0% found this document useful (0 votes)
106 views28 pages

WEG cfw500 Softplc Manual 10002299985 Manual English

This document provides a user manual for the SoftPLC CFW500. It summarizes the memory structure including data memory sections like constants, physical I/O, variables, and parameters. It then describes the main function blocks available in the SoftPLC like contacts, coils, movement blocks, PLC blocks, calculation blocks, and transfer blocks. It also covers parameter settings for the inverter and SoftPLC-exclusive parameters. Finally, it lists the main functions of the programming software interface like creating and opening projects, viewing compilation information, and compiling programs.

Uploaded by

Jorgito Xd
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
106 views28 pages

WEG cfw500 Softplc Manual 10002299985 Manual English

This document provides a user manual for the SoftPLC CFW500. It summarizes the memory structure including data memory sections like constants, physical I/O, variables, and parameters. It then describes the main function blocks available in the SoftPLC like contacts, coils, movement blocks, PLC blocks, calculation blocks, and transfer blocks. It also covers parameter settings for the inverter and SoftPLC-exclusive parameters. Finally, it lists the main functions of the programming software interface like creating and opening projects, viewing compilation information, and compiling programs.

Uploaded by

Jorgito Xd
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 28

Motors I Automation I Energy I Transmission & Distribution I Coatings

SoftPLC
CFW500

User’s Manual
SoftPLC Manual

Series: CFW500
Language: English
Document Number: 10002299985 / 01

Publication Date: 06/2015


Summary

SUMMARY

ABOUT THE MANUAL ..................................................................................................................................... 5


ABBREVIATIONS AND DEFINITIONS ......................................................................................................... 5
NUMERICAL REPRESENTATION ............................................................................................................... 5
1 INTRODUCTION TO SOFTPLC ................................................................................................................ 6
1.1 SYMBOL OF THE DATA TYPES ........................................................................................................ 6
2 SOFTPLC MEMORY ................................................................................................................................. 7
2.1 MEMORY ............................................................................................................................................ 7
2.2 DATA MEMORY ................................................................................................................................. 7
2.2.1 Constants.................................................................................................................................... 7
2.2.2 Physical Inputs and Outputs (Hardware) ................................................................................. 7
2.2.3 Volatile Markers (Variables) ...................................................................................................... 8
2.2.4 System Markers ......................................................................................................................... 8
2.2.5 Parameters ............................................................................................................................... 10
2.3 MODBUS .......................................................................................................................................... 11
2.3.1 Modbus protocol SoftPLC addresses ................................................................................... 11
2.3.2 Protocol..................................................................................................................................... 11
3 RESUME OF THE FUNCTION BLOCKS ................................................................................................ 12
3.1 CONTACTS ...................................................................................................................................... 12
3.1.1 Normally Open Contact – NO CONTACT ............................................................................... 12
3.1.2 Normally Closed Contact – NC CONTACT ............................................................................ 12
3.1.3 AND Logic with Contacts ........................................................................................................ 12
3.1.4 OR Logic with Contacts .......................................................................................................... 12
3.2 COILS ............................................................................................................................................... 13
3.2.1 Normal Coil - COIL ................................................................................................................... 13
3.2.2 Negated Coil – NEG COIL........................................................................................................ 13
3.2.3 Set Coil – SET COIL ................................................................................................................. 13
3.2.4 Reset Coil – RESET COIL ........................................................................................................ 13
3.2.5 Positive Transition Coil – PTS COIL ....................................................................................... 13
3.2.6 Negative Transition Coil – NTS COIL ..................................................................................... 13
3.3 MOVEMENT BLOCKS ..................................................................................................................... 13
3.3.1 Speed and/or Torque Reference – REF ................................................................................. 13
3.4 PLC BLOCKS ................................................................................................................................... 14
3.4.1 Timer – TON .............................................................................................................................. 14
3.4.2 Incremental Counter – CTU .................................................................................................... 14
3.4.3 Proportional-Integral-Derivative Controller – PID ............................................................... 14
3.4.4 Low-pass or High-pass Filter – FILTER ................................................................................. 15
3.5 CALCULATION BLOCKS ................................................................................................................ 15
3.5.1 Comparator – COMP ............................................................................................................... 15
3.5.2 Math Operation – MATH .......................................................................................................... 15
3.5.3 Math Function - FUNC ............................................................................................................. 16
3.5.4 Saturator – SAT ........................................................................................................................ 16
3.6 TRANSFER BLOCKS ....................................................................................................................... 17
3.6.1 Data Transfer – TRANSFER .................................................................................................... 17
3.6.2 Conversion from Integer (16 bits) to Floating Point – INT2FL ............................................. 17
3.6.3 User Fault or Alarm Generator - USERERR .......................................................................... 17
3.6.4 Convert from Floating Point to Integer (16 bits) – FL2INT ................................................... 18
3.6.5 Indirect Data Transfer – IDATA ............................................................................................... 18
3.6.6 Multiplex – MUX ....................................................................................................................... 18
3.6.7 Demultiplexer – DMUX ............................................................................................................ 19
4 1. INVERTER PARAMETER SETTINGS ................................................................................................. 20
4.1 SYMBOLS FOR PROPERTY DESCRIPTION .................................................................................. 20
4.2 CFW500 CONFIGURATION PARAMETERS ................................................................................... 20

