement is listed on the IEEE-
SA Website at http://standards.ieee.org/about/sasb/patcom/patents.html. Letters of Assurance may indicate
whether the Submitter is willing or unwilling to grant licenses under patent rights without compensation
or under reasonable rates, with reasonable terms and conditions that are demonstrably free of any unfair
discrimination to applicants desiring to obtain such licenses.
Essential Patent Claims may exist for which a Letter of Assurance has not been received. The IEEE is not
responsible for identifying Essential Patent Claims for which a license may be required, for conducting inquiries
into the legal validity or scope of Patents Claims, or determining whether any licensing terms or conditions
provided in connection with submission of a Letter of Assurance, if any, or in any licensing agreements are
reasonable or non-discriminatory. Users of this standard are expressly advised that determination of the
validity of any patent rights, and the risk of infringement of such rights, is entirely their own responsibility.
Further information may be obtained from the IEEE Standards Association.
5
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
Participants
At the time this standard was submitted to the IEEE-SA Standards Board for approval, the Fiber Optics
Standards Working Group had the following membership:
The following members of the individual balloting committee voted on this standard. Balloters may have
voted for approval, disapproval, or abstention.
When the IEEE-SA Standards Board approved this standard on 14 February 2017, it had the following
membership:
*Member Emeritus
6
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
Introduction
This introduction is not part of IEEE Std 1591.2-2017, IEEE Standard for Testing and Performance of Hardware for All-
Dielectric Self-Supporting (ADSS) Fiber Optic Cable.
IEEE Std 1591.2 is the hardware test standard for all-dielectric self-supporting (ADSS) fiber optic cable
applications. Hardware for ADSS is identified as hardware in direct contact with the ADSS cable in an ADSS
cable and hardware system. This test standard provides standardization of terminology, performance, and test
requirements for ADSS hardware. This hardware standard compliments IEEE Std 1222™ 1 for ADSS cable, as
many of the terms and tests requirements are common for consistency and testing efficiency.
Acknowledgments
Table 5 reproduction of information with permission from the International Electrotechnical Commission
(IEC). The author thanks the IEC for permission to reproduce information from its International Standard IEC
61897 ed.1.0 (1998). All such extracts are copyright of IEC, Geneva, Switzerland. All rights reserved. Further
information on the IEC is available from www.iec.ch. IEC has no responsibility for the placement and context
in which the extracts and contents are reproduced by the author, nor is IEC in any way responsible for the other
content or accuracy therein.
1
Information on references can be found in Clause 2.
7
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
Contents
1. Overview ..................................................................................................................................................... 9
1.1 Scope .................................................................................................................................................... 9
1.2 Purpose ................................................................................................................................................. 9
5. Tests .......................................................................................................................................................... 17
5.1 Classification of tests .......................................................................................................................... 17
5.2 General guidelines for optical measurements ..................................................................................... 17
5.3 Retesting............................................................................................................................................. 21
5.4 Sample selection for hardware characteristics tests ............................................................................ 21
5.5 Qualification tests ............................................................................................................................... 22
8
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Standard for Testing and
Performance of Hardware for
All-Dielectric Self-Supporting (ADSS)
Fiber Optic Cable
1. Overview
1.1 Scope
This standard covers the construction, mechanical and electrical performance, test requirements,
environmental considerations, and acceptance criteria for qualifying hardware for use with all-dielectric self-
supporting (ADSS) fiber optic cable.
1.2 Purpose
The purpose of this standard is to establish performance and testing specifications for hardware used on ADSS
systems in order to standardize testing, simplify procurement specifications, and assure product quality.
ASTM A153/A153M, Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware.2
ASTM B117, Standard Practice for Operating Salt Spray (Fog) Apparatus.
IEC 61897, Overhead Lines—Requirements and Tests for Stockbridge Type Aeolian Vibration Dampers.3
IEEE Std 664™, IEEE Guide for Laboratory Measurement of the Power Dissipation Characteristics of
Aeolian Vibration Dampers for Single Conductors.4,5
2
ASTM publications are available from the American Society for Testing and Materials (http://www.astm.org/).
3
IEC publications are available from the International Electrotechnical Commission (http://www.iec.ch) and the American National
Standards Institute (http://www.ansi.org/).
4
IEEE publications are available from the Institute of Electrical and Electronics Engineers (http://standards.ieee.org/).
5
The IEEE standards or products referred to in Clause 2 are trademarks owned by the Institute of Electrical and Electronics Engineers,
Incorporated.
9
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
IEEE Std 1222™, IEEE Standard for Testing and Performance for All-Dielectric Self-Supporting (ADSS)
Fiber Optic Cable for Use on Electric Utility Power Lines.
ISO 1461, Hot dip galvanized coatings on fabricated iron and steel articles—Specifications and test methods.6
breaking strength: The calculated maximum tensile load that the cable is estimated to reach upon mechanical
failure. Mechanical failure is primarily associated with the cable strength member however other cable
components may contribute to the overall strength. The maximum rated cable load is typically less than 60%
of the breaking strength. Syn: breaking tension.
every day tension (EDT): The final tension with no ice and no wind at the average annual mean temperature
throughout the year. This temperature is assumed as 16 °C (60 °F). This number is often used in specifying
motion control devices such as vibration dampers.
hardware: Attachments or fittings that are in direct contact with the cable.
maximum hardware safety tension (MHST): This is the maximum hardware tension rating for dead-end
hardware to hold all-dielectric self-supporting cable that can exceed the cable maximum rated cable load
(MRCL) rating. Maximum hardware safety tension is greater than the maximum loaded tension (MLT) or
MRCL and may approach the cable estimated breaking strength. If the hardware tension rating is less than or
equal to the cable MRCL then the MLT terminology is used.
maximum installation tension (MIT): This is the initial tension at which the cable is pulled during the
sagging portion of the installation process. This tension is used to achieve the appropriate installation sag
defined by the manufacturer relative to conductors, other cables, and the ground. Syn: sagging tension.
NOTE—This is the same as the everyday tension when specified at 16 °C (60 °F).8
maximum loaded tension (MLT): The system tension that represents the tension above maximum installation
tension (MIT) caused by environmental load conditions such as wind and ice. This tension shall not exceed
the cable MRCL or the maximum tension allowed by the hardware (whichever is less). The load is greater
than MIT but less than or equal to maximum rated cable load (MRCL). It is also referred to as maximum
operating tension or short-term load. It may also be referred to as the National Electric Safety Code® (NESC®)
(Accredited Standards Committee C2-2012 [B1]) loaded tension, which corresponds with local regions across
the United States that are referenced in the NESC.
NOTE—For example, the MLT may be used in a case where the MRCL is higher than the expected loading on the cable
(i.e., a stronger cable used than needed) and lower strength hardware is suitable.
6
ISO publications are available from the International Organization for Standardization (http://www.iso.org/) and the American National
Standards Institute (http://www.ansi.org/).
7IEEE Standards Dictionar
y Online is available at http://dictionary.ieee.org.
8
Notes in text, tables, and figures are given for information only and do not contain requirements needed to implement the standard.
10
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
maximum rated cable load (MRCL): This is the maximum tensile load the cable is designed to withstand
during its lifetime without reducing the performance of the optical fibers. This tension rating is determined
by the cable manufacturer and is sometimes referred to as maximum rated design tension by the IEEE or the
maximum allowed tension by the IEC. MRCL may be expressed in terms of tension or as a percentage of
breaking strength. MRCL is typically the load the cable is designed to withstand when the cable is installed in
its maximum specified span length while experiencing the maximum specified weather load. The weather load
or environmental load factors in local wind and ice load.
NOTE—See Figure 1.
optical time domain reflectometer (OTDR): Used to determine the degree and location of attenuation in
optical fibers by transmitting a light source and measuring time of flight and strength of reflected optical signal.
standard jacket: The outer plastic layer or protective sheath of an ADSS cable that is designed for applications
in lower voltage environments. Cables with standard jackets are identified as Class A and are typically installed
in electrical distribution systems.
NOTE—Further information covering the effects on Class A cable from electrical field, space potential, corona, and
pollution can be found in the annexes of IEEE Std 1222-2011.9
stringing tension (STT): The stringing tension, also known as the pulling tension, is defined as the tension
used to pull the cable through sheaves during the stringing portion of the installation process. This should
never be greater than the sagging tension or maximum installation tension.
system: The cable and hardware described in this standard function as an integrated unit.
track resistant jacket: The outer plastic layer or protective sheath of an all-dielectric self-supporting cable
that is designed for applications in higher voltage environments. Cables with track-resistant jackets are
identified as Class B and are typically installed in electrical transmission systems.
NOTE—Further information covering the effects on Class B cable from electrical field stress, space potential, corona, and
pollution can be found in the annexes of IEEE Std 1222-2011.
9
Information on references can be found in Clause 2.
11
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
dry band arcing: When wet pollution on all-dielectric self-supporting cable jacket dries, high resistance dry
bands form. Induced voltage of sufficient magnitude across dry bands will produce an arc that can potentially
damage the jacket.
electric field: The change in space potential over a change in distance. The basic concept is E ≅ dV/ds and
E is a vector that has magnitude and direction. Magnitude is described in units of volts/meter (common
abbreviations are V/m, kV/m, and kV/cm). Direction may be in the form of components such as Ex, Ey, and Ez
or given by unit direction vectors (Ux, Uy, Uz).
induced voltage (Voc): In this document, Voc refers to the induced voltage across a formed dry band in the
absence of an arc, often called “voltage open circuit.”
NOTE—For further information, consult Annex D and Annex E of IEEE Std 1222-2011.
pollution index: This is the exponent of the wet pollution linear resistance in ohms/meter. Example: An index
of 5.7 indicates a resistance of 105.7 or 501 kΩ/m.
NOTE—For further information, consult Annex D and Annex E of IEEE Std 1222-2011.
pollution resistance: The wet pollution resistance on the all-dielectric self-supporting (ADSS) jacket surface
in ohms/meter. This parameter is used to determine currents in the wet pollution layer as well as for computing
dry band arc voltage. These currents and voltages form the basis of the test described in IEEE Std 1222.
NOTE—ADSS cable wet pollution is normally very conductive compared to dry pollution. In general, 108 Ω/m or less is
considered conductive. For further information, consult Annex D and Annex E of IEEE Std 1222-2011.
space potential: A level of voltage in space between energized as well as grounded objects (e.g., conductors
of a high voltage transmission line and tower members). The magnitude is described in units of volts.
Mathematically this is a scalar value. See: electric field.
surface gradient: Defined as the electric field on a surface. Levels near 20 kV/cm are high enough to
breakdown air resulting in corona. See also: electric field.
