Ceiling-Mounted Duct Installation Guide
Ceiling-Mounted Duct Installation Guide
INSTALLATION MANUAL
MODELS
Ceiling-mounted Duct type
FXMQ48MFVJU
FXMQ72MFVJU
English
FXMQ96MFVJU
Français
FXMQ48MFVJU
FXMQ72MFVJU VRVII Outdoor-Air Processing Unit Installation manual
FXMQ96MFVJU
1 English
01_EN_3P086156-12Y.fm Page 2 Wednesday, September 16, 2009 2:09 PM
• Securely fasten the outside unit terminal cover (panel). If • The indoor unit is for R-410A. See the catalog for indoor
the terminal cover/panel is not installed properly, dust or models that can be connected. Normal operation is not
water may enter the outside unit causing fire or electric possible when connected to other units.
shock. • Remote controller (wireless kit) transmitting distance
• When installing or relocating the system, keep the refrig- can be shorter than expected in rooms with electronic
erant circuit free from substances other than the speci- fluorescent lamps (inverter or rapid start types). Install
fied refrigerant (R-410A) such as air. Any presence of air the indoor unit far away from fluorescent lamps as much
or other foreign substance in the refrigerant circuit can as possible.
cause an abnormal pressure rise or rupture, resulting in • Indoor units are for indoor installation only. Outdoor
injury. units can be installed either outdoors or indoors.
• Do not change the setting of the protection devices. If • Do not install the air conditioner in the following loca-
the pressure switch, thermal switch, or other protection tions:
device is shorted and operated forcibly, or parts other (a)Where a mineral oil mist or oil spray or vapor is pro-
than those specified by Daikin are used, fire or explosion duced, for example, in a kitchen.
may occur.
Plastic parts may deteriorate and fall off or result in
water leakage.
CAUTION
(b)Where corrosive gas, such as sulfurous acid gas, is
• Do not touch the switch with wet fingers. Touching a produced.
switch with wet fingers can cause electric shock. Corroding copper pipes or soldered parts may result
• Do not allow children to play on or around the unit to pre- in refrigerant leakage.
vent injury. (c)Near machinery emitting electromagnetic waves.
• Do not touch the refrigerant pipes during and immedi- Electromagnetic waves may disturb the operation of
ately after operation as the refrigerant pipes may be hot the control system and cause the unit to malfunction.
or cold, depending on the condition of the refrigerant (d)Where flammable gas may leak, where there is carbon
flowing through the refrigerant piping, compressor, and fiber, or ignitable dust suspension in the air, or where
other refrigerant cycle parts. Your hands may suffer volatile flammables such as thinner or gasoline are
burns or frostbite if you touch the refrigerant pipes. To
handled. Operating the unit in such conditions can
avoid injury, give the pipes time to return to normal tem-
cause a fire.
perature or, if you must touch them, be sure to wear
proper gloves. • Take adequate measures to prevent the outside unit
• Heat exchanger fins are sharp enough to cut. from being used as a shelter by small animals. Small ani-
To avoid injury wear glove or cover the fins when work- mals making contact with electrical parts can cause mal-
ing around them. functions, smoke, or fire. Instruct the customer to keep
the area around the unit clean.
• Install drain piping to proper drainage. Improper drain
piping may result in water leakage and property damage.
NOTE
• Insulate piping to prevent condensation.
• Install the power supply and control wires for the indoor
• Be careful when transporting the product. and outdoor units at least 3.5 feet away from televisions
• Do not turn off the power immediately after stopping op- or radios to prevent image interference or noise.
eration. Always wait for at least 5 minutes before turning Depending on the radio waves, a distance of 3.5 feet may
off the power. Otherwise, water leakage may occur. not be sufficient to eliminate the noise.
• Do not use a charging cylinder. Using a charging cylin- • Dismantling the unit, treatment of the refrigerant, oil and
der may cause the refrigerant to deteriorate. additional parts must be done in accordance with the rel-
• Refrigerant R-410A in the system must be kept clean, evant local, state, and national regulations.
dry, and tight. • Do not use the following tools that are used with conven-
(a)Clean and Dry -- Foreign materials (including mineral tional refrigerants: gauge manifold, charge hose, gas
oils such as SUNISO oil or moisture) should be pre- leak detector, reverse flow check valve, refrigerant
vented from getting into the system. charge base, vacuum gauge, or refrigerant recovery
(b)Tight -- R-410A does not contain any chlorine, does equipment.
not destroy the ozone layer, and does not reduce the • If the conventional refrigerant and refrigerator oil are
earth’s protection again harmful ultraviolet radiation. mixed in R-410A, the refrigerant may deteriorate.
R-410A can contribute to the greenhouse effect if it is • This air conditioner is an appliance that should not be
released. Therefore take proper measures to check accessible to the general public.
for the tightness of the refrigerant piping installation. • The wall thickness of field-installed pipes should be
Read the chapter Refrigerant Piping and follow the selected in accordance with the relevant local, state, and
procedures. national regulations.
• Since R-410A is a blend, the required additional refriger-
ant must be charged in its liquid state. If the refrigerant
is charged in a state of gas, its composition can change
and the system will not work properly.