CFW500 | 3
Summary

4.3 SOFTPLC EXCLUSIVE PARAMETERS ........................................................................................... 21


P1000 – SOFTPLC STATUS ........................................................................................................................... 21
P1001 – SOFTPLC COMMAND ....................................................................................................................... 21
P1002 – SCAN CYCLE TIME ........................................................................................................................... 22
P1010 TO P1059 – SOFTPLC USER PARAMETERS ......................................................................................... 22
5 SUMMARY OF THE WLP MAIN FUNCTIONS....................................................................................... 23
5.1 PROJECT – NEW.............................................................................................................................. 23
5.2 PROJECT – OPEN ............................................................................................................................ 23
5.3 PROJECT – PROPERTIES ............................................................................................................... 23
5.4 VIEW – COMPILATION INFORMATION .......................................................................................... 24
5.5 VIEW – USER PARAMETER CONFIGURATION ............................................................................. 24
5.6 CONSTRUCT – COMPILE ............................................................................................................... 25
5.7 COMMUNICATION – CONFIGURATION ........................................................................................ 25
5.8 COMMUNICATION – DOWNLOAD ................................................................................................. 26
5.9 COMMUNICATION – UPLOAD ....................................................................................................... 26
6 ALARMS, FAULTS AND POSSIBLE CAUSES ...................................................................................... 28

CFW500 | 4
About the Manual

ABOUT THE MANUAL


This manual provides the required information for the operation of the CFW500 frequency inverter using the
user’s programming module, called SoftPLC. This manual must be used together with the user’s manual of the
CFW500 and WLP software.

ABBREVIATIONS AND DEFINITIONS

PLC Programmable Logic Controller


CRC Cycling Redundancy Check
RAM Random Access Memory
WLP Ladder Language Programming Software
USB Universal Serial Bus

NUMERICAL REPRESENTATION

Decimal numbers are represented by means of digits without suffix. Hexadecimal numbers are represented with
the letter 'h' after the number.

CFW500 | 5
Introduction to SoftPLC

1 INTRODUCTION TO SOFTPLC
The SoftPLC is a resource that adds the functionalities of a PLC to the CFW500, providing the product with
flexibility and allowing the user to develop its own applications (user’s programs).

The main SoftPLC characteristics are:

Programming in “Ladder Language” using the WLP software.


Access to all Parameters and I/Os of the CFW500.
50 configurable parameters for the user’s use.
PLC, Mathematical and Control Blocks
On-line transfer and monitoring of the software application via Serial/USB interface.
Transfer of the application software installed on the CFW500 to the PC with password restriction.
Storage of the software application on the FLASH memory board.
Execution directly on the RAM.

1.1 SYMBOL OF THE DATA TYPES

%KW word-type constants (16 bits)


%KF float type constants (32 bits, floating point)
%MX bit markers
%MW word markers (16 bits)
%MF float markers (32 bits, floating point)
%SX system bit markers
%SW system word markers (16 bits)
%IX digital Inputs
%IW analog inputs (16 bits)
%QX digital outputs
%QW analog outputs (16 bits)
%UW user parameters (16 bits)
%UW user parameters (16 bits)
%PD drive parameter (16 bits)

CFW500 | 6
SoftPLC MEMORY

2 SOFTPLC MEMORY
The total size of the SoftPLC parameter is 7684 bytes for program memory and data memory.

NOTE!
The SoftPLC application is stored in the memory of the plug-in used at the moment of download.
Therefore, if the plug-in is changed, it will be necessary to download the application again.

2.1 MEMORY

SoftPLC function: 7684 bytes


SoftPLC User Parameter: 508 bytes

2.2 DATA MEMORY

The SoftPLC data memory area (user variables) is shared with the programming memory. Therefore, the total
size of an application may vary as a function of the number of variables applied by the user.

The bit, word and float markers are allocated according to the LAST address used on the application, that is,
the longer the last address, the larger the allocated area. Therefore, it is recommended to use the markers in a
SEQUENTIAL manner.

The word and float constants do also use program memory space.

2.2.1 Constants

Table 2.1: Constant Memory Map

Sym. Description Bytes


It depends on the number of different word constants.
E.g.: If there were used:
Word Constants
%KW - %KW: 327 = 2 bytes
(16 bits)
- %KW: 5; 67 = 4 bytes
- %KW: 13; 1000; 13; 4 = 6 bytes
It depends on the number of different float constants. E.g.:
If there were used:
Float Constants
%KF - %KF: -0,335 = 4 bytes
(32 bits – IEEE)
- %KF: 5,1; 114,2 = 8 bytes
- %KF: 0,0; 115,3; 0,0; 13,333 = 12 bytes

2.2.2 Physical Inputs and Outputs (Hardware)

Table 2.2: I/O Memory Map

Sym. Description Range Bytes


%IX Digital Inputs 1 ... 8 2
%QX Digital Outputs 1 ... 5 2
%IW Analog Inputs/Frequency 1 ... 4 8
%QW Analog Outputs/Frequency 1 ... 3 6

NOTE!
The %IW4 marker corresponds to the frequency input. In order to activate this input, it is necessary
to set P0246 to 1.