12
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
System testing is typically conducted to demonstrate hardware and ADSS cable compatibility. This standard
describes the type of test, performance requirements, and acceptance criteria for respective hardware in Clause 5.
Guidelines for optical measurements are established in 5.2. This subclause is referenced in hardware tests that
require optical results as a measure of acceptance.
This standard covers requirements for hardware specifically designed for and in direct contact with ADSS
cable such as dead-ends and suspensions. Conventional hardware fittings that do not come in direct contact
with the cable such as Y-clevis, extension links, yoke plates, etc., are not covered by this standard.10
ADSS hardware design dimension tolerances shall ensure that the product components and interface areas
meet their specified mechanical and electrical requirements.
Suspension and dead-end hardware, some types of vibration damper hardware, and downlead clamps for
ADSS cable are usually designed for a specific (narrow range) size and/or (specific) type of ADSS cable.
Hardware is generally not designed to accommodate a large range of sizes or classes/types of ADSS cable.
Factors that can influence the interaction of the hardware to the ADSS cable interface are as follows:
a) Excessive contact pressure imposed by the hardware can impair the optical signal or cause localized
mechanical damage or stress risers to the ADSS cable.
b) High voltage environments can induce electrical potential differences causing problems such as
tracking or corona. Proper design or application of hardware can mitigate electrically induced damage.
c) Contact between dissimilar materials may cause excessive corrosion in some environments.
d) Hardware surfaces may require coatings or shaping to avoid scoring or cuts into the cable sheath that
may lead to exposure of the underlying aramid strength member.
It is therefore recommended that hardware and other accessories connected electrically and mechanically to
the ADSS cable be compatible with the ADSS cable being used.
4.2.2.1 Dead-ends
13
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
The user may specify higher hardware or holding strength beyond the parameters above for a factor of
safety. This is defined as maximum hardware safety tension (MHST).
— Dead-ends have a provision to transfer cable load to the structure and allow ample distance for cable
minimum bend radius.
— Dead-ends may have a provision for strain relief to protect against long-term fatigue.
— Dead-ends may have a method of mechanical protection to prevent crushing at the cable interface.
— Dead-ends may have a provision for ground connection. (See Annex C for further information.)
— Dead-ends shall be specified for the appropriate ADSS cable jacket application (i.e., standard jacket,
track resistant jacket, or both).
4.2.2.3 Damper
— Dampers are required to damp aeolian vibration—a high frequency, low amplitude cable vibration
induced by laminar wind flow. This type of motion can be detrimental to the life of the system due to
fatigue damage of the cable and/or hardware.
— Methods of mechanical protection may be necessary at the interface to prevent crushing.
— Stockbridge type dampers shall be designed to meet the general requirements of IEC 61897. Stockbridge
damper designs typically include damper weights mounted to messenger wire (stranded cable) that is
secured to a clamp. The damper clamp provides a method of attaching the damper to the ADSS.
— Impact type dampers (also known as spiral type) made from non-metallic materials shall be designed
to survive ultraviolet light exposure and high voltage field conditions. Mitigating the effects of high
electrical field strength can be accomplished with proper damper location (see Annex B). The damper
shall function without causing damage to the ADSS surface. A provision to secure the damper to the
ADSS without damage is required.
14
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
The functions specific to come-along hardware types or sagging tension devices are as follows:
— In high voltage environments, corona suppression devices are applied to cable attachment hardware
in areas susceptible to high electrical stress such as small protrusions or sharp corners. Corona
suppression devices reduce electrical stress to help prevent damage from corona on the ADSS cable.
— Corona suppression devices provide a method of attachment to the cable attachment hardware without
introducing stress risers and/or damage to the cable jacket.
— Downlead clamps train and secure the ADSS along the structure—typically to or from a splice
enclosure.
— Downlead clamps shall be made from a material compatible with ADSS plastic jackets.
— Downlead clamps have provisions to mount to various structures.
The material used in the fabrication of the ADSS hardware shall be selected to provide required durability,
ductility, and compatibility with ADSS cable material for the system’s service life requirements.
In the case of non-metallic material, selection shall be made to withstand degradation due to aging, ultraviolet
radiation, and pollution for the expected range of service temperatures. The materials shall not induce
corrosion in contact with the attachment hardware or cable.
4.3.2 Finish/workmanship
— Castings, forgings, and extrusions shall be uniform, without sharp edges or corners, free of cracks, and
shall not contain defects to the extent that the strength or suitability is affected.
— Holes shall be cylindrical and clean-cut. Holes in plates or terminal pads may be sub-punched and
reamed, drilled, or cast in place. The periphery of the hole shall be free from burrs.
— The finish of all bearing surfaces shall be smooth and contoured and the outer edges and corners shall
be rounded as required. The ADSS hardware shall be free of metal particles, dirt, and oils.
— Aluminum oxide grit used to enhance mechanical holding for certain formed wire hardware is not
considered a contaminant.
— Marking shall provide manufacturing lot traceability for the product.
15
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
Welding shall be in accordance with AWS D1.1 or an equivalent that meets or exceeds this standard. All welds
shall be smooth, uniform, and without overlaps or excessive undercutting. Rough surfaces, scale, slag, and/
or splatter shall be removed by grinding, sanding, or other acceptable practices. Distortions and stresses, if
occurring due to welding, shall be properly corrected. Welders and welding operators shall be qualified in
accordance with AWS D1.1 or an equivalent that meets or exceeds this standard. Proper stress relief methods
shall be employed where necessary.
Adequate corrosion resistant treatment per 4.4 shall be applied to all ferrous materials as agreed upon by
the customer and manufacturer. Special requirements are necessary for threaded fasteners. If no other
specifications are referenced, ferrous materials shall be hot-dip galvanized in accordance with ASTM A153 or
ISO 1461, or equivalent.
These areas are defined as installation locations that have low or very low levels of corrosive materials such
as moisture, salts, industrial pollution, volcanic pollution, naturally occurring atmospheric/animal corrosive
pollutants, or any combinations of these materials. Care shall still be taken when considering hardware that
may be affected by other corrosive or damaging elements such as wind-blown sand.
In general, most types of ADSS hardware defined in this standard can be installed in low-corrosion installation
sites. These include, but are not limited to, designs of similar and dissimilar materials such as aluminum,
galvanized steel, stainless steel, brass, or copper.
These areas are defined as installation locations that contain high or very high levels of corrosive materials
such as moisture, salts, industrial pollution, volcanic pollution, naturally occurring atmospheric/animal
corrosive pollutants, or any combinations of these or other non-listed corrosive materials. Care shall be
taken when considering hardware that may be affected by additional corrosive or damaging products such as
agricultural aerial spraying, wind-blown salt and sand, and burning carbons from petrochemical activities,
burning agricultural crop fields, forest fires, etc.
Corrosion resistant hardware (CR-hardware) shall pass the qualification tests as described for respective
hardware in 5.5.2.3.5, 5.5.3.3.7, 5.5.4.3.3, and 5.5.6.3.2.
Not all types of hardware defined in this standard can be installed in high corrosion installation sites. Only
designs that have passed the appropriate CR-hardware corrosion qualification tests can be installed in these
locations. This generally includes, but is not limited to, designs that are made of complete or nearly complete
similar noble materials as shown in the chemical electromotive series, such as all aluminum, some stainless
steels, coated galvanized steel, brass, or copper. Unless they pass the appropriate corrosion qualification test,
designs of dissimilar materials as shown in the chemical electromotive series are in general not allowed.
Galvanized steels are not normally acceptable in high-corrosion zones; hence the user and manufacturer shall
be clear on the limitations of galvanized hardware being supplied for use in high-corrosion zones. New or
novel designs can be acceptable if they allow the hardware to pass the appropriate corrosion qualification test.
16
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
4.5 Installation
Suppliers shall provide documented procedures and supporting illustrations with the product for proper
installation.
5. Tests
The tests described in this standard for ADSS hardware are based on the intended overhead installation of the
system. Overhead installations encounter physical phenomena that affect the operation and performance of
any line hardware included in the ADSS system.
Testing to this standard is based on design, manufacture, installation, and application variables that may affect
the performance of hardware for use on ADSS. As a result, tests were selected to provide some assurance to the
user that the hardware is suitable for the expected lifetime of the application.
ADSS hardware shall successfully pass a number of mandatory tests in order to be qualified per this standard.
Any test(s) may be waived if an ADSS cable and hardware of sufficiently similar design has been previously
tested to demonstrate the hardware and cable compatibility and performance. The definition of “similar
design” shall be agreed upon between the supplier and the user.
An assumption for the tests for this standard is that the cables include the most bend-sensitive fiber for the
application. The optical performance of bend-insensitive fiber can mask improper compatibility between
cable and hardware. If bend-insensitive fiber is used, this shall be declared to the end user, and special attention
shall be paid to mechanical deformities of the optical buffer units.
17
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
The parameters specified in this standard may be affected by measurement uncertainty arising from
measurement error or calibration error from the lack of suitable standards. Acceptance criteria shall consider
this uncertainty. For the purpose of this standard, the total uncertainty shall be considered to be <0.05 dB for
attenuation or <0.05 dB/km for attenuation coefficient. Any measurement within this range is considered “no
change” in attenuation.
Optical fiber performance can generally be performed by the following two methods:
a) Monitor individual fibers for attenuation change: This method can determine the maximum change of
any individual fiber tested. When the change for all individually tested fibers is averaged, the “average
change” for all fibers can be determined. The minimum number of fibers to be monitored is provided
in Table 2.
b) Loop-back measurements: This method splices the fibers under test to each other so that they are
concatenated or loop-backed with each other in a continuous length. The attenuation change is
determined by dividing the attenuation change across all loop-back fibers under test by the number of
loop-backed fibers. This provides an attenuation change per fiber. This result is actually the average
attenuation change across all the loop-back fibers. The minimum number of fibers to be monitored is
provided in Table 2.
In the testing standard for ADSS cable (IEEE Std 1222), tests such as crush, low/high temperature bend, twist,
cyclic flex, impact, and mid-span buffer tube storage do not specify loop-back testing and instead require the
monitoring of individual fibers. Laboratories equipped to monitor fibers individually may find it convenient
to measure signal change for each fiber without concatenation for ADSS hardware tests such as suspension
unbalanced load, turning angle, or damper clamp bolt tightening test.
Under dynamic test conditions such as Aeolian vibration, loop-back measurements can provide continuous
optical monitoring to capture events during the test (whereas monitoring fibers individually may utilize
optical switching to intermittently check each fiber during the test). Under less dynamic or point loss
tests, the concatenated method may be used with the understanding that the total end-to-end spliced fiber
attenuation change shall be less than the maximum individual attenuation fiber specification. If the loop-back
measurements exceed the maximum individual attenuation fiber specification, additional testing to isolate
individual fibers is necessary to determine if the individual fibers are within the acceptance criteria. For further
illustration of loop-back compliance, the following note includes an example:
NOTE—Loop-back testing may determine compliance to a maximum specification if the “total end-to-end loop-back
attenuation change” is less than the “maximum individual attenuation fiber specification”; however, if “total end-end-
loop-back” measurement is greater than the “maximum individual fiber” specification, it cannot be used to determine a
failure to the specification.
