Multi-DENCO®

TECHNICAL DATA
Type Code Multi-DENCO
Basic Unit

Example D M A 0 1 0 D P S I S 4 P E 1

Heat Exchanger
Product

Filter

Power Supply
Cooling System

Panel Configuration

Compressor Control

Humidifier
Range

Unit Size

Fan

Heating
Airflow Direction
D DENCO
M Multi-DENCO
A Air cooled
C Chilled water
X Split system
010 Size 010
018 Size 018
030 Size 030
045 Size 045
065 Size 065
092 Size 092
130 Size 130
D Downflow
U Upflow
P Front full height panel
F Front air inlet grille panel
L Front low level air discharge panel
S Standard heat exchanger
L Large heat exchanger
C CombiCool
I Inverter compressor scroll
F Fixed speed compressor scroll
N Not fitted
S Steam humidifier standard conductivity
L Steam humidifier low conductivity
H Steam humidifier high conductivity
N Not fitted
4 Filter G4
7 Filter F7
2 Filter washable G2
P EC plug fan
E Electric heating
T Modulating electric heating
W Hot water heating
R Remote signal 0-10 V
N Not fitted
1 3~ 400 V, N, PE, 50 Hz
7 3~ 400 V, N, PE, 60 Hz

NOTES!
Full selection typecode available on page 40.
Some options are only available in certain regions. Full type code is displayed above and particular com-
binations of options are not feasible. For further details please contact your local office.
FläktGroup reserves the right to modify/change/amend and update design and options without prior
notice.

2 PR-2014-0103-GB • Subject to Modifications • R3-05/2019


Multi-DENCO

Type Code .................................................................................................... 2


Basic Unit .............................................................................................................. 2
Range of Application ................................................................................... 4
Inverter Technology .............................................................................................. 4
Capacity Overview ....................................................................................... 5
Minimum and Maximum Values ............................................................................ 5
Components ................................................................................................. 6
Basic Unit .............................................................................................................. 6
Technical Data ............................................................................................. 9
A-Version .............................................................................................................. 9
C-Version ............................................................................................................ 11
A-Version + CombiCool ...................................................................................... 13
C-Version + CombiCool ...................................................................................... 15
Outdoor Units (Condensers) ............................................................................... 17
Accessories and Options ......................................................................... 19
Substructures ...................................................................................................... 19
Optional Components ......................................................................................... 21
Outdoor Components and Options ..................................................................... 25
Dimensions and Weights .......................................................................... 26
Size 010 - 130 ..................................................................................................... 26
Weights and Centre of Gravity ............................................................................ 27
Clearances ................................................................................................. 28
Service Area and Airflow Configuration .............................................................. 28
Frame Details ............................................................................................. 30
Top and Bottom Details ...................................................................................... 30
Schematics ................................................................................................. 31
Legend ................................................................................................................ 31
A-Version ............................................................................................................ 32
C-Version ............................................................................................................ 33
A-Version + CombiCool ...................................................................................... 34
System Layouts .................................................................................................. 34
Unit Variations ........................................................................................... 35
Inside Multi-DENCO ............................................................................................ 34
Connections ............................................................................................... 36
Mechanical and Electrical Connections .............................................................. 36
Customer Terminals ............................................................................................ 39
Notes ........................................................................................................... 40

PROTECTION NOTICES
The reproduction, distribution and utilization of this document as well as the communication of its contents to others without express
authorization is prohibited. Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of
a patent, utility model or design.

PR-2014-0103-GB • Subject to Modifications • R3-05/2019 3


Range of Application Multi-DENCO
Inverter Technology

The Multi-DENCO range utilises inverter technology in the compressors to ensure that
no energy is wasted in achieving the cooling demand of the room.
The compressors used in either a single compressor or tandem operation.

The technology brings several advantages:


– Variable control to reduce consumption by lower pressure difference in part load
compared to fixed speed compressors
– Greater accuracy of control with ability to control temperatures up to +/- 0.3 °C
– Reduction in the number of stop/starts required by the compressor;
therefore increasing the part's durability and extending it's total lifespan
– Self-regulation of oil return: compressors have the ability to monitor oil and time
spent running at lower speeds, they can then perform 'oil return boost' and protect
themselves from damage
– Quieter operation: reduction in number of starts means less noise created during
operation
– Permanent magnet motor technology provides greater efficiency compared to an
equivalent induction motor and enables the compressors to respond faster to speed
or load changes
– Lower minimum operating capacity: for example DMA065 can operate from capa-
cities as low as 8 kW, DMA130 can operate from 25 kW

4 PR-2014-0103-GB • Subject to Modifications • R3-05/2019


Multi-DENCO Capacity Overview
Minimum and Maximum Values

[kW] 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160

A-Version
010

C-Version
CombiCool

A-Version
018

C-Version
CombiCool

A-Version
030

C-Version
CombiCool

A-Version
045

C-Version
CombiCool

A-Version
065

C-Version
CombiCool

A-Version
092

C-Version
CombiCool

A-Version
130

C-Version
CombiCool

Pic. 1: Data calculated using 24 °C Supply Temperature, 45 % Relative Humidity, 45 °C Condensing Temperature.
FläktGroup reserves the right to modify data without prior notice.

Operating Limits – Airflow

Size Min Max

m3/h m3/s m3/h m3/s

10 1,197 0.33 2,993 0.83

18 2,059 0.57 5,148 1.43

30 3,456 0.96 8,640 2.40

45 5,089 1.41 12,722 3.53

65 7,335 2.04 18,338 5.09

92* 10,368 2.88 23,740 6.59

130* 14,904 4.14 33,100 9.19

* Airflow only valid for A-Version units. Other versions may vary.

Operating Limits – Temperature

Version Air Inlet Temperature Condensing Temp

Min Max

°C °C °C

A-Version 10 30 63

C-Version 10 40 N/A

CombiCool 10 40 63 / N/A

PR-2014-0103-GB • Subject to Modifications • R3-05/2019 5


Components Multi-DENCO
Basic Unit

Cabinet
The cabinet is made of aluminium profile frame painted black connected together using
aluminium triangular gussets and white laminate panels that are removable using a
screwdriver to allow access.
The front curved doors are hinged, but removable and houses the touchscreen display
in standard configuration.
The panels are insulated according to "O" class using non-eroding material and pro-
vide both acoustic and thermal insulation.

Cooling Coil
Inclined, high performance coil with rippled aluminium fins, spaced at 1.8 mm.
Aluminium intermediate drip tray with a stainless steel condensate drain tray with
U trap.
For A-Version: Copper tubes 4 rows deep
For C-Version: 4 row and 6 row coils available
For CombiCool: 3 row / 3 row configuration used
(A-Version + CombiCool or C-Version + CombiCool)

Fans
Direct driven variable speed high efficiency EC plug fan with 7 backward curved three
dimensional profiled blades.
Impeller optimally balanced according to ISO1940 and fan speed modulates on stan-
dard settings.
Variable speed regulation is performed using a 0-10 V controller signal.

Electronic Expansion Valve (EEV)


Used within A-Version (with or without CombiCool) units, the EEV comprises of a
valve, pressure sensor and temperature sensor.
The EEV has the ability to close itself in the event of a power failure by using a power
supply stored with the controller.
The EEV comes with an in built sight glass also.

6 PR-2014-0103-GB • Subject to Modifications • R3-05/2019


Multi-DENCO Components
Basic Unit

Electric Heaters
Units with electrical heating are equipped with sturdy sheated elements with stainless
steel finning and are rated to operate at black heat in order to prevent annealing con-
ditions and sparking.
Overheat protection is provided through a thermostat (Klixon).
The available heating duty is sufficient to prevent low supply temperatures in the dehu-
midification mode.

Air Filters
The filters have 30 % ASHRAE 52/76 standard, Eurovent 4/5, efficiency rate 90 %
(G4).
The filters are installed before the heat exchanger in the return air flow and are held by
quick release retaining clips/wire.
They are accessible from the front doors for replacement.

Humidifier
An electrode boiler humidifier can be installed into the bottom of the unit to allow humi-
dity to be controlled.
The humidifier generates steam using proportional regulation of untreated mains cold
water.
Electrode boiler humidifiers generate sterile, odourless and steam free of mineral
deposits.
The humidifier has an inlet hose connection and a water drain connection to remove
any remaining water.