NOTE!
The %QW3 marker corresponds to the frequency output. In order to activate this output, it is
necessary to set P0257 according to the desired function. Furthermore, note that the DO2 circuit is
configured in open collector.

CFW500 | 7
SoftPLC MEMORY

NOTE!
The values of the Analog/Frequency Inputs (%IW) and of the Analog/Frequency Outputs (%QW)
respectively read and written via SoftPLC respect their gains (P0232, P0237, P0242, P0247:
%IW1−%IW4 and P0252, P0255, P0258: %QW1−%QW3) and offsets (P0234, P0239, P0244,
P0249: %IW1−%IW4).

NOTE!
The values read or written via SoftPLC obey the following rules, respecting the parameters related
to the analog input and output signal types (P0233, P0238, P0243: %IW1−%IW3 and P253, P256:
%QW1−%QW2):
Option: 0 to 10V/20mA
 0V or 0mA =0
 10V or 20mA = 32767
Option: 4 to 20mA
 4mA = 0
 20mA = 32767
Option: 10V/20mA to 0
 10V or 20mA = 0
 0V or 0mA = 32767
Option: 20 to 4mA
 20mA = 0
 4mA = 32767

2.2.3 Volatile Markers (Variables)

They consist of variables that can be applied by the user to execute the applicative logics. They can be bit
markers (1 bit), word markers (16 bit) or float markers (32 bit – IEEE).

Table 2.3: Volatile Marker Memory Map

Sym. Description Range Bytes


It depends on the last used marker. They are organized
in byte pairs. E.g.:
- last marker: %MX5000 = 2 bytes
%MX Bit Markers 5000 ... 6099
- last marker: %MX5014 = 2 bytes
- last marker: %MX5016 = 4 bytes
- last marker: %MX5039 = 6 bytes
It depends on the last used marker. E.g.:
- last marker: %MX8000 = 2 bytes
%MW Word Markers 8000 ... 8199
- last marker: %MX8001 = 4 bytes
- last marker: %MX8007 = 16 bytes
It depends on the last used marker. E.g.:
- last marker: %MX9000 = 4 bytes
%MF Float Markers 9000 ... 9199
- last marker: %MX9001 = 8 bytes
- last marker: %MX9007 = 32 bytes

NOTE!
In order to minimize the application size, use the markers in a sequential manner.
E.g.:
Bit markers: %MX5000, %MX5001, %MX5002, ...
Word markers: %MW8000, %MW8001, %MW8002, ...
Float markers: %MF9000, %MF9001, %MF9002, ...

2.2.4 System Markers

They consist of special variables that allow the user to read and change inverter data that may or may not be
available in the parameters. They can be: system bit markers (1 bit) or system word markers (16 bits).

CFW500 | 8
SoftPLC MEMORY

Table 2.4 (a): Memory Map for the Odd System Bits – Writing/Command

Sym. Description Range Bytes


Type System Bits 3000 ... 3040 4 bytes
Writing/Command (odd)
0: It disables the inverter completely, interrupting the supply for the motor.
3001 General Enabling
1: It enables the inverter, allowing the motor operation.
0: It stops the motor with deceleration ramp.
3003 Run/Stop The motor rung according to the acceleration ramp until reaching the speed
reference value.
0: It runs the motor in the counterclockwise direction.
3005 Speed Direction
1: It runs the motor in the clockwise direction.
0: It disables the JOG function.
3007 JOG
1: It enables the JOG function.
%SX 0: The inverter goes to the local situation.
3009 LOC/REM
1: The inverter goes to the remote situation.
0: No function.
1: If in fault condition, it resets the inverter.
3011 Fault reset
NOTE: When this command is executed, the inverter and the SoftPLC
Application are reinitialized. This is also valid for reset via keypad.
0: The values for the motor acceleration and deceleration are those from the
first Ramp (P0100 and P0101).
3021 Activates the Second Ramp 1: The values for the motor acceleration and deceleration are those from the
second Ramp (P0102 and P0103).
Note: Program P0105 in 6 in order to enable the selection via SoftPLC.

