Two Way Flat Plate Concrete Floor Slab Design Detailing - CSA23.3 14 PDF
Two Way Flat Plate Concrete Floor Slab Design Detailing - CSA23.3 14 PDF
Version: Jul-11-2018
Two-Way Flat Plate Concrete Floor System Analysis and Design
The concrete floor slab system shown below is for an intermediate floor to be designed considering partition weight
= 1 kN/m2, and unfactored live load = 1.9 kN/m2 . Flat plate concrete floor system does not use beams between
columns or drop panels and it is usually suited for lightly loaded floors with short spans typically for residential and
hotel buildings. The lateral loads are independently resisted by shear walls. The two analysis procedures prescribed in
CSA A23.3-14 Direct Design Method (DDM) and Elastic Frame Method (EFM) are illustrated in detail in this
example. The hand solution from EFM is also used for a detailed comparison with the analysis and design results of
the engineering software program spSlab.
Version: Jul-11-2018
Contents
1. Preliminary Member Sizing .....................................................................................................................................1
2. Two-Way Slab Analysis and Design ........................................................................................................................4
2.1. Direct Design Method (DDM) ..........................................................................................................................5
2.1.1. Direct design method limitations ............................................................................................................5
2.1.2. Design moments .....................................................................................................................................5
2.1.3. Flexural reinforcement requirements......................................................................................................6
2.1.4. Factored moments in columns ................................................................................................................8
2.2. Elastic Frame Method (EFM) ...........................................................................................................................9
2.2.1. Elastic frame method limitations .......................................................................................................... 10
2.2.2. Frame members of elastic frame .......................................................................................................... 10
2.2.3. Elastic frame analysis ........................................................................................................................... 12
2.2.4. Design moments ................................................................................................................................... 13
2.2.5. Distribution of design moments ........................................................................................................... 15
2.2.6. Flexural reinforcement requirements.................................................................................................... 15
2.2.7. Column design moments ...................................................................................................................... 17
3. Design of Interior, Edge, and Corner Columns ...................................................................................................... 19
3.1. Determination of factored loads ...................................................................................................................... 20
3.2. Column Capacity Diagram (Axial-Moment Interaction Diagram) ................................................................. 21
4. Two-Way Slab Shear Strength ............................................................................................................................... 25
4.1. One-Way (Beam action) Shear Strength ........................................................................................................ 25
4.2. Two-Way (Punching) Shear Strength ............................................................................................................ 26
5. Two-Way Slab Deflection Control (Serviceability Requirements) ........................................................................ 29
5.1. Immediate (Instantaneous) Deflections ........................................................................................................... 29
5.2. Time-Dependent (Long-Term) Deflections .................................................................................................... 39
6. Computer Program Solution ................................................................................................................................... 40
7. Summary and Comparison of Two-Way Slab Design Results ............................................................................... 60
8. Deflection Calculation Methods ............................................................................................................................. 62
9. Comparison of Two-Way Slab Analysis and Design Methods .............................................................................. 62
Version: Jul-11-2018
Code
Design of Concrete Structures (CSA A23.3-14)
Reference
CAC Concrete Design Handbook, 4th Edition, Cement Association of Canada
Notes on ACI 318-11 Building Code Requirements for Structural Concrete, Twelfth Edition, 2013 Portland
Cement Association, Example 20.1
Design Data
Floor-to-Floor Height = 2.75 m (provided by architectural drawings)
Superimposed Dead Load, SDL = 1 kN/m2 for framed partitions, wood studs plaster 2 sides
Live Load, LL = 1.9 kN/m2 for Residential floors
f 'c 28 MPa (for slabs)
Solution
In this example deflection will be calculated and checked to satisfy project deflection limits. Minimum
member thickness and depths from CSA A23.3-14 will be used for preliminary sizing.
Using CSA A23.3-14 minimum slab thickness for two-way construction without interior beams in Section
13.2.3.
ln 0.6 f y /1000
Exterior Panels: hs ,min 1.1 187 mm CSA A23.3-14 (13.2.3)
30
But not less than 120 mm. CSA A23.3-14 (13.2.1)
ln 0.6 f y /1000
Interior Panels: hs ,min 170 mm CSA A23.3-14 (13.2.3)
30
But not less than 120 mm. CSA A23.3-14 (13.2.1)
Where ln length of clear span in the long direction = 5500 – 400 = 5100 mm
1
b. Slab shear strength – one way shear
Where:
cclear = 20 mm for 15M steel bar CSA A23.3-14 (Annex A. Table 17)
db = 16 mm for 15M steel bar
Load Combination 1:
Factored dead load, wdf 1.4 (4.56 1) 7.78 kN/m2 CSA A23.3-14 (Annex C. Table C.1 a)
Load Combination 2:
Factored dead load, wdf 1.25 (4.56 1) 6.95 kN/m2
Factored live load, wlf 1.5 1.9 2.85 kN/m2 CSA A23.3-14 (Annex C. Table C.1 a)
Check the adequacy of slab thickness for beam action (one-way shear) CSA A23.3-14 (13.3.6)
at an interior column:
The critical section for one-way shear is extending in a plane across the entire width and located at a distance,
dv from the face of support or concentrated load (see Figure 3). CSA A23.3-14 (13.3.6.1)
Consider a 1 m. wide strip.
2
5,500 400
139 1, 000
2 2
Tributary area for one-way shear is ATributary 2.41 m 2
1, 0002
V f wf ATributary 9.8 2.41 23.63 kN
Where:
1 for normal weight concrete CSA A23.3-14 (8.6.5)
0.21 for slabs with overall thickness not greater than 350 mm CSA A23.3-14 (11.3.6.2)
dv Max (0.9davg ,0.72h) Max (0.9 154,0.72 190) 139 mm CSA A23.3-14 (3.2)
139
Vc 0.65 1 0.21 28 1,000 100.4 kN Vu
1,000
Slab thickness of 190 mm is adequate for one-way shear.