Compressors and Inverter


Multi-DENCO units use variable speed inverter compressors.
These operate using R410A gas and have a high efficiency using a permanent magnet
and brushless DC Motors.
Within the unit, the configuration can be; single compressor, in tandem with a fixed
speed compressor or used in tandem with another inverter compressor.
The compressors are provided with Neoprene anti-vibrational mounts, motor protec-
tion against overcurrent and thermal overload and are able to perform periodical oil
reclaim on a cyclical basis.
Units using only fixed speed compressors are only available for sizes 010 and 018.

PR-2014-0103-GB • Subject to Modifications • R3-05/2019 7


Components Multi-DENCO
Basic Unit

Microprocessor Control
C5-12 capable of:
– Controlling temperature, humidity and performing auto-restart after power failure.
– Monitoring all digital and analogue inputs and outputs
– Acoustic alarms for issues with temperature, humidity, airflow, humidifier and com-
munication faults.
– Networking, sensor averaging and auto-changeover

Touch Screen Display


4.3" colour touch screen display that is mounted into one of the front doors of the units
(Standard Configuration).
The display settings are separated into three levels, allowing for password control from
access to system settings.
The displays are able to switch between several languages and alarms are displayed
in plain text.

Temperature and Humidity Sensor


Temperature and humidity readings fed back to the CCU are critical for controlling the
unit. There are several arrangements available with the sensors to ensure you know
the conditions of your room that can be classified into two types:
– Return Air – the sensor is taking measurements of air entering the CCU
from the room
– Supply Air – Air that is leaving/has left the CCU
The following arrangements are available:
1: Return Air: T&H inside the CCU / Supply Air: N/A
2: Return Air: T&H up to 10m from CCU / Supply Air: N/A
3: Return Air: T&H inside the CCU / Supply Air: T ONLY inside the CCU
4: Return Air: T&H inside the CCU / Supply Air: T ONLY up to10m from CCU
5: Return Air: T&H inside the CCU / Supply Air: T&H up to 10m from CCU
6: Return Air: T&H up to 10m from CCU / Supply Air: T ONLY inside the CCU
7: Return Air: T&H up to 10m from CCU / Supply Air: T&H up to 10m from CCU

8 PR-2014-0103-GB • Subject to Modifications • R3-05/2019


Multi-DENCO Technical Data
A-Version

Unit Size 010 018 030 045

Duty Required 2 % 100 100 70 100 100 70 100 100 70 100 100 70

Conditions

Air Inlet Temperature °C 24 26 26 24 26 26 24 26 26 24 26 26

Relative Humidity % 50 40 40 50 40 40 50 40 40 50 40 40

Air Volume m3/h 2,993 2,993 2,095 5,148 5,148 3,604 8,640 8,640 6,048 12,722 12,722 8,905

Air Volume m3/s 0.83 0.83 0.58 1.43 1.43 1.00 2.40 2.40 1.68 3.53 3.53 2.47

Cooling Duty 1

Gross Total Capacity kW 10.1 10.7 7.6 18.6 18.6 12.8 30.6 30.2 21.6 45.2 45.2 32.6

Net Total Capacity kW 9.5 10.1 7.3 17.0 16.9 12.2 29.1 28.7 20.9 42.7 42.6 31.5

SHR 0.98 1.00 1.00 0.95 1.00 1.00 0.96 1.00 1.00 0.96 1.00 1.00

EER Indoor 3.63 3.80 4.15 3.17 3.37 4.23 3.78 3.97 4.85 3.59 3.73 4.26

Power Consumption

Power Consumption (Cooling) kW 3.0 3.0 2.0 6.3 5.9 3.4 8.9 8.4 5.2 13.7 13.2 8.7

Compressor(s) kW 2.2 2.2 1.5 4.3 3.9 2.4 6.6 6.1 3.8 10.1 9.6 6.6

Indoor Fans kW 0.6 0.6 0.3 1.6 1.6 0.6 1.5 1.5 0.7 2.5 2.5 1.0

Outdoor Fans 4 kW 0.2 0.2 0.2 0.4 0.4 0.4 0.8 0.8 0.8 1.1 1.1 1.1

Misc Data

Minimum Capacity kW 4 7 8 8

Maximum Capacity kW 15 25 38 54

Fan Quantity 1 1 1 1

Number of Compressors 1 1 1 2

Compressor Configuration Inv Inv Inv Inv + Fix

Humidifier Capacity kg/h 3.0 3.0 8.0 8.0

Electrical Heating kW 4.0 6.0 9.0 12.0

Sound Power Level @ 100 % dB(A) 80 90 86 94

Air Filter (Standard G4)

Quantity 2 2 2 3

Height mm 490 620 1136 1084

Width mm 375 510 442 457

Depth mm 50 50 50 50

Connection Size

Discharge Line inch 1/2 5/8 5/8 3/4

Liquid Line inch 3/8 1/2 5/8 3/4

Humidifier Feed mm 15 15 15 15
3
Condensate Drain mm 22 2 x 22 2 x 22 2 x 22

Example Air Cooled Condenser 4

Unit Type DMOUCD013E DMOUCD026E DMOUCD050E DMOUCD075E

Quantity 1 1 1 1

Refrigeration Circuits 1 1 1 1

NOTES!
Data is taken from downflow configuration and is representational of upflow arrangement.
1: Units operating with a 45°C condensing temperature.
2: Duty required is a % of the nominal, i.e. 100% = unit size in kW.
3: "2 x" referes to two seperate connections for condensate; only if humidifier is fitted. When there is no humidifier
then only 1 connection is used. When "2x" is not used, one common drain incorporates both types.
4: Outdoor unit used are examples for the conditions used in this dataset.
For details of all outdoor units available please refer to the next section of this document.

PR-2014-0103-GB • Subject to Modifications • R3-05/2019 9


Technical Data Multi-DENCO
A-Version

Unit Size 065 092 130

Duty Required 2 % 100 100 70 100 100 70 100 100 70

Conditions

Air Inlet Temperature °C 24 26 26 24 26 26 24 26 26

Relative Humidity % 50 40 40 50 40 40 50 40 40

Air Volume m3/h 18,338 18,338 12,837 23,745 23,745 16,622 33,100 33,100 23,170

Air Volume m3/s 5.09 5.09 3.57 6.60 6.60 4.62 9.19 9.19 6.44

Cooling Duty 1

Gross Total Capacity kW 67.5 65.2 47.3 93.1 92.1 65.6 131.4 132.9 91.9

Net Total Capacity kW 63.4 61.1 45.6 85.8 84.9 62.8 120.7 122.1 87.7

SHR 0.95 1.00 1.00 0.94 1.00 1.00 0.94 1.00 1.00

EER Indoor 3.45 3.79 4.62 3.31 3.35 3.90 3.24 3.37 4.02

Power Consumption

Power Consumption (Cooling) kW 21.1 18.8 11.8 30.3 29.7 19.0 43.8 42.5 26.0

Compressor(s) kW 15.4 13.1 8.5 20.9 20.3 14.1 29.8 28.6 18.6

Indoor Fans kW 4.1 4.1 1.7 7.2 7.2 2.7 10.8 10.8 4.2

Outdoor Fans 4 kW 1.6 1.6 1.6 2.2 2.2 2.2 3.2 3.2 3.2

Misc Data

Minimum Capacity kW 8 18 25

Maximum Capacity kW 78 111 156

Fan Quantity 2 2 3

Number of Compressors 2 2 2

Compressor Configuration Inv + Inv Inv + Fix Inv + Fix

Humidifier Capacity kg/h 8.0 15.0 15.0

Electrical Heating kW 12.0 18.0 18.0

Sound Power Level @ 100 % dB(A) 92 97 97

Air Filter (Standard G4)

Quantity 3 3 5

Height mm 1284 2 x 463 2 x 463

Width mm 552 528 456

Depth mm 50 50 50

Connection Size

Discharge Line inch 7/8 1 1/8 1 3/8

Liquid Line inch 7/8 1 1/8 1 1/8

Humidifier Feed mm 15 15 15
3
Condensate Drain mm 2 x 22 22 22

Example Air Cooled Condenser 4

Unit Type DMOUCD050E DMOUCD075E DMOUCD100E

Quantity 2 2 2

Refrigeration Circuits 1 1 1

NOTES!
Data is taken from downflow configuration and is representational of upflow arrangement.
1: Units operating with a 45°C condensing temperature.
2: Duty required is a % of the nominal, i.e. 100% = unit size in kW.
3: "2 x" referes to two seperate connections for condensate; only if humidifier is fitted. When there is no humidifier
then only 1 connection is used. When "2x" is not used, one common drain incorporates both types.
4: Outdoor unit used are examples for the conditions used in this dataset.
For details of all outdoor units available please refer to the next section of this document.

