Data sheet 3WA1125-3CE01-8AA0
Fixed-mounted circuit breaker IEC 60947-2,
frame size 1, 3-poles, In=2500A up to 690V
AC 50/60Hz, breaking capacity S
Icu=66/50kA at 500/690V, Trip unit ETU600
LSI upgrade ready , colordisplay, bluetooth
and USB interface, Protection LT, ST, INST, N-
protection required an external N-sensor,
incl. trip alarm switch (1xCO), rear
connection vertical, able to communication,
with manual and motorized operating
mechanism (M) 208-240 V AC / 220-250 V
DC, Storage status and ready-to- close
signaling switches, Auxiliary switches
4NO+4NC, without Closing coil (CC), manual
operating mechanism with mechanical
closing, without Remote trip alarm reset coil
(RR), without 2nd shunt trip, without 1st
Shunt trip
Model
product brand name SENTRON
product designation 3WA air circuit breaker
suitability for use circuit breaker
size of the circuit-breaker I
number of poles 3.00
position / of neutral conductor no internal N-conductor
fastening method fixed-mounted circuit breakers
type of the driving mechanism manual operating mechanism/spring
charging motor with spring charge signaling
switch
design of the electronic trip unit ETU600 LSI
General technical data
insulation voltage / rated value 1,000.00 V
operating voltage / at AC / at 50/60 Hz / 690 V
rated value
power loss [W] / maximum 360 W
3WA1125-3CE01-8AA0 Subject to change without notice
Page 1/8 © Copyright Siemens
3/4/2023
Current
continuous current / rated value / maximum 2,500.00 A
continuous current / rated value 2,500.00 A
operating current
• at 40 °C / rated value 2,500 A
• at 45 °C / rated value 2,500 A
• at 50 °C / rated value 2,500 A
• at 55 °C / rated value 2,500 A
• at 60 °C / rated value 2,500 A
• at 65 °C / rated value 2,500 A
• at 70 °C / rated value 2,500 A
Switching capacity and short-time withstand current rating, according to IEC60947-2
switching capacity class of the circuit S
breaker
maximum short-circuit current breaking
capacity (Icu)
• at 500V 66 kA
• at 690V 50 kA
operational short-circuit current breaking
capacity (Ics)
• at 500V 66 kA
• at 690V 50 kA
short-circuit current making capacity (Icm)
• at 500V 145 kA
• at 690V 105 kA
Short-time withstand current (Icw) at AC
500V
• at 0,5s 66 kA
• at 1s 66 kA
• at 2s 45 kA
• at 3s 35 kA
Short-time withstand current (Icw) at AC
690V
• at 0,5s 50 kA
• at 1s 50 kA
• at 2s 45 kA
• at 3s 35 kA
Short-time withstand current (Icw) at AC
1000V
Short-time withstand current (Icw) at AC
1150V
conditional short-circuit current (Icc) / for
non-automatic air circuit breakers
conditional short-circuit current (Icc) / for
non-automatic air circuit breakers / at DC
3WA1125-3CE01-8AA0 Subject to change without notice
Page 2/8 © Copyright Siemens
3/4/2023
Electronic trip unit
product feature
• upgradable Yes
• Bluetooth and USB interface Yes
• decoder for basic protection Yes
functions
• display and function keys Yes
• SENTRON powerconfig configuration Yes
software
General protection functions
L: Overload protection LT
product feature / for L-tripping
product feature / for L-tripping / can be Yes
switched on/off
product feature / for L-tripping / selectable Yes
characteristic function
Parameter setting via eSET or rotary coding Yes
switches
L: Overload protection LT, i2t characteristic
Current setting (Ir) 0.5;0.6;0.7;0.75;0.8;0.85;0.9;0.95;1.0
Reference value for current setting (Ir) x In
Tripping time (tr) 1;2;5;8;10;14;17;21;25
Reference value for tripping time (tr) s
Current setting (Ir) via eSET 0.4-1;0.001
Absolute value current setting (Ir) via eSET 1,000.00
minimum
Absolute value current setting (Ir) via eSET 2,500.00
maximum
Tripping time (tr) via eSET 0.5-30;0.001
L: Overload protection LT, i4t characteristic
Current setting (Ir) via eSET 0.4-1;0.001
Tripping time (tr) via eSET 0.5-5;0.001
Reference value for tripping time (tr) s
3WA1125-3CE01-8AA0 Subject to change without notice
Page 3/8 © Copyright Siemens
3/4/2023
Minimum adjustable value current setting 1,000 A
(Ir) via eSET
Maximum adjustable value current setting 2,500 A
(Ir) via eSET
L: Overload protection neutral conductor
product feature / with neutral conductor
protection
product feature / with neutral conductor Yes
protection / can be switched on/off
Current setting (InN) 0.2-2;0.001
Reference value for current setting (InN) x In
Minimum adjustable value current setting 500 A
(InN) via eSET
