YS - K32
ENGLISH MANUAL
Suzhou Eshine Elevator Components CO.,Ltd.
www . eshine . com . cn
After-sales hotline:0512-82079650、82079651、82079654
CATALOGUE:
ONE:YS-K32 introduction…………………………………………..1
TWO:YS-K32 outline drawing………………………………………1
THREE:YS-K32 terminal introduction……………………………2
FOUR: YS-K32 replaced TD3200 steps……………………………2
1: Record the contact output type of original TD3200………….2
2:Wiring of YS-K32 ………………………………………………….2
3:Electrical debugging………………………………………………3
⑴:Motor tuning…………………………………………………3
⑵:Determine the direction of the encoder…………………3
⑶:Door wirth auto-learning……………………………………3
⑷:Door curve optimization……………………………………3
⑸:Set contact output type……………………………………5
⑹:into elevator system…………………………………………5
Appendix 1、Parameter list…………………………………………6
Appendix 2、Troubleshooting……………………………………...10
Appendix 3、 Operation of panel YS-P02/YS-P03………………11
ONE:YS-K32 introduction
YS-K32 is all developed by Suzhou Eshine Elevator Components CO., Ltd to
replace TD3200 breakdown machine of EMERSON.
First using YS-K32, please refer to the debugging part strictly (FOUR: YS-K32
replace TD3200 steps).
TWO:YS-K32 outline drawing
1
THREE:YS-K32 terminal introduction
In the field replacement process, in order to avoid line error, please remove the line of
TD3200 in turn and access to the corresponding interface of YS-K32.
Terminal Function description
L、N Single-phase 220Vac power input terminal
U、V、W Motor connection terminal
PE Protective earth point
Terminal Function description Specifications
X1 reserved
X2 Slow speed siginal
Input terminal Multi-function input terminals;
X3 External reset (RESET) signal input
Terminal command valid
X4 light curtain signal
when shorted with COM
Open and close OD OD command input terminal
terminal CD CD command input terminal
+24V,
User terminal 24V power supply(Terminal
P24 max output current: 100mA,
command valid when shorted with COM)
max frequency:35kHz
AB pulse input terminal of incremental PG
Output terminal A,B (A,B in YS-K32 corresponds to X1,X2 in
TD3200.)
PA,PB,PC Programmed contact output Contact rating
PAC,PC1 Door open position contact output AC:250V/2A;
PAC,PC2 Door close position contact output DC:30V/1A
FOUR:YS-K32 replaced TD3200 steps
1: Record the contact output type of original TD3200
View original TD3200 output signal set (F107 = 3 normally closed, F107 = 0 normally
open).
2:Wiring of YS-K32
Power off, remove the lines of TD3200 one by one and access to the corresponding
2
interface of YS-K32.
NOTICE: A, B in YS-K32 corresponds to X1,X2 in TD3200.
3 : Electrical debugging (according to Appendix 3 、 Operation of panel
YS-P02/YS-P03)
⑴ Motor tuning
First, remove the motor belt, make sure no-load state before motor tuning.
Set P0.01=3 to restore default parameters, check motor parameters and set the motor
parameters P1.02 ~ P1.04 (P1.02 Motor nominal current, P1.03 Motor nominal frequency,
P1.04 motor rated speed) according to motor nameplate. Set P0.06=0 by keyboard
control, and set P1.06=1 (Motor tune activate), press OD key, do motor parameter
identification. Do not install the motor belt until motor tuning finish.
Parameter identification results will be automatically stored into the controller
( P8.00 stator resistance, P8.01 rotor resistance, P8.02, P8.03 inductance, P8.04 mutual
inductance, P1.07 no-load current). And the parameter is not allowed artificial changes.
⑵ Determine the direction of the encoder
Power on again after power off, 4-digit display default shows encoder pulses.
Pull the door if 4-digit display the panel increase when door open and reduce when
door close. It means the direction of the encoder is all right. If opposite, negated P2.01
( Encoder direction).
⑶ Door width auto-learning
Set P2.05=1(door width auto-learning activated), press OD key, the door will
open-close-open-close and then stop.