Table 2.4 (b): Memory Map for the Even System Bit – Reading/State

Sym. Description Range Bytes


Type System Bits 3000 ... 3040 4 bytes
Reading/State (Even)
0: General enabling is not active.
3000 General Enabling
1: General enabling is active and the inverter is ready to run the motor.
0: The motor is stopped.
3002 Motor Running (RUN) 1: The inverter is driving the motor at the set point speed, or executing either
the acceleration or the deceleration ramp.
0: The motor is rotating counterclockwise.
3004 Speed Direction
1: The motor is rotating clockwise.
0: JOG function inactive.
3006 JOG
1: JOG function active.
0: Inverter in local mode.
3008 LOC/REM
1: Inverter in remote mode.
0: Inverter is not in fault state.
1: Some fault registered by the inverter.
3010 In Fault
Note: The number of the fault can be read through parameter P0049 –
Current Fault.
0: No undervoltage.
3012 Undervoltage
1: With undervoltage.
0: In manual mode (PID function).
%SX 3014 PID Operation Mode
1: In automatic mode (PID function).
0: Inverter is not in an alarm condition.
1: Inverter is in an alarm condition.
3016 Alarm Condition
Note: The number of the alarm can be read by means of parameter P0048 –
Current Alarm.
0: Inverter operating normally.
1: Inverter in configuration state. It indicates a special condition when the
inverter cannot be enabled:
3018 In Configuration Mode - Executing the self tuning routing.
- There is a parameter setting incompatibility.
Note: Parameter P0047 shows the cause of the parameter setting
incompatibility.
0: It indicates that the first Ramp is active.
3020 Active Ramp
1: It indicates that the second Ramp is active.
3032 Start key (1)
3034 Stop key (0) 0: Not pressed.
3036 Speed direction key () 1: Pressed during 1 scan cycle
3038 Local/Remote key
0: Not pressed.
3040 JOG key
1: Pressed.

CFW500 | 9
SoftPLC MEMORY

Table 2.5: Memory Map for the Even System Word Markers

Sym. Description Range Bytes


System Words 3300 ... 3324 48 bytes
Reading Markers/Status (Even)
3300 Motor speed [13 bits]
3302 Motor synchronous speed [rpm]
3304 Motor speed [rpm]
%SW 3306 Speed reference [rpm]
3308 Alarm
3310 Fault
3320 Inverter rated current [A x10]
3322 Unfiltered motor current (P003) [A x10]
3324 Unfiltered motor torque [% x10]

NOTE!
The system word markers %SW3300 use a 13-bits resolution (8192 0 to 8191), which the motor
synchronous speed. Thus, if the speed reference via “Reference” block (%SW3301) is 4096 for a VI
pole motor (this means a synchronous speed of 1200 rpm), the motor will run at 600 rpm.

NOTE!
Equation for the calculation of the motor speed in rpm:

Speed in rpm = synchronous speed in rpm x speed in 13 bits


8192

NOTE!
Equation for the calculation of the motor speed in Hz:

Speed in Hz = synchronous frequency in Hz (P0403) x speed in 13 bits


8192

2.2.5 Parameters

The parameters from P1010 to P1059 appear on the keypad only when there is a valid application (user
program) in the memory, i.e., when P1000 > 0.

Table 2.6: Parameter Memory Map

Sym. Description Range Bytes


System Parameters
%PD 0... 999
(refer to the CFW500 manual)
SoftPLC Parameters 1000 ... 1059 6 bytes
P1000: SoftPLC Status 0: No application
[Read-only parameter] 1: Install. Applic.
2: Incompat. App.
3: App. Stopped
%PW 4: App. Running
P1001: SoftPLC Command 0: Stop Program
1: Run Program
2: Delete Program
P1002: Scan Cycle Time [ms]
[Read-only parameter]
%UW User Parameters 1010 ... 1059 100 bytes

CFW500 | 10
SoftPLC MEMORY

2.3 MODBUS

2.3.1 Modbus protocol SoftPLC addresses

Table 2.7: SoftPLC x Modbus Address Range

Sym. Description SoftPLC MODBUS


%IX Digital Inputs 1 ... 8 2201...2208
%QX Digital Outputs 1 ... 5 2401...2405
%IW Analog Inputs/Frequency 1 ... 4 2601...2603
%QW Analog Outputs/Frequency 1 ... 3 2801...2802

NOTE!
The %IW4 marker corresponds to the frequency input. In order to activate this input, it is necessary
to set P0246 to 1.

NOTE!
The %QW3 marker corresponds to the frequency output. In order to activate this output, it is
necessary to set P0257 according to the desired function. Furthermore, note that the DO2 circuit is
configured in open collector.

NOTE!
All the other data types have the user addresses (SoftPLC) equal to the Modbus addresses. E.g.:
%PD0100 = Modbus address 100; %MX5000 = Modbus address 5000; %SW3308 = Modbus
address 3308.

2.3.2 Protocol

Refer to the RS232/RS485 Serial Communication manual, at the Modbus Protocol chapter.

CFW500 | 11
Resume of the Function Block

3 RESUME OF THE FUNCTION BLOCKS


This chapter contains a summary of the function blocks that are available for the user programming.

3.1 CONTACTS

They send to the stack the content of a programmed data (0 or 1), which can be of the following type:
%MX: Bit Marker
%IX: Digital Input
%QX: Digital Output
%UW: User Parameter
%SX: System Bit Marker – Reading

3.1.1 Normally Open Contact – NO CONTACT

Menu: Insert-Contacts-NO CONTACT.


