I LOCATION MAP IV SINGLE-LINE DIAGRAM TABLE OF CONTENTS
E1-03 SCALE: NTS E1-03 SHEET#E1 COVER PAGE
2 - #8.0mm² TW Cu I) LOCATION PLAN
II) LEGEND
THIS SITE FED FROM ANECO
COMMONAL
III) GENERAL NOTES
KWH
METER
M IV) SINGLE LINE DIAGRAM (SLD)
V) RISER DIAGRAM
SHEET#E2 VI) SCHEDULE OF LOADS
BRGY.HALL XI) ILLUMINATION COMPUTATION
N
BRGY.MAHAY Y LEMO
COVERED COURT TO BRG 2 - #8.0mm² TWCu XII) BUILDING LOAD DETAILS
SHEET#E3 VII)ELECTRICAL LAYOUT: LO&POWER
BRID GE
APAGAL
TO MAC
60AT/60AF, 2P, 1Ø, SHEET#E4 DESIGN ANALYSIS
10kAIC @230V VIII) SHORT CKT COMPUTATION
IX) VOLTAGE DROP COMPUTATION
TO BRGY.TAGABACA 15AT/30AF,6kAIC 15AT/30AF,6kAIC
X) IMPEDANCE DIAGRAM
C1 C2 XIII) ARC-FLASH HAZARD COMPUTATION
30AT/30AF,6kAIC
LOCATION MAP C3
20AT/30AF,6kAIC
C4
XIV) PROTECTION COORDINATION
20AT/30AF,6kAIC
SPARE SPACE
III GENERAL NOTES
E1-03
ALL ELECTRICAL WORKS HEREIN INCLUDED SHALL BE EXECUTED ACCORDING TO THE LATEST
REQUIREMENTS OF THE FOLLOWING:
Grounding GROUNDING
A. THE PHILIPPINES ELECTRICAL CODE -2017 PART-1 & PEC-2008 PART-2
B. REQUIREMENTS OF ANECO & NEA 1 - #5.5mm² TW Cu Electrode System BUS (Cu)
C. NATIONAL BUILDING CODE OF THE PHILIPPINES. (LATEST EDITION)
D. DOE - PHIL. DISTRIBUTION CODE- 2016
FOR REASON OF SAFETY, ENERGY CONSERVATION AND EASE OF MAINTENANCE. ALL WIRING INSTALLATION TO GROUND
CONFORMING TO A SUITABLE COLOR SCHEME. V RISER DIAGRAM
LINE 1 - BLACK GROUND - GREEN OR BARE E1-03
LINE 2 - RED
EQUIPMENT GROUND - GREEN OR BARE SOLID CONDUCTOR SHALL BE
EMPLOYED ONLY IN SYSTEM - GROUND INSTALLATION WHICH IS BONDED TO STEEL MEMBERS OF
STRUCTURAL COLUMNS AND FOUNDATIONS AND FOR DIRECT BURIAL TO THE SOIL (EARTH).
SINGLE LINE DIAGRAM
OVERHEAD SERVICE ENTRANCE: 230 V, 1Ø, 2W
THE JOB SHALL BE EXECUTED IN NECA-2015 PROVISIONS & EMPLOYING STANDARD TOOLS, -#8.0mm2 THW Copper 60Hz., A.C. WITH 32mmØ
EQUIPPED METHODS AND GOOD ENGINEERING PRACTICES. THE JOB SHALL BE DONE IN ALL ASPECTS TYPE "F" CONDULET, & SERVICE HEAD
WEATHERHEAD
AS REQUIRED IN THE PLANS & SPECIFICATIONS UNTIL FINAL COMMISSIONING .
2w - 8.0mm² THWN + 1-5.5mm²
TW (G) in 32mmØ PVC
UNLESS OTHERWISE SPECIFIED PULL BOXES AND JUNCTION BOXES SHALL BE PROVIDED
WHENEVER REQUIRED AND NECESSARY EVEN THOUGH SUCH BOXES ARE NOT INCLUDED IN THE
PLANS.