10 PR-2014-0103-GB • Subject to Modifications • R3-05/2019


Multi-DENCO Technical Data
C-Version

Unit Size 010 018 030 045

Duty Required 2 % 100 100 70 100 100 70 100 100 70 100 100 70

Conditions

Air Inlet Temperature °C 24 26 26 24 26 26 24 26 26 24 26 26

Relative Humidity % 50 40 40 50 40 40 50 40 40 50 40 40

Air Volume m3/h 2,993 2,993 2,095 5,148 5,148 3,604 8,640 8,640 6,048 12,722 12,722 8,905

Air Volume m3/s 0.83 0.83 0.58 1.43 1.43 1.00 2.40 2.40 1.68 3.53 3.53 2.47

Cooling Duty 1

Gross Total Capacity kW 10.7 11.9 9.0 18.4 20.4 15.6 31.1 34.5 26.4 46.0 51.0 39.1

Net Total Capacity kW 10.1 11.2 8.7 16.8 18.8 15.0 29.6 33.0 25.7 43.5 48.5 38.0

SHR 0.94 1.00 1.00 0.94 1.00 1.00 0.94 1.00 1.00 0.94 1.00 1.00

Power Consumption

Power Consumption (Cooling) kW 0.6 0.6 0.3 1.6 1.6 0.6 1.5 1.5 0.7 2.5 2.5 1.0

Indoor Fans kW 0.6 0.6 0.3 1.6 1.6 0.6 1.5 1.5 0.7 2.5 2.5 1.0

Chilled Water Data

Flow Rate m3/h 1.80 2.20 1.40 3.20 3.60 2.50 5.40 5.80 4.70 7.90 8.60 6.80

Flow Rate l/s 0.50 0.61 0.39 0.89 1.00 0.69 1.50 1.61 1.31 2.19 2.39 1.89

Unit Pressure Drop kPa 44 59 30 45 55 30 46 54 34 33 40 25

Other Data

Fan Quantity 1 1 1 1

Humidifier Capacity kg/h 3.0 3.0 8.0 8.0

Electrical Heating kW 4.0 6.0 9.0 12.0

Sound Power Level @ 100% dB(A) 80 90 86 94

Air Filter (Standard G4)

Quantity 2 2 2 3

Height mm 490 620 1136 1084

Width mm 375 510 442 457

Depth mm 50 50 50 50

Connection Size

Chilled Water Inlet mm 22 28 35 42

Chilled Water Outlet mm 22 28 35 42

Humidifier Feed mm 15 15 15 15

Condensate Drain mm 22 22 22 22

NOTES!
Data is taken from downflow configuration and is representational of upflow arrangement.
Units are using a 3 way valve with bypass. Other options are available.
1: Units operating a 5K approach (7/12), 100% water with a standard coil.
2: Duty required is a % of the nominal, i.e. 100% = unit size in kW.

PR-2014-0103-GB • Subject to Modifications • R3-05/2019 11


Technical Data Multi-DENCO
C-Version

Unit Size 065 092 130

Duty Required 2 % 100 100 70 100 100 70 100 100 70

Conditions

Air Inlet Temperature °C 24 26 26 24 26 26 24 26 26

Relative Humidity % 50 40 40 50 40 40 50 40 40

Air Volume m3/h 18,338 18,338 12,837 23,745 23,745 16,622 33,100 33,100 23,170

Air Volume m3/s 5.09 5.09 3.57 6.60 6.60 4.62 9.19 9.19 6.44

Cooling Duty 1

Gross Total Capacity kW 67.8 75.1 57.5 98.9 107.2 81.1 135.6 147.3 111.6

Net Total Capacity kW 63.7 71.0 55.8 84.0 100.0 78.3 124.8 136.5 107.4

SHR 0.94 1.00 1.00 0.92 1.00 0.99 0.93 1.00 0.99

Power Consumption

Power Consumption (Cooling) kW 4.1 4.1 1.7 7.2 7.2 2.7 10.8 10.8 4.2

Indoor Fans kW 4.1 4.1 1.7 7.2 7.2 2.7 10.8 10.8 4.2

Chilled Water Data

Flow Rate m3/h 11.50 13.00 9.70 16.90 18.40 13.70 23.40 25.20 19.10

Flow Rate l/s 3.19 3.61 2.69 4.69 5.11 3.81 6.50 7.00 5.31

Unit Pressure Drop kPa 35 43 25 49 56 32 44 50 30

Other Data

Fan Quantity 2 2 3

Humidifier Capacity kg/h 8.0 15.0 15.0

Electrical Heating kW 12.0 18.0 18.0

Sound Power Level @ 100% dB(A) 92 97 97

Air Filter (Standard G4)

Quantity 3 4 5

Height mm 1284 2 x 463 2 x 463

Width mm 552 495 523

Depth mm 50 50 50

Connection Size

Chilled Water Inlet mm 54 54 67

Chilled Water Outlet mm 54 54 67

Humidifier Feed mm 15 15 15

Condensate Drain mm 22 22 22

NOTES!
Data is taken from downflow configuration and is representational of upflow arrangement.
Units are using a 3 way valve with bypass. Other options are available.
1: Units operating a 5K approach (7/12), 100% water with a standard coil.
2: Duty required is a % of the nominal, i.e. 100% = unit size in kW.

12 PR-2014-0103-GB • Subject to Modifications • R3-05/2019


Multi-DENCO Technical Data
A-Version + CombiCool

Unit Size 010 018 030 045


2
Duty Required % 100 100 70 100 100 70 100 100 70 100 100 70
Conditions
Air Inlet Temperature °C 24 26 26 24 26 26 24 26 26 24 26 26
Relative Humidity % 50 40 40 50 40 40 50 40 40 50 40 40
Air Volume m3/h 2,993 2,993 2,095 5,148 5,148 3,604 8,640 8,640 6,048 12,722 12,722 8,905
Air Volume m3/s 0.83 0.83 0.58 1.43 1.43 1.00 2.40 2.40 1.68 3.53 3.53 2.47
Cooling Duty 1
Gross Total Capacity kW 10.2 10.5 7.3 18.9 18.5 13.4 30.6 31.0 22.0 46.1 45.3 32.4
Net Total Capacity kW 9.5 9.8 6.9 17.1 16.8 12.8 28.9 29.3 21.3 41.5 42.6 31.3
SHR 0.92 1.00 1.00 0.90 1.00 1.00 0.91 1.00 1.00 0.90 1.00 1.00
EER 3.24 3.31 4.00 2.94 3.09 3.89 3.27 3.50 4.38 3.21 3.43 4.01
CombiCool 2
Gross Total Capacity kW 9.1 10.4 8.0 15.5 17.6 13.6 26.0 29.6 23.0 38.4 43.7 33.9
Gross Sensible Capacity kW 8.7 10.4 8.0 14.8 17.6 13.6 24.9 29.6 23.0 36.7 43.7 33.9
SHR 0.96 1.00 1.00 0.95 1.00 1.00 0.96 1.00 1.00 0.96 1.00 1.00
Flow Rate m3/h 1.44 1.80 1.44 2.52 2.88 2.16 4.32 5.04 3.96 6.48 7.56 5.76
Flow Rate l/s 0.40 0.50 0.40 0.70 0.80 0.60 1.20 1.40 1.10 1.80 2.10 1.60
Unit Pressure Drop kPa 38 53 33 31 40 24 33 43 27 30 39 23
Power Consumption
Power Consumption (Cooling) kW 3.40 3.40 2.00 6.80 6.4 3.8 10.2 9.7 5.8 15.4 14.3 9.2
Compressor(s) kW 2.50 2.50 1.50 4.70 4.3 2.8 7.7 7.2 4.3 11.6 10.5 7.0
Indoor Fans kW 0.70 0.70 0.30 1.70 1.7 0.6 1.7 1.7 0.7 2.7 2.7 1.1
Outdoor Fans 5 kW 0.20 0.20 0.20 0.40 0.4 0.4 0.8 0.8 0.8 1.1 1.1 1.1
Misc Data
Min. Capacity kW 4 7 8 8
Max. Capacity kW 15 25 38 54
Fan Quantity 1 1 1 1
Number of Compressors 1 1 1 2
Compressor Configuration Inv Inv Inv Inv + Fix
Humidifier Capacity kg/h 3.0 3.0 8.0 8.0
Electrical Heating kW 4.0 6.0 9.0 12.0
Sound Power Level @ 100% dB(A) 81 91 87 94
Air Filter (Standard G4)
Quantity 2 2 2 3
Height mm 490 620 1136 1084
Width mm 375 510 442 457
Depth mm 50 50 50 50
Connection Size
Discharge Line inch 1/2 5/8 1 3/8 3/4
Liquid Line inch 3/8 1/2 1 3/8 3/4
CombiCool Inlet mm 22 28 35 42
CombiCool Outlet mm 22 28 35 42
Humidifier Feed mm 15 15 15 15
Condensate Drain 4 mm 22 2 x 22 2 x 22 2 x 22
Example Air Cooled Condenser 5
Unit Type DMOUCD013E DMOUCD026E DMOUCD050E DMOUCD075E
Quantity 1 1 1 1
Refrigeration Circuits 1 1 1 1

