Protection Relay Inspection Report
Protection Relay Inspection Report
INSPECTION report
Switch-gear -System
Disclaimer: This protection relay inspection report is to be used for system setting and equipment
specification only;
INTRODUCTION & OBJECTIVE
This document is intended to provide discrimination of all relays used in central and addis abeba region
in power system protection office. The objective of these protection relay inspection report is to be used
for identifying system setting, defective relays, not resettable alarms and signals, preventive maintenance
and equipment specification only.
A. Protection Relays Setting on 132kV Transformer Relay Panels for Transformer Bays R3 (TR1)
Transformer Differential Protection Relay Settings-MiCOM P632
Transformer Backup Overcurrent Protection Relay Settings-MiCOM P122
Single Stg Under Frequency Relay 27
B. Protection Relays Setting on 132kV Transformer Relay Panels for Transformer Bays RP2(TR2)
RP1 (TR1)
Transformer Differential Protection Relay Settings-SIEMENS 7UT61
Transformer Backup Overcurrent Protection Relay Settings-SIEMENS
C. Protection Relays Setting on 132kV Line Relay Panels for Line Bays R1 and R2
Line Distance Protection Relay Settings-MiCOM P442
Line Backup Overcurrent and earth fault Protection Relay Settings-MiCOM P122
Single Stg Under Frequency Relay 27
Configuration:
OUTP Relay
Function settings:
Relay Settings:
MiCOM P122 serves as backup protection for 132kV side transformer winding.
The O/C Pickup setting is usually 115% of the maximum overload acceptable.
132/15KV TRAFO2
Panel Name CT Ratio LV 1200/1
&TR1
7UT6131-5EB92-
Serial No Transf. HV 31.5
1BBO/FR
5. Transformer HV Side bay unit F87BS1 Bus bar protection relay setting-MiCOM P742
6. Transformer LV Side bay unit F87BS2 Bus bar protection relay setting-MiCOM P742
B. Protection Relays Setting on 400kV Line Relay Panels for Line Bays PPCL1, PPCL2, PPCL3, PPCL5,
PPCL6 and PPCL7
3. Line bay unit F87BS Bus bar and BFP protection relay setting-MiCOM P742
C. Protection Relays Setting on 400kV Line Relay Panel for Line Bay
D. Protection Relays Setting on 400kV Bus coupler Relay Panel (Bay PPCC1)
A. Protection Relays Setting on 230kV Transformer Relay Panels for Transformer Bays
5. Transformer HV Side bay unit F87BS1 Bus bar protection relay setting-MiCOM P742
6. Transformer LV Side bay unit F87BS2 Bus bar protection relay setting-MiCOM P742
B. Protection Relays Setting on 230kV Line Relay Panels for Line Bays PPDL1, PPDL2, PP3L3, PPDL4,
PPDL5 and PPDL6
3. Line bay unit F87BS Bus bar and BFP protection relay setting-MiCOM P742
C. Protection Relays Setting on 230kV Line Relay Panel for Line Bay
D. Protection Relays Setting on 230kV Bus coupler Relay Panel (Bay PPDC1)
A. Protection Relays Setting on 132kV Transformer Relay Panels for Transformer Bays
PPET1,
5. Transformer HV Side bay unit F87BS1 Bus bar protection relay setting-MiCOM P742