18
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
For example:
— If the specified maximum individual fiber criteria is equal to 0.10 dB and the average = 0.05 dB.
— Measured end-end attenuation across 10 loop-backed fibers = 0.15 dB = 0.015 dB/fiber. This complies
with the 0.05 dB average specification.
— Because 0.15 dB exceeds 0.10 dB maximum individual fiber specification, one cannot determine if this
complies with the maximum individual fiber specification. If the end-end attenuation loop-back fiber
measurement was 0.09 dB, this could be used to show compliance.
When individual fiber monitoring is performed to determine conformance to the “maximum change” criteria,
the average criteria is determined by averaging the individual fiber readings.
When specified by a test method, hardware manufacturers shall determine compliance to both conditions as
follows:
— The maximum change from individual fibers that are individually monitored—this requires that
individual fibers be monitored during testing.
— The average change across all monitored fibers—the manufacturer is allowed to test by using either of
the two test methods: monitoring individual fibers or monitoring loop-back fibers.
Independent third-party test labs may monitor fibers individually or may monitor fibers using the loop-back
method. If the loop-back method is used, only the “average” criteria shall be used if it is specified. For tests that
do not specify an “average” criterion, the maximum criteria shall be used and compared to the measured per
fiber value. Any number of fibers may be tested as long as they meet the minimum number specified in Table 2.
When testing optical fiber, optical measurements shall be made using a light source of the longest nominal operating
wavelength of the fiber type (i.e., 1300 nm for multimode and 1550 nm for single mode). Test wavelengths may
be measured at other longer wavelengths, with the agreement of the end user and the manufacturer. Longer
wavelengths are typically more bend sensitive, and may warrant different acceptance criteria.
When measuring with a power meter, a laser source with the appropriate wavelength is injected into an optical
splitter. The splitter divides the source signal into at least two signals. During the test, the optical measuring
system (source, splitter, and receiver) shall maintain a certain level of stability in accordance with the test.
One of the split signals is sent directly to an optical power meter and serves as the reference signal. The other
split signal is used to measure the test fibers. When individual fibers are monitored, it is acceptable to use a
switching system. During the tests, the readings from both optical power meters are monitored periodically
in a suitable manner for future analysis. Any changes in the difference between the reference and test signals
indicate a change in the attenuation in the test fiber. A net increase in attenuation means a loss in the optical
signal, and a net decrease in attenuation indicates a gain in the signal.
The following criteria shall be applied when considering the placement of fibers to be tested:
a) Cable type
Stranded tube designs: For single layer cables, a minimum of two active units should be positioned
diametrically opposite each other. For two-layer cables, four units (two in each layer) should be
positioned at 90° intervals within a cable. For multi-layer cables, similar reasoning for unit positioning
may apply.
Ribbon designs: The active units should be located in the first, last, and middle positions. At a
minimum, active fibers shall be positioned in the edge positions within these ribbons. For cables with
multi-stacks, units should be selected from stacks diametrically opposite each other.
19
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
b) Core units (i.e., tubes) shall contain a full complement of fibers; however, dummy fibers may be
allowed. The working fibers shall be disbursed in the working units. Filler rods may be allowed in place
of buffer tubes. The manufacturer shall position the working units within a cable so that these units will
be subjected to the full force of the testing stresses. The manufacturer shall demonstrate theoretically
or through testing that the positioning of the test fibers is representative of the performance of all the
fibers within the cable.
For tests where the ADSS is subjected to tension, the samples are terminated in a manner such that the optical
fibers at both ends of the sample cannot move relative to the ADSS cable. Although other arrangements may
be used, an example of an arrangement for preparing loops between the test sample and the fiber splice tray
is shown in Figure 2. Three loops of cable with a diameter of 1 m are formed and secured as close as possible
to the dead-end tension clamps. Another three loops of the fiber optic unit only are formed just in front of the
splice tray. This configuration will help ensure that all non-metallic and fiber components are prevented from
relative movement during the test.
Unless otherwise stated, a permanent or temporary increase in optical attenuation greater than 0.1 dB/km
within the cable and hardware test sample under test at nominally 1550 nm for concatenated single mode fibers
shall constitute failure. When measuring fibers not concatenated, the maximum individual fiber attenuation
shall not exceed 0.1 dB at 1550 nm for single mode fiber and the average increase of all fibers under test shall
not exceed 0.05 dB per fiber, unless otherwise stated.
20
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
As mentioned in 5.2.1, for tests that apply static load with potential point losses (such as suspension
unbalanced load, turning angle, or damper clamp bolt tightening), laboratories may elect to measure fibers
individually without concatenation and use the decibel loss criteria in the previous paragraph. If, however,
they choose the concatenated method, the same criteria applies with the exception that if the concatenated fiber
exceeds 0.1 dB, further evaluation by separating the concatenated fiber may be necessary to measure the fibers
individually and assure they are within the individual fiber criteria.
5.3 Retesting
In the event of a failure, a review of the product and test set-up is recommended. If an anomaly is discovered,
the test may be repeated if mutually agreed upon by the purchaser and the supplier.
Hardware product lines with four or more distinct sizes for use on a line of ADSS shall have the largest,
smallest, and one intermediate size tested per this standard.
Range taking hardware (single hardware size for use on multiple ADSS cable sizes) shall meet the requirements
throughout the range specified. Availability of cable designs may limit testing within the range specified,
however it is preferred to test the maximum and minimum of the range for verification.
Minimum sample quantities to be used for each size and each range are provided in Table 3 and within the
associated test method subclause of this standard.
A line of hardware tested with one type of ADSS may be considered qualified for other types of ADSS product
lines after review. The review can include the following considerations for ADSS comparison:
— ADSS specifications including cable diameter, jacket construction, cable core construction, mechanical
characteristics, dry band arcing resistance. Round ADSS cable is shown in Figure 3.
— ADSS conformance to IEEE Std 1222.
— Quality control of materials and processes.
— History of proposed ADSS design or similarities to an existing design in the industry.
21
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
The listing of the tests to be performed for the specific types of hardware is given in Table 3. Tests can be
performed on isolated hardware (I) or as a system (S) (hardware and cable) when appropriate, as shown in
Table 3 and described in the identified test subclause. The minimum number of samples for each test are listed
as well. More than one test sample may be required to demonstrate repeatability of results.
22
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
Table 4 classifies the qualification tests for each hardware type. The key classifications drawn from 5.1 include
hardware characteristics, installation tests, and in-service tests. Beginning with 5.5.2, qualification tests are
organized according to the key classifications for each hardware type within this document.
23
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
5.5.2 Dead-ends
Dead-ends are designed to hold cable MIT at elevated temperatures and MLT at temperatures expected under
local environmental conditions without introducing unacceptable levels of optical attenuation. The user may
specify MHST that by definition exceeds the cable MRCL and possibly approach the cable breaking strength.
Tension above MRCL can permanently reduce optical performance or fiber lifetime, thus only mechanical
performance is verified. The dead-end shall terminate the tensioned span of cable, and allow proper grounding
(where applicable) of the ADSS cable. Some of the tests for qualifying dead-ends may be performed
individually or, when suitable, as a system (specified in Table 3). Tests for dead-ends (as well as all hardware
covered in this standard) are summarized in Table 4.
24
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
5.5.2.1.1.1 General
Classification
Intent
The tensile test is a mechanical and optical test designed to simulate performance under various tensile load
conditions, and to demonstrate the ability of the system to reach its MRCL or MLT rating without introducing
unacceptable signal attenuation while maintaining its mechanical integrity. This test, by its nature, also tests in
service crush forces of the dead-end during load conditions.
Tensile loading in overhead applications is a function of installation tension as well as tension due to
environmental and seasonal factors. Testing at MIT and elevated temperatures is necessary to demonstrate
hardware performance on softening plastic jacket material. Testing at higher loads approaching MRCL is
necessary to demonstrate hardware performance under loads produced by wind and/or ice loading. Cycling
the tensile load is included to demonstrate the effects of environmental and seasonal conditions that can cause
load fluctuation. Testing above MRCL to an MHST may be required to determine the rated holding strength of
the dead-end to verify mechanical performance. Optical monitoring above MRCL is not required as the optical
fibers are not expected to function properly; however, monitoring can demonstrate reaction to hardware at the
excess load condition.
Objective
The tensile test subjects the sample dead-end hardware to various tensile loads to help ensure the following:
a) Hardware and ADSS cable reach MIT and MLT (or MRCL) at respective temperature conditions.
b) The optical signal integrity is not adversely affected beyond acceptable limits under tensile loading up
to MLT (or MRCL).
c) The hardware is mechanically sound for overhead loading applications up to MLT (or MRCL) and
above if specified.
d) The ADSS is not damaged by the hardware beyond acceptable limits.
Set-up
Measure the diameter of the cable in an area designated for dead-end placement. These measurements shall be
performed and marked at three locations on the cable that will be under pressure within the length of the dead-
end; one near each end and one near the middle. Each measurement shall include the maximum and minimum
for each location. The dead-ends shall then be installed per the manufacturer’s standard practice. For optical
attenuation measurements, the ADSS cable shall be prepared according to Table 3 with the adequate cable
length extended beyond the exterior edge of each dead-end.
The terminated ADSS test sample shall be installed in a suitable tensile test machine and heat chamber. The
heat chamber encloses one dead-end completely, whereas the other dead-end remains at room temperature
outside the chamber. The length of the cable between the inner edges of the dead-ends shall be a minimum of
10 m (Figure 4) for samples that are optically tested. Mechanical tensile tests without fiber optic monitoring
require 3 m minimum length between the dead-ends and 3 m beyond each cable termination coiled in a loop
similar to that shown in Figure 1. The test sample shall be preloaded to 5% of MRCL. Place thermocouples
25
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
to monitor the cable jacket, dead-end near the cable surface, and ambient temperature within the chamber.
Place reference marks on the ADSS cable at the inner and outer edges of each dead-end and measure the cable
outer diameter near each end of the dead-end—recording the minimum and maximum for each location. The
markings help to visually monitor relative movement and the measurements are used to compare before and
after results. A suitable transducer such as a load cell or dynamometer shall be used to measure the tension in
the test sample.
NOTE—The intent of the optical test is to have 100 m of fiber under strain. If test bed does not allow 10 m between dead-
ends, shorter length and additional numbers of fibers under strain may be concatenated. The minimum length between
dead-ends is 3 m.
