Bat-Dwg-Dd-Me-01-Al-1601.01 - R0 - Lightning Protection Installation Layout

The document contains a diagram showing the layout of an existing lightning protection system for a building. It includes details on the positioning of air terminals, earth pits, bonding bars, and a grounding ring buried around the building perimeter. Notes specify that earth pits should be spaced no more than 20 meters apart, the target earth resistance is 3 ohms or less, and the grounding ring should be buried 600mm deep.

Uploaded by

Cosphiii
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
69 views1 page

Bat-Dwg-Dd-Me-01-Al-1601.01 - R0 - Lightning Protection Installation Layout

The document contains a diagram showing the layout of an existing lightning protection system for a building. It includes details on the positioning of air terminals, earth pits, bonding bars, and a grounding ring buried around the building perimeter. Notes specify that earth pits should be spaced no more than 20 meters apart, the target earth resistance is 3 ohms or less, and the grounding ring should be buried 600mm deep.

Uploaded by

Cosphiii
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

NORTH

CANOPY EXISTING CANOPY EXISTING


2301

8875

- ALL DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED OTHERWISE


9 - ALL LEVELS ARE IN METERS UNLESS NOTED OTHERWISE
4260

SLOPE 15°

SLOPE 15°

SLOPE 15°

SLOPE 15°

SLOPE 15°

SLOPE 15°
R1 R1 R1 R1 R1 LEGEND :

8540
8 SLOPE 3° = AIR TERMINAL COPPER ROD Ø16mm,
1500mm HEIGHT
4280

= EARTH PIT

= EARTHING BONDING BAR (COPPER BAR)


40X3MM THK, LENGTH AS REQUIRED C/W
ISOLATOR
7 = BARE COPPER LIGHTNING DOWN
CONDUCTOR 50m
4260

21710
= MAIN GROUNDING RING BC 70mm2/ SHALL BE
BURIED 600mm BELOW GRADE AND
SLOPE 3° APROXIMATELY 1,000mm FROM BUILDING
SLOPE 15°

SLOPE 15°

SLOPE 15°

SLOPE 15°
R1 R1 R1 PERIMETER.

6 NOTES :

1. DISTANCE BETWEEN EARTH PIT ±20m LENGTH


30000

12920
4400

R2 2. RESISTANCE IS 3 Ω MEASURE AT 3 DAYS RAIN OFF.


3. FOR GROUNDING POINT BUILDING SEE DWG ON
EVERY BUILDINGS.
SLOPE 15°

SLOPE 15°

SLOPE 15°

SLOPE 15°
4. USE CABLE BC TO EQUIPMENT AS FOLLOW
5 - TO PIPING 10mm²
R1 R1 R1 - TO DUCTING 10mm²
- TO CABLE TRAY 16mm²
4260

SLOPE 3° - TO STEEL STRUCTURE 16mm²


- TO TANK
- TO PANEL (VARIOUS) FOLLOW TO NYA CABLE
DIMENSION OF LEADER INSTALLATION AT EVERY
4

250
PANELS
4280

SLOPE 3°
SLOPE 3°
SLOPE 15°

SLOPE 15°

SLOPE 15°

SLOPE 15°

SLOPE 15°

SLOPE 15°
3
R1 R1 R1 R1 R1

12433
4260

= REVISION CLOUD
R2

16700
2
4143

SLOPE 15°

SLOPE 15°
1 R1 R1 R1

0 ISSUED FOR CONSTRUCTION BU IK IK 10.02.2023

4267
SLOPE 3°
NO. DESCRIPTION BY CHKD APVD DATE
THIS DRAWING IS A PRIVATE AND CONFIDENTIAL
COMMUNICATION AND THE PROPERTY OF CLIENT.IT MUST
NOT BE COPIED OR LENT WITHOUT THE COMMENT OF
CLIENT AND MUST BE RETURNED WITH TENDER AND/OR
6000 6000 6000 6000 6000 6000 6000 6000 6000 6000 ON COMPLETION OF ORDER.

5715 APPROVED BY CLIENT

2000 60000 2000

A B C D E F G H I J K L Menara 165, 12th Floor


Jl. TB Simatupang Kav. 1 Cilandak Timur
GROUP Jakarta Selatan 12560 Indonesia
Shaping Tomorrow tel +62 21 2940 6840 - fax +62 2940 6841

BATI - DETAIL DESIGN

DRAWING TITLE :

35 ELECTRICAL & ELECTRONICAL


LIGHTNING PROTECTION INSTALLATION LAYOUT

SCALE : As indicated FORMAT SIZE : A3


PROJECT DRAWING NO. REV
P-21-018 BAT-DWG-DD-ME-01-AL-1601.01 0