6DL1132-6BH00-0PH1 Et200sp - Ha - DQ - 16x24vdc - 0 - 5a - en-US - en-US

6DL1132-6BH00-0PH1 et200sp_ha_dq_16x24vdc_0_5a_en-US_en-US

Uploaded by

Tanase Georgeta
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
733 views44 pages

6DL1132-6BH00-0PH1 Et200sp - Ha - DQ - 16x24vdc - 0 - 5a - en-US - en-US

6DL1132-6BH00-0PH1 et200sp_ha_dq_16x24vdc_0_5a_en-US_en-US

Uploaded by

Tanase Georgeta
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 44

Security information 1

Preface 2
2D Matrix code (QR code /
EAN code) 3
SIMATIC
Product overview 4
ET 200SP HA
DQ 16x24VDC/0.5A
Terminal 5

Parameters 6
Equipment Manual

Displays and interrupts 7

Technical specifications 8
Parameters, diagnostics
messages and address A
space

6DL1132-6BH00-0PH1
6DL1132-6BH00-0EH1

10/2021
A5E39265993-AD
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage
to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices
referring only to property damage have no safety alert symbol. These notices shown below are graded according to
the degree of danger.

DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.

WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.

CAUTION
indicates that minor personal injury can result if proper precautions are not taken.

NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be
used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property
damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:

WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended or
approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance
are required to ensure that the products operate safely and without any problems. The permissible ambient
conditions must be complied with. The information in the relevant documentation must be observed.

Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication may
be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software described.
Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this
publication is reviewed regularly and any necessary corrections are included in subsequent editions.

Siemens AG A5E39265993-AD Copyright © Siemens AG 2021.


Digital Industries Ⓟ 11/2021 Subject to change All rights reserved
Postfach 48 48
90026 NÜRNBERG
GERMANY
Table of contents

1 Security information.............................................................................................................................. 5
2 Preface ................................................................................................................................................... 7
3 2D Matrix code (QR code / EAN code) .................................................................................................... 9
4 Product overview ................................................................................................................................. 11
4.1 I/O module......................................................................................................................... 11
4.2 Accessories ........................................................................................................................ 12
4.3 Output disable switch ........................................................................................................ 13
4.4 Pulling the I/O module in runtime....................................................................................... 13
4.5 Terminal blocks.................................................................................................................. 14
5 Terminal ............................................................................................................................................... 15
5.1 Pin assignment .................................................................................................................. 15
5.2 Sample connection scheme for 1-wire connection .............................................................. 16
5.3 Sample connection scheme for 2-wire connection .............................................................. 17
5.4 Schematic circuit diagram .................................................................................................. 17
6 Parameters........................................................................................................................................... 19
6.1 Parameter types................................................................................................................. 19
6.2 Module/channel parameters............................................................................................... 19
6.3 Explanation of the module/channel parameters .................................................................. 20
6.3.1 Diagnostics, Missing supply voltage L+ ............................................................................... 20
6.3.2 IO redundancy ................................................................................................................... 20
6.3.3 Diagnostics short-circuit to L+ ............................................................................................ 21
6.3.4 Diagnostics, Short-circuit to ground.................................................................................... 21
6.3.5 Diagnostics, Wire break ...................................................................................................... 21
6.3.6 Wire-break check ............................................................................................................... 21
6.3.7 Channel activated .............................................................................................................. 22
6.3.8 Reaction to CPU STOP......................................................................................................... 22
6.3.9 Substitute value ................................................................................................................. 22
6.3.10 Potential group .................................................................................................................. 22
7 Displays and interrupts ........................................................................................................................ 25
7.1 Status and error displays .................................................................................................... 25
7.2 LEDs .................................................................................................................................. 26
7.2.1 DIAG LED ........................................................................................................................... 26
7.2.2 MT LED .............................................................................................................................. 26
7.2.3 PWR LED ............................................................................................................................ 27
7.2.4 Channel status / fault LEDs ................................................................................................. 27
7.3 Interrupts .......................................................................................................................... 28

DQ 16x24VDC/0.5A
Equipment Manual, 10/2021, A5E39265993-AD 3
Table of contents

8 Technical specifications ....................................................................................................................... 29


A Parameters, diagnostics messages and address space ....................................................................... 37
A.1 Parameter assignment ....................................................................................................... 37
A.2 Parameter assignment and structure of the module/channel parameters............................. 38
A.3 Diagnostics messages ........................................................................................................ 40
A.4 Maintenance events........................................................................................................... 42
A.5 Address space .................................................................................................................... 42

Tables

Table A-1 Address space of the DQ 16x24VDC/0.5A HA ........................................................................... 43

DQ 16x24VDC/0.5A
4 Equipment Manual, 10/2021, A5E39265993-AD
Security information 1
Siemens provides products and solutions with industrial security functions that support the
secure operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is necessary
to implement – and continuously maintain – a holistic, state-of-the-art industrial security
concept. Siemens’ products and solutions constitute one element of such a concept.
Customers are responsible for preventing unauthorized access to their plants, systems,
machines and networks. Such systems, machines and components should only be connected to
an enterprise network or the internet if and to the extent such a connection is necessary and only
when appropriate security measures (e.g. firewalls and/or network segmentation) are in place.
For additional information on industrial security measures that may be implemented, please
visit
https://www.siemens.com/industrialsecurity.
Siemens’ products and solutions undergo continuous development to make them more secure.
Siemens strongly recommends that product updates are applied as soon as they are available
and that the latest product versions are used. Use of product versions that are no longer
supported, and failure to apply the latest updates may increase customer’s exposure to cyber
threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed
under
https://www.siemens.com/industrialsecurity.

