PCS-996R
Disturbance Fault Recorder
The PCS-996R disturbance & fault recorder (DFR) is a
multifunctional data acquisition system designed to address
Functions
the data recording requirements of substations. It captures the Recording Functions
curves of monitored quantities and aligns the values of different • Initiating recording by AC voltage
supervised objects to build disturbance records. The PCS-996R - Phase voltage over upper limit
helps users simplify disturbance analysis by combining the discrete - Phase voltage under lower limit
records in different protective relays. - Sudden increase/decrease of phase voltage over limit
- Negative sequence voltage over upper limit
The disturbance & fault recording system architecture can be
- Zero sequence voltage over upper limit
centralized or distributed based upon customers’ requests.DFRs
can also be applied to a substation independently with a local - Sudden change of zero-sequence over limit
computer and HMI software. The protocol for the communication - Frequency over upper limit
network can be IEC 61850, FTP and IEC 60870- 5-103 based on
- Frequency under lower limit
LAN. GOOSE function is integrated to receive information from the
- Absolute value of df/dt over limit
process bus.
• Initiating recording based on AC current out-of-limit
Standard format - Phase current over upper limit
Disturbance Fault
PCS-996R DFRs are equipped with 48 analog channels and 60 - Sudden change of phase current over limit
binary channels in one unit. Furthermore, it can be synchronized - Negative sequence over upper limit Recording
via an external time source.
- Zero sequence over upper limit
Recording - Sudden change of zero sequence over limit
- Power swing
• Triggered recording @ 9600Hz, for short-term transient
process. • Initiating recording based on binary input
• Continuous recording @1200Hz, for mid-term dynamic • Continuous recording (24hours of uninterrupted recording)
process
• Slow recording @1 ~ 50Hz , for long-term power quality
monitoring
• Extract recording @ 9600Hz, isolate fault channels
DXWRPDWLFDOO\IRULQIRUPDWLRQHI¿FLHQF\
153
Protection Automation Control
DFR Manager System
500kV Disturbance & Fault Recorder
GPS
@ 220kV Disturbance & Fault Recorder
Email
110kV Disturbance & Fault Recorder
Server 1 Server 2 Local DFR Analysis Workstation
Front end Front end
Communication Communication
Server 1 Server 2
Station A Station B
Station A
WAN/LAN
Station E Station D Station C
Station G Station F
Station I Station H
Station J
Station K
Station L Station M Station N Station O
Station R
Station Q
Station P
Station S Station T Station U Station V
Figure 1 Typical application of the PCS-996R in a wide-area DFR system
Auxiliary Function Features
• Self diagnostic test
• The robust hardware platform adopted for DFR is the same
• Loss of DC power supply alarm as NR Electric’s protection and control system, which has
EHHQZHOOSURYHQLQ¿HOG
• Hardware circuit online detection
• This device adopts a fully-closed chassis with a well
• Support IRIG-B time synchronization
designed structure, providing separate spaces for low and
high voltage systems. The traditionally integrated circuit
Communications board mode is abandoned. Furthermore, anti-interference
• 1 RJ45 Ethernet port complies with IEC60870-5-103 and measures are integrated into the software, thus enhancing
IEC61850 protocol anti-interference capabilities.
• 1 RS-485 serial port used for GPS time synchronization • This device makes use of an advanced hardware platform,
which includes 16 bits parallel A/D converter, 320*240
• 56VHULDOSRUWXVHGWRWHVWDQGFRQ¿JXUHGHYLFH
graphic dot matrix LCD, and real-time multi-task operating
system. The advanced hardware platform can achieve the
• 1 Ethernet interface used for FTP service for continuous
high-capacity, high-precision, high-speed, and real-time data
recording and real-time waveform display
processing. The high-precision parallel A/D converter can
• 7ZR¿EHU(WKHUQHWSRUWVZKLFKVXSSRUW,(&DQG sample all the AC signals simultaneously in order to ensure
IEC61850 protocol (available for PCS-996R) the accuracy of these measurements.