Check the adequacy of slab thickness for punching shear (two-way shear) at an interior column (Figure 4):
1, 000
The factored resisiting shear stress, Vr shall be the smallest of : CSA A23.3-14 (13.3.4.1)
2 2
a) vr vc 1 0.19c f 'c 1 0.19 0.65 28 1.96 MPa
c 1
d 4 154
b) vr vc s 0.19 c f 'c 0.19 1 0.65 28 1.61 MPa
o
b 2216
Vf 223.37 kN
V f , ave 1, 000 0.655 MPa
bod 2, 216 154
3
Vr
2 1.2 CAC Concrete Design Handbook 4th Edition (5.2.3)
V f , ave
Figure 3 – Critical Section for One-Way Figure 4 – Critical Section for Two-Way
Shear Shear
d. Column dimensions - axial load
Pr ,max (0.2 0.002h) Pro 0.80Pro (For tied column along full length) CSA A23.3-14 (Eq. 10.9)
Pr ,max 1,882.32 kN Pf
1 0.85 0.0015 f 'c 0.85 0.0015 28 0.808 0.67 CSA A23.3-14 (Eq. 10.1)
CSA A23.3 states that a regularslab system may be designed using any procedure satisfying conditions of
equilibrium and compatibility with the supports, provided that it is shown that the factored resistance at every
section is at least equal to the effects of the factored loads and that all serviceability conditions, including specified
limits on deflections, are met. CSA A23.3-14 (13.5.1)
4
CSA A23.3 permits the use of Plastic Plate Theory Method (PPTM), Theorems of Plasticity Method (TPM),
Direct Design Method (DDM) and Elastic Frame Method (EFM); known as Equivalent Frame Method in the
ACI; for the gravity load analysis of orthogonal frames. The following sections outline the solution per DDM,
EFM, and spSlab software respectively.
Two-way slabs satisfying the limits in CSA A23.3-14 (13.9) are permitted to be designed in accordance with
the DDM.
5
Table 2 - Lateral Distribution of the Total Design Strip Moment, MDES
Total Design
Moment in Two
Strip Column Strip
Location Half Middle Strips,
Moment, Moment, (kN.m)
(kN.m)
(kN.m)
Exterior
34.8 1.00 × MDES = 34.8 0.00 × MDES = 0.0
Negative*
Exterior Span Positive 69.6 0.6 × MDES = 41.8 0.4 × MDES = 27.8
Interior
93.68 0.8 × MDES = 74.94 0.2 × MDES = 18.7
Negative*
Interior Span Positive 46.8 0.6 × MDES = 28.1 0.4 × MDES = 18.7
*
All negative moments are at face of support.
Mf 34.8 106
As 678 mm2
s f y jd 0.85 400 0.95 150.9
As f y 700 400
a 5.29 mm2
0.9 f 'c b 0.9 28 2,100
jd d a 0.98d
2
Therefore, the assumption that jd equals to 0.98d is valid.
Min As 0.002 Ag 0.002 190 2,100 = 798 mm2 676.24 mm2 CSA A23.3-14 (7.8.1)
Provide 4 - 15M bars concentrated within the band bb (800 mm2 > 798 mm2)
Maximum spacing: CSA A23.3-14 (13.10.4)
6
Negative reinforcement in the band definded by bb:
1.5hs 285 mm 250 mm
Remaining negative moment reinforcement (reinforcement for column strip that is not included in
the band bb):
3hs 570 mm 500 mm
For the exterior negative reinforcements within the band bb, the maximum spacing is 250 mm. To distribute
the bars uniformly, the maximum spacing in the band bb is applied along the whole column strip.
Provide 9 - 15M bars with As 200 mm2 and s 2,100 / 9 233 mm < s max
Note that the number of bars for this section is governed by the maximum spacing allowed by the code.
Based on the procedure outlined above, values for all span locations are given in Table 3.
b. Calculate additional slab reinforcement at columns for moment transfer between slab and column
When gravity load, wind, earthquake, or other lateral forces cause transfer of moment between slab and
column, a fraction of unbalanced moment given by f shall be transferred by flexural reinforcement placed
7
Figure 5 – Critical Shear Perimeters for Columns
Table 4 - Additional Slab Reinforcement required for moment transfer between slab and column (DDM)
Effective
As req’d As prov. For
Mf* γf Mf slab d Add’l
Span Location γf within bb flexure within bb
(kN.m) (kN.m) width, bb (mm) Reinf.
(mm2) (mm2)
(mm)
End Span
Exterior Negative 34.8 0.62 21.5 970 154 420 1,000 -
Column Strip
Interior Negative 0.0 0.60 0.0 970 154 0.0 800 -
*Mf is taken at the centerline of the support in Equivalent Frame Method solution.
M f 0.07 wdf 0.5wlf l2a ln2 wdf' l2' a (ln' )2 CSA A23.3-14 (13.9.4)
0.07 6.95 0.5 2.85 4.2 5.12 6.95 4.2 5.12 10.9 kN.m
With the same column size and length above and below the slab,
10.9
M column 5.45 kN.m
2
b. Exterior Columns:
8
Total exterior negative moment from slab must be transferred directly to the column: M f 34.8 kN.m With
the same column size and length above and below the slab,
34.8
M column 17.4 kN.m
2
The moments determined above are combined with the factored axial loads (for each story) for design of
column sections as shown later in this example.
EFM (as known as Equivalent Frame Method in the ACI 318) is the most comprehensive and detailed procedure
provided by the CSA A23.3 for the analysis and design of two-way slab systems where these systems may, for
purposes of analysis, be considered a series of plane frames acting longitudinally and transversely through the
building. Each frame shall be composed of equivalent line members intersecting at member centrelines, shall
follow a column line, and shall include the portion of slab bounded laterally by the centreline of the panel on
each side. CSA A23.3-14 (13.8.1.1)
Probably the most frequently used method to determine design moments in regular two-way slab systems is to
consider the slab as a series of two-dimensonal frames that are analyzed elastically. When using this analogy,
it is essential that stiffness properties of the elements of the frame be selected to properly represent the behavior
of the three-dimensional slab system.