E.g.: It sends to the stack the content of bit marker 5000.

3.1.2 Normally Closed Contact – NC CONTACT

Menu: Insert-Contacts-NC CONTACT.


E.g.: It sends to the stack the negated content of digital output 1.

3.1.3 AND Logic with Contacts

When the contacts are in series, an AND logic is executed among them, storing the result in the stack.
Examples:

Example Truth Table


%IX1 %IX2 Stack
0 0 0
0 1 0
1 0 0
%IX1.%IX2 1 1 1
%UW1010 %QX1 Stack
0 0 0
0 1 0
1 0 1
%UW1010. (~%QX1) 1 1 0

3.1.4 OR Logic with Contacts

When the contacts are in parallel, an OR logic is executed among them, storing the result in the stack.
Examples:

Example Operation Truth Table


%IX1 %IX2 Stack
0 0 0
0 1 1
%IX1 + %IX2 1 0 1
1 1 1

%UW1010 %QX1 Stack


0 0 1
0 1 0
%UW1010 + (~%QX1) 1 0 1
1 1 1

CFW500 | 12
Resume of the Function Block

3.2 COILS

They save the content of the stack on the programmed data (0 or 1), which can be of the following type:

%MX: Bit Marker


%QX: Digital Output
%UW: User Parameter
%SX: System Bit Marker – Writing

It is allowed to add coils in parallel at the last column.

3.2.1 Normal Coil - COIL

Menu: Insert-Coils-COIL
E.g.: It sets the bit marker 5001 with the stack content

3.2.2 Negated Coil – NEG COIL

Menu: Insert-Coils-NEG COIL


E.g.: It sets the digital output 2 with the negated content of the stack

3.2.3 Set Coil – SET COIL

Menu: Insert-Coils-SET COIL


E.g.: It sets the user parameter 1011, provided that the content of the stack is not 0

3.2.4 Reset Coil – RESET COIL

Menu: Insert-Coils-RESET COIL


E.g.: It resets the user parameter 1011, provided that the content of the stack is not 0

3.2.5 Positive Transition Coil – PTS COIL

Menu: Insert-Coils-PTS COIL


E.g.: It sets the bit marker 5002 during 1 scan cycle, provided that a transition from 0 to 1 in
the stack is detected.

3.2.6 Negative Transition Coil – NTS COIL

Menu: Insert-Coils-NTS COIL


E.g.: It sets the system bit marker 3011 during 1 scan cycle, provided that a transition from 1
to 0 in the stack is detected.

3.3 MOVEMENT BLOCKS

3.3.1 Speed and/or Torque Reference – REF

Menu: Insert-Function Blocks-Movement-REF


Input:
EN: Enables block
Output:
ENO: Goes to 1 when EN ≠ 0 and without error
Properties:
MODE: 0=Speed Mode
SPEED: Speed reference [RPM,13 Bits, Hz (x10)]
TORQUE: Not available

CFW500 | 13
Resume of the Function Block

In the example above, if the EN is active, and the digital input 1 is off, then the block will generate a speed
reference according to the user parameter 1010 in the rpm unit. If there is no error (example: disabled inverter),
the ENO output goes to 1.

3.4 PLC BLOCKS

3.4.1 Timer – TON

Menu: Insert-Function Blocks-PLC-TON


Input:
IN: Enables the block
Output:
Q: Goes to 1 when IN ≠ 0 and ET ≥ PT
Properties:
PT: Programmed time (Preset Time)
ET: Elapsed Time

In the example above, if the IN input is active and the content of the word marker 8000 is greater than or equal
to the content of the user parameter 1010, the output Q is set.

3.4.2 Incremental Counter – CTU

Menu: Insert-Function Blocks-PLC-CTU


Inputs:
CU: Captures the transitions from 0 to 1 at this input (Counter Up)
R: Resets CV
Output:
Q: Goes to 1 when CV ≥ PV
Properties:
PV: Programmed value (Preset Value)
CV: Counter Value (Counter Value)
In the example above, if the content of the word marker 8001 is greater than or equal to 20, the output Q is set.

3.4.3 Proportional-Integral-Derivative Controller – PID

Menu: Insert-Function Blocks-PLC-PID


Inputs:
EN: Enables the block
Output:
ENO: EN Input image
Properties:
TS: Sampling time
SELREF: Automatic/manual reference
REF: Automatic reference
δREF: Time constant of the automatic
reference filter
REFMANUAL: Manual reference
FEEDBACK: Process feedback
KP: Proportional gain
KI: Integral gain
KD: Derivative gain
MAX: Maximum output value
MIN: Minimum output value
TYPE: Academic/parallel
OPT: Direct/reverse
OUT: Controller output

In the example above, if the input EN is active, the controller starts its operation. The content of the user
parameter 1010 selects the reference that is active, that is, whether it is the float marker 9001 (automatic
reference) or 9003 (manual reference). There is a 0.05s filter for the automatic reference. Since the derivative
gain is fixed in 0, this indicates that de PID was converted into a PI. The value of the control output OUT,

CFW500 | 14
Resume of the Function Block

represented by the float marker 9004, has the maximum and minimum limits of 100 and -100 and the sampling
time of 0.050s.