English 2
01_EN_3P086156-12Y.fm Page 3 Wednesday, September 16, 2009 2:09 PM
3 English
01_EN_3P086156-12Y.fm Page 4 Wednesday, September 16, 2009 2:09 PM
• Do not use in seaside locations with a lot of salt in the air, fac-
tories and other locations where the voltage fluctuates, in
automobiles, or in marine vessels.
44 or more
(Service space) (length: in.)
Fig. 1
English 4
01_EN_3P086156-12Y.fm Page 5 Wednesday, September 16, 2009 2:09 PM
Approx. 5-7/8
Fig. 5
5 English
01_EN_3P086156-12Y.fm Page 6 Wednesday, September 16, 2009 2:09 PM
(4) Tighten both upper and lower nuts <1>, <3>. Table 2
(Refer to Fig. 4) Flare dimen-
Pipe Tightening torque
(5) Insulate the four hanger sions Flare shape (in.)
Slit of size (ft·lbf)
brackets with the sealing Sealing pad 6)
A (in.)
sealing
pad. (accessory 6)) Insu- pad
late the hanger brackets so φ 3/8” 24.1 – 29.4 0.504 – 0.520
0
R0.016-0.031
45 ±2
that the surface and edges Hanger
0
0
90 ±2
of the hanger brackets bracket
A
cannot be seen.
φ 5/8” 45.6 – 55.6 0.760 – 0.776
(Refer to Fig. 6)
Fig. 6
CAUTION NOTE
Setting the unit at an angle opposite to the drain socket or Use the flare nuts attached with the unit.
air inlet side might cause leaks.
CAUTION
Over-tightening may damage the flare and cause a refriger-
6. REFRIGERANT PIPING ant leakage.
〈For refrigerant piping between outdoor unit and this unit,
see the installation manual attached to the outdoor unit.
(Refer to Table 1)〉 Ester oil or ether oil.
〈Execute heat insulation work completely on both sides of
the gas pipe and the liquid pipe. Otherwise, a water leakage
can result sometimes.〉
〈When using a heat pump, the temperature of the gas pipe
can reach up to approximately 248°F, so use insulation Fig. 7
which is sufficiently resistant.〉
〈Improve the insulation on the refrigerant piping depending Torque wrench
on the installation environment. If the insulation is not suffi-
cient, condensate may form on the surface of the insulation.〉
〈Before refrigerant piping work, check which type of refrig-
erant is used. Proper operation is not possible if the types Spanner
of refrigerant are not the same.〉
CAUTION Piping union
• Use a pipe cutter and flare suitable for the type of refrig- Flare nut
erant. Fig. 8
• Apply ester oil or ether oil inside the flare portions
before connecting. (Refer to Fig. 7)
• To prevent dust, moisture or other foreign matter from Not recommendable but in case of emergency
infiltrating the tube, either pinch the end or cover it with You must use a torque wrench but if you are obliged to
tape. install the unit without a torque wrench, you may
• Do not allow anything other than the designated refrig- follow the installation method mentioned below.
erant to get mixed into the refrigerant circuit, such as air,
After the work is finished, make sure to check that
etc. If any refrigerant gas leaks while working on the
there is no gas leak.
unit, ventilate the room thoroughly right away.
When you keep on tightening the flare nut with a spanner,
• The outdoor unit is charged with refrigerant. there is a point where the tightening torque suddenly
• Be sure to use both a spanner and torque wrench together, increases. From that position, further tighten the flare nut
as shown in the drawing, when connecting or disconnecting the angle shown below:
pipes to/from the unit. (Refer to Fig. 8)
• Refer to Table 2 for the dimensions of flare nut spaces. Table 3
• When connecting the flare nut, coat the flare section inside Further tightening Recommended arm length of
Pipe size
with ester oil or ether oil, rotate three or four times first, then angle tool
screw in. (Refer to Fig. 7) φ 3/8” 60 to 90 degrees Approx. 7-7/8in.
• Refer to Table 2 for tightening torque. φ 5/8” 30 to 60 degrees Approx. 11-13/16in.
Table 1
Liquid pipe
Unit to be connected Gas pipe diameter
diameter
FXMQ48MFVJU φ5/8
FXMQ72MFVJU φ3/4 Use attached pipe. φ3/8
FXMQ96MFVJU φ7/8 Use attached pipe.
English 6
01_EN_3P086156-12Y.fm Page 7 Wednesday, September 16, 2009 2:09 PM
Fig. 10
(Install with a downward slope of at least 1/100)
CAUTION Fig. 12
Be sure to insulate any field pipe all the way to the pipe con-
nection inside the unit. Any exposed pipe may cause
cndensate or burns if touched.
7 English
01_EN_3P086156-12Y.fm Page 8 Wednesday, September 16, 2009 2:09 PM
English 8
01_EN_3P086156-12Y.fm Page 9 Wednesday, September 16, 2009 2:09 PM
(2) Indoor unit – Remote controller: • Power supply wire, Ground wire (Refer to Fig. 17)
Max. 1640ft. Connect the wire to L1 and L2 on the power supply terminal
(3) Max. branches No. of branches :16 block (X1M). Also, connect the ground wire to the ground ter-
3. Up to 16 branches are possible for unit-to unit cabling. No minal. Take the power supply wire and the ground wire into
branch is allowed after first branch. (Refer to Fig. 15) the unit through the wiring through hole <1>, and firmly
secure them together using the clamp (accessory 11)).
