0% found this document useful (0 votes)
82 views2 pages

01 80 13 Project Site Design Criteria PDF

This document outlines the site design criteria for a project in Dubai, United Arab Emirates. It provides details on the location, altitude, wind and seismic loads, temperature, rainfall, and fuel storage requirements. The wind speed is 160 km/hr, seismic design category is D, maximum temperature is based on the latest ASHRAE handbook, maximum rainfall is 46mm per hour, and fuel storage capacity is 48 hours. Equipment, components, structures, and paving must meet these criteria unless otherwise specified.

Uploaded by

Aditya Jain
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
82 views2 pages

01 80 13 Project Site Design Criteria PDF

This document outlines the site design criteria for a project in Dubai, United Arab Emirates. It provides details on the location, altitude, wind and seismic loads, temperature, rainfall, and fuel storage requirements. The wind speed is 160 km/hr, seismic design category is D, maximum temperature is based on the latest ASHRAE handbook, maximum rainfall is 46mm per hour, and fuel storage capacity is 48 hours. Equipment, components, structures, and paving must meet these criteria unless otherwise specified.

Uploaded by

Aditya Jain
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

SECTION 01 80 13

PROJECT SITE DESIGN

CRITERIA

PART 1 GENERAL

1.1 SUMMARY

A. Section includes the Site Design Criteria.

1.2 SITE DESIGN CRITERIA

A. Provide equipment, components, structures, and paving in accordance with the


following design criteria unless otherwise specified:
1. Location:
a. County: United Arab Emirates.
b. City: Dubai.
2. Altitude: 8 meters MSL.
3. Wind Load: As required according to the International Building Code
a. Wind Speed (3 second gust): 160Km/hr
b. Importance Factor IW = 1.15.
c. Exposure Factor = C.
d. Occupancy Category IV.
e. Internal wind pressure coefficient shall not be less than zero.
4. Seismic Load: As required according to the International Building Code
a. Importance Factor IE = 1.5.
b. Response Modification Factor R per ASCE 7-05 Table 12.2-1.
c. Site Class D.
d. Occupancy
Category IV. e. SDS
= 0.57g, S1 = 0.28g
f. Seismic Design Category D.
5. Temperature:
Heat load calculations shall be based on the ASHRAE Handbook being used by
the Uptime Institute for Tier certification. The below values are based on latest
ASHRAE Handbook; it is the Contractor’s responsibility to verify with the
Uptime Institute that this is the Handbook edition being used for Uptime
certification.
6. Rainfall (Maximum): 46mm per

hour

7. Fuel storage: 48 hrs

PART 2 PRODUCTS (NOT USED)

PART 3 EXECUTION (NOT USED)

END OF
April 2021 Khazna Data Centre Project Design Criteria S 01 80 13 - Page 1
SECTION

April 2021 Khazna Data Centre Project Design Criteria S 01 80 13 - Page 2