NOTES!
Data is taken from downflow configuration and is representational of upflow arrangement.
1: Units operating with a 45°C condensing temperature.
2: Units operating a 5 K approach (7/12), 100% water with a standard coil.
3: Duty required is a % of the nominal, i.e. 100% = unit size in kW.
4: "2 x" referes to two seperate connections for condensate; if humidifier is fitted. When "2x" is not used, one common
drain incorporates both typest.
5: Outdoor unit used are examples for the conditions used in this dataset. For details of all outdoor units available
please refer to the next section of this document.

PR-2014-0103-GB • Subject to Modifications • R3-05/2019 13


Technical Data Multi-DENCO
A-Version + CombiCool

Unit Size 065 092 130


2
Duty Required % 100 100 70 100 100 70 100 100 70
Conditions
Air Inlet Temperature °C 24 26 26 24 26 26 24 26 26
Relative Humidity % 50 40 40 50 40 40 50 40 40
Air Volume m3/h 18,338 18,338 12,837 23,745 23,745 16,622 33,100 33,100 23,170
Air Volume m3/s 5.09 5.09 3.57 6.60 6.60 4.62 9.19 9.19 6.44
Cooling Duty 1
Gross Total Capacity kW 65.8 65.5 47.9 94.7 93.2 65.9 133.7 131.2 92.3
Net Total Capacity kW 59.4 61.0 46.1 83.7 86.0 63.0 117.9 120.6 87.9
SHR 0.90 1.00 1.00 0.88 0.97 1.00 0.88 0.97 1.00
EER 3.13 3.33 4.22 3.00 3.14 3.70 3.01 3.06 3.78
CombiCool 2
Gross Total Capacity kW 56.7 64.4 50.0 74.1 83.9 65.8 107.5 120.9 95.6
Gross Sensible Capacity kW 54.2 64.4 50.0 70.7 83.9 65.8 102.4 120.9 95.6
SHR 0.96 1.00 1.00 0.95 1.00 1.00 0.95 1.00 1.00
Flow Rate m3/h 9.72 11.16 8.64 12.60 14.40 11.16 18.36 20.52 16.56
Flow Rate l/s 2.70 3.10 2.40 3.50 4.00 3.10 5.10 5.70 4.60
Unit Pressure Drop kPa 30 38 24 28 35 22 34 43 28
Power Consumption
Power Consumption (Cooling) kW 22.6 21.3 13.0 33.8 31.9 20.0 47.5 46.0 27.5
Compressor(s) kW 16.5 15.2 9.6 24.4 22.5 14.9 33.7 32.2 20.0
Indoor Fans kW 4.5 4.5 1.8 7.2 7.2 2.9 10.7 10.7 4.4
Outdoor Fans 5 kW 1.6 1.6 1.6 2.2 2.2 2.2 3.1 3.1 3.1
Misc Data
Min. Capacity kW 8 18 25
Max. Capacity kW 78 111 156
Fan Quantity 2 2 3
Number of Compressors 2 2 2
Compressor Configuration Inv + Inv Inv + Fix Inv + Fix
Humidifier Capacity kg/h 8.0 15.0 15.0
Electrical Heating kW 12.0 18.0 18.0
Sound Power Level @ 100% dB(A) 93 96 97
Air Filter (Standard G4)
Quantity 3 3 5
Height mm 1284 2 x 463 2 x 463
Width mm 552 528 456
Depth mm 50 50 50
Connection Size
Discharge Line inch 7/8 1 1/8 1 3/8
Liquid Line inch 7/8 1 1/8 1 3/8
Chilled Water Inlet mm 54 54 67
Chilled Water Out mm 54 54 67
Humidifier Feed mm 15 15 15
Condensate Drain 4 mm 2 x 22 22 22
5
Example Air Cooled Condenser
Unit Type DMOUCD050E DMOUCD075E DMOUCD100E
Quantity 2 2 2
Refrigeration Circuits 1 1 1

NOTES!
Data is taken from downflow configuration and is representational of upflow arrangement.
1: Units operating with a 45°C condensing temperature.
2: Units operating a 5 K approach (7/12), 100% water with a standard coil.
3: Duty required is a % of the nominal, i.e. 100% = unit size in kW.
4: "2 x" referes to two seperate connections for condensate; if humidifier is fitted. When "2x" is not used, one common
drain incorporates both typest.
5: Outdoor unit used are examples for the conditions used in this dataset. For details of all outdoor units available
please refer to the next section of this document.

14 PR-2014-0103-GB • Subject to Modifications • R3-05/2019


Multi-DENCO Technical Data
C-Version + CombiCool

Unit Size 010 018 030 045

Duty Required 2 % 100 100 70 100 100 70 100 100 70 100 100 70

Conditions

Air Inlet Temperature °C 24 26 26 24 26 26 24 26 26 24 26 26

Relative Humidity % 50 40 40 50 40 40 50 40 40 50 40 40

Air Volume m3/h 2,993 2,993 2,095 5,148 5,148 3,604 8,640 8,640 6,048 12,722 12,722 8,905

Air Volume m3/s 0.83 0.83 0.58 1.43 1.43 1.00 2.40 2.40 1.68 3.53 3.53 2.47
1
Cooling Duty

Gross Total Capacity kW 10.7 13.5 10.5 15.5 17.6 13.6 26.1 29.7 23.1 38.4 43.7 33.9

Net Total Capacity kW 10.0 12.8 10.2 13.7 15.9 13.0 24.4 28.0 22.4 35.7 41.0 32.8

SHR 0.94 0.88 0.83 0.96 1.00 1.00 0.96 1.00 1.00 0.96 1.00 1.00
3
Flow Rate m /h 1.80 2.16 1.80 2.52 2.88 2.16 4.32 5.04 3.96 6.48 7.56 5.76

Flow Rate l/s 0.50 0.60 0.50 0.70 0.80 0.60 1.20 1.40 1.10 1.80 2.10 1.60

Unit Pressure Drop kPa 44 67 44 31 40 24 35 45 28 30 39 23


1
CombiCool

Gross Total Capacity kW 9.1 11.5 9.1 15.5 17.6 13.6 26.0 29.6 23.0 38.4 43.7 33.9

Net Total Capacity kW 8.7 10.4 8.1 14.8 17.6 13.6 24.9 29.6 23.0 36.7 43.7 33.9

SHR 0.96 0.90 0.89 0.95 1.00 1.00 0.96 1.00 1.00 0.96 1.00 1.00

Flow Rate m3/h 1.44 2.16 1.44 2.52 2.88 2.16 4.32 5.04 3.96 6.48 7.56 5.76

Flow Rate l/s 0.40 0.60 0.40 0.70 0.80 0.60 1.20 1.40 1.10 1.80 2.10 1.60

Unit Pressure Drop kPa 38 70 38 31 40 24 33 43 27 30 39 23

Power Consumption

Power Consumption (Cooling) kW 0.7 0.7 0.3 1.7 1.7 0.6 1.7 1.7 0.7 2.7 2.7 1.1

Indoor Fans kW 0.7 0.7 0.3 1.7 1.7 0.6 1.7 1.7 0.7 2.7 2.7 1.1

Other Data

Fan Quantity 1 1 1 1

Humidifier Capacity kg/h 3.0 3.0 8.0 8.0

Electrical Heating kW 4.0 6.0 9.0 12.0

Sound Power Level @ 100% dB(A) 81 91 87 94

Air Filter (Standard G4)

Quantity 2 2 2 3

Height mm 490 620 1136 1084

Width mm 375 510 442 457

Depth mm 50 50 50 50

Connection Size

Chilled Water Inlet mm 22 28 35 42

Chilled Water Outlet mm 22 28 35 42

CombiCool Inlet mm 22 28 35 42

CombiCool Outlet mm 22 28 35 42

Humidifier Feed mm 15 15 15 15

Condensate Drain mm 22 22 22 22

NOTES!
Data is taken from downflow configuration and is representational of upflow arrangement.
Units are using a 3 way valve with bypass. Other options are available.
1: Units operating a 5 degrees approach (7/12), 100% water with a CombiCool coil.
2: Duty required is a % of the nominal, i.e. 100% = unit size in kW.

