0% found this document useful (0 votes)
475 views2 pages

Control and Power Cable Specifications

This document provides technical specifications for two types of cables produced by SHIV SHAKTI STAR: 12C x 2.5 sqmm bare stranded copper, PE insulated, armored, PVC sheathed control cables and 4C x 6.0 sqmm bare stranded copper, PE insulated, armored, PVC sheathed power cables. It lists details on applicable standards, materials used, electrical parameters, physical dimensions, testing procedures, markings, and drum packaging. The specifications cover conductor size and material, insulation thickness, armor coverage, voltage rating, bending radius, fire resistance, and other key characteristics.

Uploaded by

Vyrax Falcon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
475 views2 pages

Control and Power Cable Specifications

This document provides technical specifications for two types of cables produced by SHIV SHAKTI STAR: 12C x 2.5 sqmm bare stranded copper, PE insulated, armored, PVC sheathed control cables and 4C x 6.0 sqmm bare stranded copper, PE insulated, armored, PVC sheathed power cables. It lists details on applicable standards, materials used, electrical parameters, physical dimensions, testing procedures, markings, and drum packaging. The specifications cover conductor size and material, insulation thickness, armor coverage, voltage rating, bending radius, fire resistance, and other key characteristics.

Uploaded by

Vyrax Falcon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Data Sheet/Technical Specification

4C x 6.0 sqmm BARE Stranded


12C x 2.5 sqmm BARE Stranded
Copper,PE Insulated, Armd,PVC
S. No. Particulars/Parameters Copper,PE Insulated, Armd,PVC Sheath-
Sheath-Power Cables as per BS 5803
Control Cables as per BS 5803 pt.-1
pt.-2
1 Make SHIV SHAKTI STAR SHIV SHAKTI STAR

BS 5308 part-1-2/6387/7655/IS BS 5308 part-1-2/6387/7655/IS


2 Applicable Standard-
8130/5831/3975/694/UL/7098 /1554 pt.1 8130/5831/3975/694/UL/7098 /1554 pt.1

3 Voltage Grade - 1000 V 1000 V


4 No. of cores /Pairs- 12C 4C
5 Conductor- Bare Copper Bare Copper
a) Size & Strands dia. 2.5sqmm-36/0.3±0.02 4.0sqmm-84/0.3±0.02
b) Conductor bunched dia. 1.9 3
Conductor Resistance max. at 20⁰C
c) 7.98 3.3
(ohm/km)/Loop Resistance Themocouple

d) Annealing Min.% 13.5 13.5


e) Class of Conductor CLASS 5 CLASS 5
Tensile Strength in N/MM sqmm-
f) NA NA
Aluminium
g) Wrapping Test -Aluminium NA NA

6 Mineral /Mica Over Lapped by 125%- NA NA

7 Insulation-
a) Material Type PE (Polyethelene) PE (Polyethelene)
b) Core Colours Identification Grey or Black number printings on each cores Red +Blue+Black+ Green
c) Nominal thickness (mm) 0.7mm 0.7mm

IND./Over Shielded(Screen)
8 NA NA
/Unshielded -
9 Inner Sheath-1
a) Material Type NA NA
b) Thickness Min. NA NA
10 Braiding % Cov.
a) Type of Braiding NA NA
b) Nominal Dia. Of wire(mm) NA NA
c) Coverage % NA NA
11 Inner Sheath-2
a) Material Type NA NA
b) Thickness Min. NA NA
12 Armoured NA NA
a) Material Galvanised Iron Steel Galvanised Iron Steel
b) Type of armouring Flat Strip Flat Strip
c) Nominal size of armour (mm) 4 x0.8±10% 5 x0.8±10%
d) Coverage %
13 PVC Outer Sheath-
a) Material Type PVC Type ST-1 PVC Type ST-1
b) Colour of outer sheath BLACK BLACK
c) Thickness (mm) Min. 1.2 1.2
14 Electrical Parameters
a) Insulation Resistance min. Mohm/km 1000 1000

b) Capacitance (nf/km) max. NA NA


c) Inductance NA NA
d L/R ratio max. NA NA
HV test 1.0 kv for 1 min./3.0kv for 5.0
e) 3.0KVfor 5 minutes 3.0KVfor 5 minutes
min.
Max. conductor tempt. under normal
f) 90⁰C 90⁰C
operating conditions
Max.conductor tempt. at the short circuit
g) 250⁰C 250⁰C
condition
h A.C.Resistance at 70ᵒC in Ὡ/Km Max. 9.576 3.96
i A.C.Reactance in Ὡ/Km Max. 0.105 0.105
j Impedance in Ὡ/Km Max. 9.576 3.96
Approx. overall diameter in mm±
15 18.5 15.6
2.0mm
16 Minimum bending radius 8 x Overall diameter 8 x Overall diameter
17 Fire resistance Test as per IEC 60331/332 as per IEC 60331/332
18 Oil Resistance test NA NA

19 FRLS/LSZH/ZHFR PROPERTIES
a) Oxygen Index as per ASTM D-2863 NA NA
b) Temperature Index as per ASTM D-2863 NA NA
c) Smoke Density Rating as per ASTM D-2863 NA NA
d) Acid Gas Generation as per IEC - 754- 1 NA NA
Circuit Integrity Test For Fire Survival
20 NA NA
Cable
SHIV SHAKTI STAR/ Size/1000 V Grade/
SHIV SHAKTI STAR/ Size/1000 V Grade/ BARE/PE/Armd/
21 Printing PVC/Control Cable/Year etc./meter marking.
BARE/PE/Armd/ PVC/Power Cable/Year etc./meter
marking.
22 Wooden Drums Packing
a) Quantity in Mts 400 500
b) Drum Size in inches 28 D x14 barrel x22 W 28 D x14 barrel x22 W
c) Tare Weight with falli 75 75
d) Cables Weight /km 400 300
e) App. Cables Weight Kgs 160 150
d) Gross Weight Of Drums in Kgs 235 225