DQ 16x24VDC/0.5A
Equipment Manual, 10/2021, A5E39265993-AD 5
Security information

DQ 16x24VDC/0.5A
6 Equipment Manual, 10/2021, A5E39265993-AD
Preface 2
Validity of the documentation
This equipment manual describes the following I/O modules:

System family I/O module Article No.


SIMATIC Distributed I/O System ET 200SP DQ 16x24VDC/0.5A 6DL1132-6BH00-0PH1
HA
SIMATIC Distributed I/O System ET 200SP DQ 16x24VDC/0.5A 6DL1132-6BH00-0EH1
HA

It complements the system manual for the ET 200SP HA Distributed I/O System.
Functions that generally relate to the system are described in this manual.
The information in this device manual and the system/function manuals enables you to put the
ET 200SP HA into operation.

Conventions
Please also observe notes marked as follows:

Note
A note contains important information on the product described in the documentation, on the
handling of the product or on the section of the documentation to which particular attention
should be paid.

DQ 16x24VDC/0.5A
Equipment Manual, 10/2021, A5E39265993-AD 7
Preface

DQ 16x24VDC/0.5A
8 Equipment Manual, 10/2021, A5E39265993-AD
2D Matrix code (QR code / EAN code) 3
The 2D matrix code on the product is a coded representation of the product-specific article
number.

Access to product-related information


For reading the 2D matrix code, SIEMENS offers an app for mobile use.
Information about the app and the download can be found on the Internet: "Mobile use via app
(https://support.industry.siemens.com/cs/ww/en/sc/2067)".
The app provides direct access to the technical forum and product-related posts, such as:
• FAQs
• Application examples
• Manuals
• Certificates
• Product notices

DQ 16x24VDC/0.5A
Equipment Manual, 10/2021, A5E39265993-AD 9
2D Matrix code (QR code / EAN code)

DQ 16x24VDC/0.5A
10 Equipment Manual, 10/2021, A5E39265993-AD
Product overview 4
4.1 I/O module

Definition
The DQ 16x24VDC/0.5A I/O module is a digital output module with 16 power outputs for process
control.
In addition to the technical specifications, this module has the following properties:
• Suitable for solenoid valves, DC contactors, and indicator lights
• Parameter reassignment in RUN
• Output disable switch

DQ 16x24VDC/0.5A
Equipment Manual, 10/2021, A5E39265993-AD 11
Product overview
4.2 Accessories

Description
The I/O module consists of the following components:

 DQ
16x 24V DC/ 0,5A HA

 DIA G MT


 1 DQ. 0+
3 DQ. 2+ DQ.1+ 2
DQ a

5 DQ. 4+ DQ. 3+ 4
7 DQ. 6+ DQ. 5+ 6
DQ. 7+
 9 DQ. 0+ 8
11 DQ. 2+ DQ.1+ 10
DQ b

13 DQ. 4+ DQ. 3+ 12
15 DQ. 6+ DQ. 5+ 14
DQ. 7+ 16
17
19 18
21 20
23 22
25 24
M

27 26

29 28
31 30
32

1P1 L+ 24V
2P1 L+ 24V DC M 1P2
DC
MA X. 10 A M 2P2


.0 .1
F0 F1
.2 .3


F2 F3
DQ a

.4 .5


F4 F5
.6 .7
F6 F7
.0 .1
F0 F1


.2 .3
F2 F3
DQ b

.4 .5
F4 F5 X 2
.6 .7 3 4


F6


F7 V 1.0.0
PW R
CC0 2


6DL113 2-6BH
00- 0PH1

① Module type and designation ⑧ Output disable switch


② LED for diagnostics ⑨ Module type color coding
③ LED for maintenance ⑩ Product version
④ 2D matrix code ⑪ Function status and firmware version
⑤ Wiring diagram ⑫ Color code for selection of the color-coded labels
⑥ LEDs for channel status/channel ⑬ Serial number
fault
⑦ LED for supply voltage ⑭ Article number

4.2 Accessories

Definition
Accessories for the I/O module must be ordered separately.

Description
The following accessories are available:
• Labeling strips
• Color-coded labels

DQ 16x24VDC/0.5A
12 Equipment Manual, 10/2021, A5E39265993-AD
Product overview
4.4 Pulling the I/O module in runtime

• Reference identification label


• Shield connector
• Terminal blocks

4.3 Output disable switch

Definition
The output disable switch switches the I/O module load-free.

NOTICE
Dangerous plant conditions possible (disconnect the load)
If you want to pull the I/O module in runtime, you have to press the output disable switch for
3 seconds for the I/O module to be load free (deenergized).
Pulling the I/O module in runtime (Page 13)

4.4 Pulling the I/O module in runtime

Requirement
The normally closed contacts are closed.

Procedure
Press the output disable switch for 3 seconds.

Note
Pressing the output disable switch interrupts any ongoing firmware update. A firmware update
cannot be performed when the device is deenergized.

Result
The I/O module is load-free.
The LED DIAG flashes red, the LED MT lights up yellow and the I/O module generates a
diagnostics message.
Status and error displays (Page 25)

DQ 16x24VDC/0.5A
Equipment Manual, 10/2021, A5E39265993-AD 13
Product overview
4.5 Terminal blocks

4.5 Terminal blocks

Definition
The terminal blocks provide the process terminals (push-in terminals) for components such as
devices to be connected.

Description
The following terminal blocks are available for the I/O module:

Article number Color Description


6DL1193-6TP00-0DH1 Lit
6DL1193-6TP00-0BH1 Dark
6DL1193-6TP00-0DM1 Lit For redundant configuration
6DL1193-6TP00-0BM1 Dark For redundant configuration
6DL1193-6TP00-0DN0 Lit With additional potential distributors for ground connection of the actuators
6DL1193-6TP00-0BN0 Dark With additional potential distributors for ground connection of the actuators

Note
Terminal blocks are not included in the scope of delivery of the I/O module and must be ordered
separately.
You can find additional information on the configuration in the system manual.