PR-2014-0103-GB • Subject to Modifications • R3-05/2019 15


Technical Data Multi-DENCO
C-Version + CombiCool

Unit Size 065 092 130

Duty Required 2 % 100 100 70 100 100 70 100 100 70

Conditions

Air Inlet Temperature °C 24 26 26 24 26 26 24 26 26

Relative Humidity % 50 40 40 50 40 40 50 40 40

Air Volume m3/h 18,338 18,338 12,837 23,745 23,745 16,622 33,100 33,100 23,170

Air Volume m3/s 5.09 5.09 3.57 6.60 6.60 4.62 9.19 9.19 6.44
1
Cooling Duty

Gross Total Capacity kW 56.7 64.4 50.0 83.1 92.7 71.5 116.0 130.0 100.2

Net Total Capacity kW 52.3 59.9 48.2 78.0 87.7 69.5 108.6 122.6 97.2

SHR 0.96 1.00 1.00 0.95 1.00 1.00 0.95 1.00 1.00
3
Flow Rate m /h 9.72 11.16 8.64 14.04 15.84 12.24 19.80 22.32 17.28

Flow Rate l/s 2.70 3.10 2.40 3.90 4.40 3.40 5.50 6.20 4.80

Unit Pressure Drop kPa 30 38 24 37 46 28 42 53 32


1
CombiCool

Gross Total Capacity kW 56.7 64.4 50.0 83.1 92.7 71.5 116.0 130.0 100.2

Net Total Capacity kW 54.2 64.4 50.0 78.8 92.7 71.5 110.2 130.0 100.2

SHR 0.96 1.00 1.00 0.95 1.00 1.00 0.95 1.00 1.00
3
Flow Rate m /h 9.72 11.16 8.64 14.04 15.84 12.24 19.80 22.32 17.28

Flow Rate l/s 2.70 3.10 2.40 3.90 4.40 3.40 5.50 6.20 4.80

Unit Pressure Drop kPa 30 38 24 37 46 28 42 53 32

Power Consumption

Power Consumption (Cooling) kW 4.5 4.5 1.8 5.1 5.1 2.0 7.3 7.3 2.9

Indoor Fans kW 4.5 4.5 1.8 5.1 5.1 2.0 7.3 7.3 2.9

Other Data

Fan Quantity 2 2 3

Humidifier Capacity kg/h 8.0 15.0 15.0

Electrical Heating kW 12.0 18.0 18.0

Sound Power Level @ 100% dB(A) 93 94 95

Air Filter (Standard G4)

Quantity 3 4 5

Height mm 1284 2 x 463 2 x 463

Width mm 552 495 523

Depth mm 50 50 50

Connection Size

Chilled Water Inlet mm 54 54 67

Chilled Water Outlet mm 54 54 67

CombiCool Inlet mm 54 54 67

CombiCool Outlet mm 54 54 67

Humidifier Feed mm 15 15 15

Condensate Drain mm 22 22 22

NOTES!
Data is taken from downflow configuration and is representational of upflow arrangement.
Units are using a 3 way valve with bypass. Other options are available.
1: Units operating a 5 degrees approach (7/12), 100% water with a CombiCool coil.
2: Duty required is a % of the nominal, i.e. 100% = unit size in kW.

16 PR-2014-0103-GB • Subject to Modifications • R3-05/2019


Multi-DENCO Technical Data
Outdoor Units (Condensers)

Unit Size DMOUCD008 DMOUCD013 DMOUCD021 DMOUCD026

2
Type EC Max EC AC EC Max EC AC EC Max EC AC EC Max EC AC

Conditions

Heat of Rejection 1 kW –4 6.8 6.8 15.2 11.3 11.3 23.1 16.8 16.8 27.3 22.8 22.8

3
Airflow m /h – 2,590 2,590 7,100 4,104 4,104 10,900 6,840 6,840 12,000 8,208 8,208

Airflow m3/s – 0.72 0.72 1.97 1.14 1.14 3.03 1.90 1.90 3.33 2.28 2.28

Fan Data

Power Consumption kW – 0.2 0.2 0.8 0.2 0.2 1.0 0.3 0.5 1.0 0.3 0.5

Speed 1/min – – 4 – 1,439 877 – 1,189 770 – 1,197 825 –

Sound Power Level dB(A) – 65 65 82 70 71 79 70 76 79 71 76

Misc Data

Heat Exchanger Face Area m2 0.25 0.49 0.72 1.00

Heat Exchanger Rows 3 3 3 3

Fan Quantity 1 1 1 1

Fan Diameter mm 450 500 630 630

Connection Size

Discharge Line inch 5/8 3/4 7/8 1 1/8

Liquid Line inch 5/8 3/4 7/8 1 1/8

Dimensions and Weight

Length mm 645 825 975 1,125

Width mm 571 717 867 1,021

Height mm 690 790 810 945

Weight 3 mm 35 45 50 70

NOTES!
1: Units operating with a 45°C condensing temperature in a 32 °C ambient temperatures.
2: "EC Max" represents EC fan configuration at Maximum airflow. "EC" data is at the same airflow as "AC" for direct
comparision.
3: For EC fans only. AC fans may vary.
4: Data currently unavailable.
AC Fans only available in certain regions to to ErP legislation. Please contact your region's sales office for further
details.

PR-2014-0103-GB • Subject to Modifications • R3-05/2019 17


Technical Data Multi-DENCO
Outdoor Units (Condensers)

Unit Size DMOUCD032 DMOUCD050 DMOUCD075 DMOUCD100

2
Type EC Max EC AC EC Max EC AC EC Max EC AC EC Max EC AC

Conditions

Heat of Rejection 1 kW 31.1 24.5 24.5 52.3 44.1 44.1 77.4 58.3 58.3 112.9 86.7 86.7

3
Airflow m /h 12,400 8,748 8,748 23,900 15,840 15,840 34,900 22,356 22,356 47,800 31,680 31,680

Airflow m3/s 3.44 2.43 2.43 6.64 4.40 4.40 9.69 6.21 6.21 13.28 8.80 8.80

Fan Data

Power Consumption kW 0.9 0.3 0.5 1.9 0.6 1.0 3.0 0.9 1.6 3.8 1.2 2.1

Speed 1/min 1.198 844 – 1.197 802 – 1.199 784 – 1.197 802 –

Sound Power Level dB(A) 79 72 76 82 74 79 84 75 81 85 77 82

Misc Data

Heat Exchanger Face Area m2 1.21 1.96 2.60 3.92

Heat Exchanger Rows 3 3 3 3

Fan Quantity 1 2 3 4

Fan Diameter mm 630 630 630 630

Connection Size

Discharge Line inch 1 1/8 1 3/8 1 3/8 1 5/8

Liquid Line inch 1 1/8 1 3/8 1 3/8 1 5/8

Dimensions and Weight

Length mm 1,225 2,095 2,760 2,415

Width mm 1,121 1,067 1,067 2,440

Height mm 945 945 945 1,045

Weight 3 mm 80 135 210 412

NOTES!
1: Units operating with a 45°C condensing temperature in a 32 °C ambient temperatures.
2: "EC Max" represents EC fan configuration at Maximum airflow. "EC" data is at the same airflow as "AC" for direct
comparision.
3: For EC fans only. AC fans may vary.
4: "Data currently unavailable.
AC Fans only available in certain regions to to ErP legislation. Please contact your region's sales office for further
details.