5.5.2.1.1.2 Procedure
5.5.2.1.1.2.1 General
Test A is conducted for standard tension requirements to MLT not to exceed MRCL. Test B is conducted to
verify customer specified load of MHST above MRCL that may conform to customer’s hardware strength and/
or holding standards. In addition, test B is run to determine ultimate tensile load of the dead-end and cable
system, and the failure mode.
Test samples for tensile test A shall be tensioned at a rate of 20% MRCL per minute and optically monitored
during the following test sequence:
26
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
In the example shown in Figure 5, MIT is 20% of MRCL and MLT is 90% of MRCL. MIT and MLT shall be
specified by the user.
27
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
Test samples for tensile test B shall be tensioned at a rate of 20% MRCL per minute. Optical monitoring is
optional.
a) The test sample shall show no permanent increase in optical attenuation greater than 0.05 dB/fiber
from preload to MIT after heat soak cycle. The test sample shall show no permanent increase in optical
attenuation greater than 0.10 dB/ fiber from preload to the MLT of the cable at 1550 nm ± 20 nm for
single-mode fibers and at 1300 nm for multimode fibers. The minimum length of 100 m shall be
measured for each case.
b) The tested samples shall survive the mechanical loading with no more than 50 mm at MRCL of relative
movement in relation to the pre-marked ADSS cable at the internal and external edge of the dead-end,
and shall exhibit no signs of damage such as breaking or cracking of the dead-end or cable at any time
during the tensile load testing up to MLT not to exceed MRCL.
NOTE—Certain style designs may exhibit “seating” characteristics during this test where the cable moves
initially with respect to the dead-end components. In these cases, the allowable movement of the cable relative to
the components shall not exceed the manufacturer’s stated maximum value.
28
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
5.5.2.3.2.1 General
The Aeolian vibration test can be run for dead-ends and suspensions simultaneously.
Classification
In-service test/Mechanical/Environmental/Mandatory
Intent
The intent of the Aeolian vibration test is to subject the ADSS cable and hardware to Aeolian vibrations. This
type of vibration is caused by laminar wind flow as it passes over bare cable and is a common occurrence in the
field. Aeolian vibration motion can fatigue components of the cable and/or hardware at attachment locations.
Aeolian vibration may adversely affect the optical signals of the cable as well. It is the intent that this test
method is the same as in IEEE Std 1222.
Objective
a) The hardware is mechanically sound to withstand a referenced level of vibration cycling associated
with overhead applications.
b) The mechanical performance of the ADSS is not damaged by the hardware when subjected to the
specified vibration conditions.
c) The optical performance of the ADSS is not adversely affected by the hardware when subjected to the
specified vibration conditions.
Set-up
The general arrangement to be used for the Aeolian vibration tests and support details are shown in Figure 6.
Figure 6 depicts the industry accepted practice of testing dead-ends and suspensions simultaneously.
The end abutments are used to load and maintain tension in the fiber optic cable. The test section is contained
between the two intermediate abutments. End and intermediate abutments need not be separate units if the
combined unit affords sufficient space for the apparatus specified in the next paragraph and in Figure 6. The
fiber optic cable to be tested should be cut a sufficient length beyond the intermediate abutments to allow
removal of the cable coverings and to allow access to the optical fibers. Suitable dead-end assemblies or end
abutments are installed on the fiber optic cable to fit between the intermediate abutments. The test sample shall
be terminated at both ends prior to tensioning in a manner such that the optical fibers cannot move relative to
the cable. A dynamometer, load cell, calibrated beam, or other device should be used to measure cable tension.
29
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
Some means should be provided to maintain constant tension to allow for temperature fluctuations during the
testing. For most of the test, the cable is tensioned to 100% of the rated MIT. A thermocouple shall be used to
measure the air temperature.
In order to achieve repeatability of test results, the active span should be approximately 20 m or more, with a
suitable suspension (tangent) assembly located approximately two‑thirds of the distance between the two
dead‑end assemblies. Longer active and/or back spans may be used. (See Figure 6.) The vibration amplitude in
the back-span shall be significantly less than the activity of the active span (e.g., less than 15%). The suspension
assembly shall be supported at a height such that the static sag angle of the cable to horizontal is 1.75° ± 0.75°
in the active span.
A laser micrometer or other suitable means shall be provided for measuring and monitoring the mid‑loop (anti-
node) vibration amplitude at a free loop, not a support loop.
An electronically controlled shaker shall be used to excite the cable in the vertical plane. The shaker armature
shall be securely fastened to the cable so that it is perpendicular to the cable in the vertical plane.
The shaker should be located in the span to allow for a minimum of six vibration loops between the suspension
assembly and the shaker.
The test length (i.e., between dead‑end assemblies) of the optical fiber shall be a minimum of 100 m. To
achieve this length, several fibers may be spliced together in accordance with Table 3. At least one fiber shall
be tested from each buffer tube or fiber bundle. Splices should be made so the optical equipment can be located
at the same end. Optical measurements shall be made using a light source with a nominal wavelength of
1550 nm for single-mode fibers and 1300 nm nominal for multimode fiber. Test wavelengths may be measured
at other nominal wavelengths with the agreement of end users and the manufacturer.
The source shall be split into two signals. One signal shall be connected to an optical power meter and shall act
as a reference. The other signal shall be connected to a free end of the test fiber. The returning signal shall be
connected to a second optical power meter. All optical connections and splices shall remain intact through the
entire test duration.
An initial optical measurement shall be taken when the span is pre‑tensioned to approximately 10% of MIT
prior to final tensioning to MIT. The difference between the two signals for the initial measurement provides a
reference level. The change in this difference during the test will indicate the change in attenuation of the test
fiber.
The optical power signals, peak-to-peak free loop amplitude, vibration frequency, number of cycles, cable
tension, and air temperature shall be recorded at periodic intervals by a suitable data logging system.
30
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
5.5.2.3.2.2 Procedure
The ADSS shall be tensioned to the MIT ±5% and the exit angles of the cable from the suspension clamp
measured.
The cable shall be subjected to a minimum of one hundred million vibration cycles. The frequency of the test
span shall be equal to and maintained at the nearest resonant frequency produced by a 16.1 km/h wind (i.e.,
frequency = 82.92 ÷ diameter of cable in centimeters). The free loop peak‑to‑peak anti-node amplitude shall
be maintained at a level equal to one‑half the diameter of the cable.
In the initial stages, the test span requires continuous attention and recordings shall be taken approximately
every 15 min until the test span has stabilized. After the span has stabilized, readings shall be taken a minimum
of two times per day, typically at the start and end of the working day.
A final optical measurement shall be taken at least 15 min after the completion of the vibration test. Note
that IEEE Std 1222 requires 2 h (it is expected to be reduced in the next update). After completion of the
Aeolian vibration test, a section of cable from the location of the hardware dead-end in the active span shall be
loaded to the MRCL to verify mechanical integrity. The section of cable having tangent hardware may also be
included in the section to verify mechanical integrity of the cable for both areas.
a) Any cracking or breaking of any component of the ADSS cable or the hardware shall constitute failure.
This assessment is made with the naked eye. Each hardware sample shall be removed to do a complete
visual inspection.
b) A permanent or temporary increase in optical attenuation greater than 0.2 dB/test fiber km at nominal
wavelength 1550 nm for single-mode fiber and 1300 nm for multimode fiber shall constitute failure.
5.5.2.3.3.1 General
The galloping test requirements are optional for qualifying dead-ends to this standard. In general, ADSS is
not specifically designed to withstand the rigors of galloping. In the event the effects of galloping need to be
investigated, the following tests and criteria apply.
Classification
In-service test/Mechanical/Conditional
Intent
The intent of the galloping test is to subject the ADSS cable and support hardware to galloping motions. This
type of conductor motion is caused by the wind as it passes over round profile cables that have been iced or
cables with oblong shapes (e.g., as flat or figure eight). Fatigue or other damage can occur on the components
of the cable, hardware, and/or to the structure. The optical signals may also be adversely affected by galloping.
It is the intent that this test method is the same as in IEEE Std 1222.
The galloping test is an optical and mechanical test conducted to simulate the effects of low frequency, high-
amplitude motion on ADSS hardware.
31
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
Objective
The galloping test subjects the sample dead-ends to high amplitude vibration loads to help ensure the following:
a) The optical signal integrity is not adversely affected beyond acceptable limits as a result of mechanical
degradation due to hardware induced stress.
b) The hardware is mechanically sound to withstand high amplitude vibration cycling associated with
overhead applications.
c) The ADSS cable is not damaged by the hardware beyond acceptable limits.
Set-up
The general arrangement to be used for the galloping test is shown in Figure 7.
The overall span between dead‑end assemblies should be a minimum of 35 m. For free tangent hardware with
higher degrees of freedom (such as suspensions), the length of the active span and back span are typically
equal to achieve consistent galloping motion. Certain fixed tangents such as supports can prevent the galloping
motion from passing through to the back span thus the back span may be shortened. The end abutments are
used to load and maintain tension in the fiber optic cable. The test section is contained between the two
intermediate abutments. End and intermediate abutments need not be separate units if the combined unit
affords sufficient space for the apparatus specified in the next paragraph and in Figure 7. The fiber optic cable
to be tested should be a sufficient length beyond the intermediate abutments to allow removal of the cable
outer coverings and to allow access to the optical fibers. The test sample shall be terminated at both ends prior
to tensioning in a manner such that the optical fibers cannot move relative to the cable. A dynamometer, load
cell, calibrated beam, or other device should be used to measure cable tension. Some means should be provided
to maintain constant tension to allow for temperature fluctuations during the testing. However, some tension
fluctuations are expected from the galloping activity itself. The cable should be tensioned to a minimum of
50% of the MIT (also called maximum sagging tension) or a maximum of 500 kg. (For some cable designs, the
test tension may need to be lowered to 250 kg in order to induce galloping. For these designs, the 250 kg test
tension is acceptable.)
A suitable suspension (tangent) assembly shall be located approximately midway between the two dead‑end
assemblies. It shall be supported at a height such that the static sag angle of the cable to horizontal shall not
exceed one degree.
32
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
Means shall be provided for measuring and monitoring the mid‑loop (anti-node), single loop galloping
amplitude.
A suitable shaker shall be used to excite the cable in the vertical plane. The shaker armature shall be securely
fastened to the cable in the vertical plane.