6. Transformer LV Side bay unit F87BS2 Bus bar protection relay setting-MiCOM P742
B. Protection Relays Setting on 132kV Line Relay Panels for Line Bays PPEL1, PPEL2, PPEL3, PPEL5,
PPEL6 and PPEL7
3. Line bay unit F87BS Bus bar and BFP protection relay setting-MiCOM P742
C. Protection Relays Setting on 132kV Line Relay Panel for Line Bay
D. Protection Relays Setting on 132kV Bus coupler Relay Panel (Bay PPEC1)
Configuration:
Function Settings:
3 IN1>3 En SelectionTabl 0 1 1
8.46 Status abled e
3 IN1>3 N SelectionTabl 0 2 1
8.47 Direction on- e
Directiona
l
3 IN1>3 7 AnalogueFloa A 0.08 3 0
8.4A Current tingPoint 2 .01
3 IN1>3 Time 0 AnalogueFloa s 0 2 0
8.4B Delay tingPoint 00 .01
Voltag
Bay Protection ANSI Code CT & VT characteristics
e
level
21/50/51/50N/51N
P443 – F21-1 67/67N/27/59/50BF
25/79
CT 1500-3000/1A
21/50/51/50N/51N
AKAKI-II CVT 400kV/√3 / 100V/√3
400kV D60 – F21-2 67/67N/27/59/50BF
Line-1 CVTBB 400Kv/√3 / 100V/√3
25/79
AKAKI-II
P841 – F79 25/79
Line-2
P841 - FFL FL
P742 – F87BB 87BB/50BF CT 1500-3000/1A
P741 87BB
Busbar coupler
400kV P742 87BB/50BF
n°1 CT 4000-2000/1A
P14D-F50 50/51/50N/51N
Busbar coupler P742 87BB/50BF
400kV CT 4000-2000/1A
n°2 P14D-F50 50/51/50N/51N
P742-87BB1 87BB/50BF CT 4000-2000/1A
Busbar
400kV P742-87BB2 87BB/50BF CT 4000-2000/1A
Sectionalizer
P14D-F50 50/51/50N/51N CT 4000-2000/1A
1&2
Voltag
Bay Protection ANSI Code CT & VT characteristics
e
level CT1 400kV - 1000-
87T/49/46/87TN 500/1A CT2 230V - 2000-
P642 -F87T
24/50BF 1000/1A CTN1 - 400/1A
VT 400kV/√3/100V/√3
Autotransformer P742-F87BB-1 87BB/50BF CT 1000-500/1A
1&2 400/230kV P742-F87BB-2 87BB/50BF CT 2000-1000/1A
400/230kV CT 400kV - 1000-500/1A
P14D-F50-1 50/51/50N/51N
VT 400kV/√3/100V/√3
CT 230V - 2000-1000/1A
P14D-F50-2 50/51/50N/51N
VT 230kV/√3/100V/√3
P14N-F50N 50N/51N CTN - 400/1A
CT2 1600-800-400/1A
87L/21/51/51N
P543-F87L CVT 230Kv/√3 / 100V/√3
67/67N/50BF/79/25
CVTBB 230Kv/√3 / 100V/√3
21/51/51N/27/59
DUKEM line 1 P443-F21 CT3 1600-800-400/1A
67/67N/50BF/79/25
& 230kV CVT 230Kv/√3 / 100V/√3
P841-FFL FL
DUKEM line CVTBB 230Kv/√3 / 100V/√3
P14D-F67N 67N
2
CVT 230Kv/√3 / 100V/√3
P841-F79 79/25
CVTBB 230Kv/√3 / 100V/√3
P742-F87BB 87BB/50BF CT4 1600-800-400/1A
CT2 1600-800-400/1A
87L/21/51/51N
P543-F87L CVT 230Kv/√3 / 100V/√3
67/67N/50BF/79/25
CVTBB 230Kv/√3 / 100V/√3
21/51/51N/27/59
P443-F21 CT3 1600-800-400/1A
67/67N/50BF/79/25
MODJO II line 1 230kV CVT 230Kv/√3 / 100V/√3
P841-FFL FL
CVTBB 230Kv/√3 / 100V/√3
P14D-F67N 67N
CVT 230Kv/√3 / 100V/√3
P841-F79 79/25
CVTBB 230Kv/√3 / 100V/√3
P742-F87BB 87BB/50BF CT4 1600-800-400/1A
CT 230kV - 400-200/1A
87T/87TN/49 CT 15kV - 3000-1500/1A
230/15kV P642-F87T
46/24/50BF CTN2 230kV - 100-
200/1A
Power 230kV P742-F87BB 87BB/50BF CVT 230Kv/√3
CT4 400-200/1A/ 100V/√3
transformers 1&2 CT3 400-200/1A
230kV P14D-F51-1 50/51/51N/67N
230/15kV CVT 230Kv/√3 / 100V/√3