18 PR-2014-0103-GB • Subject to Modifications • R3-05/2019


Multi-DENCO Accessories and Options
Substructures

Substructures

Plinth
If an upflow unit is required for a room without a raised floor, a plinth should be used to
allow space underneath the unit, so that refrigerant and drain connections can be
made through the side of the plinth.
The standard plinth is 200 mm tall and made of the same frame and panel construction
as the close control unit, therefore give a natural looking height extension.
The panels are fixed to the unit using the same screw (crosshead) as the unit panel so
only one tool is required to remove all panels.

Base stand
For units to be used with a raised floor (upflow and downflow), a base stand should be
used underneath the close control unit.
The base stand comes complete with adjustable feet (+/- 25 mm available). The sur-
face between the base stand and the close control unit is lined with a 3mm semi-hard
gasket.
The height of the base stand frame can be from a minimum of 300 mm tall.
Other versions of the base stand design are available on special request: such as
sheeted and lined sides, scoops and grilles.

Raised Floor Tile Support


To complement the use of a base stand, raise floor tile support can be added to the
base stand to allow for the floor tiles that are closest to the close control unit to be sup-
ported.

Ceiling Connection Duct


For units that wish to connect with a suspending ceiling, whether it is to receive the air
or supply the air (upflow and downflow), a ceiling connection duct can be used to create
this air path.
For downflow units, the ceiling connection duct could be used instead to draw warmer
air from a higher position within the room that will help improve efficiency of the return
air temperature.
The ceiling connection duct is made of the same material as the unit panels. Heights
of ceiling connection ducts are made to specification and they can bolt onto the top of
the close control unit through a service panel on either side.

PR-2014-0103-GB • Subject to Modifications • R3-05/2019 19


Accessories and Options Multi-DENCO
Substructures

Horizontal Air Discharge


For upflow units that do not have ceiling voids, a horizontal air discharge section can
be used to change the airflow direction.
It consists of a sheet metal box (same colour and material as the unit panels) with a
double deflection grille fitted in either the front panel (1 way blow) or the front panel and
both side panels (3 way blow).
The assembly is bolted onto the top of the close control unit through the frame. This
can be accessed via the service panels on either side of the unit.

Shut Off Damper


A top mounted damper is available for downflow units to restrict or stop air entering into
the close control unit.
This control is linked to the unit's controller and can be made to open/close depending
on the unit's operation or can close if a critical alarm is generated. It can also be linked
to fire alarm shutdown routines to protect your units.

Protection Grille
This is the standard grille that is placed directly on top of a close control unit to protect
individuals from gaining access to the rotating fan blades during operation.
There are two variations depending on the unit's airflow direction:
Upflow: Top Air Discharge Protection Grille
Downflow: Top Air Inlet Protection Grille

Front Low Level Air Discharge Panels


For 'in room' cooling of air, low level grilles can be mounted into the front doors of the
unit. Discharge grilles are used for downflow units and intake grilles are used for
upflow units.
Both grilles are double deflection and are a standard size throughout the range.
This option is required when there is no raised floor.

Under Unit Drip Tray


Top protect the floor underneath a close control unit from any condensation a drip tray
can be mounted underneath.
This drip tray can be used in a raised floor (underneath a base frame) or with a plinth.
It is designed to hold a small volume of water and should be used along with water
detection tape or spot sensor to prevent any significant build-up of water.

20 PR-2014-0103-GB • Subject to Modifications • R3-05/2019


Multi-DENCO Accessories and Options
Optional Components

Condensate Pump
In situations where it is not possible to use gravity operated drains, a condensate pump
is available to remove water collected by the condensate tray underneath the cooling
coil.
For any given unit there are two types of condensate pumps: 'Hot Water' for close con-
trol units that have humidifiers and 'Cold Water' for those without humidifiers.

Special Colours
The Multi-DENCO range is able to accommodate a variety of different panel colours,
including accessories.
For standard configuration, the frame is black and the panels are white. Colour
swatches can be provided upon request. Please contact your regional sales office for
details.
For special paint finish please provide a BS number, RAL-number or similar, if availa-
ble otherwise please provide swatches of panel requirements.

Filters
The CCU comes with standard EU4 filters (G4) to protect the coil against dust and dirt.
As an option, fine dust filters of EU7 grade (F7) filters are an alternative available with
all units.

Shut Off Valves (SOV)


Enable easy isolation of parts of your refrigerant circuit with the use of shut off valves.
As standard a SOV is provided on the liquid line, but as an additional option, SOVs can
be installed on the suction and discharge line, allowing for service or maintenance
without evacuation of the system.
Similar valves are available on entry/exit position of chilled water systems.

Refrigerant Leak Detection


A sensor to detect any refrigerant particles present in the airflow through the unit.
Once detected an alarm can be generated and shown on the unit's display.

PR-2014-0103-GB • Subject to Modifications • R3-05/2019 21


Accessories and Options Multi-DENCO
Optional Components

Service Connections
Three Schrader connection points that utilise capillaries to each line, enabling use of
testing points without the removal of commissioning plates.

Interfaces
C5-12 controllers have inbuilt Modbus (RS485) connectivity.
Additional interfaces are able to be installed into the controller.
Protocols availble are as follows:
– BACnet SNMP Webpage Interface
– BACnet MS/TP Interface
– LonWorks Interface
– Trend BMS Interface is available as a separate accessory.

Water Detection
5 m long water sensing tapes can be installed below the unit to monitor any leaks or
excessive condensation, along with a sensor that detects when too much water is wit-
hin the tray.
Options for spot sensors (of varying numbers) are available to allow for a different
sample of water detection.

Run Status Volt Free Contact (VFC)


A volt free contact can be added to communicate the operating status of the unit to the
controller or onto a BMS system.

Air Volume Monitoring


Airflow measurements using a pressure sensor located within the fan's inlet ring to pro-
duce live readings of air pressure that can be shown on the unit's display.

Energy Monitoring
Power meter with current transformer for each phase with the controller monitoring
voltage, current, power and total unit power consumption.
Values taken by this module are also viewable through the touchscreen display to give
live readings.
Values from the energy monitoring option are accessible via a BMS system.

22 PR-2014-0103-GB • Subject to Modifications • R3-05/2019


Multi-DENCO Accessories and Options
Optional Components

Automatic Transfer Switch (ATS)


A power switch to allow for the automatic change over between two power supplies
upon the failure of one of the power supplies.
The equipment also has a manual override feature.

Smoke Detection
A sensor to detect smoke particles in the airflow through the unit.
Upon detection an alarm can be generated to shut down the unit and close the
Air Damper (if fitted/required).

Pipework Connections
Several pipework connections are available for chilled water units (C-Version and
CombiCool):
1 Solder Connection
2 British Standard Pipe (BSP) Male Connections
1 2 3 3 Flange connections (PN06 and PN16)

Water Temperature Monitor


Sensors to monitor and display the temperature of the water entering and exiting the
unit and can show them on the unit's display.

Valves and Actuators


A variety of modulating ball valves are available with the Multi-DENCO units:
– 3 way valve
– 3 way valve with double regulating valve (DRV)
– 2 way valves
– 2 way pressure independent control (PIC) valves
All valves are fully modulating and are placed within the return pipework.
Multi-DENCO actuators come in 2 varieties:
– Drive Open Drive Close (DODC)
– 0-10 V control
These options, combined with the variety of valves, ensure that you have a valve and
actuator combination that meets your exact requirements.

PR-2014-0103-GB • Subject to Modifications • R3-05/2019 23


Accessories and Options Multi-DENCO
Optional Components

Filter Gauge
Differential pressure gauge mounted within the front door connected via flexible hoses
to measuring points across the filter.

Remote Display
The 4.3" touchscreen display can be mounted remotely up to 50m away from the
close control unit.

60 Hz Power Supply
60 Hz power supply is now available for all sizes Multi-DENCO when used with EC
fans on the outdoor unit.
Components within Multi-DENCO units are dual rated for 50 Hz and 60 Hz allowing for
a standard configuration for both situations.

24 PR-2014-0103-GB • Subject to Modifications • R3-05/2019


Multi-DENCO Accessories and Options
Outdoor Components and Options

Fans
Multi-DENCO outdoor units are available with AC* or EC fans.
These are like for like replacements between them therefore they do not affect the
overall dimensions of the condensers.
* AC fans only available for a limited time for countries within the EU due to EU Regulation (ErP).
Other countries outside the EU may have continued availability.