The cable shall be prepared for optical attenuation measurements as described in Table 3. The test length (i.e.,
between dead‑end assemblies) of the optical fiber shall be a minimum of 100 m. To achieve this length, several
fibers may be spliced together. At least one fiber shall be tested from each buffer tube or fiber bundle. Splices
should be made so the optical equipment can be located at the same end. Optical measurements shall be made
using a light source with a nominal wavelength of 1550 nm for single-mode fibers and 1300 nm nominal for
multimode fiber. Test wavelengths may be measured at other nominal wavelengths with the agreement of the
end users and the manufacturer. The source shall be split into two signals. One signal shall be connected to an
optical power meter and shall act as a reference. The other signal shall be connected to a free end of the test
fiber. The returning signal shall be connected to a second optical power meter. All optical connections and
splices shall remain intact through the entire test duration.
An initial optical measurement shall be taken when the span is pre-tensioned to approximately 5% of MIT
prior to final tensioning to MIT. The difference between the two signals for the initial measurement provides a
reference level. The change in this difference during the test shall indicate the change in attenuation of the test
fiber.
The free loop peak-to-peak antinode amplitude, galloping frequency, optical power signals, tension, and
number of cycles shall be recorded at periodic intervals. They may be recorded manually or with a data logging
system.
5.5.2.3.3.2 Procedure
The cable shall be subjected to a minimum of one hundred thousand galloping cycles. The test frequency shall
be the single loop resonant frequency. The minimum peak‑to‑peak anti-node amplitude/loop length ratio shall
be maintained at a value of 1/25, as measured in the active span.
Mechanical and optical data shall be read and recorded approximately every 2000 cycles.
The optical power meters shall be monitored beginning at least 1 h before the test.
A final optical measurement shall be taken at least 15 min after the completion of the galloping test. Note that
IEEE Std 1222 requires 2 h (it is expected to be reduced in the next update). After completion of the galloping
test, a section of cable from the location of the hardware dead-end in the active span shall be loaded to the
MRCL to verify mechanical integrity. The cable section having tangent hardware may also be included in the
section to verify mechanical integrity of the cable for both areas.
a) At the completion of all vibration cycling and optical test requirements, the hardware shall be removed
and the ADSS cable shall be visually inspected for damage at the hardware location(s). Any cracking
or breaking of any component of the ADSS cable or supporting hardware shall constitute failure.
Any damage to the hardware samples tested that is not a function of installation or removal shall also
constitute a failure. This assessment is made with the naked eye.
b) A permanent or temporary increase in optical attenuation greater than 0.2 dB/test fiber km at nominal
wavelength 1550 nm for single mode fiber and 1300 nm for multimode fiber shall constitute failure.
33
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
5.5.2.3.5.1 General
The test described in this subclause focuses on hardware corrosion. A similar approach may be used to test the
hardware and ADSS cable system to determine compatibility.
Classification
In-service/ Environmental/Conditional
Intent
To subject the hardware to an accelerated salt fog corrosion test that may be experienced in the field.
Objective
The objective of this test is to determine the effects of a controlled salt atmosphere on the hardware sample.
Set-up
This test is a 1000 h saltbox spray test. The hardware samples shall be placed uniformly into the box for
testing. In the event that hardware samples exceed the length of the test chamber, the samples may be cut to fit.
The cut ends shall be protected (sealed) from exposure within 76 mm from the cut end. The final configuration
of the sample shall be agreed upon between the user and supplier.
5.5.2.3.5.2 Procedure
a) The hardware test samples are to be placed into a standard salt spray-testing box as defined by ASTM
B117 and ISO 9227. The hardware samples are to be placed horizontally in the test chamber to simulate
a standard horizontally suspended hardware position. The test is to run continuously for 1000 h of salt
spray testing.
g) For system testing, install hardware onto a short piece of ADSS and perform the same test. The ADSS
cut cable ends shall be protected or drawn outside the chamber to avoid salt fog exposure.
At the end of the test, the hardware is to be removed and dissected for corrosion damage. The hardware passes
the test if the following criteria are met:
a) For coated samples (galvanized steel, aluminum coated steel, copper coated steel, etc.), there shall be
no locations where the samples have been pitted so as to expose the underlying strength member in
any way.
b) There are no locations where solid aluminum, stainless steel, brass or copper, hardware that have been
point pitted beyond a depth of 10% of the total hardware thickness cross-section of the hardware at the
point of the pit.
c) There shall be no damage to the hardware and cable and hardware system such that it may affect the
operation of the cable.
34
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
d) In the case of “other hardware designs that are new or novel,” there can be no removal of the coating
or material thicknesses in any way. The functionality of the hardware and its usability to perform its
intended application cannot be altered or changed in any manner.
5.5.3.1.1.1 General
Tangent hardware is designed to support vertical loads resulting from system cable weight and environmental
load conditions. Hardware vertical load demand can increase significantly in areas with extreme ice and wind
loading conditions.
Classification
Hardware Characteristics/In-service/Mechanical/Environmental/Mandatory
Intent
The intent of the vertical load test is to verify the manufacturer’s strength rating of the hardware. Vertical
load testing can simulate potential field conditions of extreme ice and wind loading. The angle Ө in Figure 7
is defined as the maximum turning angle specified by the manufacturer. This angle is used when testing with
flexible members that simulate cable—another option is to test with a rigid bar (in place of the flexible member)
to reach the maximum vertical load rating. This test is purely a mechanical test that loads the hardware to
destruction. It is up to the user to verify that the rating meets or exceeds the requirements of their ADSS cable
system.
Objective
a) To verify the manufacturer’s published mechanical strength of the tangent hardware when subjected
to extreme vertical loading
b) To identify failure mode and record the test results
Set-up
The tangent hardware shall be mounted in the test apparatus to reflect field load applications. Figure 8 depicts
the general arrangement and orientation for a tangent suspension. Tangent supports and tangent trunnions
are to be mounted and loaded according to respective field attachments as provided in the manufacturer’s
installation procedures. To reach high mechanical loads, a wire rope cable may be used within the ADSS
tangent hardware for this test. Install the terminated wire rope in a test fixture and apply the tangent hardware.
The maximum turning angle Ө is specified by the manufacturer. As an option, the test may be performed using
a rigid bar in place of the flexible member. In this case, the turning angle Ө essentially remains zero throughout
the test. The tangent hardware can be confined to components necessary to demonstrate the vertical load
connection to the structure. Use a load cell to monitor tension.
35
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
5.5.3.1.1.2 Procedure
Load the tangent hardware perpendicular to the axis of flexible cable or rigid bar until failure occurs. For
flexible cable, maintain the maximum turning angle for the simulated cable set-up. For rigid bar set-up, the
maximum turning angle is zero. A suggested load rate is 50% of the hardware rating per minute. Record the
load rate, maximum load, and failure mode.
The hardware passes the test if the maximum vertical load meets or exceeds the manufacturer’s published
rating without fracture of any component.
5.5.3.1.2.1 General
Single attachment ADSS tangent hardware has maximum turning angle ratings that allow for horizontal and
vertical changes in direction. Figure 8 shows the set-up for turning angle testing with a maximum rated turning
angle that shall be specified by the manufacturer. For field applications that exceed the turning angle rating
of single attachment tangent hardware, double attachment tangent hardware may be appropriate, or the use of
two dead-ends can be implemented. Consequently, the larger the turning angle rating for single attachment
tangent hardware, the less need there may be to install double attachment tangent hardware or two dead-ends.
With more degrees of freedom, single attachment tangent suspension hardware is commonly rated for greater
turning angles. Single attachment tangent suspensions are designed for both distribution and transmission
environments. Supports and trunnions are typically designed for distribution applications.
36
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
In-service or operating conditions include initial installation and maximum environmental loads as found in
sag and tension calculations. Everyday load conditions by definition are at or below MIT and periodically the
system may approach MLT that is less than or equal to MRCL. At excess loads above MRCL the system is not
expected to perform optically, however the system mechanical strength may exceed MRCL.
Classification
Hardware characteristics/Installation/In-service/Mechanical/Environmental/Mandatory
Intent
The turning angle test is a mechanical and optical test that simulates application conditions ADSS hardware
may be subjected to in-service. The turning angle test simulates line angle changes that commonly occur in
overhead aerial application due to horizontal directional changes and/or elevation changes.
Objective
The turning angle test subjects the tangent hardware to increasing tensile loads at the maximum recommended
line angle of the tangent hardware to help ensure the following:
a) The optical signal is not adversely affected beyond acceptable limits as a result of either a severe bend
at the hardware or inappropriate force applied to the ADSS by the tangent hardware.
b) The hardware is mechanically sound to withstand the forces applied by turning angles.
c) The ADSS is not damaged by the hardware beyond acceptable limits.
Set-up
The tangent hardware shall be mounted in the test apparatus to reflect field load applications. Figure 9 depicts
the general arrangement and orientation for a tangent suspension. Tangent supports and tangent trunnions
are to be mounted and loaded according to respective field attachments as provided in the manufacturer’s
installation procedures. For optical measurements, the test sample shall be prepared according to Table 3. The
length of the ADSS cable between the inner edges of the dead-end terminations shall be approximately 8 m.
Note that the intent of establishing some distance is to allow for the length of mechanical elements in the set-
up and achieve at least 100 m of fiber under strain. If test bed does not allow 8 m between dead-ends, shorter
length and additional numbers of fibers under strain may be concatenated. The minimum length between
dead-end and tangent is 1 m. Install the tangent hardware at the center of the ADSS test sample length and
hoist to develop the maximum recommended turning angle (±2 degrees) of the tangent hardware under test.
The method of attachment, while not required to be rigid, shall limit the twisting of the cable occurring near
the terminations. The roller shown in Figure 8 is used to keep the test turning angle constant as load is applied
by the tensile ram. A torque balanced wire rope link may be used to connect the test sample termination to the
tensile ram and avoid potential test sample attenuation induced by traveling through the roller.
37
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
5.5.3.1.2.2 Procedure
The ADSS shall be axially loaded and monitored in the following sequence (reference Table 3 for optical
measurement methodology):
An additional step may be added during the load sequence [step a) through step g)] to include an entry at MIT.
Record optical signal at end of 5 min hold.
MRCL may be used in place of MLT if agreed to by the purchaser and the manufacturer.
a) For 80% MLT or less, there shall be no increase in optical attenuation greater than 0.1 dB/fiber at
nominal wavelength of 1550 nm for single-mode fiber and 1300 nm for multimode fiber. The average
increase of all fibers under test shall not exceed 0.05 dB per fiber. For greater than 80% MLT up to
MLT, there shall be no permanent increase in optical attenuation greater than 0.2dB/fiber at nominal
wavelength of 1550 nm for single mode fiber and 1300 nm for multimode fiber. The average increase
of all fiber under test shall not exceed 0.1 dB per fiber. For systems tested to MRCL, replace MLT with
MRCL for the aforementioned acceptance criteria.
38
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
b) The tested samples shall exhibit no signs of detrimental damage such as breaking or cracking at any
time during the axial loading.
c) The tangent hardware shall be removed from the ADSS, and the ADSS shall be visually inspected for
damage at the hardware location. Any jacket perforation or tear shall constitute a failure.