In a typical frame analysis it is assumed that at a beam-column cconnection all members meeting at the joint
undergo the same rotaion. For uniform gravity loading this reduced restrtaint is accounted for by reducing the
effective stiffness of the column by either Clause 13.8.2 or Clause 13.8.3. CSA A23.3-14 (N.13.8)
Each floor and roof slab with attached columns may be analyzed separately, with the far ends of the columns
considered fixed. CSA A23.3-14 (13.8.1.2)
The moment of inertia of column and slab-beam elements at any cross-section outside of joints or column
capitals shall be based on the gross area of concrete at that section. CSA A23.3-14 (13.8.2.5)
An equivalent column shall be assumed to consist of the actual columns above and below the slab- beam plus
an attached torsional member transverse to the direction of the span for which moments are being determined.
CSA A23.3-14 (13.8.2.5)
9
2.2.1. Elastic frame method limitations
In EFM, live load shall be arranged in accordance with 13.8.4 which requires slab systems to be analyzed
and designed for the most demanding set of forces established by investigating the effects of live load placed
in various critical patterns. CSA A23.3-14 (13.8.4)
Complete analysis must include representative interior and exterior equivalent elastic frames in both the
longitudinal and transverse directions of the floor. CSA A23.3-14 (13.8.1.1)
Panels shall be rectangular, with a ratio of longer to shorter panel dimensions, measured center-to-center of
supports, not to exceed 2. CSA A23.3-14 (3.1a)
For slab systems with beams between sypports, the relative effective stiffness of beams in the two directions
is not less than 0.2 or greater than 2. CSA A23.3-14 (3.1b)
Column offsets are not greater than 20% of the span (in the direction of offset) from either axis between
centerlines of successive columns. CSA A23.3-14 (3.1c)
The reinforcement is placed in an orthogonal grid. CSA A23.3-14 (3.1d)
For cF1 cF 2 , stiffness factors, kNF kFN 4.13 PCA Notes on ACI 318-11 (Table A1)
Ecs I s Ecs I s
Thus, K sb k NF 4.13 PCA Notes on ACI 318-11 (Table A1)
1 1
2.4 109 3
K sb 4.13 26, 739 10 48.2 10 N.m
6
5,500
h3 4, 200(190)3
where, Is s
2.4 109 mm4
12 12
1.5
10
b. Flexural stiffness of column members at both ends, Kc
Referring to Table A7, Appendix 20A, ta 95 mm , tb 95 mm ,
ta H
H 2.75 m = 2, 750 mm, t 190 mm, Hc 2560 mm, 1, 1.07
tb Hc
4.74 Ecc I c
Kc PCA Notes on ACI 318-11 (Table A7)
c
2.13 109 3
Kc 4.74 31, 047 10 114 10 N.m
6
2, 750
c 4 (400)4
Where I c 2.13 109 mm4
12 12
1.5
c 2.75 m = 2,750 mm
x x3 y
Where C 1 0.63 CSA A23.3-14(13.8.2.9)
y 3
190 400
C 1 0.63 190
3
6.4110 mm
8 4
400 3
c2 400 mm , and 2 4.2 m = 4200 mm
(2 114)(2 49.5)
Kec 106
[(2 114) (2 49.5)]
Figure 6 - Torsional Member
11
Kec 69.1106 N.m
column, and Kc is for the upper and lower columns at the slab-
beam joint of an intermediate floor.
e. Slab-beam joint distribution factors, DF
At exterior joint,
48.2
DF 0.41
(48.2 69.1)
At interior joint, Figure 7 – Column and Edge of Slab
48.2
DF 0.29
(48.2 48.2 69.1)
COF for slab-beam 0.509
b. Moment distribution. Computations are shown in Table 5. Counterclockwise rotational moments acting on
the member ends are taken as positive. Positive span moments are determined from the following equation:
12
( M uL M uR )
M u (midspan) M o
2
Where M o is the moment at the midspan for a simple beam.
When the end moments are not equal, the maximum moment in the span does not occur at the midspan, but
its value is close to that midspan for this example.
Positive moment in span 1-2:
Joint 1 2 3 4
Member 1-2 2-1 2-3 3-2 3-4 4-3
DF 0.41 0.29 0.29 0.29 0.29 0.41
COF 0.509 0.509 0.509 0.509 0.509 0.509
FEM +104.7 -104.7 +104.7 -104.7 +104.7 -104.7
Dist -42.93 0.0 0.0 0.0 0.0 42.93
CO 0.0 -21.85 0.0 0.0 21.85 0.0
Dist 0.0 6.34 6.34 -6.34 -6.34 0.0
CO 3.23 0.0 -3.23 3.23 0.0 -3.23
Dist -1.32 0.94 0.94 -0.94 -0.94 1.32
CO 0.48 -0.67 -0.48 0.48 0.67 -0.48
Dist -0.2 0.33 0.33 -0.33 -0.33 0.2
CO 0.17 -0.10 -0.17 0.17 0.1 -0.17
Dist -0.07 0.08 0.08 -0.08 -0.08 0.07
CO 0.04 -0.04 -0.04 0.04 0.04 -0.04
Dist -0.02 0.02 0.02 -0.02 -0.02 0.02
CO 0.01 -0.01 -0.01 0.01 0.01 -0.01
Dist 0.00 0.01 0.01 -0.01 -0.01 0.00
CO 0.01 0.00 -0.01 0.01 0.00 -0.01
Dist 0.0 0.0 0.0 0.0 0.0 0.0
Neg. M 64.1 -119.7 108.5 -108.5 119.7 -64.1
M at
63.8 47.2 -86.6
midspan
13
Figure 9 - Positive and Negative Design Moments for Slab-Beam (All Spans Loaded with Full Factored Live Load)
14
2.2.5. Distribution of design moments
After the negative and positive moments have been determined for the slab-beam strip, the CSA code permits
the distribution of the moments at critical sections to the column strips, beams (if any), and middle strips in
accordance with the DDM. CSA A23.3-14 (13.11.2.2)
M r 44.31 kN.m
Use average davg = 154 mm
In this example, jd will be assumed to be taken equal to 0.97d. The assumptions will be verified once the
area of steel in finalized.