Notice: If first close and then open the door, means motor lines reversed, just change
any two-phase wiring of motor and re-do door width auto-learning.
⑷ Door curve optimization
Press OD key, the door will open, press CD key, the door will close, check the door
curve. Set the rational door curve and door torque according to function parameters
3
(Appendix 1、Parameter list).
In general, you just need to change the door speed parameters (P3.03 opening
speed, P4.03 closing speed) and deceleration point parameters (P3.04 open deceleration
position, P4.04 close deceleration position). For heavy-duty doors, avoid stuck situation,
increase the low-speed parameters (P3.01 Open start speed, P3.06 Open creeping speed,
P4.01 Close start speed, P4.06 Close creeping speed1, P4.08 Close creeping speed2),
and door torque(P5.01 Open holding torque1,P5.05 Close holding torque1)
Open start dis Open Acc openning Open Dec
P3.00 P3.02 P3.03 P3.05 Open end T
T Dec time
P5.00 P5.03
Open Open Dec position Open
Open Open
Start P3.04 Creeping Holding
Acc
speed speed T1
Open Open
P3.02 P3.01 P3.06 P5.01 holding
T2
P5.02
T: torque
In open process, torques response as follows, first switch to P5.00 (open start
torque), then turn to P5.01 ( Open holding T1), until the door fully opened, and after the
waiting time P5.03 (T Dec time ) the torque turns to P5.02(Open holding T2).
In general , P5.00>P5.01>P5.02.
Close start dis Close Acc closing Close Dec
Close end Positin
P4.00 P4.02 P4.03 P4.05 T Dec time
P4.07 Close end T P5.07
P5.04
Close Dec position
Close Close Close Close
Close P4.04
Acc start Creeping creeping Holding
Close
speed speed1 speed2 T1
Holding
Close
P4.02 P4.01 P4.08 P5.05 T2
P4.06
P5.06
T: torque
4
In close process, torques response as follows, first switch to P5.04 (close start
torque),then turn to P5.05( Close holding T1), until the door fully close,and after the
waiting time P5.07 (T Dec time ) the torque turns to P5.06(Close holding T2).
In general , P5.04>P5.05>P5.06.
⑸ Set contact output type
Set P6.00(0:contact is normally closed; 1:contact is normally open) according to
original TD3200 output signal set.
⑹ into elevator system
Set P0.06=1 terminal mode, and let the elevator control the door.
5
Appendix 1、Parameter list
“○”: can be set on running status and stop status.
“×”: can be set on stop status.
“* ” : register value, can’t be set.
Parameter name Setting rage MS setting
code Asyn motor
P0.00 User password 0:no password 0 ○
1~9999:user password;
Use 2801 to reclear all the password
P0.01 Parameter batch program 0:no function 0 ×
Upload 1:parameter upload
Download 2:parameter download
Restore 3: synchronous motor
4:clear remembrance information
5:reserved
11:70W asynchronous motor
13:150W asynchronous motor
P0.02 Upload NO. 1~12 0 ×
P0.03 Download NO. 1~12 0 ×
P0.04 Parameter batch confirm 0,no function 0 ×
0~1,confirm
P0.05 Mode selection 0:debugging mode 1 ×
1:door control mode
P0.06 Controller mode 0: panel mode (OD: door open, CD: door 1 ×
close, STOP: stop)
1: terminal mode (OD signal: door open, CD
signal: door close)
2: Demo mode
P0.07 Max output frequency 1.00~ 99.99Hz 50.00Hz ×
P0.08 Two level code Input the two level code to see the protected 9888 ×
parameter, such as P7.00
P0.09 Control mode selection 0: YS-K32 motor control 0 ×
1: Asyn motor FVC control
2: syn motor FVC control
P1.00 Motor rating power 1~750W 250W ×
P1.01 Motor rating voltage 1~300V 220V ×
P1.02 Motor rating current 0.10~10.00A(check Motor nameplate) 0.55/0.90 ×