DQ 16x24VDC/0.5A
14 Equipment Manual, 10/2021, A5E39265993-AD
Terminal 5
5.1 Pin assignment

Definition
The pin assignment provides information about the arrangement and marking of the
connections when wiring a connector.

Note
The M terminals are intended exclusively for the 1 or 2-wire connection system. You may not use
these terminals as the ground terminals for other devices in the system. Ensure that the total
current does not exceed 2A for each M terminal.

DQ 16x24VDC/0.5A
Equipment Manual, 10/2021, A5E39265993-AD 15
Terminal
5.2 Sample connection scheme for 1-wire connection

Description
The pin assignment is structured as follows:

Terminal Assignment Terminal Assignment Description


1 DQ a/DQ.0+ 2 DQ a/DQ.1+ DQ a /DQ.n+: Output signal, channel n (0…7)
3 DQ a/DQ.2+ 4 DQ a/DQ.3+ DQ b /DQ.n+: Output signal, channel n (8…15)
5 DQ a/DQ.4+ 6 DQ a/DQ.5+ M: Ground
7 DQ a/DQ.6+ 8 DQ a/DQ.7+ 1P1: Supply voltage L+ of the voltage bus 1P
9 DQ b/DQ.0+ 10 DQ b/DQ.1+ 2P1: Supply voltage L+ of the voltage bus 2P
11 DQ b/DQ.2+ 12 DQ b/DQ.3+ 1P2: Ground reference of the voltage bus 1P
13 DQ b/DQ.4+ 14 DQ b/DQ.5+ 2P2: Ground reference of the voltage bus 2P
15 DQ b/DQ.6+ 16 DQ b/DQ.7+ 1 DQ.0+ DQ.1+ 2
3 DQ.2+ 4

DQ a
17 M 18 M DQ.3+
5 DQ.4+ DQ.5+ 6
19 M 20 M 7 DQ.6+ DQ.7+ 8
21 M 22 M 9 DQ.0+ DQ.1+ 10
11 DQ.2+ DQ.3+
DQ b
12
23 M 24 M 13 DQ.4+ DQ.5+ 14
25 M 26 M 15 DQ.6+ DQ.7+ 16
27 M 28 M 17 18
19 20
29 M 30 M 21 22
23 24
31 M 32 M
M

25 26
1P1 L+ 1P2 M 27 28
29 30
2P1 1
L+ 2P2 M 31 32

1P1 L+ 24VDC M 1P2


2P1 L+ 24VDC M 2P2
MAX. 10 A

1
If the module is plugged into a TB45R-P32 terminal block suitable for IO redundancy, the potential at this terminal is 1P3.

5.2 Sample connection scheme for 1-wire connection

Example

'4Q

'4 Q 

'4 Q 

DQ 16x24VDC/0.5A
16 Equipment Manual, 10/2021, A5E39265993-AD
Terminal
5.4 Schematic circuit diagram

5.3 Sample connection scheme for 2-wire connection

Example

'4Q

5.4 Schematic circuit diagram

Definition
A block diagram contains the schematic representation of individual function blocks.

Description
The circuit diagram for the I/O module is structured as follows:


%DFNSODQHEXVLQWKHDGDSWHUPRGXOH

(763+$

%DFNSODQHEXV
FRQQHFWLRQ


3RZHUEXVLQWKH
WHUPLQDOEORFN

0 
5HYHUVHSRODULW\
SURWHFWLRQ 0
33
/ /
33 3
,QIHHGRIPRGXOHVXSSO\
ZLWKOLJKWWHUPLQDOEORFN

The supply voltage L+ must be applied to the I/O module at the start of a firmware update and
during the firmware update.

DQ 16x24VDC/0.5A
Equipment Manual, 10/2021, A5E39265993-AD 17
Terminal
5.4 Schematic circuit diagram

DQ 16x24VDC/0.5A
18 Equipment Manual, 10/2021, A5E39265993-AD
Parameters 6
6.1 Parameter types

Definition
You define and thereby influence the functions supported by the module operation of the I/O
module via the parameter types.

6.2 Module/channel parameters

Definition
Module/channel parameters are specific parameters whose configuration can affect the entire
module or channels.

Note
Each configuration change resets the corresponding reaction.

Description
The following module/channel parameters are available:

Parameters Value range Default Parameter re‐ Efficiency range


assignment in
RUN
Diagnostics, Missing supply • Enabled Enabled Yes Module
voltage L+ (Page 20) • Disabled
IO redundancy (Page 20) • None None No Module
• 2 modules
Diagnostics, Short-circuit to • Enabled Enabled Yes Channel
ground (Page 21) 3 • Disabled
Diagnostics short-circuit to L • Enabled Enabled Yes Channel
+ (Page 21) • Disabled
Diagnostics, Wire break • Enabled Enabled Yes Channel
(Page 21) 1 • Disabled
Wire-break check (Page 21) • Enabled Enabled Yes Channel
• Disabled

DQ 16x24VDC/0.5A
Equipment Manual, 10/2021, A5E39265993-AD 19
Parameters
6.3 Explanation of the module/channel parameters

Parameters Value range Default Parameter re‐ Efficiency range


assignment in
RUN
Channel activated • Enabled Enabled Yes Channel
(Page 22) • Disabled
Reaction to CPU STOP • Shutdown Shutdown Yes Channel
(Page 22) • Keep last value
• Output substitute value
Substitute value (Page 22) • 0 0 Yes Channel
2
• 1
Potential group (Page 22) • Potential group of the left mod‐ Use potential No Module
ule (dark gray terminal block) group of the left
module
• New potential group (light gray
terminal block)
• No potential group (black termi‐
nal block)
1
The wire break diagnostics can only be enabled when the "Check for wire break" parameter is enabled.
2
Only in effect when "Substitute value" has been enabled for the "Reaction to CPU STOP" parameter.
3
In case of a short-circuit, only the specific channel with short-circuit is switched off; all other channels of the digital output
module are still operable.