Assume jd 0.97 d 149.4mm
15
jd d a 0.97d
2
Therefore, the assumption that jd equals to 0.97d is valid.
Min As 0.002 Ag 0.002 190 2,100 = 798 mm2 872 mm2 CSA A23.3-14 (7.8.1)
For the negative reinforcements at the exterior span within the band b b, the maximum spacing is 250 mm. To
distribute the bars uniformly, the maximum spacing in the band bb is applied along the whole column strip.
Provide 9 - 15M bars with As 200 mm2 and s 2,100 / 9 233 mm < s max
Note that the number of bars for this section is governed by the maximum spacing allowed by the code.
Based on the procedure outlined above, values for all span locations are given in Table 7.
Table 7 - Required Slab Reinforcement for Flexure [Elastic Frame Method (EFM)]
As Req’d for
Mr b d Min As Reinforcement As Prov. for
Span Location flexure
(kN.m) (m) (mm) 2 (mm2) Provided flexure (mm2)
(mm )
End Span
Exterior Negative 44.31 2.1 154 872 798 9 - 15M 1,800
Column
Strip
Positive 38.28 2.1 154 754 798 6 - 15M 1,200
Interior Negative 76.69 2.1 154 1,548 798 8 - 15M 1,600
Exterior Negative 0 2.1 154 0 798 6 - 15M 1,200
Middle
Strip
Positive 25.52 2.1 154 496 798 6 - 15M 1,200
Interior Negative 19.17 2.1 154 371 798 6 - 15M 1,200
Interior Span
Column
Strip
Positive 28.32 2.1 154 552 798 6 - 15M 1,200
Middle
Strip
Positive 18.88 2.1 154 365 798 6 - 15M 1,200
b. Calculate additional slab reinforcement at columns for moment transfer between slab and column by
flexure
When gravity load, wind, earthquake, or other lateral forces cause transfer of moment between slab and
column, a fraction of unbalanced moment given by f shall be transferred by flexural reinforcement placed
1
f CSA A23.3-14 (13.10.2)
1 (2 / 3) b1 / b2
16
Where
b1 = Width width of the critical section for shear measured in the direction of the span for which moments
are determined according to CSA A23.3-14, clause 13 (see Figure 5).
b2 = Width of the critical section for shear measured in the direction perpendicular to b1 according to CSA
A23.3-14, clause 13 (see Figure 5).
bb = Effective slab width = c2 3 hs CSA A23.3-14 (3.2)
Table 8 - Additional Slab Reinforcement required for moment transfer between slab and column (EFM)
Effective slab As req’d As prov. For
Mu* γf Mu d Add’l
Span Location γf width, bb within bb flexure within bb
(kN.m) (kN.m) (mm) Reinf.
(mm) (mm2) (mm2)
End Span
Column Exterior Negative 64.1 0.62 39.6 970 154 778 1,000 -
Strip Interior Negative 13.2 0.60 7.93 970 154 152 800 -
*Mu is taken at the centerline of the support in Equivalent Frame Method solution.
The unbalanced moment from the slab-beams at the supports of the equivalent frame are distributed to the
support columns above and below the slab-beam in proportion to the relative stiffness of the support columns.
Referring to Figure 9, the unbalanced moment at joints 1 and 2 are:
Joint 1= +64.1 kN.m
Joint 2= -119.7 + 108.5 = -11.2 kN.m
The stiffness and carry-over factors of the actual columns and the distribution of the unbalanced slab
moments (Msc) to the exterior and interior columns are shown in Figure 10a.
17
Figure 10a - Column Moments (Unbalanced Moments from Slab-Beam)
In summary:
M col , Exterior 30.33 kN.m
The moments determined above are combined with the factored axial loads (for each story) and factored
moments in the transverse direction for design of column sections. Figure 10b shows the moment diagrams
in the longitudinal and transverse direction for the interior and exterior equivalent frames. Following the
previous procedure, the moment values at the face of interior, exterior, and corner columns from the
unbalanced moment values can be obtained. These values are shown in the following table.
18
Figure 10b – Moment Diagrams (kips-ft)
This section includes the design of interior, edge, and corner columns using spColumn software. The preliminary
dimensions for these columns were calculated previously in section one. The reduction of live load will be
ignored in this example. However, the detailed procedure to calculate the reduced live loads is explained in the
“wide-Module Joist System” example.
19
3.1. Determination of factored loads
20
3.2. Column Capacity Diagram (Axial-Moment Interaction Diagram)
21
Edge Column (Column #2):
22
Edge Column (Column #3):
23
Corner Column (Column #4):
24
4. Two-Way Slab Shear Strength
Shear strength of the slab in the vicinity of columns/supports includes an evaluation of one-way shear (beam
action) and two-way shear (punching) in accordance with CSA A23.3-14 clause 13.
Where:
dv Max (0.9davg ,0.72h) Max (0.9 154,0.72 190) 139 mm CSA A23.3-14 (3.2)
139
Vc 0.65 1 0.21 28 4200 421.67 kN > V f
1000
Because Vr V f at all the critical sections, the slab has adequate one-way shear strength.
Figure 11 – One-way shear at critical sections (at distance d from the face of the supporting column)
25
4.2. Two-Way (Punching) Shear Strength CSA A23.3-14 (13.3.2)
Two-way shear is critical on a rectangular section located at d/2 away from the face of the column as shown in
Figure 5.
a. Exterior column:
The factored shear force (Vf) in the critical section is computed as the reaction at the centroid of the critical
section minus the self-weight and any superimposed surface dead and live load acting within the critical section
(d/2 away from column face).