P1.03 Motor rating frequency 1.00Hz~99.99Hz 50.00Hz ×
P1.04 Motor rating speed 1~6000rpm 900rpm ×
P1.05 Drive ratio 1.00~9.99(useless for YS-K32, could be 4.67/5.6 ×
unset)
6
Parameter name Setting rage MS setting
code Asyn motor
P1.06 Motor tune 0:no function 0 ×
0→1:confirm
P1.07 Im 0.01~10.00A 0.40/0.60 ×
P1.08 Rs 0.01~99.99Ω 51.50 ×
P1.09 magnetic pole angle 0.0~359.9° 0.0 ×
P2.00 Encoder number 0~9999 100 ×
P2.01 Encoder direction 0:no change 1 ×
1:direction change
P2.02 Slow speed setting 0.01~15.00Hz 7.00Hz ○
P2.03 Initial speed setting 0.01~15.00Hz 7.00Hz ○
P2.04 Door width auto-learning speed 0.01~15.00Hz 7.00Hz ○
setting
P2.05 Door width auto-learning confirm 0:no function 0 ×
0 →1:confirm
P2.06 Door width(low bit) 0~9999(pulse number) 360 ×
P2.07 Door width(high bit) 0~9999(pulse number) 0 ×
P3.00 Open start distance 0~9999(pulse number) 45 ○
P3.01 Open start speed 0~15.00Hz 5.50Hz ○
P3.02 Open Acc time 0.1~99.9s 1.1s ○
P3.03 Open speed 0.00~P0.07 36.00Hz ○
P3.04 Open Dec position 50.0%~90.0%(door width) 70.0% ○
P3.05 Open Dec time 0.1~99.9s 1.0s ○
P3.06 Open creeping speed 0~15.00Hz 4.00Hz ○
P3.07 Open limit position 80.0~99.9%(door width) 95.0% ○
P3.08 Reopen area 10.0%~90.0%(door width) 90.0% ○
P4.00 Close start distance 0~9999(pulse number) 0 ○
P4.01 Close start speed 0~15.00Hz 5.00Hz ○
P4.02 Close Acc time 0.1~99.9s 1.1s ○
P4.03 Close speed 0.00~ P0.07 30.00Hz ○
P4.04 Close Dec position 50.0%~90.0%(door width) 66.0% ○
P4.05 Close Dec time 0.1~99.9s 1.0s ○
P4.06 Close creeping speed1 0~15.00Hz 4.5Hz ○
P4.07 Close end position 1~9999(pulse number) 40 ○
P4.08 Close creeping speed2 0~15.00Hz 5.5Hz ○
P4.09 Close limit position 1~9999(pulse number) 30 ○
P5.00 Open start torque 20.0%~150.0%(motor rating torque) 60.0% ○
P5.01 Open holding torque1 30.0%~150.0%(motor rating torque) 55.0% ○
P5.02 Open holding torque2 0.0%~100.0%(motor rating torque) 45.0% ○
P5.03 Open holding torque Dec time 0.1~999.9s 60.0s ○
P5.04 Close end torque 20.0%~150.0%(motor rating torque) 50.0% ○
7
Parameter name Setting rage MS setting
code Asyn motor
P5.05 Close holding torque1 30.0%~150.0%(motor rating torque) 45.0% ○
P5.06 Close holding torque2 0.0%~100.0%(motor rating torque) 35.0% ○
P5.07 Close holding torque Dec time 0.1~999.9s 60.0s ○
P5.08 Close passenger protection torque 0~150.0%(motor rating torque) 50.0% ○
P5.09 No Passenger protection area 0~50.0%(door width) 1.0% ○
P5.10 End torque under slow speed 30.0%~150.0%(motor rating torque) 50.0% ○
running
P5.11 open passenger protection torque 0~150.0%(motor rating torque) 0 ○
P5.12 open passenger protection time 0.1~9.9S 3.0 ○
P6.00 relay output logical selection 0:signal open represent that door arrived 0 ×
position, door position output (relay normally
closed contact)
1:signal closed represent that door arrived
position, door position output (relay normally
open contact)
this function is active for the PC1, PC2,
PA/PB/PC
P6.01 PA/PB/PC function selection 0:door position output 0 ×
1:reopen signal output
P6.02 Door position output setting 0.1~99.9% (door width) 90.0% ○
P6.03 Passenger protection Dec time 0.1~2.0s 0.5s ○
P6.04 Interval time of Demo running 0.1~360.0 3.0s ○
P6.05 Control running status 0:running 2 ○
holding selection 1:stop
P6.06 Special holding torque 0~150.0% (motor rating torque) 100% ○
P7.00 Kp(high speed) 10~3000 800 ○
P7.01 KI(high speed) 0(no function),1~1000 500 ○
P7.02 Kp(low speed) 10~3000 800 ○
P7.03 KI(low speed) 0(no function),1~1000 500 ○
P7.04 ASR switch frequency 0.00~99.99Hz(F1.04) 8.00Hz ○