3.4.4 Low-pass or High-pass Filter – FILTER

Menu: Insert-Function Blocks-PLC-FILTER


Inputs:
EN: Enables the block
Output:
ENO: EN Input image
Properties:
TS: Sampling time
IN: Input data
TIMECONST: Filter time constant
TYPE: Low-pass/High-pass
OUT: Input data filtered value

In the example above, if the EN input is active, the content of the float marker 9000 will be filtered with a time
constant of 0.25s by a low-pass and filter and will be transferred to the float marker 9001.

3.5 CALCULATION BLOCKS

3.5.1 Comparator – COMP

Menu: Insert-Function Blocks-Calculation-COMP


Input:
EN: Enables the block
Output:
ENO: Goes to 1 when the comparison condition is
fulfilled
Properties:
FORMAT: Integer or floating point
DATA 1: Comparison data 1
OPERATOR: Comparison operator
DATA 2: Comparison data 2

In the example above, if the EN input is active and the content of the float marker 9000 is greater than the float
marker 9001, then the output ENO is set.

NOTE!
If FORMAT is integer, all the numerical data are considered words of 15 bits + signal (-32768 to 32767).

3.5.2 Math Operation – MATH

Menu: Insert-Function Blocks-Calculation-MATH


Input:
EN: Enables the block
Output:
ENO: Indicates if the calculation has been executed
Properties:
FORMAT: Integer or floating point
DATA1: Calculation Data 1. It may also appear as DATA1H
and DATA1L (representing the high and low parts of
data 1)
OPERATOR: Mathematic operator (+, -, *, etc)
DATA2: Calculation Data 2. It may also appear as DATA2H
and DATA2L (representing the high and low parts of
data 2)
RES: Calculation result. It may also appear as RESH and

CFW500 | 15
Resume of the Function Block

RESL (representing the high and low parts of the


result) and also as QUOC and REM (representing
the quotient and remainder of a division)
OVER: Indicates if the result exceeded its limit
SIGNAL: Result sign

In the example above, when the input EN is active, the value of the word marker 8000 is incremented at each
scan cycle. When the bit marker 5000 goes to 1, it indicates overflow and the word marker 8000 remains in
32767.

NOTE!
If FORMAT is integer, all the numerical data are considered words of 15 bits + sign (-32768 to 32767).

3.5.3 Math Function - FUNC

Menu: Insert-Function Blocks-Calculation-FUNC


Input:
EN: Enables the block
Output:
ENO: Indicates if the calculation has been executed
Properties:
FORMAT: Integer or floating point
IN: Data to be calculated
FUNCTION: Mathematic function (sin, cos, etc)
OUT: Calculation result

In the example above, when the EN input is active, the float marker 9001 presents the result of the float marker
9000 sine calculation.

NOTE!
If FORMAT is integer, all the numerical data are considered words of 15 bits + sign (-32768 to 32767).

3.5.4 Saturator – SAT

Menu: Insert-Function Blocks-Calculation-SAT


Input:
EN: Enables the block
Output:
ENO: Indicates if saturation has occurred, provided that
EN ≠ 0
Properties:
FORMAT: Integer or floating point
IN: Input data
MAX: Maximum allowed value
MIN: Minimum allowed value
OUT: Output data

In the example above, when the EN input is active, the word marker 8000 contains the user parameter 1010
value, but limited between the maximum of 100 and the minimum of -100.

NOTE!
If FORMAT is integer, all the numerical data are considered words of 15 bits + sign (-32768 to 32767).

NOTE!
If the value of MIN is greater than the MAX, the outputs OUT and ENO are reset to zero.

CFW500 | 16
Resume of the Function Block

3.6 TRANSFER BLOCKS

3.6.1 Data Transfer – TRANSFER

Menu: Insert-Function Blocks-Transfer-TRANSFER


Input:
EN: Enables the block
Output:
ENO: Indicates that the transfer has been done
Properties:
SRC: Source data
DST: Destine data

In the example above, if the EN input is active, the word constant 1 is transferred to the system bit marker 3001
(general enable).

3.6.2 Conversion from Integer (16 bits) to Floating Point – INT2FL

Menu: Insert-Function Blocks-Transfer-INT2FL


Input:
EN: Enables the block
Output:
ENO: Indicates that the transfer has been done
Properties:
INT: Integer data
FLOAT: Data converted into floating point

In the example above, if the EN input is active, the content of word marker 8153 (taking into account its sign) is
converted to floating point to the float marker 9005.

NOTE!
INT is treated as word of 15 bits + sign (-32768 to 32767).