The factored unbalanced moment used for shear transfer, Munb, is computed as the sum of the joint moments to
the left and right. Moment of the vertical reaction with respect to the centroid of the critical section is also taken
into account.
For the exterior column in Figure 5, the location of the centroidal axis z-z is:
b1d 3 db13 b1
2
Vf v M unb e
vf CSA A23.3-14 (Eq.13.9)
bo d J
The factored resisiting shear stress, Vr shall be the smallest of : CSA A23.3-14 (13.3.4.1)
26
2 2
a) vr vc 1 0.19c f 'c 1 0.19 0.65 28 1.96 MPa
c 1
d 3 154
b) vr vc s 0.19 c f 'c 0.19 1 0.65 28 1.71 MPa
bo 1508
Since vr vf at the critical section, the slab has adequate two-way shear strength at this joint.
b. Interior column:
554 554
V f 113.19 123.3 9.8 233.48 kN
10
6
For the interior column in Figure 5, the location of the centroidal axis z-z is:
b1 554
cAB 277 mm
2 2
b d 3 db 3 b
2
Vf v M unb e
vf CSA A23.3-14 (Eq.13.9)
bo d J
The factored resisiting shear stress, Vr shall be the smallest of : CSA A23.3-14 (13.3.4.1)
2 2
a) vr vc 1 0.19c f 'c 1 0.19 0.65 28 1.96 MPa
c 1
27
d 4 154
b) vr vc s 0.19 c f 'c 0.19 1 0.65 28 1.61 MPa
bo 2216
Since vr vf at the critical section, the slab has adequate two-way shear strength at this joint.
c. Corner column:
In this example, interior equivalent elastic frame strip was selected where it only have exterior and interior
supports (no corner supports are included in this strip). However, the two-way shear strength of corner supports
usually governs. Thus, the two-way shear strength for the corner column in this example will be checked for
educational purposes. Same procedure is used to find the reaction and factored unbalanced moment used for
shear transfer at the centroid of the critical section for the corner support for the exterior equivalent elastic
frame strip.
477 477
V f 56.56 9.8 54.33 kN
10
6
For the corner column in Figure 5, the location of the centroidal axis z-z is:
b d 3 db 3 b
2
Where:
1
f
1 (2 / 3) b1 / b2
1
f 0.60
1 (2 / 3) 477 / 477
28
bo (400 154 / 2) (400 154 / 2) 954 mm
Vf v M unb e
vf CSA A23.3-14 (Eq.13.9)
bo d J
The factored resisiting shear stress, Vr shall be the smallest of : CSA A23.3-14 (13.3.4.1)
2 2
a) vr vc 1 0.19c f 'c 1 0.19 0.65 28 1.96 MPa
c 1
d 2 154
b) vr vc s 0.19 c f 'c 0.19 1 0.65 28 1.76 MPa
bo 954
Since vr vf at the critical section, the slab has adequate two-way shear strength at this joint.
Since the slab thickness was selected based on the minimum slab thickness equations in CSA A23.3-14, the
deflection calculations are not required. However, the calculations of immediate and time-dependent deflections
are covered in this section for illustration and comparison with spSlab model results.
29
Ma = Maximum moment in member due to service loads at stage deflection is calculated.
The values of the maximum moments for the three service load levels are calculated from structural analysis as
shown previously in this document. These moments are shown in Figure 12.
M cr
fr I g
3.17 / 2 (2.4 109 ) 106 40.11 kN.m CSA A23.3-14 (Eq.9.2)
Yt 95
30
l2 h3 4200 190
3
The calculations shown below are for the design strip (frame strip). The values of these parameters for column
and middle strips are shown in Table 9.
As calculated previously, the exterior span frame strip near the interior support is reinforced with 14 – 15 M
bars located at 350 mm along the section from the top of the slab. Figure 13 shows all the parameters needed
to calculate the moment of inertia of the cracked section transformed to concrete.
1.5 1.5
2, 447
Ecs (3,300 f c' 6,900) c (3,300 28 6,900) 26, 739 MPa CSA A23.3-14(8.6.2.2 )
2,300 2,300
Es 200, 000
n 7.48 CAC Concrete Design Handbook 4th Edition (Table 6.2a)
Ecs 26, 739
b 4200
B 0.2 mm1 CAC Concrete Design Handbook 4th Edition (Table 6.2a)
n As 7.48 14 200
3
The effective moment of inertia procedure is considered sufficiently accurate to estimate deflections. The
effective moment of inertia, Ie, was developed to provide a transition between the upper and lower bounds of
Ig and Icr as a function of the ratio Mcr/Ma. For conventionally reinforced (nonprestressed) members, the
effective moment of inertia, I e, shall be calculated by Eq. (9.1) in CSA A23.3-14 unless obtained by a more
comprehensive analysis.
31
For continuous prismatic members, the effective moment of inertia may be taken as the weighted average of
the values obtained from Eq. (9.1) in CSA A23.3-14 for the critical positive and negative moment sections.
CSA A23.3-14(9.8.2.4)
For the exterior span (span with one end continuous) with service load level (D+LLfull):
For negative moment section:
3
M
I ec I cr I g I cr cr , since M cr 40.11 kN.m < M a = 91.24 kN.m CSA A23.3-14 (Eq.9.1)
Ma
Where Iec is the effective moment of inertia for the critical negative moment section (near the support).
3
40.11
I ec 3.57 108 2.4 109 3.57 108 5.3 10 mm
8 4
91.24
For positive moment section:
M cr 40.11 kN.m < M a =49.2 kN.m
Two of these bars are not continuous and will be conservatively excluded from the calculation of Icr since they
might not be adequately developed or tied (10 bars are used).
b 4, 200
B 0.28 mm1 PCA Notes on ACI 318-11 (Table 10-2)
n As 7.48 10 200
4200 (29.75)3
I cr 7.48 10 200 154 29.75 2.68 108 mm4
2
3
3
M
I em I cr I g I cr cr , since M cr 40.11 kN.m < M a = 49.2 kN.m CSA A23.3-14 (Eq.9.1)
Ma
3
40.11
I em 2.68 108 2.4 109 2.68 108 1.42 10 mm
9 4
49.2
Where Iem is the effective moment of inertia for the critical positive moment section (midspan).