P7.05 Current loop kp 10~9999 100 ○
P7.06 Current loop KI 0~9999 1000 ○
P7.07 Torque limited 0.0~200.0%(motor rating torque) 120.0% ○
P7.08 Speed filter 0~7 2 ○
P8.00~ reserved ○
P8.13
P8.14 First start mode selection 0-2 0 ○
8
Parameter name Setting rage MS setting
code Asyn motor
P9.00 fault 3 0:no record
P9.01 fault 2 1:E001
P9.02 fault 1 2:E002
3:E003
4:E004
5:reserved
6:E006
7:E007
8:E008
9~13:reserved
14:E014
15:reserved
16:E016
17:E017
18:E018
19~22:reserved
23:E023
24:reserved
25:E025
26:E026
-Lu-:low voltage
P9.03 Fault DC bus voltage 0~999V
P9.04 Fault output current 0.00~99.99A
P9.05 Fault output frequency 0.00Hz~99.99Hz
P9.06 Fault door position 0~65535
P9.07 Open-close count(low bit) 0~9999
P9.08 Open-close count(high bit) 0~9999(×10000)
P9.09 Running hour 0~ 23
P9.10 Running day 0~ 9999
P9.11 Module temperature 0.0~150.0
P9.12 Controller software version 1.00~99.99
P9.13 Panel software version 1.00~99.99
9
Appendix 2、Troubleshooting
sequence Fault name Fault Fault reason countermeasure
number code
0 Ready / / /
Low voltage Lu 1)power switch on/off 1)normal
2)input voltage is lower 2)check input voltage
3)wiring error 3)check wiring
1 Over voltage E001 1)input voltage is higher 1)check input voltage
2)Dec time is shorter 2)setting correct Dec time
3)wiring error 3)check wiring
2 Over current(hardware) E002 1)motor wiring error 1)check motor wiring
3 Over current(software) E003 2)motor parameter error 2)setting correct parameter
3)encoder error 3)check encoder and wiring
4)wiring error 4)check wiring
5)Acc/Dec time is shorter 5)setting correct Acc/Dec time
4 Encoder Loss E004 Encoder Loss Check encoder wiring
5 reserved E005 Keyboard compatibility issues contact manufacturer
6 Motor parameter tuning E006 1)incorrect motor rating parameter 1)setting correct motor rating parameter
error 2)motor wiring error 2)check motor wiring
7 Over load E007 1)over load 1)adjust machine
2)block in door 2)check door
8 Over heat E008 1)circuit error 1)contact manufacturer
2)blowhole jam 2)check controller blowhole
9 Reserved E009
10 Reserved E010
11 Reserved E011
12 Reserved E012
13 Reserved E013
14 Controller EEPROM E014 Circuit error contact manufacturer
read/write error
15 Reserved E015
16 Output phase loss E016 1)motor phase dissymmetry 1)check motor
2)motor wiring error 2)check motor wiring
17 IPM fault E017 1)circuit error 1)contact manufacturer
2)earth short 2)check wiring
18 Current detecting circuit E018 circuit contact manufacturer
fault
19 Reserved E019
20 Reserved E020
21 Reserved E021
22 Parameter setting error E022
23 Encoder error E023 1)encoder failure 1)check, change encoder
10
2)encoder wiring error 2)check encoder wiring
3)encoder pulse number setting error 3)setting correct encoder pulse number
24 Reserved E024
25 Panel EEPROM E025 Circuit error contact manufacturer
read/write error
26 Door width auto-learning E026 1)encoder failure 1)check, change
error 2)encoder wiring error 2)check encoder wiring
3)parameter P2.04 and P5.10 setting 3)setting correctly
Appendix 3、 Operation of panel YS-P02/YS-P03
1: Panel &display
YS-P02/YS-P03 keypad definition
Key Name Description
PRG Programme/escape Switch programming and monitoring, entry/exit programming
Set Confirm after parameter setting
Shift Selecting display parameter and shift bit
Up Number increase by degrees
Down Number descending
OD Door open command Door open operation command
CD Door close command Door close operation command
11
STOP Stop Stop operation; reset fault.