CT3 3000-1500/1A
15kV P14D-F51-2 50/51/50N/51N
VT 15Kv/√3 / 100V/√3
230kV P14N-F51N-1 50N/51N CTN1 100-200/1A
15kV P14N-F51N-2 50N/51N CTN1 200/1A
P742 87BB/50BF CT 3200-1600/1A
Busbar protection 230kV P741 87BB -
P14D 51/51N CT 3200-1600/1A
Z3 = 15 Ω; tz3 = 1s
R3ph = R3G = 70 Ω
Z4 = 1,75 Ω ; tz4 =
SODO LINE 1 1,5s R4ph = R4G =
& 70 Ω
PPC CT 1600-800-400/1A
SODO CVT 230Kv/√3 / 100V/√3 Line characteristics: Zone 1 is forward
L5 L = 5275 m; θ = 65 °
LINE 2
PPC Zd = 2,22 Ω ; KZ0=0,62 Zone 2 forward
L6 12°
400Kv OHL Z1 = 1,75 Ω; tz1 = 0s Zone 3 is forward
R1ph = R1G = 17,5 Ω
Zone 4 is reverse
Z2 = 2,66 Ω; tz2 = 400
21B R2ph = R2G = 26,6 Ω
Z3 = 15 Ω; tz3 = 1s
R3ph = R3G = 70 Ω
Z4 = 1,75 Ω ; tz4 =
MICOM
1,5s R4ph = R4G =
P443 70 Ω
[I>1] = 1050 A; TMS =
0,5
IEC SI curve
50/51 [I>2] = 1500 Directional
A [tI>2] = forward (to the
1s line)
[In>1] = 160 A; TMS = 1
67N IEC SI curve
Dir. Forward; Angle = -
50BF [I<] = 0,1In; tBF1 = Retrip. Backtrip is in P742
100ms;
Protectio ANSI
Designation Bay CT and VT ratio Setting Note
n Code
Live line&bus:
[U>]=106kV Dead
25 line&bus:[U<]=40 kV
ΔV= 13kV; f =
1P trip mode 1/3
Nb of shots 2
MICOM 1P dead time 1 600ms
P443 & 3P dead time 1 300ms
P543 Dead time 2 60s
& P841-F79 79
DUKEM line 1 Reclaim Time 60s
& Discriminating Time 100ms
EF1 CT 1600-800-400/1A AR Inhibit wind 5s
DUKEM
1 CVT 230Kv/√3 / 100V/√3 Initiate AR Z1, Z2&TAC
line 2
EF1 Reclosure conditions Live bus
[V<1] = 184
2 27 Alarm
230Kv OHL kV [tV<1] =
MICO [V>1] =
Alarm
M 253kV
59 [V>2] =
P443 Tripping
265kV
[In>1] = 160 A; TMS =
P14D-F67N 67N 0,4
IEC SI curve
Protection ANSI
Designation Bay CT and VT ratio Setting Note
relay Code
Is1 = 0,1pu = 160
MICOM A K1 = 30 %
87L
P543 Is2 = 1pu = 1600
A K2 = 150 %
Line characteristics: Zone 1 is forward
L = 20571 m; θ = 65 °
Zd = 8,68 Ω ; KZ0=0,62 Zone 2 forward
12°
Z1 = 6,9 Ω; tz1 = 0s Zone 3 is forward
R1ph = R1G = 45 Ω
Zone 4 is reverse
Z2 = 10,45Ω; tz2 = 400
21 R2ph = R2G = 56 Ω
MODJ Z3 = 21 Ω; tz3 = 1s
CT 1600-800-400/1A
EF13 CVT 230Kv/√3 / 100V/√3 R3ph = R3G = 70 Ω
O line
Z4 = 1,75 Ω ; tz4 =
MICOM
1 1,5s R4ph = R4G =
P443 & P543 70 Ω
230Kv [I>1] = 1050 A; TMS =
0,5
OHL IEC SI curve
50/51
(standard
inverse)
[I>2] = 1500 Directional
A [tI>2] = forward (to the
1s line)
Dir. Forward; Angle =
[In>1] = 160 A; TMS = 1
67N IEC SI curve
Dir. Forward; Angle = -
60°
50BF [I<] = 0,1In; tBF1 = Retrip. Backtrip is in P742
100ms;
Protectio ANSI
Designation Bay CT and VT ratio Setting Note
n Code
[I>1] = 2000
51
MICO A [tI>1] =
M [In>1] = 200
51N
P14D A [tIn>1] =
1,5s
[ID>1] = 40 A;
k1 = 10%
230Kv Busbar protection EF15 CT 3200-1600/1A [ID>2] = 1200 A
87BB k2 = 60%
MICOM [IDCZ>2] = 1200 A
P741/P742 kCZ = 30%
[ID>1] Alarm Timer = 5s
I< = 10%*In TC
50BF tBF 1 & 3 = 100 ms
tBF 2 & 4 = 200 ms
PPC
T1,
PPC NA
46 NA IEC SI curve
T2 CT1 400kV 800/1A CT2 /Hz Set=2.100 V/Hz
400/230kV & 230kV -1600/1A CTN1 V/Hz Delay=15.
