Abb Ag: RTU560 / RTU211

The document provides instructions for connecting and setting up the ABB AG Adaptor 23AD64 for use with RTU211 and RTU560 remote terminal units. The adaptor is used to extend the serial peripheral bus and connect additional I/O modules. It can be configured using DIP switches to set the rack and starting module addresses. Connections are provided for power, RS485 bus, fiber optic cable, and I/O modules. Diagrams demonstrate example uses including connecting multiple racks and modules with different address settings.

Uploaded by

Cosmic Garash 2
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
508 views6 pages

Abb Ag: RTU560 / RTU211

The document provides instructions for connecting and setting up the ABB AG Adaptor 23AD64 for use with RTU211 and RTU560 remote terminal units. The adaptor is used to extend the serial peripheral bus and connect additional I/O modules. It can be configured using DIP switches to set the rack and starting module addresses. Connections are provided for power, RS485 bus, fiber optic cable, and I/O modules. Diagrams demonstrate example uses including connecting multiple racks and modules with different address settings.

Uploaded by

Cosmic Garash 2
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

ABB AG RTU560 / RTU211

Remote Terminal Unit


Connections and Settings
Adaptor 23AD64

Application, characteristics and technical data The DIP switch S2 (1-4) sets the starting ad-
have to be taken from the hardware data dress of the I/O modules. This address is nor-
sheet: mally 1 (S2 (1-4) = Off). Other starting ad-
dresses are necessary, if the whole address
23AD64 1KGT 150 670 space of the I/O modules is needed (see Table
2).
Operation
The Adaptor 23AD64 is an adaptor to connect
RTU211 extension racks. It is also used to ex- Start- S2-1 S2-2 S2-3 S2-4
tend the serial peripheral bus over distances of Address
more than app. 30 cm. The interface adaptor 1 Off Off Off Off
is always used together with the power supply
unit 23PU63. 2 On Off Off Off

Processing Functions 3 Off On Off Off

The adaptor is used to terminate the serial pe- 4 On On Off Off


ripheral bus (Wired-OR Bus). The RS485 or
5 Off Off On Off
Fiber Optical Input (alternative) will be con-
verted to the Wired-OR Bus again. The rack 6 On Off On Off
address can be set by DIP switches. In addi-
tion it will generate automatically the module 7 Off On On Off
address within the rack, while the module
starting address can be set by additional DIP 8 On On On Off
switches individually.
9 Off Off Off On

Settings 10 On Off Off On


The rack address will be set by DIP switch S1 11 Off On Off On
(1-3) according to Table 1.
12 On On Off On
13 Off Off On On
Rack No S1-1 S1-2 S1-3
1 Off Off Off 14 On Off On On
2 On Off Off 15 Off On On On
3 Off On Off 16 On On On On
4 On On Off
5 Off Off On
Table 2: Setting of Starting address
6 On Off On
7 Off On On

Table 1: Setting of Rack Address

Doc.-No.: 1KGT 150 671 V001 1 1


ABB AG
RTU560 / RTU211 Connections and Settings 23AD64

Signaling The fiber optical connector X3 will be connected


to the superordinated device (e.g. 23AD63. The
The adaptor has 5 LEDs showing the activities connector X4 can be used for additional racks.
on the serial peripheral bus (see Figure 1). At connector X7 all internal supply voltages are
 LED 1: Activity on X1 or X3 available for test purpose.
 LED 2: Activity on X8 Please note:
 LED 3: Activity on X5 After the first connection 23AD63/23AD64 the
transmission media (RS485 / Fiber Optical) can’t
 LED 4: Activity on X4
be changed anymore.
 LED 5: Power Supply
Addition I/O modules are connected to X5.
Connections Please note: De-energize the system, before
plugging or unplugging this connector
The RS485 Bus will be connected to X1 and
X2. Connection according Table 3. Power Supply
The supply power 24 – 110 V DC for the power
supply unit 23PU63 will be connected to X6
X1-1 X1-2 X1-3 (1,2). The process voltage 24 V DC for addi-
X2-1 X2-2 X2-3 tional modules is available on X6 (4,5).

TB TA Shield Connection Examples


The principle usage of the adaptor 23AD64
Table 3: RS485 Bus Connector X1, X2 within an RTU211 or RTU560 is shown in Figure
Please note: PE (X6-3) must always be con- 2 to 7.
nected to functional earth.

Figure 1: Position of connections and setting elements

2 Doc.-No.: 1KGT 150 671 V001 1


ABB AG
Connections and Settings 23AD64 RTU560 / RTU211

Figure 2: 23AD64 used in RTU211

Figure 3: 23AD64 connected to a star coupler 23SC60

3 Doc.-No.: 1KGT 150 671 V001 1


ABB AG
RTU560 / RTU211 Connections and Settings 23AD64

Figure 4: 23AD64 used with 560CMG10

Figure 5: 23AD64 used in RTU560

4 Doc.-No.: 1KGT 150 671 V001 1


ABB AG
Connections and Settings 23AD64 RTU560 / RTU211

Figure 6: 23AD64 used in RTU560

Figure 7: 23AD64 with module starting address > 1

Dok.-Nr.. 1KGT 150 671 V001 1 5


ABB AG
RTU560 / RTU211 Connections and Settings 23AD64

ABB AG
Power Technologies Division
Power Technology Systems

Kallstadter Str. 1, D-68309 Mannheim


Telephone +49 (0) 621 381 – 7592
Fax +49 (0) 621 381 – 7622

www.abb.com/pt

Subject to alteration

6 Doc.-No.: 1KGT 150 671 V001 1