6.3 Explanation of the module/channel parameters

6.3.1 Diagnostics, Missing supply voltage L+

Definition
Enabling of the diagnostics for missing or insufficient supply voltage L+.

6.3.2 IO redundancy

Definition
You can configure two identical modules redundantly. To do so, plug both modules into a
redundant terminal block side by side. You can find additional information on mounting
modules in an IO redundancy configuration in the ET 200SP HA System Manual, section
"Installing", "Installing terminal block".
In IO redundancy mode, the left module is the master and the right module is the slave. The
HART communication takes place exclusively via one of the two redundant channels.

DQ 16x24VDC/0.5A
20 Equipment Manual, 10/2021, A5E39265993-AD
Parameters
6.3 Explanation of the module/channel parameters

Description
Both redundant modules measure simultaneously and independently in the process. Both
redundant modules form diagnostics, interrupts and process values.

6.3.3 Diagnostics short-circuit to L+

Definition
When the digital output is enabled, you can enable diagnostics that report a digital output short
circuit to L+.

6.3.4 Diagnostics, Short-circuit to ground

Definition
When the digital output is enabled, you can enable diagnostics that report a digital output short
circuit to M.
A short circuit to M is only recognized when the output is switched on (output value = 1).

Note
Short-circuit signal
If the output is disabled with pending short circuit (output value = 0), the diagnostics Short-
circuit to M is reset.

6.3.5 Diagnostics, Wire break

Definition
With activated wire break checking, the diagnostics are enabled when the line is from the
actuator is interrupted.

6.3.6 Wire-break check

Definition
Enable for wire break check. The I/O module can only detect a wire break if wire-break is
activated.

DQ 16x24VDC/0.5A
Equipment Manual, 10/2021, A5E39265993-AD 21
Parameters
6.3 Explanation of the module/channel parameters

6.3.7 Channel activated

Definition
Specifies whether a channel is activated or deactivated.

6.3.8 Reaction to CPU STOP

Definition
Specifies the behavior of the digital output as a reaction to CPU stop or to failure of
communication between the interface module and CPU.

6.3.9 Substitute value

Definition
The substitute value is output by the module at CPU STOP if you set the "Reaction to CPU STOP"
parameter to "Substitute value".

Description
The entered substitute value is output by the I/O module in the following cases:
• When there is no connection to the CPU (for example, PROFInet cable unplugged)
• With CPU STOP

6.3.10 Potential group

Definition
A potential group consists of a group of directly adjacent I/O modules within an ET 200SP HA
station that are supplied via a common supply voltage.

Description
A potential group is built up from left to right by using terminal blocks.
A new potential group starts on the left side with a light gray terminal block, via which the supply
voltage for the potential group is fed in.
The potential group is continued to the right with dark gray terminal blocks and ends when a
new potential group is built up next to it.

DQ 16x24VDC/0.5A
22 Equipment Manual, 10/2021, A5E39265993-AD
Parameters
6.3 Explanation of the module/channel parameters

The potential group also ends if there is a black terminal block next to it. Black terminal blocks
are fed individually and cannot be included in potential groups.
You can find additional information on the configuration of the potential group in the system
manual SIMATIC; Distributed I/O System; ET 200SP HA.

DQ 16x24VDC/0.5A
Equipment Manual, 10/2021, A5E39265993-AD 23
Parameters
6.3 Explanation of the module/channel parameters

DQ 16x24VDC/0.5A
24 Equipment Manual, 10/2021, A5E39265993-AD
Displays and interrupts 7
7.1 Status and error displays

Definition
The LED displays are status and error indicators.
Diagnostics messages and maintenance events, as well as their possible causes or solutions are
described in the diagnostics messages and maintenance events.
Diagnostics messages (Page 40).

Description
The following figure explains the LED displays of the I/O module.


DQ HA
16x24VDC/0,5A
DIAG MT

1 DQ.0 + DQ.1+ 2
3 DQ.2 + DQ.3 + 4
DQ a

5 DQ.4 + DQ.5 + 6
7 DQ.6 + DQ.7 + 8
9 DQ.0 + DQ.1+ 10
11 DQ.2 +
DQ b

DQ.3 + 12
13 DQ.4 + DQ.5 + 14
15 DQ.6 + DQ.7 + 16
17 18
19 20
21 22
23 24
M

25 26
27 28
29 30
31 32

1P1 L+ 24VDC M 1P2


2P1 L+ 24VDC M 2P2
MAX. 10 A

.0 .1
F0 F1
 .2 .3
DQ a

F2 F3
.4 .5
F4 F5
.6 .7
F6 F7
.0 .1
F0 F1
.2 .3
DQ b

F2 F3
.4 .5 X 2
F4 F5 3 4
.6 .7
V 1.0.0
F6 F7

 PWR CC02

6DL1132-6BH00-0PH1

① DIAG LED (Page 26) (green/red)


② MT LED (Page 26) (yellow)
③ Channel status / fault LEDs (Page 27) (green)
④ Channel status / fault LEDs (Page 27) (red)
⑤ PWR LED (Page 27) (green)

DQ 16x24VDC/0.5A
Equipment Manual, 10/2021, A5E39265993-AD 25
Displays and interrupts
7.2 LEDs

7.2 LEDs

7.2.1 DIAG LED

Definition
The DIAG LED provides you diagnostic information.

