0% found this document useful (0 votes)
196 views

High Impedance Busbar Differential Protection

The document discusses high impedance busbar differential protection, including: 1) It provides an equivalent circuit diagram to illustrate how a high impedance busbar protection scheme functions, showing how current flows during an external fault. 2) It calculates the maximum voltage that could occur across a non-saturated current transformer during an external fault when another CT saturates, to ensure the CTs can handle this voltage. 3) It determines the minimum allowable CT saturation voltage to ensure proper operation of the protection scheme, by doubling the maximum voltage calculation.

Uploaded by

ዛላው መና
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
196 views

High Impedance Busbar Differential Protection

The document discusses high impedance busbar differential protection, including: 1) It provides an equivalent circuit diagram to illustrate how a high impedance busbar protection scheme functions, showing how current flows during an external fault. 2) It calculates the maximum voltage that could occur across a non-saturated current transformer during an external fault when another CT saturates, to ensure the CTs can handle this voltage. 3) It determines the minimum allowable CT saturation voltage to ensure proper operation of the protection scheme, by doubling the maximum voltage calculation.

Uploaded by

ዛላው መና
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 16

High Impedance Busbar Differential Protection

relaytraining.com/high-impedance-busbar-differential-protection

July 5, 2016

We covered the basic operating principles of high impedance busbar differential


protection in our previous post, I Want to Know How a High Impedance Differential
Scheme Works. You should read that post first before we dig deep into the calculations
and considerations that explain how high impedance busbar differential schemes
function.

BONUS: Click here to sign up and we'll send you the free High Impedance Busbar
Protection Cheat Sheet you can take with you.

We received this question from the Ask Chris section at relaytraining.com. Follow this
link to ask your own question and it might appear in a future blog post.

I had a lot of help with this question from Rodney Hughes at Rod Hughes Consulting Pty
Ltd (www.rodhughesconsulting.com). His explanations are much more comprehensive
than this one and I highly recommend you visit his website to really dig into it.

High Impedance Busbar Protection Principles and Calculations


The previous article left off with a single line drawing of our busbar protection.

The equivalent circuit of this busbar protection scheme would look like the following:

1/16
That is far too complicated for our purposes. We can combine 52-2 CT, 52-3 CT, and 52-4
into one CT to simplify the circuit to look like the following:

But we’re going to apply an external fault through two feeders to make it easier to
understand.

2/16
Any current flowing through the 52-1 CT (52-1CT IP1) is shown on the left hand side of
our two-feeder equivalent circuit below. The primary current creates a magnetic field (Ie1,
Ze1) that usually uses a small amount of current to inject the secondary current (IS1) into
the CT secondary circuit.

The secondary winding is made from a conductor that has resistance and is coiled around
a core to create inductance. That impedance is shown on the drawing as ZCT1. The
external conductors connecting the CT to the rest of the circuit also have an impedance
that is represented by ZL1.

Our high impedance busbar protective equipment has a 2000Ω impedance represented
by the Rs, 87, 87Z, and MOV (Metal Oxide Varistor) in the middle of the circuit.

The 52-2 CT has the same characteristics as the 52-1 CT, which is represented on the
right-hand side of the equivalent circuit. The CTs are connected in parallel with all
polarity marks connected to the same point so that external faults theoretically cancel
each other out, and internal faults combine to create larger currents during a fault for
shorter trip times.

3/16
What Happens Inside a High Impedance Busbar Protection
Scheme During an External Fault When One CT Saturates?

This scenario is THE reason why busbar protection can’t use simple instantaneous
overcurrent elements (50). We have the same fault current as the ideal example in the
previous single line drawing, but the 52-2 CT has saturated. The CT could have saturated
because of:

The DC Offset that commonly occurs during faults (You can get more info in the
What is DC Offset? Ask Chris post)

4/16
Residual magnetism in the CT (Remanence) from previous faults or improper
testing
Too much burden on the CT secondaries

A normal CT has a CT ratio (1200:5 in our example), which defines the turns-ratio (240:1
in our example). 83.33 should be exported When 20,000A flows through the 240 turns in
a properly functioning CT, but:

A normally insignificant amount of excitation current (0.035A) is used to create a


magnetic field inside the CT to maintain the current transformation, which means
83.295A is injected out of the CT secondary terminals. (The actual CT ratio may be
slightly higher than the reported 240:1 to compensate for the excitation current
losses.)