5.5.3.3.3.1 General
ADSS cable designs meet various fiber counts, jacket types, and strength requirements using a mixture of non-
metallic component materials. As a result, it is possible to have ADSS cables with a common size that vary
significantly in strength, surface friction, and resistance to compression. Unlike dead-ends, tangent hardware is
not required to hold maximum loaded tension MLT of the cable. Allowing slip under excessive load conditions
through the tangent hardware can reduce the risk of damaging the ADSS or supporting structure. Hardware
manufacturers supply the minimum unbalance load rating for the respective tangent hardware design.
Classification
In-service test/Mechanical/Mandatory
Intent
The unbalanced load test is a mechanical and optical test that simulates application conditions ADSS hardware
is subjected to during in-service conditions. The unbalanced load test simulates load imbalances to ADSS
that can occur in overhead aerial application as caused by tree limb impacts, ice loading and unloading, wind-
induced motion, and other similar phenomena.
Objective
The unbalanced load test creates an imbalance in tensile loading on the tangent hardware to help ensure the
following:
a) The optical signal is not adversely affected beyond acceptable limits as a result of unbalanced loading.
b) The hardware is mechanically sound to withstand the forces applied by unbalanced loads.
c) The ADSS is not damaged by the hardware beyond acceptable limits.
39
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
The general arrangement for the unbalanced load test is shown in Figure 10. For optical measurements, the test
sample shall be prepared according to Table 3. The hardware under test is mounted on a suitable fixed support
frame and the test sample length from the tangent hardware to the dead-end is 10 m. Note that the intent of
establishing a distance is to allow for length of mechanical elements in the set-up and achieve at least 100 m of
fiber under strain. If test bed does not allow 10 m between dead-ends, shorter length and additional numbers of
fibers under strain may be concatenated. The minimum length between dead-end and tangent hardware is 3 m.
Mark the ADSS cable at the suspension edge and between hardware components to visually monitor relative
movement.
The ADSS on one side of the tangent hardware is un-tensioned to permit tension imbalance. On the other side
of the tangent hardware, the ADSS shall be loaded according to the following sequence (reference Table 3 for
optical measurement methodology):
a) Load to eliminate cable slack and hold for 1 min. Record optical signal at end of hold.
b) Continue loading to manufacturer’s minimum unbalance load rating and hold for 1 min. Record
optical signal at end of hold. (Increase load at a suggested rate of 50% of unbalance load rating per
minute.)
c) Continue loading until relative movement between the cable and hardware is detected. Record the
load and optical signal immediately before reducing load to slack load (no slipping).
d) Reduce to slack load and record optical signal.
If the cable moves relative to the tangent hardware prior to the manufacturer’s rating, record the load and
optical signal. Note any damage to the hardware or cable.
a) There shall be no permanent increase in optical attenuation greater than 0.1 dB/fiber at nominal
wavelength of 1550 nm for single-mode fiber and 1300 nm for multimode fiber. The average increase
of all fibers under test shall not exceed 0.05 dB per fiber.
b) The tested samples shall exhibit no signs of detrimental damage such as breaking or cracking at any
time during the unbalanced loading.
40
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
c) The tangent hardware shall be removed from the ADSS, and the ADSS shall be visually inspected for
damage at the hardware location. Any jacket perforation or tear shall constitute a failure. Dissection
of cable to inspect buffer tube compression is optional. Measure the buffer tubes in the areas within
the hardware length at the ends of the hardware and hardware center. Use acceptance criteria found
in tensile test subclause (5.5.2.1.1). This can be compared to buffer tubes in areas of the cable that
were not exposed to the tension and vibration (beyond the termination ends). Note that dissection
inspection should begin within 0.5 h of unloading the tested sample.
d) Slipping at a load below the manufacturer’s minimum rating shall constitute a failure.
Same as the test in 5.5.2.3.2 except the tangent hardware becomes the primary subject and the dead-end is
secondary.
NOTE—The general arrangement in Figure 6 lists a suspension assembly but represents the location and
placement for any type of tangent hardware. It is important to mount the respective hardware in accordance
with standard field installations to demonstrate proper performance.
NOTE—The general arrangement in Figure 7 lists a suspension assembly but represents the location and placement for any
type of tangent hardware. It is important to mount the respective hardware in accordance with standard field installations
to demonstrate proper performance.
5.5.3.3.8.1 General
Stringing blocks are temporarily used at structures to safely support and guide the cable through aerial line
installation as the cable is being pulled in. Stringing blocks can vary in size depending on the direction change
of the pull. Sharp turning angles can require large stringing blocks based on the diameter of the cable in
order to properly support the cable under stringing tension (STT). Tangent support and trunnion hardware
may be designed to string cable at structures with relatively small turning angles. Hardware manufacturers
supply maximum turning angle ratings for hardware. Tangent hardware is commonly used for stringing in
distribution systems as it can save time and labor by eliminating the need to install and remove conventional
stringing blocks at every structure.
Classification
Installation/Mechanical/Conditional
Intent
The stringing test is a mechanical and optical test that simulates installation conditions ADSS hardware is
subjected to during cable stringing. ADSS cable is cycled through the tangent to simulate exposure to several
structure locations in a cable route. Stringing operations are normally carried out during calm conditions for
safety reasons and to reduce the possibility of cable damage.
41
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
Objective
The stringing test cycles cable through tangent hardware to help ensure the following:
a) The optical signal is not adversely affected beyond acceptable limits as a result of pulling cable
through the tangent hardware at the manufacturer’s maximum turning angle rating.
b) The hardware is mechanically sound to withstand the forces applied by stringing loads and turning
angles.
c) The ADSS is not affected by the hardware beyond acceptable limits.
The general arrangement for the stringing test is shown in Figure 11. For optical measurements, the test sample
shall be prepared according to Table 3. A swivel shall be placed in line with the cable test sample to simulate
common practice during field installations. The hardware under test shall be mounted on a structure midspan
to establish a turning angle at the hardware manufacturer’s rating plus 30% minus zero. The minimum test
sample length between dead-ends is 10 m. The test length of the optical fiber shall be a minimum of 100 m.
Mark the ADSS cable at the tangent edge and between hardware components to visually monitor relative
movement for informational purposes. Tension the cable to the STT and maintain the load throughout the test.
Mark a 1.5 m ± 0.2 m section of cable to represent the test section exposed to stringing through the tangents.
Measure and record the maximum and minimum diameter of the cable near the center of the test section
before the first cycle. Pass this section over the tangent 120 times (60 times in each direction) at a rate of 2 s
to 3 s per pass. Measure and record the maximum and minimum diameter of the cable near the center of the
test section after test cycling. Record the average of the maximum and minimum to compare before and after
measurements. Record optical measurements and any notable wear or damage during the test.
42
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
a) There shall be no permanent increase in optical attenuation greater than 0.1 dB/fiber at nominal
wavelengths of 1550 nm for single mode fibers and 1300 nm for multimode fibers. The average
increase of all fibers under test shall not exceed 0.05 dB per fiber.
b) The cable sample test length shall exhibit no signs of detrimental damage such as excess wear as
agreed upon by the user and manufacturer. Jacket perforation or tearing during the stringing test shall
constitute failure.
c) The tangent hardware shall be visually inspected for damage or excess wear upon completion of
the test. Any cracking or breaking shall constitute failure. Percentage change of the average cable
diameter greater than 15% shall constitute failure.
5.5.4 Dampers
Historically, dampers have been used to protect shield wire and conductor lines from Aeolian vibration by
limiting the level of vibration. It has been demonstrated that dampers can reduce Aeolian vibration to a strain
level that the line can endure nearly indefinitely.
Two types of dampers are addressed in this standard and they can be referred to as 1) Stockbridge type and
2) impact type (as referenced in 4.2.2.3). Stockbridge dampers are characterized as having flexible messenger
wire with weights that respond to motion in the line without direct contact. Impact dampers can be characterized
as a device that disrupts the line motion by interacting directly with the line.
Test standards have been established primarily for the Stockbridge type to measure damper performance and
requirements, and these standards are referenced where applicable. In some cases, the same test standards
established for Stockbridge-type dampers are applicable to impact dampers with further explanation covered
in this standard.
Except for damper performance testing, the tests covered in IEC 61897 and listed in Table 5 shall apply for
Stockbridge dampers. For damper performance testing, either IEC 61897 or IEEE Std 664 may be used.
43
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
procedures, and acceptance criteria for the above tests are found in Test Methods, Clause 7 of IEC 61897. The tests
listed in this table represent the minimum technical details to be agreed upon by the purchaser and supplier as per IEC
61897, Annex A. Additional tests from IEC 61897 including visual examination, verification of dimensions/materials/
mass, corrosion protection tests, attachment of weights to messenger, and attachment of clamp to messenger cable may
be added if agreed upon by the purchaser and supplier.
a
For application of damper clamps on ADSS optical, attenuation shall be measured and the ADSS cable shall be prepared
according to Table 3. Conventional metallic damper clamps designed for metallic cables cannot be directly applied to ADSS
and require application over an intermediate protection such as armor rods or hardware rods. Assure that adequate ADSS
extends beyond the exterior edge of each damper assembly to measure optical results.
Acceptance criteria is as follows:
a) A permanent or temporary increase in optical attenuation greater than 0.2 dB/test fiber km at nominally 1550 nm
for single mode fibers shall constitute failure.
b) The tested samples shall exhibit no signs of detrimental damage such as breaking or cracking at any time during
the axial loading.
b
Induced voltage on ADSS stockbridge hardware may approach levels such that corona is created. In cases where corona is
a consideration, refer to applicable IEC standards for corona tests. See “Corona considerations for ADSS hardware” in
Annex A for further information.
Reprinted with permission from IEC 61284 ed. 1.0 [B11], Copyright® 1998 IEC Geneva, Switzerland. www.iec.ch.
5.5.4.1.1.1 General
Four basic laboratory test methods of determining damper dissipation characteristics covered in IEEE Std
664 include: 1) decay, 2) inverse standing wave ratio, 3) power, and 4) forced response. (Note that IEC 61897
references IEEE Std 664 as well.) In each of these methods, pure sinusoidal vibration is introduced to the
sample and the sample response is measured to determine dissipation characteristics. Unlike the Stockbridge
damper, the active nature of the impact damper introduces in essence another component to the conductor
motion during vibration—as is, only the decay method can be used to compare decay rates between dampers.
In order to calculate power dissipation, a practical approach to the power method may be used through the use
of electronic filters and is described in this subclause.
Classification
Hardware characteristics/In-service/Mechanical/Mandatory
44
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
Intent
The intent of the power dissipation test is to measure damper performance and determine suitability for
protection against Aeolian vibration on ADSS lines.