Since midspan stiffness (including the effect of cracking) has a dominant effect on deflections, midspan section
is heavily represented in calculation of Ie and this is considered satisfactory in approximate deflection
calculations. The averaged effective moment of inertia (Ie,avg) is given by:
I e, avg 0.85 I em 0.15 I ec for one end continuous CSA A23.3-14 (Eq.9.4)
I e, avg 0.85 1.42 109 0.15 5.3 108 1.29 109 mm4
32
For the interior span (span with both ends continuous) with service load level (D+LLfull):
3
M
I ec I cr I g I cr cr , since M cr 41.11 kN.m < M a = 82.8 kN.m CSA A23.3-14 (Eq.9.1)
Ma
3
40.11
I ec 3.57 10 2.4 10 3.57 10
8 9
5.89 10 mm
8 8 4
82.8
I e, avg 0.70 2.4 109 0.15 5.89 108 5.89 108 1.86 109 mm4
Where:
Ie1 = The effective moment of inertia for the critical negative moment section at end 1 of continuous beam span.
Ie 2 = The effective moment of inertia for the critical negative moment section at end 2 of continuous beam span.
Table 9 provides a summary of the required parameters and calculated values needed for deflections for exterior
and interior equivalent elastic frame. It also provides a summary of the same values for column strip and middle
strip to facilitate calculation of panel deflection.
33
Table 9 – Averaged Effective Moment of Inertia Calculations
For Frame Strip
Ma, kN.m Ie, mm4 (×108) Ie,avg, mm4 (×108)
Ig, Icr, Mcr,
Span zone mm4 mm4 D+ D+ D+ D+ D+ D+
(×108) (×108) D kN.m D D
LLSus Lfull LLSus Lfull LLSus Lfull
Left 3.78 -36.64 -36.64 -49.17 24 24 14.5
Ext Midspan 2.68 36.67 36.67 49.2 24 24 14.4 21.6 21.6 12.9
Right 3.57 -68.00 -68.00 -91.24 7.76 7.76 5.3
24 40.11
Left 3.57 -61.71 -61.71 -82.80 9.18 9.18 5.89
Int Mid 2.68 26.58 26.58 35.67 24 24 24 19.6 19.6 18.6
Right 3.57 -61.71 -61.71 -82.80 9.18 9.18 5.89
Deflections in two-way slab systems shall be calculated taking into account size and shape of the panel,
conditions of support, and nature of restraints at the panel edges. For immediate deflections two-way slab
systems the midpanel deflection is computed as the sum of deflection at midspan of the column strip or column
line in one direction (Δcx or Δcy) and deflection at midspan of the middle strip in the orthogonal direction (Δmx
or Δmy). Figure 14 shows the deflection computation for a rectangular panel. The average Δ for panels that have
different properties in the two direction is calculated as follows:
cx my cy mx
PCA Notes on ACI 318-11 (9.5.3.4 Eq. 8)
2
To calculate each term of the previous equation, the following procedure should be used. Figure 15 shows the
procedure of calculating the term Δcx. same procedure can be used to find the other terms.
34
Figure 15 –Δcx calculation procedure
Where:
1.5
(23.35)(5,500)4 3
frame, fixed 10 0.96 mm
384(26, 739)(21.6 108 )
I frame
c , fixed LDFc frame, fixed PCA Notes on ACI 318-11 (9.5.3.4 Eq. 11)
Ic
Where LDFc is the load distribution factor for the column strip. The load distribution factor for the column strip
can be found from the following equation:
35
LDFl LDFR
LDF
LDFc 2
2
And the load distribution factor for the middle strip can be found from the following equation:
LDFm 1 LDFc
For the end span, LDF for exterior negative region (LDFL¯), interior negative region (LDFR¯), and positive
+
region (LDFL ) are 1.00, 0.75, and 0.60, respectively (From Table 6 of this document). Thus, the load
distribution factor for the column strip for the end span is given by:
1.0 0.8
0.6
LDFc 2 0.75
2
Ic,g = The gross moment of inertia (Ig) for the column strip for service dead load = 1.2×109 mm4
2.4 109
c , fixed 0.75 0.96 1.45 mm
1.2 109
( M net , L ) frame
c , L PCA Notes on ACI 318-11 (9.5.3.4 Eq. 12)
K ec
Where:
c, L = Rotation of the span left support.
(M net , L ) frame 36.64 kN.m = Net frame strip negative moment of the left support.
36.64 103
c , L 0.00053 rad
69.1106
l Ig
c , L c , L PCA Notes on ACI 318-11 (9.5.3.4 Eq. 14)
8 I e frame
Where:
c, L = Midspan deflection due to rotation of left support.
Ig
= Gross-to-effective moment of inertia ratio for frame strip.
I e frame
Where
36
c , R = rotation of the span right support.
M net , R frame = Net frame strip negative moment of the right support.
Where:
c, R = Midspan deflection due to rotation of right support.
cx cx, fixed cx, R cx, L PCA Notes on ACI 318-11 (9.5.3.4 Eq. 9)
Following the same procedure, Δmx can be calculated for the middle strip. This procedure is repeated for the
equivalent frame in the orthogonal direction to obtain Δcy, and Δmy for the end and middle spans for the other
load levels (D+LLsus and D+LLfull).