M Multi-function
YS-P02 pilot lamp
LED pilot lamp Lamp color Description
OD Green controller door open operation display lamp
CD Green controller door close operation display lamp
ALM Green controller alarm display lamp
LO/RE Green controller panel/control terminals control status display lamp
LOCK Green panel lock status display lamp
Hz Green frequency display unit lamp
A Green current display unit lamp
V Green voltage display unit lamp
RPM Green speed display unit lamp
% Green indicate “%”
2: Parameter setting and display
We need Panel YS-P02 to set and display parameter of YS-K03 controller.
There are four display status of the panel, just as follows:
(1) Display under stop status
Stop status display parameter: door position pulse, door arrived signal, speed
command, input terminals status, DC bus voltage. Press key to achieve every status
selection.
(2) Display under run status
Run status display parameter: door position pulse, door arrived signal, speed
command, output speed, output voltage, output current, output torque, DC bus voltage,
input terminal status. Press key to achieve every status selection.
(3) Example for setting parameter
Example: setting P1.01 to 25V.
STEP 1, press PRG key, panel display –P0-. The first menu;
STEP 2, press key, panel display –P1-. The internal parameter group;
STEP 3, press key, panel display P1.00.
STEP 4, press key, panel display P1.01.
12
STEP 5, press key, panel display 24V and into the function code;
STEP 6, press key, till panel display content is 25V.
STEP 7, press key, the parameter P1.01 has been changed to 25V and panel
display P1.02.
STEP 8, press PRG key, panel display –P1-. Return to the first menu;
STEP 9, press PRG key, panel display. Back to operation stop and monitoring status;
(4) Fault display
Panel display fault code when controller fault occurs. Reset fault by pressing STOP
key, panel returns to stop status display.
Fault display refers to appendix 2 troubleshooting.
3: Upload/download and restore parameter
YS-K03 door controller design has control curve parameter storage and batch upload
and download function to meet the requirement of high-efficient elevator debugging and
maintenance.
For the same door width and type door machine can use the same curve parameter
to achieve door control. Upload the experience curve parameter from the controller of
debugging good results to the panel. Then download from the panel to the same door
width and type door machine to achieve good door control.
Example: door 1 and door 2 have the same door width and door mechanical
configuration type. After debugging door 1 operation curve, upload the curve parameter
from controller A to the panel corresponding position and compile group number. Then
download the curve parameter from the panel corresponding group number position to the
controller B to achieve good door 2 control. It can batch copy to the same controller (3~n)
in the same way. If the operation test is normal it can be packed from factory. Parameter
batch upload and download function can improve the efficiency of producing and
maintaining.
13
The panel has 12 parameter macro spaces. You can upload parameter from the
controller to one of the 12 macro spaces or download supported experience parameter
from 12 macro spaces to the target controller to simple the parameter setting at
debugging.
Upload and download parameter range: P0.05~P8.15 (except P1.09 and P2.01);
Example: upload the controller parameter to 8 group space; when uploading, set
P0.01 to 2 and P0.02 to 8, then set P0.04 to 1 and confirm, panel displays , finally
parameter upload finished and into monitoring status.
Example: download the panel 7 group space parameter to the controller; when
downloading, set P0.01 to 2 and P0.03 to 7, then set P0.04 to 1 and confirm, panel
displays , finally parameter download finished and into monitoring status.
Special note: all parameters are the controller default parameter until upload the
panel parameter data.
14