MICOM P643- 230kV - 200/1A CVT 24 (alarm)
AUTOTRA PPC
T3 F87T 400Kv/√3 / 100V/√3 V/Hz>1 Trip Set= 2.300
NSFORME
RS V/Hz V/Hz>1 Delay=
20.00 s
AT1,AT2 &
AT3 NA
87TN
50BF NA
Protectio ANSI
Designation Bay CT and VT ratio Setting Note
n Code
[I>1] = 720 A; TMS = 0.355
IEC SI curve (standard
inverse))
CT 400kV - 1000-500/1A 50/51
400/230kV MICOM
P14D-F50- VT 400kV/√3/100V/√3 [I>3] = 6400
AUTOTRANSFORM
E AT1,AT2 & AT3 1 A [tI>3] = 0
PPCT1,PP
HV side (400Kv) ms
CT2 &
PPCT3 [I>3] = 10000
A [tI>3] =
100 ms
[In>1] = 160
50N/51N
A [TMS>1]
= 0.375 s
[I<] = 0.2In
P742-F87BB CT4 800/1A 50BF
tBF1 =
100ms
Protection ANSI
Designation Bay relay CT and Code Setting Note
VT ratio
[I>3] = 1.3 A
50/51 [tI>3] = 6.3s
MICOM
P141 [In>3] = 0.65 A
50N/51N [tIn>3] = 6.3s
[ID>1] = 160 A; k1 =
10% [ID>2] = 1800 A
400Kv Bus PPCC1
3200/1A
k2 = 60%
bar 87BB [IDCZ>2] = 1760 A kCZ
protection MICOM = 30%
P741/P742 [ID>1] Alarm Timer = 5s
I< = 10%*In TC
50BF tBF 1 & 3 = 100 ms
tBF 2 & 4 = 200 ms
[I>1] = 2000 A [tI>1]
50/51 = 2,1s
400Kv bus PPCC1 MICOM 3200/1A
P141 [In>1] = 240 A
coupler 50N/51N [tIn>1] = 2,1s
Protection ANSI
Designation Bay CT and VT ratio Setting Note
relay Code
Line characteristics: Zone 1 is forward
L = 16194 m; θ = 85
° Zone 2 forward
Zd = 6,34 Ω ; KZ0=0,6 | 0°
Z1 = 5 Ω; tz1 = 0s Zone 3 is forward
R1ph = R1G = 50 Ω
Zone 4 is reverse
21 Z2 = 8 Ω; tz2 = 400 ms
R2ph = R2G = 66 Ω
Z3 = 126 Ω; tz3 = 1s
CT 1600-3000/1A R3ph = R3G = 82 Ω
DEBREZIE
PPCL7 MICOM
CVT 400kV/√3 / 100V/√3 Z4 = 5 Ω ; tz4 =
EE01 P443 & D60
T LINE 1,5s R4ph = R4G =
CVTBB 400Kv/√3 / 100V/√3 82 Ω
1&2 [I>1] = 1575 A; TMS = 0,6
IEC SI curve
400Kv (standard inverse)
50/51
[I>2] = 2000 A Directional forward
OHL [tI>2] = 1s (to the line)
Dir. Forward; Angle = 30°
[In>1] = 150 A; TMS = 1
67N IEC SI curve
Dir. Forward; Angle = -
60°
50BF [I<] = 0,1In; tBF1 = Retrip. Backtrip is in P742
100ms;