2/19/23, 10:31 AM MZQE.
EX16243 - Fire Hose, Lined, Uncoupled, for Municipal and Industrial Use | UL Product iQ
MZQE.EX16243 - Fire Hose, Lined, Uncoupled, for
Municipal and Industrial Use
Fire Hose, Lined, Uncoupled, for Municipal and Industrial Use
See General Information for Fire Hose, Lined, Uncoupled, for Municipal and Industrial Use
NEWAGE FIRE FIGHTING CO LTD EX16243
Plot 93 / 94 Lms Compound
Gidc Phase 1
Wadhwan, Surendrangr, 363030 INDIA
MODEL: Pyroprotect, Permaline, Pyroblind, Aquarush, Aquasurge, Pyrosurge, Pyrostream
Hose Size Service.Test.Pressure
(in.) (psig) Hose Type Ratings Comments
1-1/2, 2- 250 Single- Ozone Lining (NBR/PVC) Jacket (Woven Polyester)
1/2 jacketed Resistant Cover (NBR/PVC)
Conductive Heat Exposure: Steel Block at 400°C (752°F)
Hose Size (in.) Exposure Duration Avg Leakage Rate @ 150 psi Max Leakage Rate @ 150 psi
1-1/2 7 min 31 sec < 1 GPM < 1 GPM
2-1/2 1 min 28 sec < 1 GPM < 1 GPM
Radiant Heat Exposure: 30 kw/m2
Hose Size (in.) Exposure Duration Avg Leakage Rate @ 150 psi Max Leakage Rate @ 150 psi
1-1/2
Reddish brown 1 min 44 sec 20 GPM 20 GPM
2-1/2
Reddish brown 1 min 33 sec 2.22 GPM 3.55 GPM
MODEL: Premier, Supreme, Firemaster Super, Commander Super, Fire Chief, Fire Out RRL, Firestorm, Aquastrike, Flameblitz, MELTON, MELTON
PLUS, PREMIER EXTRA & NOVADURA.
Hose Size Service.Test.Pressure
(in.) (psig) Hose Type Ratings Comments
1-1/2, 2-1/2 250 Single- Ozone Lining (EPDM) Jacket (Woven
jacketed Resistant Polyester)
Conductive Heat Exposure: Steel Block at 400°C (752°F)
https://iq.ulprospector.com/en/profile?e=68109 1/3
2/19/23, 10:31 AM MZQE.EX16243 - Fire Hose, Lined, Uncoupled, for Municipal and Industrial Use | UL Product iQ
Hose Size (in.) Exposure Duration Avg Leakage Rate @ 150 psi Max Leakage Rate @ 150 psi
1-1/2 1.56 sec 20 GPM 20 GPM
2-1/2 2.11 sec 20 GPM 20 GPM
Radiant Heat Exposure: 30 kw/m2
Hose Size (in.) Exposure Duration Avg Leakage Rate @ 150 psi Max Leakage Rate @ 150 psi
1-1/2
Reddish brown 1 min 57 sec < 1 GPM < 1 GPM
2-1/2
Reddish brown 1 min 56 sec < 1 GPM 1.30 GPM
MODEL: PREMIER DJ, HYDROLINE, HYDROLINE EXTRA, FIRE CHIEF DJ, AQUASTRIKE DJ
Hose Size Service.Test.Pressure
(in.) (psig) Hose Type Ratings Comments
1-1/2, 2-1/2 300 Double- Ozone Lining (EPDM) Jackets (Woven
jacketed Resistant Polyester)
Conductive Heat Exposure: Steel Block at 400°C (752°F)
Hose Size (in.) Exposure Duration Avg Leakage Rate @ 150 psi Max Leakage Rate @ 150 psi
1-1/2 9.08 sec 20 GPM 20 GPM
2-1/2 38.26 sec 3.77 GPM 11.10 GPM
Radiant Heat Exposure: 30 kw/m2
Hose Size (in.) Exposure Duration Avg Leakage Rate @ 150 psi Max Leakage Rate @ 150 psi
1-1/2
Reddish 2 min 33 sec < 1 GPM < 1 GPM
2-1/2
Reddish 3 min 04 sec < 1 GPM 1.10 GPM
Trademark and/or Tradename: "Aquastrike", "Flameblitz",
Last Updated on 2020-06-02
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL Solutions' Follow - Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL
Solutions' Follow - Up Service. Always look for the Mark on the product.
https://iq.ulprospector.com/en/profile?e=68109 2/3
2/19/23, 10:31 AM MZQE.EX16243 - Fire Hose, Lined, Uncoupled, for Municipal and Industrial Use | UL Product iQ
UL Solutions permits the reproduction of the material contained in Product iQ subject to the following conditions: 1. The Guide Information,
Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading manner,
without any manipulation of the data (or drawings). 2. The statement "Reprinted from Product iQ with permission from UL Solutions" must appear
adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "©2023 UL LLC."
https://iq.ulprospector.com/en/profile?e=68109 3/3