Assuming square panel, Δcx = Δcy= 1.92 mm. and Δmx = Δmy= 0.96 mm
The average Δ for the corner panel is calculated as follows:
(cx my ) (cy mx )
cx my cy mx 1.92 0.96 2.88 mm
2
37
Table 10 – Immediate (Instantaneous) Deflections in the x-direction
D D
Span LDF Δframe-fixed, Δc-fixed, θc1, θc2, Δθc1, Δθc2, Δcx, LDF Δframe-fixed, Δm-fixed, θm1, θm2, Δθm1, Δθm2, Δmx,
mm mm rad rad mm mm mm mm mm rad rad mm mm mm
Ext 0.75 0.96 1.45 0.00053 0.000091 0.41 0.07 1.92 0.25 0.96 0.48 0.00053 0.000091 0.41 0.07 0.96
Int 0.7 1.06 1.49 -0.00091 -0.00091 -0.08 -0.08 1.33 0.30 1.06 0.64 -0.00009 -0.00009 -0.08 -0.08 0.48
D+LLsus D+LLsus
Span LDF Δframe-fixed, Δc-fixed, θc1, θc2, Δθc1, Δθc2, Δcx, LDF Δframe-fixed, Δm-fixed, θm1, θm2, Δθm1, Δθm2, Δmx,
mm mm rad rad mm mm mm mm mm rad rad mm mm mm
Ext 0.75 0.96 1.45 0.00053 0.000091 0.41 0.07 1.92 0.25 0.96 0.48 0.00053 0.000091 0.41 0.07 0.96
Int 0.7 1.06 1.49 -0.00091 -0.00091 -0.08 -0.08 1.33 0.30 1.06 0.64 -0.00009 -0.00009 -0.08 -0.08 0.48
D+LLfull D+LLfull
Span LDF Δframe-fixed, Δc-fixed, θc1, θc2, Δθc1, Δθc2, Δcx, LDF Δframe-fixed, Δm-fixed, θm1, θm2, Δθm1, Δθm2, Δmx,
mm mm rad rad mm mm mm mm mm rad rad mm mm mm
Ext 0.75 2.16 3.25 0.00071 0.00012 0.91 0.16 4.31 0.25 2.16 1.08 0.00071 0.00012 0.91 0.16 2.15
Int 0.7 1.50 2.1 -0.00012 -0.00012 -0.11 -0.11 1.88 0.30 1.50 0.9 -0.00012 -0.00012 -0.11 -0.11 0.68
LL LL
Span LDF Δcx, LDF Δmx,
mm mm
Ext 0.75 2.39 0.25 1.19
38
From the analysis in the transverse direction the deflection values below are obtained:
cy
cy
cy
These values for the x-direction are shown in Table 10. Then, the total midpanel deflection is calculated by
combining the contributions of the column and middle strip deflections from the X and Y directions:
cx my cy mx
PCA Notes on ACI 318-11 (9.5.3.4 Eq. 8)
2
Where:
(sust )Inst Immediate (instantaneous) deflection due to sustained load
Unless values are obtained by a more comprehensive analysis, the total immediate plus long-term deflection
for flexural members shall be obtained by multiplying the immediate deflection caused by the sustained load
considered by the factor ζs, as follows: CSA23.3-14 (9.8.2.5)
s
s 1
1 50 '
CSA23.3-14 (Eq .9.5)
For the exterior span
s = 2, consider the sustained load duration to be 60 months or more. CSA A23.3-14 (9.8.2.5)
' = 0, conservatively.
39
s 2
2
1 50 ' 1 50 0
Table 11 shows long-term deflections for the exterior and interior spans for the analysis in the x-direction, for
column and middle strips.
spSlab program utilizes the Elastic (Equivalent) Frame Method described and illustrated in details here for
modeling, analysis and design of two-way concrete floor slab systems. spSlab uses the exact geometry and
boundary conditions provided as input to perform an elastic stiffness (matrix) analysis of the equivalent frame
taking into account the torsional stiffness of the slabs framing into the column. It also takes into account the
complications introduced by a large number of parameters such as vertical and torsional stiffness of transverse
beams, the stiffening effect of drop panels, column capitals, and effective contribution of columns above and
below the floor slab using the of equivalent column concept.
spSlab Program models the equivalent elastic frame as a design strip. The design strip is, then, separated by spSlab
into column and middle strips. The program calculates the internal forces (Shear Force & Bending Moment),
moment and shear capacity vs. demand diagrams for column and middle strips, instantaneous and long-term
deflection results, and required flexural reinforcement for column and middle strips. The graphical and text results
are provided below for both input and output of the spSlab model.