Description
The diagnostic display of the DIAG LED is as follows:

DIAG LED Meaning


The power supply of the ET 200SP HA is disrupted or switched off.
Off
Module is not configured.
flashes
Module parameters are assigned. No diagnostic message is pending.
On
Module parameters are assigned. At least one diagnostic message is pending.
flashes

7.2.2 MT LED

Definition
The MT LED provides maintenance information.

Description
The MT LED indicates the following maintenance status:

MT LED Meaning
No maintenance is required.
Off
Maintenance is required. At least one maintenance event has occurred.
On

DQ 16x24VDC/0.5A
26 Equipment Manual, 10/2021, A5E39265993-AD
Displays and interrupts
7.2 LEDs

7.2.3 PWR LED

Definition
The PWR LED provides you status information about supply voltage L+.

Description
The PWR LED indicates the following status:

PWR LED Meaning


Supply voltage L+ missing.
Off
Supply voltage L+ present.
On

7.2.4 Channel status / fault LEDs

Definition
The channel status and channel fault LEDs provide you information about the status and faults
of the channels.

Description
The channel status and channel fault LEDs indicate the following:

LED channel status LED channel error Meaning


• Channel disabled or module switched off
Off Off • Process signal = 0, channel enabled and no channel diagnostics pending
• Module diagnostics pending
Process signal = 1, channel enabled and no channel diagnostics / module diag‐
On Off nostics pending
Process signal = 0, channel enabled and channel diagnostics pending
Off On
Process signal = 1, channel enabled and channel diagnostics pending
On On

DQ 16x24VDC/0.5A
Equipment Manual, 10/2021, A5E39265993-AD 27
Displays and interrupts
7.3 Interrupts

7.3 Interrupts

Definition
A diagnostics interrupt is an alarm that reports activated events of a device status to the system
operator with the appropriate operating authorization (maintenance and service).

Description
The I/O module generates a diagnostics interrupt at the following events:
• Short-circuit to L+
• Short-circuit to ground
• Wire break
• Supply voltage missing
• Parameter assignment error
• Channel/component temporarily unavailable
• Retentive memory in carrier module defective
• Retentive memory in the terminal block defective
• Shutdown on button activation
• IO redundancy parameter assignment inconsistent

The I/O module generates a maintenance message for the following events:
• Redundancy partner has different hardware/firmware
• IO redundancy warning
• Retentive memory in carrier module defective
• Retentive memory in the terminal block defective

DQ 16x24VDC/0.5A
28 Equipment Manual, 10/2021, A5E39265993-AD
Technical specifications 8
Technical specifications of the DQ 16x24VDC/0.5A HA

Article number 6DL1132-6BH00-0PH1


General information
Product type designation DQ 16x24VDC/0.5A HA
Firmware version V1.0
• FW update possible Yes
Usable terminal block TB type H1, M1 and N0
Color code for module-specific color identifica‐ CC02
tion plate
Product function
• I&M data Yes; I&M0 to I&M3
Engineering with
• STEP 7 TIA Portal configurable/integrated V16
from version
• STEP 7 configurable/integrated from version V5.6
• PCS 7 configurable/integrated from version V9.0
• PROFINET from GSD version/GSD revision GSDML V2.3
Operating mode
• DQ Yes
• DQ with energy-saving function No
Redundancy
• Redundancy capability Yes; With TB type M1
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption (rated value) 60 mA; without load
Current consumption, max. 70 mA; without load
Power loss
Power loss, typ. 1.2 W; minimum - typ. specification not possible
because load-dependent
Address area
Address space per module
• Address space per module, max. 2 byte; + 2 bytes for QI information
Digital outputs
Current-sourcing Yes

DQ 16x24VDC/0.5A
Equipment Manual, 10/2021, A5E39265993-AD 29
Technical specifications

Article number 6DL1132-6BH00-0PH1


Digital outputs, parameterizable Yes
Short-circuit protection Yes; Ensure sufficient low-resistance cable routing
to the sensor/actuator in order to attain the re‐
sponse threshold. Depending on the cable cross-
section used, there may be constraints regarding
the usable length of cable.
• Response threshold, typ. 0.7 A to 1.3 A (for IO redundancy up to max 2.6 A)
Open-circuit detection Yes; 0.7 mA test current for wire-break diagnostics;
this value is doubled in the case of IO redundancy
Overload protection Yes
Limitation of inductive shutdown voltage to L+ -(37 to 41V)
Controlling a digital input Yes
Switching capacity of the outputs
• with resistive load, max. 0.5 A
• on lamp load, max. 5W
Load resistance range
• lower limit 48 Ω
• upper limit 12 kΩ
Output current
• for signal "0" residual current, max. 0.7 mA; Test current for wire-break diagnostics; this
value is doubled in the case of IO redundancy
Output delay with resistive load
• "0" to "1", typ. 50 µs
• "1" to "0", typ. 100 µs
Parallel switching of two outputs
• for uprating No
• for redundant control of a load Yes
Switching frequency
• with inductive load, max. 2 Hz
• on lamp load, max. 10 Hz
Total current of the outputs
• Current per channel, max. 0.5 A
Total current of the outputs (per module)
horizontal installation
– up to 30 °C, max. 8A
– up to 40 °C, max. 8A
– up to 50 °C, max. 8A
– up to 60 °C, max. 5.5 A
– up to 70 °C, max. 3A
vertical installation
– up to 30 °C, max. 8A
– up to 40 °C, max. 6.33 A
– up to 50 °C, max. 4.67 A
– up to 60 °C, max. 3A

DQ 16x24VDC/0.5A
30 Equipment Manual, 10/2021, A5E39265993-AD
Technical specifications