Objective
The laboratory test set-up has the same general configuration described in IEEE Std 664 and shown in
Figure 12.
The minimum free span length shall be 30 m. Install transducers to measure the force and velocity or
acceleration imparted to the ADSS cable at the shaker. The force and velocity/acceleration signals are filtered
by an electronic filter or FFT analyzer, which displays the frequency spectrum of each signal and the phase
angle between the two signals, to remove signals other than the driving frequency. The force and velocity
signals should be averaged independently to reduce the signal distortion caused by random impacts. Guidance
on the measurements of power dissipation of Aeolian vibration dampers is given in IEEE Std 664. Detailed
procedures for setting up and controlling tests can be found in these procedures.
Measurements are executed to determine the dissipated power at frequencies for which resonance occurs
within the range 0.18/d to 1.4/d, where d is the conductor diameter in meters, unless a narrower frequency
range is agreed upon by the purchaser and the supplier.
Suggested methods of controlling amplitudes include strain gage methods as described in IEC 61897 and
constant velocity methods as described in IEEE Std 664.
Per IEC 61897 controlling amplitude via strain gage method is described as follows: Conductor bending strain
shall be monitored adjacent to the rigid clamp at the span end with the damper. Depending on the impact
damper attachment design, discretion may be used for the need to monitor conductor strain at the impact
damper attachment area. Attach two strain gages at the uppermost strands of the ADSS at each designated
45
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
location within 2 mm from the rigid clamp edge and “if needed” 5 mm from the damper clamp edge. Signals
from the strain gage amplifiers are electronically filtered and averaged in a manner similar to the force and
velocity signals referenced above.
Per IEEE Std 664, testing shall be performed at a constant loop velocity of 200 mm/s at each tunable harmonic
frequency. This velocity corresponds approximately to an antinodal amplitude (mm) of 67/f where f is the
frequency of vibration. Additional testing at other loop velocities (100 mm/s, 300 mm/s, etc.) can be used
to provide a good spectrum of results for the end user’s evaluation. The input antinodal velocity should be
maintained within ± 2% of the calculated value at each test frequency. The measurement of nodal and antinodal
amplitudes (when required) should be made within ± 5%. The measurement of input force and velocity signals
at the vibration shaker should be made within ± 5% of the measured value. The measurement of the phase
angle between the input force and velocity signals should be made with sufficient accuracy to ensure that the
cosine of the phase angle is within ± 1% of the measured value.
At each tunable frequency, adjust the shaker input to achieve the desired amplitude based on the method
chosen (strain gage method corresponding to 150 microstrain or constant velocity method at 200 mm/s).
The antinode amplitude shall be measured at the first free vibration loop from the damper. A non-contact
measuring instrument is preferred, but a low mass transducer or accelerometer can be installed on the
conductor. The signal should be filtered and averaged as described above. The velocity of the antinode
amplitude may then be calculated.
The dissipated power is then calculated from the force, acceleration, and phase angle between the respective
signals. Dissipated Power is calculated from the following equation:
1
P = ( FVs ) cos θ v
2
If an accelerometer is used for data acquisition, the power dissipated by the damper can be calculated from the
following equation:
1
P= FAs sin θ a
4π f
where
P = D 4 × f 3 × fnc(Y / D) × L
where
P is power (W)
F is the measured force at the shaker (N)
46
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
At each tunable resonant frequency, the dissipated power shall be greater than the wind power input for the
designated span.
5.5.4.1.2.1 General
Impact dampers fabricated from non-metallic materials can be damaged from the ultraviolet content of
sunlight. The sunlight spectrum includes visible light that measures above 400 nm wavelength and UV below
400 nm wavelength. UV wavelengths are categorized into three regions: UVA (400 nm to 315 nm), UVB
(315 nm to 280 nm), and UVC (280 nm to 100 nm). In the case of overhead line hardware, UVA can cause
polymer damage and represents the applicable UV test level. Industry accepted plastic dampers made from
PVC have been used since the 1970s—although other materials may be considered. This test standard bases
testing parameters and acceptance criteria on that established with the PVC material. General guidance for test
equipment and methods of UVA exposure can be found in ISO 4892.
Classification
Intent
The intent of this test is to determine the comparative performance of non-metallic impact dampers exposed
to ultraviolet light waves that can be experienced in sunlight. Sunlight is defined as global noon midsummer
sunlight, also known as “solar maximum.”
Objective
To determine the ability of the damper to resist damage from UVA after soaking it for 3000 h at solar maximum.
Place test sample(s) approximately 305 mm long in a UV exposure test chamber with controlled irradiance
and controlled temperature. Provisions shall be made to assure exposure uniformity for each sample. Set
equipment to maintain temperature at 60 °C and UVA wavelength emission. UVA type florescent lamps can be
used that closely simulate sunlight in the critical short wave UV region from 365 nm down to the solar cutoff of
295 nm—the peak emission is at 340 nm (irradiance approximately 0.7 Wm2/nm). Soak for 3000 hours. Check
samples a minimum of once per week to record observations.
47
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
5.5.4.2.1.1 General
Classification
Installation/Mechanical/Conditional
Stockbridge dampers
Refer to Table 5—the clamp bolt tightening test shall apply. Use the manufacturer’s installation
recommendations for installation torque and applications over hardware rods.
Impact dampers
Intent
Hardware is required to protect ADSS cable from excess wind-induced motion without introducing excess
strain, stress risers, or fiber attenuation. Excess stress coupled with wind-induced motion can greatly reduce
the life of the cable system. The intent of this test is to apply the hardware to an ADSS cable and verify that
installation alone does not distort or damage the ADSS cable.
Objective
To verify that the ADSS cable is not exposed to excess damage from crush upon initial installation of hardware
Set-up
The ADSS sample length shall allow for a minimum of three hardware installations and 1 m beyond each end
of the hardware trial application. Identify and mark the three proposed areas of hardware installation along the
length of ADSS cable sample. The load on the test cable shall be sufficient enough to keep the cable taut during
installation and not exceed 5% of the breaking strength.
5.5.4.2.1.2 Procedure
Install hardware per manufacturer’s instructions at one of the designated areas. Mark the final position of the
hardware at both ends of the ADSS cable under test.
Remove the hardware per manufacturer’s instructions. Visually inspect the cable within the reference marks
and compare to the adjacent open areas of the cable. If there is no visible damage to the cable, optical testing
is not required.
a) There shall be no cracking, splitting, or similar damage to exterior cable. Cable exterior deformation
shall not be considered as damage. This assessment is made with the naked eye.
b) For optical measurements there shall be no permanent increase in optical attenuation greater than
0.1 dB at nominally 1550 nm for single-mode fibers. The average increase of all fibers under test shall
not exceed 0.05 dB.
48
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
For direct application of impact dampers on ADSS that may potentially create significant clamping force,
optical attenuation shall be measured and the ADSS cable shall be prepared according to Table 3, with the
adequate ADSS extended beyond the exterior edge of each damper clamp, and the test length of optical fiber
shall be a minimum of 100 m long.
See Annex B.
5.5.5 Come-alongs
Come-alongs or temporary tensioning grips are designed to maintain the cable tension during the sagging
process and installation of dead-ends. It may also be used for general line work and maintenance. This section
applies to tools specifically designed for sagging. Formed wire dead-ends that are used to dead-end the system
are commonly used temporarily for sagging. In this case, the formed wire dead-end is used once for sagging
and then permanently installed in the next dead-ended location. This method is referenced in IEEE Std 524™
and is acceptable with an adequately formed wired dead-end that meets sagging load requirements. The come-
alongs shall not cause damage to the cable in any way.
Classification
Installation/Mechanical/Conditional
Intent
Hardware is required to secure ADSS cable without introducing excess strain and stress risers, which may
reduce the life of the system and cause fiber attenuation. The intent of this test is to apply the hardware to an
ADSS cable and verify that installation alone does not distort or damage the ADSS cable.
The objective, set-up, procedure, and acceptance criteria are the same as those in 5.5.4.2.1 (impact dampers).
49
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
5.5.5.3.1.1 General
Classification
In-service/Mechanical/Mandatory
Intent
The tensile test is a mechanical test to simulate performance under sagging tensile load conditions and to
demonstrate the ability of the system to reach sagging tensions (SAT) without damage to the cable.
Objective
The tensile test subjects the sample come-along to various tensile loads to help ensure the following:
Set-up
The come-along shall be installed per the manufacturer’s standard practice on one end of a length of ADSS
cable of minimum 5 m length. The other end of the cable shall be connected to a tensile machine using a
suitable clamp or other means. The position of the ADSS shall be pre-marked at one end of the come-along
under test.
5.5.5.3.1.2 Procedure
Come-alongs shall be loaded at a rate of no greater than 10% breaking strength per minute. The optical signal
need not be monitored during this test. The come-along samples shall be loaded to 125% of the come-along
rating, and held for 15 min at that tension.
The tested samples shall successfully hold the cable to 125% of the come-along tension rating with no more
than 50 mm of relative movement in relation to the pre-marked cable, and shall exhibit no signs of detriment
on the cable.
Downlead clamps are typically used to secure cable leading from the dead-end to the splice case for fiber optic
splices. Securing the cable helps maintain minimum bend radius of the cable and avoid abrasion from excess
motion.
50
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
5.5.6.3.1.1 General
Classification
In-service/Mechanical/Mandatory
Intent
Downlead clamps experience loading from the ADSS cable weight and environmental conditions such as
wind and ice. To adequately train and secure the ADSS cable to the structure, hardware instructions cover
recommended tightening and spacing distance between downlead clamps. The intent of this test is to verify
that the downlead clamp adequately secures ADSS before slip occurs.
Objective
Tensile load the ADSS cable secured in the downlead clamp to help ensure the following:
The unbalanced load test (Figure 9) shows a similar set-up except load is applied to two cables secured with
a downlead clamp. Mount the downlead clamp in a suitable tensile machine and follow the manufacturer’s
instructions to install two ADSS cables within the clamp—the terminated end of the ADSS cables shall be
connected to the load cell in a manner that equalizes the load between each cable as tension is applied to the
sample. The overall sample length shall be a minimum of 2 m from the end of the cable termination to the
downlead clamp. Premark the ADSS cable at the end of the downlead clamp and dead-end to observe relative
movement. Procedures are as follows:
a) Preload the cable to 67 N/leg and set load rate to 222 N/min.
b) Continue loading to the manufacturer’s minimum slip withstand rating and hold for 1 min.
c) Continue loading until 5 mm of relative movement between the cable and downlead is detected. Pause
loading, measure and record slip distance and load.
d) Increase load until slip is continuous and record load.