THE MINIMUM SIZE OF CONDUIT WIRING INSTALLATION SHALL BE 20mm DIAMETER uPVC (80sch).
ALL CONDUITS SIZES LISTED IN THE SCHEDULE OF LOADS SHALL BE CONSIDERED MINIMUM
REQUIREMENT.
THE MINIMUM SIZE OF FEEDER CONDUCTOR SHALL BE 3.5mm² THW Cu WIRE. 5.5mm² TW GROUND WIRE in
1800 mm
15mmØ C CLAMPED TO V LEGEND
COPPER-CLAD GROUNDING E3-04 SCALE: NTS
CONDUITS PIPE FOR INSTALLATION INSIDE CEILING, WOOD PARTITION, ROD
UNDER GROUND OR EMBEDDED IN THE FLOOR SLAB SHALL BE uPVC.
1800 mm SYMBOL DESCRIPTION
ALL RECEPTACLE OUTLETS SUPPLYING POWER TO OFFICE BUSINESS MACHINES, HEATING ELEMENTS,
POWER TOOLS AND SIMILAR DEVICES SHALL BE GROUNDED TYPE, (I.E THREEPRONG GROUNDED PANEL BOARD
RECEPTACLE).
DUPLEX CONVENIENCE OUTLET
AUXILLIARY CIRCUITS FOR COMMUNICATION, FIRE ALARM, SECURITY SYSTEM, ETC. MUST BE PROVIDED
LED 9W
WITH SEPARATE RACEWAY APART FROM THOSE INSTALLED FOR ELECTRICAL POWER SYSTEM PROVIDE AT
LEAST 150mm DISTANCE SEPARATION BETWEEN ELECTRICAL CIRCUITS AND AUXILLIARY CIRCUITS SYSTEMS. SPECIAL OUTLET
XX
ALL CONVENIENCE OUTLET AT DELIVERY AREA MUST BE 450mm ABOVE FLOOR LINE. XX CIRCUIT HOMERUN
ACU# AIRCONDITIONING UNIT
ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A LICENSED ELECTRICAL
CEILING FAN
PRACTITIONER WHOSE LICENSE AND CERTIFICATE OF REGISTRATION IS STILL VALID (R.A. 7920) .
DESIGNED BY: THIS DRAWING IS ISSUED FOR :
SEAL R.A.9266 Section 33 PROJECT TITLE APPROVED BY SHEET CONTENT MEV1 SHEET NO.
AS BUILT ESTIMATE
ENGR. MARIO E. VINAS Drawing and specifications and other I) LOCATION PLAN /VICINITY PLAN AS SHOWN DRAFTED BY:
contr act documents signed, stamped or BIDDING FABRICATION
PROFESSIONAL ELECTRICAL ENGINEER sealed, as instruments of service, are the
intellectual property and documents of the
architect, whether the object for which they are
PROPOSED 1-STOREY RESIDENTIAL BUILDING
MR & MRS NORBERTO P. ESTROZO
GENERAL NOTES NA
DATE DRAFTED:
BUILDING PERMIT OWNER'S APPROVAL E 1
SINGLE LINE DIAGRAM NA 10SEPT2021 CONSTRUCTION DEVELOPMENT PERMIT
PRC NO: 1869 DATE : 2/28/2024
made is executed or not, if shall be unlawful
for any person to duplicate or to make copies ELECTRICAL PLAN RISER DIAGRAM NA REVISIONS DATE REVISIONS DATE NO. ALL SHEETS
of said documents for use in the repetition of OWNER
and for other projects of building, whether
PTR NO: 2011898 DATE : 1/4/2021 executed partly in whole, without the written
consent of ar chitect or author of said
LOCATION: Brgy. Mahay, Butuan City ADDRESS: BRGY. MAHAY, BUTUAN CITY