Article number 6DL1132-6BH00-0PH1


Cable length
• shielded, max. 1 000 m
• unshielded, max. 600 m
Interrupts/diagnostics/status information
Diagnostics function Yes
Diagnoses
• Monitoring the supply voltage Yes
• Wire-break Yes; channel by channel
• Short-circuit to M Yes; channel by channel
• Short-circuit to L+ Yes; channel by channel
• Group error Yes
Diagnostics indication LED
• MAINT LED Yes; Yellow LED
• Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
• Channel status display Yes; green LED
• for channel diagnostics Yes; red LED
• for module diagnostics Yes; green/red DIAG LED
Potential separation
Potential separation channels
• between the channels No
• between the channels and backplane bus Yes
Isolation
Isolation tested with 1 500 V DC/1 min, type test
Ambient conditions
Ambient temperature during operation
• horizontal installation, min. -40 °C
• horizontal installation, max. 70 °C
• vertical installation, min. -40 °C
• vertical installation, max. 60 °C
Dimensions
Height 115 mm
Depth 138 mm
Weights
Weight, approx. 137 g

DQ 16x24VDC/0.5A
Equipment Manual, 10/2021, A5E39265993-AD 31
Technical specifications

Article number 6DL1132-6BH00-0EH1


General information
Firmware version V1.0
• FW update possible Yes
Usable terminal block TB type H1 and M1
Color code for module-specific color identifica‐ CC02
tion plate
Engineering with
• SPPA-T3000 can be configured/integrated V8.0
from version
Operating mode
• DQ Yes
• DQ with energy-saving function No
Redundancy
• Redundancy capability Yes; With TB type M1
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption (rated value) 60 mA; without load
Current consumption, max. 70 mA; without load
Power loss
Power loss, typ. 1.2 W; minimum - typ. specification not possible
because load-dependent
Address area
Address space per module
• Address space per module, max. 8 byte; PII: 0 bytes, +2 bytes for QI information, +2
bytes of PROFINET status data; PIO: 2 bytes, +2
bytes of PROFINET status data
Digital outputs
Short-circuit protection Yes; Ensure sufficient low-resistance cable routing
to the sensor/actuator in order to attain the re‐
sponse threshold. Depending on the cable cross-
section used, there may be constraints regarding
the usable length of cable.
• Response threshold, typ. 0.7 A to 1.3 A (for IO redundancy up to max 2.6 A)
Open-circuit detection Yes; 0.7 mA test current for wire-break diagnostics;
this value is doubled in the case of IO redundancy
Overload protection Yes
Limitation of inductive shutdown voltage to L+ -(37 to 41V)
Controlling a digital input Yes
Switching capacity of the outputs
• with resistive load, max. 0.5 A

DQ 16x24VDC/0.5A
32 Equipment Manual, 10/2021, A5E39265993-AD
Technical specifications

Article number 6DL1132-6BH00-0EH1


• on lamp load, max. 5W
Load resistance range
• lower limit 48 Ω
• upper limit 12 kΩ
Output current
• for signal "0" residual current, max. 0.7 mA; Test current for wire-break diagnostics; this
value is doubled in the case of IO redundancy
Output delay with resistive load
• "0" to "1", typ. 50 µs
• "1" to "0", typ. 100 µs
Parallel switching of two outputs
• for uprating No
• for redundant control of a load Yes
Switching frequency
• with inductive load, max. 2 Hz
• on lamp load, max. 10 Hz
Total current of the outputs
• Current per channel, max. 0.5 A
Total current of the outputs (per module)
horizontal installation
– up to 30 °C, max. 8A
– up to 40 °C, max. 8A
– up to 50 °C, max. 8A
– up to 60 °C, max. 5.5 A
– up to 70 °C, max. 3A
vertical installation
– up to 30 °C, max. 8A
– up to 40 °C, max. 6.33 A
– up to 50 °C, max. 4.67 A
– up to 60 °C, max. 3A
Cable length
• shielded, max. 1 000 m
• unshielded, max. 600 m
Interrupts/diagnostics/status information
Diagnoses
• Monitoring the supply voltage Yes
• Wire-break Yes; channel by channel
• Short-circuit to M Yes; channel by channel
• Short-circuit to L+ Yes; channel by channel
• Group error Yes
Diagnostics indication LED
• MAINT LED Yes; Yellow LED

DQ 16x24VDC/0.5A
Equipment Manual, 10/2021, A5E39265993-AD 33
Technical specifications

Article number 6DL1132-6BH00-0EH1


• Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
• Channel status display Yes; green LED
• for channel diagnostics Yes; red LED
• for module diagnostics Yes; green/red DIAG LED
Potential separation
Potential separation channels
• between the channels No
• between the channels and backplane bus Yes
Ambient conditions
Ambient temperature during operation
• horizontal installation, min. -40 °C
• horizontal installation, max. 70 °C
• vertical installation, min. -40 °C
• vertical installation, max. 60 °C
Dimensions
Height 115 mm
Depth 138 mm

Derating curve
The following figure shows the load current derating with horizontal and vertical mounting
positions.

9,00
/RDGFXUUHQWLQ$

8,00 Total current I / A


Horizontal mounting position
7,00
6,00 Total current I / A
Vertical mounting position
5,00
4,00
3,00
2,00
1,00
0,00
-40 -20 0 20 40 60 80

7HPSHUDWXUHLQr&

DQ 16x24VDC/0.5A
34 Equipment Manual, 10/2021, A5E39265993-AD
Technical specifications

Note
You can avoid the derating by deactivating channels 8 to 16.

Test current for signal state "0"

Note
If the "Check for wire break" parameter is activated, a test current flows, even if the signal state
for the output is "0" (singular mode: Approx. 700 μA, redundant operation: approx. 1.4 mA).

Cycle time
The cycle time describes the time slice in which signals from the inputs are acquired and
processed. The cycle time of the I/O module is 1 ms.