Subbranching
Branch • Transmission wire, Remote controller wire (Refer to Fig. 17)
F1 F2 F1 F2 F1 F2
Connect the transmission wire to F1 and F2 on the transmis-
sion terminal block (X2M). Connect the remote controller
wire to P1 and P2 on the transmission terminal block (X2M).
F1 F2 F1 F2 Take them into the unit through the wiring through hole <2>,
and firmly secure the wires using the clamp (accessory 11)).
Fig. 15
Electrical components box
Power supply wiring 1. Use round crimp-style terminals for connecting wires to the
Insulation tube Clamp or power supply terminal block.
(accessory 2)) (accessory 11)) Transmission wiring If unavailable, observe the following points when wiring.
• Do not connect wires of different gauge to the same
power supply terminal.
(3in.) (Looseness in the connection may cause overheating.)
9 English
01_EN_3P086156-12Y.fm Page 10 Wednesday, September 16, 2009 2:09 PM
• Use the specified electric wire. Connect the wire securely 10-2 WIRING EXAMPLE
to the terminal. Lock the wire down without applying • Fit the power supply wiring of each unit with a switch and
excessive force to the terminal. fuse as shown in the drawing.
Attach insulation sleeve
COMPLETE SYSTEM EXAMPLE (3 SYSTEMS)
3. Do not connect wires of different gauge to the same ground Power supply Power supply Power supply Power supply
208-230V 208-230V 208-230V 208-230V
terminal. Looseness in the connection may deteriorate pro- Outdoor unit
tection. 60Hz Control box
60Hz 60Hz 60Hz
IN/D OUT/D
4. Outside of the unit, keep transmission wire and remote con- L1 L2
F 1 F2 F1 F 2
L1 L2 L1 L2 L1 L2
troller wire at least 2in. away from power supply wire and
ground wire. The unit may malfunction if subjected to elec-
trical noise (external static).
5. For remote controller wiring, refer to the “INSTALLATION
MANUAL OF REMOTE CONTROLLER” attached to the
L1L2 P1 P2 F1 F2 T1 T2 L1L2 P1 P2 F1 F2 T1 T2 L1L2 P1 P2 F1 F2 T1 T2 L1L2 P1 P2 F1 F2 T1 T2
remote controller.
6. Never connect power supply wire to the transmission Unit A Unit B Unit C
terminal block (X2M). A mistake of the sort could dam-
P1 P2 P1 P2 P1 P2 P1 P2
age the entire system. Most
7. Use only specified wire and tightly connect wires to termi- downstream
nals. Be careful wires do not place external stress on termi- unit
nals. Keep wiring in neat order and so as not to obstruct Fig. 19
other equipment such as the electrical components box lid. 2. For group control or control by 2 remote controllers
Make sure the lid closes tight. Incomplete connections Note: It is not necessary to designate indoor unit
could result in overheating, and in worse case, electric address when using group control.
shock or fire. The address is automatically set when
power is activated.
Outdoor
Power supply unit Power supply Power supply Power supply
208-230V Control box 208-230V 208-230V 208-230V
IN/D OUT/D
F1 F 2 F 1 F 2
Most
downstream
unit
L1 L2 P1 P2 F1 F2 T1 T2 L1 L2 P1 P2 F1 F2 T1 T2 L1 L2 P1 P2 F1 F2 T1 T2 L1 L2 P1 P2 F1 F2 T1 T2
Control by 2
Fig. 20 remote controllers
[ PRECAUTIONS ]
1. A single switch can be used to supply power to units on the
same system. However, branch switches and branch
ground fault circuit interrupters must be selected carefully.
English 10
01_EN_3P086156-12Y.fm Page 11 Wednesday, September 16, 2009 2:09 PM
10-3 CONTROL BY 2 REMOTE CONTROLLERS (Con- Wire specification Sheathed vinyl cord or cable (2 wire)
trolling 1 indoor unit by 2 remote controllers) Size AWG18-16
• When using 2 remote controllers, one must be set to Length Max. 328ft.
“MAIN” and the other to “SUB”.
Contact that can ensure the minimum appli-
External terminal
MAIN/SUB CHANGEOVER cable load of 15 V DC, 1 mA.
F2 T1 T2
FORCED 11-2 How to select FORCED OFF and ON/OFF
OFF OPERATION
• When in the field set mode, select mode No. 12, then set
Input A
the first code (switch) No. to “1”. Then set second code
(position) No. to “01” for FORCED OFF and “02” for ON/
OFF OPERATION. (FORCED OFF at factory set)
11 English
01_EN_3P086156-12Y.fm Page 12 Wednesday, September 16, 2009 2:09 PM
NOTE
Air discharge temperature is not displayed on remote controller.
English 12
00_CV_3P086156-12Y.fm Page 2 Thursday, September 17, 2009 1:19 PM