3.6.3 User Fault or Alarm Generator - USERERR

Menu: Insert-Function Blocks-Transfer-USERERR


Input:
EN: Enables the block
Output:
ENO: It indicates 1 when EN = 1 and the alarm or error has
been effectively generated.
Properties:
CODE: Fault or alarm code.
TYPE: 0: Generates alarm, 1: Generates fault
TEXTL1: HMI line 1 text (Not available)
TEXTL2: HMI line 2 text (Not available)

In the example above, if the EN input is active, A750 will appear.

NOTE!
If this block is configured as Fault, it is necessary to reset the drive so as to enable it again.

CFW500 | 17
Resume of the Function Block

3.6.4 Convert from Floating Point to Integer (16 bits) – FL2INT

Menu: Insert-Function Blocks-Transfer-FL2INT


Input:
EN: Enables the block
Output:
ENO: Indicates that the transfer has been done
Properties:
FLOAT: Floating point data
INT: Data converted into integer

In the example above, if the EN input is active, the float constant 4.54x104 is converted into an integer with sign
via word marker 8000. However, after the conversion, the word marker 8000 will remain with the value 32767,
because this is the positive limit for a Word.

NOTE!
INT is treated as word of 15 bits + sign (-32768 to 32767).

3.6.5 Indirect Data Transfer – IDATA

Menu: Insert-Function Blocks-Transfer-IDATA


Input:
EN: Enables the block
Output:
ENO: Indicates that the transfer has been done
Properties:
CMD: Read/Write command
DATATYPE: Data type
ADDRESS: User address
VALUE: Read content/Value to be written

In the example above, if the EN input is active, the content of the bit marker 5000 is written to the digital output
whose address is the content of the word marker 8000.

3.6.6 Multiplex – MUX

Menu: Insert-Function Blocks -Transfer-MUX


Input:
EN: Enables the mathematic operation
Output:
ENO: Indicates that the transfer has been done
Properties:
X0-X15: Binary data vector
W: Resulting word

In the example above, when the EN input is active, the digital inputs 1, 2 and 3 transfer their content to the bits
0, 1 and 2 of the user parameters P1010.

CFW500 | 18
Resume of the Function Block

3.6.7 Demultiplexer – DMUX

Menu: Insert-Function Blocks-Transfer-DMUX


Input:
EN: Enables the mathematic operation
Output:
ENO: Indicates that the transfer has been done
Properties:
W: Source word
X0-X15: Resulting binary data vector

In the above example, when the EN input is active, the bits 1, 2, 5, 6, 11, 13 and 15 of the word marker 8000
are transferred respectively to the bit markers 5001, 5002, 5005, 5006, 5011, 5013 and 5015.

CFW500 | 19
Inverter Parameter Settings

4 INVERTER PARAMETER SETTINGS


In the continuation, only the parameters of the CFW500 frequency inverter that are related to the SoftPLC will be
presented.

4.1 SYMBOLS FOR PROPERTY DESCRIPTION

RO Read-only parameter.
CFG Parameter that can be changed only with a stopped motor.
Parameter visible on the keypad if the inverter has a network interface installed –
Net
RS232, RS485, CAN, Profibus – or if the USB interface is connected.
Parameter visible on the keypad if the inverter has the RS232 or RS485 interface
Serial
installed.
USB Parameter visible on the keypad if the inverter USB interface is connected.

4.2 CFW500 CONFIGURATION PARAMETERS


P0100 – ACCELERATION TIME

P0101 – DECELERATION TIME

P0220 – LOCAL/REMOTE SELECTION SOURCE

P0221 – SPEED REFERENCE SELECTION – LOCAL SITUATION

P0222 – SPEED REFERENCE SELECTION – REMOTE SITUATION

P0223 – FORWARD/REVERSE SELECTION – LOCAL SITUATION

P0226 – FORWARD/REVERSE SELECTION – REMOTE SITUATION

P0224 – RUN/STOP SELECTION – LOCAL SITUATION

P0227 – RUN/STOP SELECTION – REMOTE SITUATION

P0225 – JOG SELECTION – LOCAL SITUATION

P0228 – JOG SELECTION – REMOTE SITUATION

P0246 – FREQUENCY INPUT FI

P0251 – AO1 FUNCTION

P0254 – AO2 FUNCTION

P0276 – DO2 FUNCTION

P0263 – DI1 FUNCTION

P0264 – DI2 FUNCTION

P0265 – DI3 FUNCTION

P0266 – DI4 FUNCTION

P0267 – DI5 FUNCTION

P0268 – DI6 FUNCTION

P0269 – DI7 FUNCTION

CFW500 | 20
Inverter Parameter Settings

P0270 – DI8 FUNCTION

P0271 – DIGITAL INPUT SING

P0275 – DO1 FUNCTION (RL1)

P0276 – DO2 FUNCTION (RL2)

P0277 – DO3 FUNCTION (RL3)

P0278 – DO4 FUNCTION

P0279 – DO5 FUNCTION

NOTE!
The resources of available inputs and outputs depend on the used plug-in module.
For further information, please, refer to the CFW500 Programming Manual.

