The CM-MPN.52S is a three-phase monitoring relay that monitors phase parameters like over/undervoltage, unbalance, and failure. It has adjustable thresholds and can select phase sequence monitoring or automatic correction. The relay has a 2 contact output configurable as 1 or 2 contacts, with contacts rated up to 250V/4A. It is designed to operate on 350-580VAC input at 50/60Hz and has adjustable trip delays from instantaneous to 30 seconds.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
60 views4 pages

1SVR750487R8300 CM MPN 52s

The CM-MPN.52S is a three-phase monitoring relay that monitors phase parameters like over/undervoltage, unbalance, and failure. It has adjustable thresholds and can select phase sequence monitoring or automatic correction. The relay has a 2 contact output configurable as 1 or 2 contacts, with contacts rated up to 250V/4A. It is designed to operate on 350-580VAC input at 50/60Hz and has adjustable trip delays from instantaneous to 30 seconds.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

PRODUCT-DETAILS

CM-MPN.52S
CM-MPN.52S Three-phase monitoring relay
2c/o, 0,0.1-30s, L1-L2-L3=3x350-580VAC

Información General
Tipo de producto extendido CM-MPN.52S
Código de producto 1SVR750487R8300
EAN 4016779851916
Descripción corta CM-MPN.52S Three-phase monitoring relay 2c/o, 0,0.1-30s, L1-L2-L3=3x350-580VAC
The CM-MPN.52S is a multifunctional relay from the CM three-phase monitors range. It
operates with a rated control supply voltage / three-phase measuring voltage of 350-
580 V AC 50/60 Hz and has a 2 c/o (SPDT) output with contacts rated at 250 V / 4 A.
This relay monitors all phase parameters such as over/undervoltage, phase unbalance
and phase failure. The corresponding threshold values are adjustable. The CM-
MPN.52S also offers selection of phase sequence monitoring, automatic phase
Descripción larga sequence correction as well as an ON or OFF tripping delay. The output contacts can
be configured as 1x2 c/o (SPDT) contacts (common signal) or 2x1 c/o (SPDT) contact
(separate signal for over- and undervoltage thresholds) operation. The tripping delay
is adjustable over a range of instantaneous to 30 s (0, 0.1-30 s). A sealable transparent
cover for protection against unauthorized changes is available as accessory. The
device offers screw connection technology with double-chamber cage connection
terminals.

Clasificación
Cantidad mínima de 1 piece
pedido
Código arancelario 85364900

Descargas Populares
CM-MPN.52S 2

Ficha técnica, 2CDC112177D0201


información técnica
Instrucciones y 1SVC730730M1000
manuales 1SVC730730M0000

Dimensiones
Ancho del product 45 mm
Largo del product 104.8 mm
Alto del producto 85.6 mm
Peso del product 0.23 kg

Technical
Función Automatic phase sequence correction
Over- and undervoltage monitoring
Phase failure detection
Phase unbalance detection
Phase sequence monitoring
Normas CAN/CSA C22.2 No.14
IEC/EN 63000
IEC/EN 60255-27
IEC/EN 61000-6-2
IEC/EN 61000-6-3
UL 508
Rango de medición (L-L) 350 ... 580 V AC
Tensión nominal de (L-L) 350 ... 580 V AC
alimentación de control
(U s )
Frecuencia nominal (f) Supply Circuit 50/60 Hz
Salida 2 x 1 c/o or 1 x 2 c/o contacts, configurable
Rango de tiempo 0 s or 0.1 ... 30 s tripping delay (ON or OFF)
200 ms start-up delay
Tipo de terminal Screw Terminals
Corriente nominal de (230 V) 4 A
funcionamiento AC-12 (I e
)
Corriente nominal de (230 V) 3 A
funcionamiento AC-15 (I e
)
Corriente nominal de (24 V) 4 A
funcionamiento DC-12 (I
e)
Corriente nominal de (24 V) 2 A
funcionamiento DC-13 (I
e)
Capacidad mínima de 24 V
conmutación 10 mA
Tensión nominal de Input Circuit / Output Circuit 1000 V
aislamiento (U i ) Output Circuit 1 / Output Circuit 2 300 V
Tensión nominal Input Circuit 8 kV
soportada por impulsos Output Circuit 4 kV
(U imp )
Grado de protección Housing IP50
Terminals IP20
Categoría de III
sobretensión
Grado de contaminación 3
Dispositivos de Output Circuit NC - F Type Fuses 6 A
protección contra Output Circuit NO - F Type Fuses 10 A
cortocircuitos
Durabilidad eléctrica AC-12 100000 cycle
Durabilidad mecánica 30000000 cycle
CM-MPN.52S 3

Capacidad de conexión Flexible with Ferrule 1x 0.5 ... 2.5 mm²


Flexible with Ferrule 2x 0.5 ... 1.5 mm²
Flexible with Insulated Ferrule 1x 0.5 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.5 ... 1.5 mm²
Flexible 1x 0.5 ... 2.5 mm²
Flexible 2x 0.5 ... 1.5 mm²
Rigid 1x 0.5 ... 4 mm²
Rigid 2x 0.5 ... 2.5 mm²
Par de apriete 0.6 ... 0.8 N·m
Longitud de pelado del 8 mm
cable
Destornillador 4.5
recomendado 0.8 x 4
Pozidriv 1
Posición de montaje 1 ... 6
Montaje en contactores TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715

Ambiente
Temperatura ambiente Funcionamiento -25 ... +60 °C
Almacenamiento -40 ... +85 °C
Altitud máxima de Without Derating 2000 m
funcionamiento
permisible
Estado de RoHS Following EU Directive 2011/65/EU

Technical UL/CSA
Tensión máxima de Output Circuit 300 V AC
funcionamiento UL/CSA
Clasificación de los B300
contactos UL/CSA
Capacidad de conexión Flexible 1x 18-14 AWG
UL/CSA Flexible 2x 18-16 AWG
Rigid 2x 20-14 AWG
Rigid 1x 20-12 AWG
Par de apriete UL/CSA 7.08 in·lb

Certificados y Declaraciones (Número de Documento)


Certificado CB CB_DK-27946-UL
Certificado CQC CQC2009010303326655
Certificado cULus cULus508_20120829-E140448
Declaración de 2020980303000197
conformidad - CCC
Declaración de 1SVD981014-00
conformidad - CE
Declaración de 1SVD981014-10
conformidad - UKCA
Certificado DNV GL DNV_GL_TAA000017D
Certificado EAC EAC_RU_C-DE.ME77.B.03424
Instrucciones y 1SVC730730M1000
manuales 1SVC730730M0000
Información sobre RoHS 1SVD981014-00

Información de Embalaje
Embalaje Nivel 1 box 1 piece
Unidades
Embalaje Nivel 1 Ancho 97 mm
CM-MPN.52S 4

Embalaje Nivel 1 Alto 109 mm


Embalaje Nivel 1 Largo 52.5 mm
Embalaje Nivel 1 Peso 0.255 kg
Embalaje Nivel 1 EAN 4016779851916

Clasificaciones
Código de clasificación B
de objetos
ETIM 4 EC001441 - Phase monitoring relay
ETIM 5 EC001441 - Phase monitoring relay
ETIM 6 EC001441 - Phase monitoring relay
ETIM 7 EC001441 - Phase monitoring relay
Clase electrónica V11.0 : 27371803
UNSPSC 39121536
Número E (Finlandia) 2712264
Número E (Suecia) 3860592
ETIM 8 EC001441 - Phase monitoring relay

Categorias

Productos y sistemas de baja tensión  → Aparatos de control  → Relés electrónicos  → Three Phase Monitors

You might also like