DQ 16x24VDC/0.5A
Equipment Manual, 10/2021, A5E39265993-AD 35
Technical specifications

DQ 16x24VDC/0.5A
36 Equipment Manual, 10/2021, A5E39265993-AD
Parameters, diagnostics messages and address
space A
A.1 Parameter assignment

Parameter assignment in the user program


You can reconfigure individual channels of the module in RUN without this having an effect on
the other channels.

Changing parameters in RUN


The parameters are transferred to the module with the "WRREC" instruction via data record 128.

Output parameter STATUS


If errors occur when transferring parameters with the "WRREC" instruction, the module
continues operation with the previous parameter assignment. The STATUS output parameter
contains the corresponding error code.
The STATUS output parameter is 4 bytes long and is configured as followed:
• Byte1: Function_Num, general error code
• Byte2: Error_Decode, location of the error code
• Byte3: Error_Code_1, error code
• Byte4: Error_Code_2, manufacturer-specific extension of the error code
Module-specific errors are displayed via Error_Decode = 0x80 and Error_Code_1 / Error_Code_2.

Error_ Error_ Cause Remedy


Code_ Code_
1 2
0xB0 0x00 Number of the data record unknown Enter valid number for data record.
0xB1 0x01 Length of the data record is incorrect Enter valid value for data record length.
0xB2 varia‐ Module cannot be reached • Check station - is the module plugged in cor‐
ble rectly?
• Check the parameters of the WRREC instruction.
0xE0 0x01 Wrong version in the header Correct the version number of the parameter block.
0xE0 0x02 Header error (number or length of parameter block) Correct the length and number of the parameter
blocks.
0xE1 0x01 Reserved bit set Check and correct the parameters
0xE1 0x02 Invalid diagnostics enable bit set for operating mode
0xE1 0x06 Invalid coding for substitute value reaction
0xE1 0x0E Invalid redundancy parameter assignment

DQ 16x24VDC/0.5A
Equipment Manual, 10/2021, A5E39265993-AD 37
Parameters, diagnostics messages and address space
A.2 Parameter assignment and structure of the module/channel parameters

A.2 Parameter assignment and structure of the module/channel


parameters

Structure of data record 128


Data record 128 has a length of 44 bytes.
It contains the channel parameters of the 16 channels.

%\WH +HDGHULQIRUPDWLRQ PRGXOH

%\WH 0RGXOHSDUDPHWHUV

%\WH +HDGHULQIRUPDWLRQ FKDQQHO

%\WH &KDQQHO
'LJLWDORXWSXW

%\WH &KDQQHO
'LJLWDORXWSXW

%\WH &KDQQHO
'LJLWDORXWSXW

%\WH &KDQQHO
'LJLWDORXWSXW

%\WH &KDQQHO
'LJLWDORXWSXW

DQ 16x24VDC/0.5A
38 Equipment Manual, 10/2021, A5E39265993-AD
Parameters, diagnostics messages and address space
A.2 Parameter assignment and structure of the module/channel parameters

Header information and module parameters


The following figure shows the configuration of the header information and module parameters.

       
%\WH        

0LQRUYHUVLRQ
0DMRUYHUVLRQ
5HVHUYHG

       
%\WH         1XPEHURIWKHIROORZLQJSDUDPHWHUVWUXFWXUHV

       
%\WH         1XPEHURIWKHIROORZLQJPRGXOHSDUDPHWHUEORFNV

       
%\WH         /HQJWKRIWKHPRGXOHSDUDPHWHUEORFN

       
%\WH     
'LDJQRVWLFV1RVXSSO\YROWDJH/
5HGXQGDQF\UROH
 2II
 0DVWHU
 6ODYH

       
%\WH         5HVHUYHG

        6LQJOHPRGH,UUHOHYDQW
%\WH 5HGXQGDQF\PRGH/RJLFEDVLFDGGUHVVKLJKE\WH

        6LQJOHPRGH,UUHOHYDQW
%\WH 5HGXQGDQF\PRGH/RJLFEDVLFDGGUHVVORZE\WH

        6LQJOHPRGH,UUHOHYDQW
%\WH 5HGXQGDQF\PRGH/RJLFEDVLFDGGUHVVRIWKHSDUWQHUPRGXOHKLJK
E\WH

        6LQJOHPRGH,UUHOHYDQW
%\WH 5HGXQGDQF\PRGH/RJLFEDVLFDGGUHVVRIWKHSDUWQHUPRGXOHORZ
E\WH

       
%\WH         1XPEHURIWKHIROORZLQJFKDQQHOSDUDPHWHUEORFNV 

       
%\WH         /HQJWKRIDFKDQQHOSDUDPHWHUEORFN E\WH

DQ 16x24VDC/0.5A
Equipment Manual, 10/2021, A5E39265993-AD 39
Parameters, diagnostics messages and address space
A.3 Diagnostics messages

Channel parameters
Each channel parameter block contains the cable parameters for the digital output (4 bytes).
The following figure shows the configuration of the channel parameters for channels 0 to 15.
x = 12 + (channel number * 2); with channel number 0…15
All unused bits and the bits or bytes marked as "reserved" must be set to zero.
You activate a channel parameter by setting the corresponding bit to "1" or the corresponding
value.