When a CT saturates, the magnetic field requires more current than normal to maintain
the current transformation, which means that there is less current injected into the CT
secondary circuit. We’re showing the worst case scenario in our example where ALL of the
primary current is used in the magnetic field, and zero amps is injected into the CT
secondaries.

One hundred percent CT saturation is rare because the waveform becomes distorted when
a CT saturates (as shown below), and most CTs will have varying degrees of saturation
throughout a cycle, which makes the math in our equivalent circuit extremely difficult.
Therefore, most high impedance busbar differential protection calculations use extremes
to make the math easier.

High Impedance Busbar Differential Protection Maximum Voltage


Calculation

5/16
The high impedance differential busbar protection has an impedance of 2000Ω. That
means that the current will want to flow around the outside of the equivalent circuit
because the outside circuit has a lower impedance path during external faults. When 52-2
CT fully saturates, its magnetic field impedance is effectively 0.00Ω. Let’s see what that
does to our equivalent circuit.

We can combine the ZCT1 and ZL1 impedance to get Z1 = 0.5Ω (0.387Ω + 0.113Ω). Then
we can simplify the ZL2, ZCT2, and Ze2 impedances to get Z2 = 0.5Ω (0.387Ω + 0.113Ω +
0.00Ω).

We can combine the Z2 and Z87 impedances to get 0.5Ω (2000Ω*0.5Ω / (2000Ω+0.5Ω)).

6/16
The equivalent circuit impedance for the 52-1 CT is 1.0Ω when 52-2 CT is saturating.
Using Ohm’s Law, the voltage across 52-1 CT’s magnetic field with 83.33A of fault current
is 83.33V.

Anyone designing or creating settings for a high impedance busbar differential protection
scheme should calculate the maximum voltage that will be applied during an external
fault with a 100% saturated CT as we just did in our example. We will use this maximum
voltage to make sure that the CTs are sized appropriately for the application. Our CTs
must operate normally with a secondary voltage of 83.33V.

High Impedance Busbar Differential Protection Minimum Allowable CT


Saturation Voltage Calculation
High impedance busbar differential protection will not work properly if the CTs are not
sized correctly for the connected circuit. We calculated that the voltage across the non-
saturated CT, when another CT saturates, is 83.33V. Any CT with a saturation voltage
greater than 83.33V should work correctly in our example. However, electrical engineers
should always err on the side of caution when designing protection schemes; so we
usually double the high impedance busbar differential protection maximum voltage
calculation to determine the minimum CT saturation voltage to make sure that the CTs
are adequately sized for the application. Our CTs should operate normally when 166.66V
(2 * 83.33V) appears across the secondary terminals to be safe.

CT Ratings

A protection class CT is usually defined by its ratio, accuracy, construction, and burden.
We’ve already discussed the CT ratio (1200:5 in our example). If you look back to the
single line drawing, you’ll see that there was another designation beside the CTs (C200).

7/16
This designation defines:

The accuracy class in percent (10% if no number appears in front of the letter)
How the CT was constructed using a letter (C = Minimum leakage flux and CT
performance can be calculated)
The burden and saturation voltage in volts (200)

How can a voltage define the burden, you might ask? All standard protection class CT
ratings are valid between 1 to 20x nominal current. If our CT’s have 5A nominal
secondary currents, they are allowed to be +/-10% accurate between 5 and 100A
secondary. If the maximum burden is 200V, we can apply Ohm’s Law to determine that
the maximum impedance connected to the CT secondaries is 2.0Ω (200V / 100A). That’s
the standard calculation that ALL CT testers should know and apply when they are
performing their CT tests. Did you?

All protection class CTs also have a saturation curve like the graph below. The 200 in our
rating means that if the voltage across the CT’s magnetic field is greater than 200V, the
CT is no longer guaranteed to operate within its 10% error. 200V is greater than 166.66V
(our minimum allowable CT saturation voltage), so the CTs in our example are
appropriate for our application.