Winter Start Kits


Generally recommended for temperatures between -25 °C and -40 °C and at wind
exposed installations, winter start kits comprises of a horizontal type liquid receiver
with trace heater and a pressure relief valve to assist with the restarts of units when
they have been in cold temperatures.
For vertically blow condensers, the kit is situated in a special section below the con-
denser/condensing unit.
For horizontal blow condensers a special base section is fitted to house this below the
unit (typically 400 mm tall).

Heat Exchanger Coating


Blygold coating or Epoxy coating is available to coat the condenser's cooling coil to add
further protection, generally used when units are located near costal regions.

Special Colours
Special colours for outdoor units upon request.
Please provide samples or colour standard reference to enable accurate supply.

PR-2014-0103-GB • Subject to Modifications • R3-05/2019 25


Dimensions and Weights Multi-DENCO
Size 010 - 130

Unit Overview All Sizes

Example Example
front view side view Size 010 Size 018 Side view

Height

Length Depth

Size 030 Size 045 Size 065 Side view

Size 092 Size 130 Side view

26 PR-2014-0103-GB • Subject to Modifications • R3-05/2019


Multi-DENCO Dimensions and Weights
Weights and Centre of Gravity

Centre of Gravity dimensions are approximations. CombiCool and other options may vary the data given below.
For more informations please see specific customer drawings.

A-Version
Size Weight [kg] Centre of Gravity [mm]
X Y Z
010 170 280 275 830
018 180 410 265 895
030 256 600 340 885
045 362 870 340 845
065 462 1,450* 350 800
092 583 1,435 430 900
130 785 2,000 440 885
Tab. 1
* Upflow Version = 950 mm

C-Version
Size Weight [kg] Centre of Gravity [mm]
X Y Z
010 143 310 285 1,010
018 156 380 290 995
030 237 590 365 975
045 310 850 375 975
065 413 1,450* 370 890
092 512 1,175 405 1,000
130 674 1,570 435 1,010
Tab. 2
* Upflow Version = 950 mm

Dimensions all Units

Size Length [mm] Depth ** [mm] Height [mm]


010 600 600 1,940
018 800 600 1,940
030 1,180 780 1,940
045 1,670 780 1,940
065 1,992 780 1,968
092 2,500 880 1,968
130 3,380 880 1,968
Tab. 3
** Depth is a measurement for the frame dimension. Please see notes below for curved door overhang.

Example side view NOTE!


Multi-DENCO units utilise a curved door design,
therefore this provides a 37 mm overhang when
compared to the frame.

Detail A
Height

Depth

PR-2014-0103-GB • Subject to Modifications • R3-05/2019 27


Clearances Multi-DENCO
Service Area and Airflow Configuration

Clearances for Maintenance and Service


Multi-DENCO units have been designed to allow for maintenance from the front exclu-
sively. The front doors are hinged and the doors are removable for access and main-
tenance. Parts of some frame mullions are removable to allow removal of larger
components.

Size Minimum Clearance Required [mm]


010 600
018 600
030 600
045 600
Service Area 065 600
092 880
130 880
Tab. 4

28 PR-2014-0103-GB • Subject to Modifications • R3-05/2019


Multi-DENCO Clearances
Service Area and Airflow Configuration

Airflow configuration

In Room Downflow In Room Upflow

Suspended Ceiling Downflow Suspended Ceiling Upflow

Raised Floor Downflow Raise Floor Upflow

Combination Downflow Combination Upflow

PR-2014-0103-GB • Subject to Modifications • R3-05/2019 29


Frame Details Multi-DENCO
Top and Bottom Details

The standard top arrangement for


all units.
The box frame is the same all
around the edge of the unit and
allows for a 20 mm recess to be
used for top connections.
Top Detail All Units Ceiling return Sections, Top
Air Discharge Protection Grilles
(Eyelash) and Top Air Inlet Protec-
tion Grille (Eggcrate) sit on top of
the unit matching the unit's outside
edge.

Panel
Box Frame

Box Frame
Panel

The standard bottom arrangement


for smaller units.
The box frame is the same all
around the edge of the unit and
Bottom Detail Sizes 010 - 045 allows for a 20 mm recess.
All plinths/base frames match the
outside edge of the unit.

Panel Box Frame Baseframe

Larger units require an additional


base frame to support the unit.
This raises the height of the unit by
Bottom Detail with 28 mm.
Sizes 065 - 130
Base frame
The base frame is made of 3 mm
sheet metal and provides a flat sur-
face below for any sub-structure
connections.

30 PR-2014-0103-GB • Subject to Modifications • R3-05/2019


Multi-DENCO Schematics
Legend

Legend

Cooling Coil PS Pressure Sensor

Electronic Expansion
TS Temperature Sensor
Valve

Filter Drier LPS Low Pressure Switch

Schrader Valve HPS High Pressure Switch

Ball Valve
Double Regulating Valve
(Shut Off Valve)

Fan Drain

Compressor Test Point

3 Way Valve

PR-2014-0103-GB • Subject to Modifications • R3-05/2019 31


Schematics Multi-DENCO
A-Version

A-Version

Optional Second Condenser

Outdoor Unit

Size 092 – 130 Only Size 045 – 130 Only

Indoor Unit

NOTES!
1: Second condenser dependent upon unit selection.
2: Fan Pressure Switch may vary depending on outdoor unit configuration.
3: Not all options are displayed on this schematic. For more details please review type code.

32 PR-2014-0103-GB • Subject to Modifications • R3-05/2019


Multi-DENCO Schematics
C-Version

C-Version

Chilled Water Supply Chilled Water Return


from Chiller to Chiller

Size 065 – 130 Only

Indoor Unit

NOTES!
1: Various valve options available (3 way, 2 way, 2 way PICV). Schematic representative of 3 way valve
with double regulating valve.
2: Double regulating valve optional.
3: Not all options are displayed on this schematic. For more details please review type code.

PR-2014-0103-GB • Subject to Modifications • R3-05/2019 33


Schematics Multi-DENCO
A-Version + CombiCool

A-Version + CombiCool

Chilled Water Supply


and Return from Chiller
Outdoor Unit

Indoor Unit

NOTES!
1: Various valve options available (3 way, 2 way, 2 way PICV). Schematic representative of 3 way valve
with double regulating valve in the CombiCool circuit.
2: Secondary condensers available for certain sizes.
3: Double regulating valve optional.
4: Not all options are displayed on this schematic. For more details please review type code.
5: C-Version + CombiCool units have the same schematics as the right hand circuit above, for both
circuits.

34 PR-2014-0103-GB • Subject to Modifications • R3-05/2019


Multi-DENCO Unit Variations
Inside Multi-DENCO

A-Version units are cooled using refrigerant. C-Version units are cooled using water or water/glycol
Main components: mixture.
– Compressors Main components:
– Evaporating Coil – Chilled Water Cooling Coil
– Electronic Expansion Valve – Valve (3 Way or 2 way)

A-Version units are used with outdoor condenser. A variety of valves, actuators and other options are
available and C-Version units are used with chillers.

A-Version + CombiCool units are a combination of both C-Version + CombiCool units are a duplication of 2 C-
the A-Version unit and the C-Version unit. Version circuits within 1 unit.
Red highlights the A-Version circuit of the unit, whereas The blue and red show independent circuits and they in
blue highlights the CombiCool circuit. turn would be connected to separate chillers/free-cooling
equipment. Each circuit uses 3 rows of the coil. Both cir-
There is only 1 coil used, but 3 rows are used for the refri-
cuits are shown with 3-Way valves and double regulating
gerant circuit and the other 3 rows are used for the chilled
valves in the bypass.
water cooling.
The refrigerant circuit would need to be connected to a
condenser and the chilled water circuit to a chiller or free-
cooling equipment.

Humidifier only shown in A-Version image for visual clarity

PR-2014-0103-GB • Subject to Modifications • R3-05/2019 35


Connections Multi-DENCO
Mechanical and Electrical Connections

Control Line 6
only applicable
for outdoor units
with EC fans.
Oil trap required

Vertical Riser = 35 m max. 2


every 5 m vertical rise

Indoor unit able


to power outdoor
unit 5

5 m max.
Q12 or Q13 Control Line

Power Line

Discharge Line 4 1 % Slope required (1 cm/m) 1

Liquid Line 4

Power In 3 Total Length = 100 m max.