       
%\WH[     (QDEOHGLDJQRVWLFV

:LUHEUHDNFKHFN
6KRUWFLUFXLWWR0
6KRUWFLUFXLWWR/
'LDJQRVWLFVZLUHEUHDN

       
%\WH[    

&KDQQHODFWLYDWHG
 %ORFN
 5HOHDVH
6XEVWLWXWHYDOXHEHKDYLRU
 6ZLWFKRII
 .HHSODVWYDOXH
 2XWSXWVXEVWLWXWHYDOXH

6XEVWLWXWHYDOXH
 6XEVWLWXWHYDOXH
 6XEVWLWXWHYDOXH

A.3 Diagnostics messages

Diagnostics alarms
A diagnostics message is generated for each diagnostics event and the DIAG LED on the DQ
16x24VDC/0.5A HA flashes red or the MT LED lights up yellow.
In addition, channel-specific channel diagnostics are displayed through the corresponding
channel error/status LEDs.
The diagnostics messages can be read in the diagnostics buffer of the CPU.
Diagnostic messages are assigned either channel-specific to an output or assigned as module
messages to all outputs. All channels are switched off for diagnostics messages that affect the

DQ 16x24VDC/0.5A
40 Equipment Manual, 10/2021, A5E39265993-AD
Parameters, diagnostics messages and address space
A.3 Diagnostics messages

entire module. Only the corresponding digital output is affected by diagnostics messages, which
refer to individual channels.

Diagnostics Error Assign‐ Meaning Remedy


message code ment
Wire break 6H Channel Actuator connection has impedance too high Use another type of actuator or
wiring, for example, use conduc‐
tors with a larger cross-section
Wire break between the module and actuator Connect the cable
Channel not connected (open) • Disable diagnostics
• Wire actuator contacts to a re‐
sistor in the load resistance
area
• Switch off wire break check
Parameter as‐ 10H Module • Parameter assignment does not match the • Correct the parameter assign‐
signment error terminal block used ment
• Incorrect parameter assignment • Check terminal block1
Supply voltage 11H Module Missing or insufficient supply voltage L+ • Check wiring of the supply
missing voltage L+ on the terminal
block
• Check terminal block type
Channel/ 1FH Module Firmware update is in progress or has been • Restart the firmware update
component canceled during the update. The module gen‐ • Wait for firmware update
temporarily un‐ erates no process and substitute values in this
available state.
Short-circuit to 105H Channel Short-circuit of the actuator supply to L+ Correction of the process wiring
L+ Only in the non-connected state (output value
0)
Short-circuit to 106H Channel Short-circuit of the actuator supply to ground Correction of the process wiring
M Only in the connected state (output value 1).
Shutdown on 122H Module The output disable switch was activated Pull module
button activa‐
tion
Inconsistent pa‐ 123H Module Errors in the redundancy parameters sent to Check the parameter assignment
rameter assign‐ the module
ment
Retentive mem‐ 154H Module An error of the memory block on the adapter Replace carrier module
ory in carrier module was detected during startup
module defec‐
tive
Retentive mem‐ 155H Module An error of the memory block on the terminal Replace terminal block
ory in the termi‐ block was detected during startup
nal block defec‐
tive
1
Only the terminal blocks (TB 45R ...) are suitable for use with I/O modules in IO redundancy.

DQ 16x24VDC/0.5A
Equipment Manual, 10/2021, A5E39265993-AD 41
Parameters, diagnostics messages and address space
A.5 Address space

A.4 Maintenance events

Maintenance events
A maintenance event is generated for each maintenance required identified. The MT LED lights
up on the module.
Maintenance messages have no direct effect on the function of the module or digital outputs.

Maintenance Error Assign‐ Meaning / Cause Remedy


message code ment
Redundancy 120H Module The redundantly configured and interconnec‐ Check the operating status and
partner has dif‐ ted I/O modules are not compatible firmware version of the modules
ferent hard‐ and replace modules or perform a
ware/firmware firmware update.
version
IO redundancy 121H Module Unable to correctly communicate with the part‐ • Check/replace right-hand
warning ner module module
• Check/replace left-hand mod‐
ule
• Check/replace terminal block
See also the "ET 200SP HA Distrib‐
uted I/O system system manual,
Chapter "Replacing an I/O module
at IO redundancy".
Retentive mem‐ 154H Module Fault detected in the data block on the carrier Replace carrier module
ory in carrier module during operation
module defec‐
tive
Retentive mem‐ 155H Module An error of the memory block on the terminal Replace terminal block
ory in the termi‐ block was detected during operation
nal block defec‐
tive

A.5 Address space

Abbreviations
• "IB" stands for input byte, that is, the module start address in the input area
• "QB" stands for output byte, that is the module start address in the output area
• "DQ" stands for digital output
• "QDIn" stands for the value status (QI) of digital input n

DQ 16x24VDC/0.5A
42 Equipment Manual, 10/2021, A5E39265993-AD
Parameters, diagnostics messages and address space
A.5 Address space

Address space
The following figure shows the mapping of the address space of the DQ 16x24VDC/0.5A HA.

Table A-1 Address space of the DQ 16x24VDC/0.5A HA

IB x + AB x + 7 6 5 4 3 2 1 0
0 - QDI7 QDI6 QDI5 QDI4 QDI3 QDI2 QDI1 QDI0
1 - QDI15 QDI14 QDI13 QDI12 QDI11 QDI10 QDI9 QDI8
- 0 DQ7 DQ6 DQ5 DQ4 DQ3 DQ2 DQ1 DQ0
- 1 DQ15 DQ14 DQ13 DQ12 DQ11 DQ10 DQ9 DQ8

Evaluate value status


There is a bit value status for each digital output in the input address space.
Irrespective of the diagnostics enables, each value status (each QI bit) provides information on
the validity of the corresponding process value.
• Value status = 1: Process value okay, "good"
• Value status = 0: Process value not okay, "bad"
Basically, the value status is set to "good" if the digital value can be output without error. The
value status is set to "bad" in the following cases:
• The digital value cannot be output due to an error.
• The digital channel is deactivated.

DQ 16x24VDC/0.5A
Equipment Manual, 10/2021, A5E39265993-AD 43
Parameters, diagnostics messages and address space
A.5 Address space

DQ 16x24VDC/0.5A
44 Equipment Manual, 10/2021, A5E39265993-AD