Determine CT Excitation Current

We can use the CT saturation curve to see how much excitation current will be used to
maintain the current transformation at 83.33V with these steps:

Start by drawing a horizontal line from 83.33V until you reach the 1200:5 curve.

8/16
Then draw a vertical line to the secondary excitation current x-axis.
Determine the excitation current using the log scale on the x-axis (0.035A).

It is important to remember that this curve is a generic one, which gives an approximation
of what the CT characteristic should be, and not what it actually is. Our class C CTs have a
+/- 10% accuracy rating and when we get numbers from this curve, there may be
significant differences between the information we calculate or obtain from the graph
compared to actual CT operation. We would have to isolate every CT in the circuit and
measure their performance to get exact performance numbers; or the design engineer
could order a special class X CT where the performance characteristics are built and
measured to ensure they meet exacting specifications.

Rodney Hughes (www.rodhughesconsulting.com) stresses that every high impedance


busbar differential scheme should use class X CTs with exacting specifications to make
sure we don’t get false trips due to CT mismatch. If you use class X CTs, you don’t have to
worry that your CTs from the 1980s might not have the same operating characteristics as
the new feeder CTs added to the scheme in the 2010s; they should have almost identical
operating characteristics. The same CANNOT be said for standard class C CTs.

We don’t have the luxury of class X CTs in our example, so we’re going to use the
excitation current (0.035A) we measured from the graph for all future calculations. The
excitation voltage across the CTs will be less under normal conditions, but we don’t want
to constantly go back and forth to this chart for every scenario. The chart states that the
excitation current won’t exceed 25%; so let’s use 0.035A (our number from the graph) for
CT1 and 0.044A (0.035 * 1.25) for CT2.

9/16
What Happens Inside a High Impedance Busbar Protection
Scheme During an External Fault Without CT Saturation?
The following single line shows an external fault with CTs that are functioning as per the
excitation graph.

We have 20,000A flowing into the primaries of the CTs in the opposite direction. A
perfect CT would send 83.33A into the secondary circuit, but the CTs’ magnetic field
requires some current to make the current transformation (0.035A and 0.044A); so the
actual CT output is 83.295A for 52-1 CT, and 83.286A for 52-2 CT. (The CT would
normally have some hidden turns added to compensate for the excitation current.) The
difference in CT secondaries creates a differential current of 0.009A that flows through
the high impedance busbar differential circuit. We can apply Ohm’s Law to calculate
18.00V across the 87Z high impedance busbar protection circuit. This means that the 87Z
pickup setting must be greater than 18.00V to prevent mis-operations during external
faults. (The differential current would likely be higher in the real world due to CT
mismatch.)

10/16
What should the high impedance busbar differential voltage setting be?

High Impedance Busbar Differential Protection Minimum Pickup


Setting Calculation
The high impedance busbar differential protection scheme’s minimum pickup setting is
calculated using our first scenario with the saturated CT.

We can re-organize and simplify the equivalent circuit to:

11/16
How much voltage is across the 87Z element in this scenario?

The 87Z element is in parallel with Z2. The 87Z circuit has a much higher impedance
compared to the Z2 impedance, which makes the equivalent impedance almost 0.5Ω. We
can use Ohm’s Law to calculate that there will be 41.65V (83.295A * 0.5Ω) across Z2 and
87Z during this scenario. Remember, we DO NOT want the relay to trip for external
faults; so the setting should be higher than 41.65V.

Let’s imagine that we set the relay to 50V. We can calculate how much differential current
will cause the relay to trip under normal conditions using Ohm’s Law. The 87Z is 2000Ω
in our example with a 50V setting. That means that 0.025A (50V / 2000Ω) of differential
current will cause the relay to trip. This setting might be OK with class X CTs with specific
operating characteristics, but we will probably get a false trip with normal class C CTs,
especially if we have different vintages of CTs in our high impedance busbar differential
circuit.

Most design engineers add a safety factor starting at 1.5x the minimum setting to account
for potential increases in fault current. We will increase the setting by a factor of two and
then round up to 100V. This means that the differential current caused by CT mismatch
(0.05A or 100V/2000Ω) must be twice our previous setting, or higher, to cause a mis-
operation during normal conditions or through-faults.

