Mark Anjelo U. Estrada: Professional Electrical Engineer

The document is a single page electrical load calculation sheet for a residential home. It includes calculations for circuit loads, feeder sizing, and overcurrent protection. Key details include a total connected load of 13,340VA served by a 2-22mm2 THHN + 1-8.0mm2 THW(G) feeder in a 32mm IMC conduit. Main protection is specified as an 80AT, 100AF, 2P, 230V, 10kAIC MCCB.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
459 views8 pages

Mark Anjelo U. Estrada: Professional Electrical Engineer

The document is a single page electrical load calculation sheet for a residential home. It includes calculations for circuit loads, feeder sizing, and overcurrent protection. Key details include a total connected load of 13,340VA served by a 2-22mm2 THHN + 1-8.0mm2 THW(G) feeder in a 32mm IMC conduit. Main protection is specified as an 80AT, 100AF, 2P, 230V, 10kAIC MCCB.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

MARK ANJELO U.

ESTRADA
PROFESSIONAL ELECTRICAL ENGINEER

PRC REG NO.: 0004102 PTR NO.: 5509352

VALIDITY: MARCH 14, 2026 ISSUED ON: JANUARY 03, 2023

TIN: 265-421-698-000 ISSUED AT: BAGUIO CITY


PP 230V, 1Ø, 60Hz, 2 WIRE + GROUND
SWITCHES Load in Volts CURRENT BREAKER WIRES/CABLES WIREWAY
CKT. DESCRIPTION LO CO kAIC
S1 S2 S3 VA (V) (A) (min) CONDUIT
NO. AT AF POLE LINE GROUND
1 LIGHTING 24 - 3 1 894.00 230 3.89 20 50 2 10 2-3.5mm² THWN 1-3.5mm² THWN 15mmø EMT
2 LIGHTING 26 - 4 - 1,011.00 230 4.40 20 50 2 10 2-3.5mm² THWN 1-3.5mm² THWN 15mmø EMT
3 CONVENIENCE OUTLET 11 1,980.00 230 8.61 20 50 2 10 2-3.5mm² THWN 1-3.5mm² THWN 15mmø EMT
4 CONVENIENCE OUTLET 3 540.00 230 2.35 20 50 2 10 2-3.5mm² THWN 1-3.5mm² THWN 15mmø EMT
5 CONVENIENCE OUTLET 8 1,440.00 230 6.26 20 50 2 10 2-3.5mm² THWN 1-3.5mm² THWN 15mmø EMT
6 2.5HP AIRCON 3,335.00 230 14.50 30 50 2 10 2-5.5mm² THWN 1-5.5mm² THWN 15mmø EMT
7 1.5HP AIRCON 2,300.00 230 10.00 30 50 2 10 2-5.5mm² THWN 1-5.5mm² THWN 15mmø EMT
8 1HP AIRCON 1,840.00 230 8.00 20 50 2 10 2-3.5mm² THWN 1-3.5mm² THWN 15mmø EMT
9 SPARE 230 0.00 30 50 2 10
10 SPARE 230 0.00 20 50 2 10

TOTAL CONNECTED LOAD 13,340.00 58.00

FOR FEEDER CONDUCTOR FOR OVERCURRENT PROTECTIVE DEVICE


IT = [13,340VA + (25% x 3,335VA)] / 230V = 61.63A IL - IFL HIGHEST RATED MOTOR = 58A - 14.50A = 43.50A
IT = 61.63A 250% IFL OF HIGHEST RATED MOTOR = 14.50A x 250% = 36.25A
43.50A + 36.25A = 79.75A

USE: 2-22mm² THHN + 1-8.0mm² THW(G) IN 32mmØ IMC MAIN: 80AT, 100AF, 2P, 230V, 10kAIC (min.), MCCB