DIAGRAM NOTES!
1: Oil trap and 1% slope are required for every vertical and horizontal section respectively.
2: Outdoor unit must no more than 10 m lower than the base of the indoor unit.
3: "Power in" demonstrates a single feed. Dual power supply option available.
4: Liquid line and Discharge Line pipe sizing dependent on multiple factors and vary from unit
to unit.
5: Indoor unit able to power outdoor unit with EC fans. Indoor unit must power outdoor unit
with AC fans. Specification of cable size/quality is responsibility of installing contractor/site
engineer, but must be relative to condenser's current consumption and cable length from
indoor unit. Q12 and Q13 demonstrate separate power supplies available for twin
condensers. Mandatory for certain configurations.
6: FläktGroup Ltd recommend any 2 core screened data cable for control wiring, for example:
a. Beldon 8761
b. Alpha 2401C
c. BICC H8082

GENERAL NOTES!
i. Terminals for power line between indoor and outdoor vary. Please refer to wiring diagram.
ii. Twin condenser option is available (not shown in diagram).

36 PR-2014-0103-GB • Subject to Modifications • R3-05/2019


Multi-DENCO Connections
Mechanical and Electrical Connections

NOTES!
Only pipe sizes with data entered are allowable. It is mandatory that these sizes are
used only, for both horizontal and vertical risers.
It is recommended that an optimum pressure drop in the discharge line should be
1.0K and that the pipe size should not be used if this value exceeds 2.5 K.
Final responsibility for pipe sizing is of the contractor or installer and it is recommen-
ded that separate calculations are made by a suitable qualified engineer.
Data shown below is of a A-Version unit, using inverter compressors, operating at
nominal capcity (i.e. size 010 = 10 kW). Data calculated using a 45 °C condensing
temperature.

Imperial Measurements

Pressure Drop Over 10 m Horizontal Run [inch]


Unit Size Line Type 3/8 1/2 5/8 3/4 7/8 1 1/8 1 3/8 1 5/8 2 x 7/8 2 x 1 1/8
Liquid 0.4 0.1 0.0 0.0
010
Discharge 0.5 0.1 0.1
Liquid 0.2 0.1 0.0
018
Discharge 0.5 0.2
Liquid 0.2 0.1 0.0
030
Discharge 1.1 0.4 0.2
Liquid 0.1 0.1 0.0
045
Discharge 0.9 0.4 0.1
Liquid 0.1 0.0
065
Discharge 0.8 0.3
Liquid 0.1 0.0
092
Discharge 0.5 0.2 0.3
Liquid 0.1 0.0
130
Discharge 0.3 0.1 0.2
Tab. 5

Pressure Drop Over 25 m Horizontal Run [inch]


Unit Size Line Type 3/8 1/2 5/8 3/4 7/8 1 1/8 1 3/8 1 5/8 2 x 7/8 2 x 1 1/8
Liquid 0.8 0.2 0.1 0.0
010
Discharge 1.3 0.4 0.1
Liquid 0.5 0.2 0.1
018
Discharge 1.1 0.4
Liquid 0.4 0.1 0.1
030
Discharge 2.8 1.0 0.5
Liquid 0.3 0.1 0.0
045
Discharge 2.2 1.0 0.3
Liquid 0.3 0.1
065
Discharge 1.9 0.7
Liquid 0.2 0.1
092
Discharge 1.2 0.4 0.7
Liquid 0.3 0.1
130
Discharge 0.8 0.4 0.4
Tab. 6

PR-2014-0103-GB • Subject to Modifications • R3-05/2019 37


Connections Multi-DENCO
Mechanical and Electrical Connections

Metric Measurements

Pressure Drop Over 10 m Horizontal Run [mm]


Unit Size Line Type 10 12 16 18 22 28 35 42 2 x 22 2 x 28
Liquid 0.3 0.1 0.0 0.0
010
Discharge 0.8 0.2 0.1
Liquid 0.4 0.1 0.0
018
Discharge 0.5 0.2
Liquid 0.2 0.1 0.0
030
Discharge 1.1 0.6 0.2
Liquid 0.2 0.1 0.0
045
Discharge 1.3 0.4 0.1
Liquid 0.1 0.0
065
Discharge 0.9 0.3
Liquid 0.1 0.0
092
Discharge 0.6 0.2 0.3
Liquid 0.1 0.0
130
Discharge 0.3 0.1 0.2
Tab. 7

Pressure Drop Over 25 m Horizontal Run [mm]


Unit Size Line Type 10 12 16 18 22 28 35 42 2 x 22 2 x 28
Liquid 0.8 0.3 0.1 0.0
010
Discharge 1.9 0.4 0.2
Liquid 0.8 0.2 0.1
018
Discharge 1.2 0.6
Liquid 0.4 0.2 0.1
030
Discharge 2.8 1.5 0.5
Liquid 0.4 0.1 0.0
045
Discharge 3.1 1.1 0.4
Liquid 0.3 0.1
065
Discharge 2.0 0.7
Liquid 0.2 0.1
092
Discharge 1.4 0.4 0.8
Liquid 0.3 0.1
130
Discharge 0.8 0.3 0.5
Tab. 8

38 PR-2014-0103-GB • Subject to Modifications • R3-05/2019


Multi-DENCO Connections
Customer Terminals

Unit Network / Remote Display / Unit Display Air intake sensor Air discharge sensor

C5-12 TERMINALS

Serial Card

Interface Card
(Optional)

CUSTOMER TERMINAL BLOCKS

Remote contact Emergency off Critical Maintenance Condensate Run status #


on/off * (Fire Alarm) * Alarm # Alarm # Pump * (Optional) (Optional)

Terminals Notes
5–6 Remote On/Off for activating and deactivating the unit via a normally open volt free contact by others.
3–5 Emergency Off, a volt free contact (supplied by others) opening, deactivates the unit (e.g. used in a fire alarm system)
10 – 11 The unit's critical alarm indication e.g. HP/LP, Airflow, High Temperature.
12 – 13 The unit's maintenance alarm indication e.g. Dirty Filter, humidifier.
5 – 17 Alarm contact of condensate pump (optional accessory)
100 – 101 Indication of unit’s operation (i.e. fans enabled)
+VDC – GND – U1 – U2 Air intake sensor
+VDC – GND – U3 – U8 Air discharge sensor (optional, only if the item is fitted).
Serial Card Interface cards for building management (optional).
Rx-/Tx- - Rx+/Tx+ - GND Unit’s network terminals for connecting multiple units. Displays already connected to these terminals.
-------- Cabling provided by others.
# Volt free contacts (voltage or signal to be provided by others).
* On-site volt free contacts must be provided (if function is required remove jumper).

NOTE!
Above details are only accurate for C5-12 controller, other controllers/interface combination may vary. In all
instances, please consult the electrical drawing for specific details. FläktGroup reserve the right to make
design modifications/updates/amendments and improvements without prior notice.

SAFE ISOLATION!
External electric circuits of Multi-DENCO must be safely isolated from active (live) components of other
non-SELV or non-PELV electric circuits through using a double or reinforced insulation!
In particular, safe isolation is required between switch contacts of external devices such as relays, contac-
tors; auxiliary switches (e.g. remote On/Off contact etc.) and their electric circuits, if these are non-SELV
and non-PELV circuits.

PR-2014-0103-GB • Subject to Modifications • R3-05/2019 39


Notes Multi-DENCO

40 PR-2014-0103-GB • Subject to Modifications • R3-05/2019


Multi-DENCO Notes

PR-2014-0103-GB • Subject to Modifications • R3-05/2019 41


Notes Multi-DENCO

42 PR-2014-0103-GB • Subject to Modifications • R3-05/2019


Multi-DENCO Notes

PR-2014-0103-GB • Subject to Modifications • R3-05/2019 43


WWW.FLAKTGROUP.COM MULTI-DENCO

FläktGroup is the European market leader for smart and energy efficient Indoor Air
and Critical Air solutions to support every application area. We offer our customers
innovative technologies, high quality and outstanding performance supported by more
than a century of accumulated industry experience. The widest product range in the
market, and strong market presence in 65 countries worldwide, guarantee that we
are always by your side, ready to deliver Excellence in Solutions.

PRODUCT FUNCTIONS BY FLÄKTGROUP


Air Treatment | Air Movement | Air Diffusion | Air Distribution | Air Filtration
Air Management | Air Conditioning & Heating | Controls | Service

» Learn more on www.flaktgroup.com


or contact one of our office

You might also like