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
7. Summary and Comparison of Two-Way Slab Design Results
Table 12 - Comparison of Moments obtained from Hand (EFM) and spSlab Solution
Hand (EFM) spSlab
Exterior Span
*
Exterior Negative 44.31 44.78
Column Strip Positive 38.28 38.78
*
Interior Negative 76.69 76.83
*
Exterior Negative 0 0
Middle Strip Positive 25.52 25.85
*
Interior Negative 19.98 19.21
Interior Span
*
Interior Negative 69.35 69.57
Column Strip
Positive 28.32 28.11
*
Interior Negative 17.34 17.39
Middle Strip
Positive 18.88 18.74
*
negative moments are taken at the faces of supports
60
Table 14 - Comparison of One-Way (Beam Action) Shear Check Results Using Hand and spSlab Solution
Vu , kN xu* , m φVc, kN
Span
Hand spSlab Hand spSlab Hand spSlab
Exterior 109.35 109.3 5.16 5.16 421.67 420.46
Interior 99.24 99.25 5.16 5.16 421.67 420.46
*
xu calculated from the centerline of the left column for each span
Table 15 - Comparison of Two-Way (Punching) Shear Check Results Using Hand and spSlab Solution
Supp
b1, mm b2, mm bo, mm Ac, mm2 Vu, kN vu, kN/mm2
ort
Hand spSlab Hand spSlab Hand spSlab Hand spSlab Hand spSlab Hand spSlab
Exter 5 5
ior
477 447 554 554 1508 1508 2.32×10 2.32×10 101.21 108.78 0.44 0.47
Interi
or
554 554 554 554 2216 2216 500.00 3.41×105 233.48 233.42 0.68 0.68
Supp
cAB, mm Jc, mm4 γv Munb, kN.m vu, MPa φvc, MPa
ort
Hand spSlab Hand spSlab Hand spSlab Hand spSlab Hand spSlab Hand spSlab
Exter
ior
150.9 150.9 6.15×109 6.15×109 0.38 0.38 51.34 50.05 0.92 0.94 1.31 1.31
Interi
or
277 277 1.78×1010 1.78×1010 0.4 0.4 11.2 11.08 0.79 0.75 1.31 1.31
Table 16 - Comparison of Immediate Deflection Results Using Hand and spSlab Solution (mm)
Column Strip
D D+LLsus D+LLfull LL
Span
Hand spSlab Hand spSlab Hand spSlab Hand spSlab
Exterior 1.92 1.80 1.92 1.80 4.31 3.49 2.39 1.69
Interior 1.33 1.24 1.33 1.24 1.88 1.74 0.55 0.50
Middle Strip
D D+LLsus D+LLfull LL
Span
Hand spSlab Hand spSlab Hand spSlab Hand spSlab
Exterior 0.96 0.91 0.96 0.91 2.15 1.65 1.19 0.74
Interior 0.48 0.46 0.48 0.46 0.68 0.65 0.20 0.19
Table 17 - Comparison of Time-Dependent Deflection Results Using Hand and spSlab Solution
Column Strip
λΔ Δcs, mm Δtotal, mm
Span
Hand spSlab Hand spSlab Hand spSlab
Exterior 2.0 2.0 3.84 3.60 8.16 7.10
Interior 2.0 2.0 2.67 2.48 4.55 4.22
Middle Strip
λΔ Δcs, mm Δtotal, mm
Span
Hand spSlab Hand spSlab Hand spSlab
Exterior 2.0 2.0 1.92 1.82 4.06 3.48
Interior 2.0 2.0 0.97 0.92 1.65 1.57
61
In all of the hand calculations illustrated above, the results are in close or exact agreement with the automated
analysis and design results obtained from the spSlab model except for the deflection were results are differs
slightly (See Section 8 for explanation). Excerpts of spSlab graphical and text output are given above for
illustration.
Deflections calculations in reinforced concrete structures can be very tedious and time consuming because of the
difficulty of accounting for the actual end boundary conditions in a building frame. As a result, numerous methods
to estimate the deflection and the member stiffness have been presented in literature. It is important to note that
these methods can only estimate deflections within an accuracy range of 20% to 40%. It is important for the
designer to be aware of this broad range of accuracy, especially in the modeling, design, and detailing of
deflection-sensitive members.
spSlab uses elastic analysis (stiffness method) to obtain deflections along the column and middle strips by
discretizing the span into 110 elements. It also takes into account the adjacent spans effects, shape effects,
supporting members stiffnesses above and below the beam, and cracked section effects based on the applied
forces. This level of detail provides the maximum accuracy possible compared with other approximate methods
used to calculate deflections. In tables 16 and 17, the deflection values calculated by spSlab is lower than the
values calculated by the approximate method recommended by PCA Notes (the method used in the hand solution).
This can be expected since the approximate method has a built-in conservatism to accommodate a wide range of
applications and conditions. The designer can use spSlab and exploit its numerous features to get a closer
deflection estimate and optimize the depth of the slab under consideration.
A slab system can be analyzed and designed by any procedure satisfying equilibrium and geometric compatibility.
Three established methods are widely used. The requirements for two of them are described in detail in CSA
A23.3-14 Clasues (13.8 and 13.9) for regular two-way slab systems. CSA A23.3-14 (13.5.1)
Direct Design Method (DDM) is an approximate method and is applicable to flat plate concrete floor systems that
meet the stringent requirements of CSA A23.3-14 (13.9.1). In many projects, however, these requirements limit
the usability of the Direct Design Method significantly.
The Elastic Frame Method (EFM) has less stringent limitations compared to DDM. It requires more accurate
analysis methods that, depending on the size and geometry can prove to be long, tedious, and time-consuming.
StucturePoint’s spSlab software program solution utilizes the EFM to automate the process providing
considerable time-savings in the analysis and design of two-way slab systems as compared to hand solutions using
DDM or EFM.
62
Finite Element Method (FEM) is another method for analyzing reinforced concrete slabs, particularly useful for
irregular slab systems with variable thicknesses, openings, and other features not permissible in DDM or EFM.
Many reputable commercial FEM analysis software packages are available on the market today such as spMats.
Using FEM requires critical understanding of the relationship between the actual behavior of the structure and
the numerical simulation since this method is an approximate numerical method. The method is based on several
assumptions and the operator has a great deal of decisions to make while setting up the model and applying loads
and boundary conditions. The results obtained from FEM models should be verified to confirm their suitability
for design and detailing of concrete structures.
The following table shows a general comparison between the DDM, EFM and FEM. This table covers general
limitations, drawbacks, advantages, and cost-time efficiency of each method where it helps the engineer in
deciding which method to use based on the project complexity, schedule, and budget.
63
Applicable
Concrete Slab Analysis Method
CSA
Limitations/Applicability
A23.3-14 DDM EFM FEM
Provision (Hand) (Hand//spSlab) (spMats)
Panels shall be rectangular, with ratio of
13.8.1.1
13.9.1.1
longer to shorter panel dimensions, measured
center-to-center supports, not exceed 2.
For a panel with beams between supports on
13.8.1.1 all sides, slab-to-beam stiffness ratio shall be
13.9.1.1 satisfied for beams in the two perpendicular
directions.
Column offset shall not exceed 20% of the
13.8.1.1
13.9.1.1
span in direction of offset from either axis
between centerlines of successive columns
13.8.1.1 The reinforcement is placed in an orthogonal
13.9.1.1 grid.
Minimum of three continuous spans in each
13.9.1.2
direction
Successive span lengths measured center-to-
13.9.1.3 center of supports in each direction shall not
differ by more than one-third the longer span
64