4.3 SOFTPLC EXCLUSIVE PARAMETERS

P1000 – SoftPLC STATUS

Adjustable 0 = No Application Factory Setting: 0


Range: 1 = Install. App.
2 = Incompat. App.
3 = App. Stopped
4 = App. Running
Properties: RO
Access groups via HMI:
01 PARAMETER GROUPS.
∟ 50 SoftPLC .

Description:
It allows the user to view SoftPLC status. If there are no applications installed, the parameters P1001 to P1059
will not be shown on the keypad.

If this parameter presents the option 2 (“Incompat. App.”), it indicates that the version that has been loaded in
the flash memory board is not compatible with the current CFW500 firmware.

In this case, it is to recompile the project in the WLP, considering the new CFW500 version and download it
again. If that is not possible, the upload of this application can be done with the WLP, provided that the
application password is known or is not enabled.

P1001 – SoftPLC COMMAND

Adjustable 0: Stop Program Factory Setting: 0


Range: 1 = Run Program
2 = Delete Program
Properties: CFG
Access groups via HMI:
01 PARAMETER GROUPS.
∟ 50 SoftPLC .

Description:
It allows stopping, running or excluding an installed application, but the motor must be disabled in order to do
so.

CFW500 | 21
Inverter Parameter Settings

P1002 – SCAN CYCLE TIME

Adjustable 0.00 to 99.99 s Factory Setting: Not


applicable
Range:
Properties: RO
Access groups via HMI:
01 PARAMETER GROUPS.
∟ 50 SoftPLC .

Description:
It consists of the application scanning time. The larger the application, the longer the scanning time.

P1010 to P1059 – SoftPLC USER PARAMETERS


Adjustable 0 to 65535 Factory Setting: 0
Range:
Properties: -
Access groups via HMI:
01 PARAMETER GROUPS.
∟ 50 SoftPLC .

Description:
They consist of use parameters defined by the user via WLP software, as described in item 5.5.

NOTE!
The parameters P1010 to P1019 can be viewed in the monitoring mode.

NOTE!
When parameter P1011 is a writing parameter and it is programmed in P0205, P0206 or P0207, then
its content can be changed with the HMI keys and .

CFW500 | 22
Summary of the WLP Main Functions

5 SUMMARY OF THE WLP MAIN FUNCTIONS


This chapter brings basic information about the operations done with the WLP software for the use of the
CFW500 inverter. More information can be obtained in the help of the WLP software

5.1 PROJECT – NEW

It creates a new project. Besides defining the project name, it is also necessary to configure the equipment and
the respective firmware version.

5.2 PROJECT – OPEN

It opens the selected project.

5.3 PROJECT – PROPERTIES

It allows the user to define the equipment and firmware version. In this box, it is also configure whether or not
the project will have upload password.

CFW500 | 23
Summary of the WLP Main Functions

5.4 VIEW – COMPILATION INFORMATION

It allows the user to know the compile application size in bytes (<projectname>.bin) to be sent to the equipment.

5.5 VIEW – USER PARAMETER CONFIGURATION

It opens an attribute visualization window for all the user parameters. With double click on the parameter, it is
permitted the configuration of these attributes, which include:

Parameter descriptive text (up to 21 characters);


Unit selection;
Minimum and maximum limit;
Number of decimal positions;
Hexadecimal or normal format;
Reading or writing only;
Modification only with a stopped motor or online;
With or without sign;
Ignores the password (allows modification regardless of the inverter password (P0000)) or normal;
Displays or hides the parameter;
Allows saving the parameter value (retentive), when it is used in some blocks (PLC, Calculations and
Transfers) on power down;
Configuration parameter which allows modification with the motor running.

Those configurations can be transferred to the CFW500 with the “Download” button.

CFW500 | 24
Summary of the WLP Main Functions

5.6 CONSTRUCT – COMPILE

It analyzes the application and generates the compiled code for the specified equipment.

5.7 COMMUNICATION – CONFIGURATION

The Serial port is used for the CFW500.

CFW500 | 25
Summary of the WLP Main Functions

5.8 COMMUNICATION – DOWNLOAD

This command allows downloading the application and/or user parameter configurations to the CFW500.

5.9 COMMUNICATION – UPLOAD

This command makes it possible to upload and open the application installed on the CFW500, provided that the
password is valid.

CFW500 | 26
Summary of the WLP Main Functions

CFW500 | 27
Alarms, Faults and Possble Causes

6 ALARMS, FAULTS AND POSSIBLE CAUSES


Table 6.1: “Alarms”, “Faults” and possible causes

Fault/Alarm Description Possible Causes


A702: It occurs when a movement block (REF Block) is Check if the drive general enabling command
Inverter Disabled active and the drive general enabling command is is active.
not active.

A704: It occurs when 2 or more movement blocks (REF Check the user program logic.
Two Movem. Enabled Block) are enabled simultaneously.

A706: It occurs when a movement block is enabled and Check the programming of the references in
Not Prog. Ref. SPLC the speed reference is not programmed for the the local and/or remote modes (P221 and
SoftPLC P222).

CFW500 | 28

You might also like