Maximum adjustable value current setting 5,000 A
(InN) via eSET
S: Short-time-delayed short-circuit protection ST
product feature / for S-tripping
product feature / for S-tripping / Yes
independent of direction / can be switched
on/off
product feature / for S-tripping / Yes
independent of direction / selectable
characteristic function
Parameter setting via eSET or rotary coding Yes
switches
S: Short-time-delayed short-circuit protection ST, characteristic i0t
Current setting (Isd) 1.5;2;2.5;3;4;5;6;8;10
Reference value for current setting (Isd) x Ir
Tripping time (tsd) 0.08;0.15;0.22;0.3;0.4
Reference value for tripping time (tsd) s
Current setting (Isd) via eSET 0.6-10;0.001
Minimum adjustable value current setting 1,500 A
(Isd) via eSET
Maximum adjustable value current setting 52.8 kA
(Isd) at 500V via eSET
Maximum adjustable value current setting 40.0 kA
(Isd) at 690V via eSET
Tripping time (Isd) via eSET 0.02-0.4;0.001
3WA1125-3CE01-8AA0 Subject to change without notice
Page 4/8 © Copyright Siemens
3/4/2023
S: Short-time-delayed short-circuit protection ST, characteristic i2t
Current setting (Isd) 1.5;2;2.5;3;4;5;6;8;10
Reference value for current setting (Isd) x Ir
Tripping time (tsd) 0.1;0.2;0.3;0.4
Current setting (Isd) via eSET 0.6-10;0.001
Minimum adjustable value current setting 1,500 A
(Isd) via eSET
Maximum adjustable value current setting 52.8 kA
(Isd) at 500V via eSET
Maximum adjustable value current setting 40.0 kA
(Isd) at 690V via eSET
Tripping time (Isd) via eSET 0.02-0.4;0.001
I: Instantaneous short-circuit protection INST
product feature / for I-tripping
product feature / for I-tripping / can be Yes
switched on/off
Parameter setting via eSET or rotary coding Yes
switches
Current setting (Ii) 1.5;2;3;4;6;8;10;12;15
Reference value for current setting (Ii) x In
Current setting (Iimax) 0.80
Reference value for current setting (Iimax) x Ics
Current setting (Ii) via eSET 1.5-15;0.001
Minimum adjustable value current setting 3,750.0 A
(Ii) via eSET
Maximum adjustable value current setting 52.8 kA
(Ii) at 500V via eSET
Maximum adjustable value current setting 40.0 kA
(Ii) at 690V via eSET
G: Ground-fault protection GF
product feature / for G-tripping
product feature / for G-tripping / can be No
switched on/off
product feature / for G-tripping / selectable No
characteristic function
G: Ground-fault protection GF : characteristic i0t
G: Ground-fault protection GF : characteristic i2t
3WA1125-3CE01-8AA0 Subject to change without notice
Page 5/8 © Copyright Siemens
3/4/2023
Further protection functions
Protection function
• maintenance mode DAS+ Yes
Measuring functions
measurement function
• current measurement Yes
Communication
communication function / prepared for Yes
communication (Ready4COM)
product function / communication function Yes
Durability
mechanical service life (switching cycles)
• without maintenance / typical 15,000.00
• with maintenance / typical 30,000.00
electrical endurance (switching cycles)
• at 690 V / without maintenance / 10,000
typical
• at 690 V / with maintenance / typical 30,000
Dimensions
height 437.00 mm
width 320.00 mm
depth 357.00 mm
Main connection
arrangement of electrical connectors / for main connection on the rear, vertical
main current circuit
Auxiliary circuits
3WA1125-3CE01-8AA0 Subject to change without notice
Page 6/8 © Copyright Siemens
3/4/2023
design of the auxiliary switch 4 NO + 4 NC
number of NC contacts / for auxiliary 4.00
contacts
number of NO contacts / for auxiliary 4.00
contacts
number of CO contacts / for auxiliary 0.00
contacts
Internal accessories
product component / undervoltage release No
product component / voltage trigger No
product component / trip indicator Yes
product component / motor drive Yes
Electronic Accessories
Environment conditions
protection class IP / on the front IP20
Ambient temperature during operation
• min -40 °C
• max 70.00 °C
Ambient temperature during storage
• min -40 °C
• max 80.00 °C
Certificates
protection class IP / on the front Q
Further information
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3WA1125-3CE01-8AA0
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3WA1125-3CE01-8AA0
Image database (product images, 2D dimension drawings, 3D models, device circuit
diagrams, ...) http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3WA1125-
3CE01-8AA0
3WA1125-3CE01-8AA0 Subject to change without notice