If the cable moves relative to the downlead prior to the manufacturer’s rating, record the load. Note any
damage to the hardware or cable.
a) The tested samples shall exhibit no signs of detrimental damage such as breaking or cracking at any
time during the loading.
b) Slipping at a load below the manufacturer’s minimum rating shall constitute a failure.
51
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
Annex A
(informative)
A.1 General
It is possible for corona to exist on ADSS and related hardware due to proximity and arrangement of adjacent
energized conductors. Corona is the result of surface electric fields (i.e., surface gradients), which exceed the
threshold level of approximately 20 kV/cm; the exact level will vary with atmospheric conditions as well as the
nature (particularly roughness) of ADSS/hardware surfaces. General geometric shape also affects the level of
the surface fields. Corona is corrosive and can be a source of radio and TV interference. Experience indicates
that hardware corona should be investigated on transmission lines of 345kVand higher, with caution that there
may be situations at lower voltages. Depending on the conditions (voltage level, conductor proximity, line
configuration), line voltages as low as 115 kV and possibly less may develop enough electrical stress for
corona to occur.
Because the highvoltage environment is identical in nature for both ADSS and ADSS hardware, IEEE Std
1222 for ADSS is suggested as a source of information for this topic.
As noted in IEEE Std 1222, three-dimensional electric field analysis techniques can indicate areas in and
around hardware where corona may exist. Mitigation is possible by application of shielding devices or careful
design of the hardware itself.
Laboratory testing is always advisable, provided electric field conditions in the test arrangement match the
“real world” as closely as possible. However, at this date, an IEEE standard for corona testing is still undergoing
development. Until that document is finalized and available, the following methodology is suggested.
NOTE 2—Some utilities may already have established corona testing procedures.
A.2 Suggested method for corona testing of ADSS hardware: Matching the
laboratory to the “real world” via electric fields
The approach is to match the electric fields in a laboratory test setup to a “real world” installation. To
demonstrate this, Figure A.1 shows a hypothetical laboratory arrangement model and a “real world” high
voltage tower model. Both models contain the ADSS hardware assembly to be checked for corona.
52
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
53
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
Annex B
(informative)
High electric fields (changes of space potential) exist near the end of ADSS armor rod assemblies. In these
high fields, impact dampers (also referred to as spiral vibration dampers) are subject to arcing between the
damper material and ADSS jacket, which can be worsened by pollution. There have been known failures due
to this phenomenon.
Mitigation is accomplished by maintaining sufficient distance between the damper and the end of the armor
rod. This locates the damper in lower electric fields. Figure B.1 is a general illustration of damper and ADSS
hardware on a high-voltage tower.
There are no known laboratory studies establishing a sufficient distance. However, in the case of one failure
on a double circuit 345 kV line—where the initial distance was only several centimeters—failures were
eliminated by moving the damper 4.6 m (15 ft) from the armor rod. A North American utility company with
low pollution has illustrated use of 3 m (10 ft) in presentations concerning ADSS and dampers on 500 kV
towers.
Further studies and tests may show less and thus more convenient separation distances; until such knowledge
is established, it is recommended to use a distance of 3 m (10 ft) for low accumulation areas and 4.6 m (15 ft)
for high accumulation areas.
NOTE—Moving the damper further into the span reduces space potential to approximately 2 kV or less end to end (across
the damper).
54
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
Annex C
(informative)
In most cases, hardware and connecting fittings made from conductive metals such as steel and aluminum are
usually adequate to provide a conductive path to the metallic structure for the low current levels expected in an
ADSS cable system. Metallic fittings, such as clevises, extension links, eye-nuts, and Y-clevises, connected in
series can be joined to the nearest grounded object. Examples of the object can be a double arming bolt that is
clipped to the wood pole structure ground or a vang on a grounded lattice tower.
If necessary, a grounding wire connection may be required to shunt capacitively induced currents that could
cause eventual damage to hardware connecting fittings. Direct connections from the main cable hardware to
the structure ground can be accomplished via separate bonding attachments or integral to the cable hardware.
Ungrounded hardware attached to wood poles will be subject to a space potential that may be sufficient to
create currents in the wood pole and eventually lead to dry band arcing. Wood pole fires have occurred in this
case. Connecting the hardware to the nearest grounded object is suggested. This object could be a downlead
connecting static wires and earth ground, or other hardware such as cross arms, clamps, etc., which are
grounded.
In electrical distribution environments, there is less need for grounding ADSS hardware. However, installers
should follow local user’s standard procedure that may require grounding in their system.
Metallic hardware components that are insulated or isolated by non-metallic (non-conductive) components
require a means to connect to a ground or metallic component that is eventually joined to ground.
55
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
Annex D
(informative)
Construction of ADSS cables vary and the protection of fibers within plastic buffer tubes vary as well,
depending on the loading the cable is expected to experience. Since ADSS was introduced in the 1980s, many
tensile tests have been performed for the industry to verify cable and dead-end compatibility. This document
provides an attempt to standardize the test method without the requirement of measuring the buffer tubes that
house the fibers in 5.5.2.1.1. Industry manufacturers and users were able to agree on the test procedure but
found it difficult to agree on acceptance criteria for buffer tube deformation. Consequently, it was decided not
to include the acceptance criteria for buffer tube deformation until more data is collected.
In order to collect data in a consistent manner, the following guidelines have been established for buffer tube
deformation and measurements:
a) Upon completion of step j) of test A in 5.5.2.1.1, begin dissecting the cable by carefully removing the
cable jacket but transfer all five premarked locations for the test dead-end to the underlying buffer
tubes. The locations represent three that were under the dead-end and two that were just beyond the
ends of the dead-end (not covered by the dead-end). Note any distinguishing characteristics of the
dead-end relative to the orientation of the buffer tubes and record observations. Unwrap the buffer
tubes to record observations and measurements at each of the five previously designated locations.
This step shall be completed within 0.5 h of the last step.
b) Upon completion of (a) above, measure the buffer tubes in an area that were not exposed to tension
approximately 1 m beyond the end of the dead-end. Record dimensions for comparison. This step
shall be completed within 1 h of the last step.
Acceptance criteria for buffer tube deformation may ultimately be included in 5.5.2.1.1 after item b) of the
acceptance criteria.
c) In test A, the buffer tubes shall exhibit no more than X% compression compared to a section of test
sample not exposed to tensile load. Excess compression constitutes failure. The percent compression
is calculated using the following equation for “ovality.”
where
56
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
Annex E
(informative)
Bibliography
Bibliographical references are resources that provide additional or helpful material but do not need to be
understood or used to implement this standard. Reference to these resources is made for informational use only.
[B1] Accredited Standards Committee C2-2012, National Electrical Safety Code® (NESC®).11
[B3] ASTM B416, Standard Specification for Concentric-Lay-Stranded Aluminum-Clad Steel Conductors.13
[B4] ASTM B549, Standard Specification for Concentric-Lay-Stranded Aluminum Conductors, Aluminum-
Clad Steel Reinforced (ACSR/AW).
[B5] ASTM E29, Practice for Using Significant Digits in Test Data to Determine Conformance with
Specifications.
[B7] IEC 60793-2-10, Optical fibres—Part 2-10: Product specifications—Sectional specification for category
A1 multimode fibres.14
[B8] IEC 60793-2-50, Optical fibres—Part 2-50: Product specifications—Sectional specification for class B
single-mode fibres.
[B9] IEC 61089-am1, Amendment 1—Round Wire Concentric Lay Overhead Electrical Stranded Conductors.
[B12] IEEE Std 1138™-2009, IEEE Standard for Testing and Performance for Optical Ground Wire (OGPW)
for Use on Electric Utility Power Lines.15,16
[B13] ITU-T G.650.1, Definitions and Test Methods for Linear, Deterministic Attributes of Single-Mode
Fibre and Cable.17
[B14] ITU-T G.650.2, Definitions and Test Methods for Statistical and Non-Linear Related Attributes of
Single-Mode Fibre and Cable.
11
The NESC is available from the Institute of Electrical and Electronics Engineers, Inc. (http://standards.ieee.org/).
12
ANSI publications are available from the American National Standards Institute (http://www.ansi.org/).
13
ASTM publications are available from the American Society for Testing and Materials (http://www.astm.org/).
14
IEC publications are available from the International Electrotechnical Commission (http://www.iec.ch/) and the American National
Standards Institute(http://www.ansi.org/).
15
The IEEE standards or products referred to in Clause 2 are trademarks owned by the Institute of Electrical and Electronics Engineers,
Incorporated.
16
IEEE publications are available from the Institute of Electrical and Electronics Engineers (http://standards.ieee.org/).
17
ITU-T publications are available from the International Telecommunications Union (http://www.itu.int/).
57
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE Std 1591.2-2017
IEEE Standard for Testing and Performance of Hardware for All-Dielectric Self-Supporting (ADSS) Fiber Optic Cable
[B15] ITU-T G.651, Characteristics of a 50/125 µm Multimode Graded Index Optical Fibre Cable.
[B17] ITU-T G.653, Characteristics of a Dispersion-Shifted Single-Mode Optical Fibre and Cable.
[B18] ITU-T G.655, Characteristics of a Non-Zero Dispersion-Shifted Single-Mode Optical Fibre and Cable.
[B19] TIA-455-78-B, IEC 60793-1-40, Optical Fibres—Part 1-40: Measurement Methods and Test
Procedures—Attenuation.18
[B20] TIA-455-80-C, IEC 60793-1-44, Optical Fibres—Part 1-44: Measurement Methods and Test
Procedures—Cut-off Wavelength.
[B21] TIA/EIA-455-25-C, Repeated Impact Testing of Fiber Optic Cables and Cable Assemblies.19
[B22] TIA/EIA-455-46-A, Spectral Attenuation Measurement for Long-Length, Graded-Index Optical Fibers.
[B23] TIA/EIA-455-50-B, Light Launch Conditions for Long-Length Graded-Index Optical Fiber Spectral
Attenuation Measurements.
[B25] TIA/EIA-455-54-A, Mode Scrambler Requirements for Overfilled Launching Conditions to Multimode
Fibers.
[B29] TIA/EIA-455-78-A, Spectral Attenuation Cutback Measurement for Single-Mode Optical Fibers.
18
TIA publications are available from the Telecommunications Industry Association (http://tiaonline.org/).
19
TIA/EIA publications are available from the Telecommunications Industry Association (http://tiaonline.org/).
58
Copyright © 2018 IEEE. All rights reserved.
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.
IEEE
standards.ieee.org
Phone: +1 732 981 0060 Fax: +1 732 562 1571
© IEEE
Authorized licensed use limited to: UNIVERSITY OF ROCHESTER. Downloaded on June 06,2018 at 13:36:33 UTC from IEEE Xplore. Restrictions apply.