Wheatstone Project

LNG Plant
Application of Proprietary Cementitious
Fireproofing
Minimum Requirements ITP Template

0 6-Oct-11 Issue for Construction RP VP KH

A 5-Jul-2011 Issued for Review RP JK KH


REV DATE DESCRIPTION ORIG CHK APPR

IP Security Public Total number of Pages (including Cover sheet): 4


Contractor
For Contract No Contractor Document No Rev.
Contractor
Documents CW695483 25657-000-GFV-GCE-00006 001

COMPANY Project Area Discipline Type Originator Package Sequence-Sht Revision


DOCUMENT
CONTROL NO. WS1 0000 CNS FRM BEC 000 00006-000 0

© Chevron Australia Pty Ltd


APPLICATION OF PROPRIETARY CEMENTITIOUS FIREPROOFING
SUBCONTRACTOR MINIMUM REQUIREMENTS
INSPECTION AND TEST PLAN (ITP)

References

Document Number Title


WS1-0000-FGS-SPC-BEC-000-00102-000
(3PS-NF00-F0002) Specification For Proprietary Cementitious Fireproofing
DISCIPLINE: Civil/Mechanical DESCRIPTION: Describes the proper installation and test procedures for the application of Proprietary Cementitious
Fireproofing

Inspection/Test Reference Method of Verification (see


Documentation/Acceptance Legend) Demonstrated Evidence
Activity Activity
Requirements Criteria Report / Checklist
No. Description Stage / Sub BEC CVX
Test or Inspection Performed Reference No.:
Frequency Code / Spec

1.0 Pre-Work Inspections


1.1 Material Verify material (Pryocrete, lath, mesh, tie In process WS1-0000-FGS-SPC-BEC- H,R S - Material Certifications
wire, studs, pins, caulking) meets project 000-00102-000 Sec 1.3.1, 4.0 Design Approvals
specification.
1.2 Mock-Up Verify Mock-Up. Per Spec WS1-0000-FGS-SPC-BEC- H,I H,I W Mock up
000-00102-000 Sec 5.0
2.0 Pre-Application Inspections
2.1 Surface Preparation Verify anchor touch-up and surface is In Process WS1-0000-FGS-SPC-BEC- I S - Proprietary Cementitious
cleaned free from oil or grease. 000-00102-000, Sec 6.1 & Fireproofing Inspection Report
Verify block-outs for temporary supports 6.3
are correct
Verify all fasteners are correctly tightened
Verify coating/galvanizing of fasteners has
been performed as applicable
Verify dimensional requirements for the
structure are in accordance with drawing.
2.2 Fireproofing Detail Verify proper detail per in process Per Drawing WS1-0000-FGS-SPC-BEC- I S - Proprietary Cementitious
standard drawings 000-00102-000 Sec 3.4 Fireproofing Inspection Report

2.3 Installation of Reinforcement Verify studs or pins properly attached. Random WS1-0000-FGS-SPC-BEC- W,I I - Proprietary Cementitious
Verify lath or mesh is installed properly. In Process 000-00102-000, Sec 4.2.2, Fireproofing Inspection Report
6.3 and 6.4 (10%)
Manufacturer’s Instructions
3.0 Proprietary Cementitious Fireproofing
Application
3.1 Apply Proprietary Cementitious Proprietary Cementitious Fireproofing In Process WS1-0000-FGS-SPC-BEC- H,I W,I - Proprietary Cementitious
Fireproofing applied properly and per the design 000-00102-000, Sec’s 4.0, Fireproofing Inspection Report
drawing. 6.5, 6.8
Verify temperature and humidity are within Manufacturer’s Instructions
tolerance for fireproofing application
3.2 Sampling and Testing Verify 3rd party tester is on site for testing In Process Manufacturer’s Instructions T,I S S 3rd Party Test Report
of Proprietary Cementitious Fireproofing ASTM E 605 Proprietary Cementitious
Verify wet thickness of fireproofing WS1-0000-FGS-SPC-BEC- Fireproofing Inspection Report
Verify density 000-00102-000, Sect. 8.3
ASTM E 605
4.0 Post-Application Inspection
Inspection/Test Reference Method of Verification (see
Documentation/Acceptance Legend) Demonstrated Evidence
Activity Activity
Requirements Criteria Report / Checklist
No. Description Stage / Sub BEC CVX
Test or Inspection Performed Reference No.:
Frequency Code / Spec

4.1 Final Inspection, repairs, and clean-up Inspection for defects and any required In Process WS1-0000-FGS-SPC-BEC- I W,I - Proprietary Cementitious
clean-up. 000-00102-000, Sec 6.8, 8.1, Fireproofing Inspection Report
Verify proper repair and clean-up. 8.3
Verify caulking is properly installed
Verify fireproofing is properly cure
4.2 Concrete Breaks Verify that core samples meet project Per Spec  WS1-0000-FGS-SPC-BEC- R R - 3rd Party Break Report
specifications. 000-00102-000 Sec 4.8, 7.3.2
4.3 Apply Topcoat (if required) Verify seal coat is properly applied In Process Manufacturer’s Instructions W,I S - Proprietary Cementitious
Verify topcoat applied properly. WS1-0000-FGS-SPC-BEC- Fireproofing Inspection Report
000-00102-000 Sec 4.4
4.4 Cementitious Fireproofing Inspection Maintain a Proprietary Cementitious In Process WS1-0000-FGS-SPC-BEC- I R R Proprietary Cementitious
Report Log Fireproofing Inspection Report Log that 000-00102-000 Sec 3.4 Fireproofing Inspection Report
identifies all shotcrete activities and
placements.
Verify documentation is completed as
required.

Legend : I – Inspection; T – Test; W - Witness Inspection Point; H - Mandatory Hold Point For Inspection; R - Document Review; S - Surveillance