What Happens Inside a High Impedance Busbar Protection


Scheme During an Internal Fault With One Source?
Here is a single line displaying what happens during an internal fault.

12/16
We have 20,000A flowing into the 52-1 CT which should equal 83.333A flowing out of its
secondary terminals. However, the CT needs excitation current to create secondary
current. If we use our previously calculated 0.035A for this scenario (that amount would
not technically apply here, but we need to pick something and I don’t want to do more
math for such a small amount of current), 83.295A should flow out of the CT secondaries.

Since the 52-2 CT has zero amps flowing in the primary windings, zero amps should flow
out of the secondaries. Without a magnetic field however, the 52-2 CT’s secondary
winding is just a bunch of coiled wire with a low impedance. The 52-1 CT secondary
current will want to flow through the low impedance in the 52-2 CT secondaries, but once
a small amount of current (0.044A from our previous example) starts flowing in the
secondary circuit, a magnetic field will be created and the CT will try to maintain its turns-

13/16
ratio. Zero amps of the primary should equal zero amps on the secondary minus the
excitation current. Once the magnetic field is built, the 52-2 CT secondaries will become
an open circuit (like it does when you perform your saturation and ratio tests) and the
remaining current will flow through the 87Z circuit because it will now have a lower
impedance.

Using Ohm’s Law, 83.251A through 2000Ω should create 166,502V. The MOV will protect
the secondary circuits from damage by limiting the possible voltage to a number much
smaller than 166,502V, but the secondary voltage could rise to the system voltage without
the MOV. Either way, it is extremely unlikely that the voltage will reach those heights
because the CT should start saturating at 200V. The CT is guaranteed to saturate during
an internal fault and will produce a waveform that looks like this:

Our relay better be able to operate when this waveform appears; so it is often beneficial to
use a single-purpose relay for a high impedance busbar differential relay scheme to
minimize the trip time. Some digital relays need extra time to measure, apply filters, and
analyze the waveform before they can operate, which may mean that the fault may stay on
the system longer than necessary. The longer a fault stays on the system, the greater
potential for system de-stabilization, which could cause a larger system outage than
necessary.

The voltage during an internal fault should always be larger than our setting and the relay
should trip in the shortest time possible.

What Happens Inside a High Impedance Busbar Protection


Scheme During an Internal Fault With Multiple Sources?
Most distribution busses have multiple sources and we should look at this scenario to see
what happens:

14/16
The CT secondary currents are headed in the same direction in this scenario and will
combine at the 87Z circuit to theoretically produce 333,162V (166.581A * 2000Ω). Both
CTs will drive the highest voltage they can while in parallel, which will trip the relay.

Conclusion
The dirty little secret about all forms of differential protection is that we know the relay
will trip for all internal faults. When we’re designing and testing differential schemes,
we’re primarily concerned with making sure the relay will NOT trip during external faults.
Did you notice that all of the important calculations above occurred during external fault
scenarios? Have you noticed that most differential tests try to find the point where the
relay will operate during an external fault (currents 180° apart), instead of applying single
source or multiple source fault in the same direction?

High impedance differential schemes can filter out non-sinusoidal differential current
that occurs when CTs saturate during external faults, but they cannot filter out true error
caused by CT mismatch. Therefore, it is important that you use class X CTs when you are
designing high impedance differential schemes, and that you are aware that CT mismatch
can cause mis-operations when using standard protection class CTs.

I hope this article helped you better understand high impedance differential schemes. If
you liked it, please share it to help us get noticed, which helps us continue to produce free
content like this.

15/16
About the Author

Chris Werstiuk 
Chris is an Electrical Engineering Technologist, a
Journeyman Power System Electrician, and a
Professional Engineer. He is also the Author of
The Relay Testing Handbook series and founder
of Valence Electrical Training Services. You can
find out more about Chris here.

Read More Articles:

Get and Manage Protective Relaying Online Training Courses for Your Entire Team

What Was Your Electrical Epiphany?

Leave a Reply

Your email address will not be published.


Required fields are marked *

16/16

You might also like