0% found this document useful (0 votes)
124 views1 page

CBI245A DC-UPS Battery Charger Data Sheet

CBI245A is an all-in-one device that provides both battery charging and uninterruptible power supply capabilities. It can charge 24V lead-acid or NiCd batteries up to 5A while simultaneously powering a load up to 5A from either the battery or AC input. It features automatic multi-stage charging, short circuit protection, diagnostics for battery status, and can charge flooded, sealed, or gel battery types by jumper settings. The unit has IP20 protection, measures power parameters, and monitors the battery for optimal performance and safety.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
124 views1 page

CBI245A DC-UPS Battery Charger Data Sheet

CBI245A is an all-in-one device that provides both battery charging and uninterruptible power supply capabilities. It can charge 24V lead-acid or NiCd batteries up to 5A while simultaneously powering a load up to 5A from either the battery or AC input. It features automatic multi-stage charging, short circuit protection, diagnostics for battery status, and can charge flooded, sealed, or gel battery types by jumper settings. The unit has IP20 protection, measures power parameters, and monitors the battery for optimal performance and safety.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

CBI245A ALL In One Input: Single-phase 115 – 277 Vac

Output Load: power supply 24 Vdc; 5 A


Output Battery: charging 24 Vdc; 5 A
Suited for the following battery types: Open Lead Acid, Sealed
Lead Acid, lead Gel and Ni-Cd
Automatic diagnostic of battery status. Charging curve IUoU,
constant voltage and constant current Battery Life Test function
(Battery Care)
Switching technology, output voltage 22-28.8Vdc Three charging
levels: Boost, Float and Recovery
Protected against short circuit and inverted polarity
Signal output (contact free) for discharged or damaged battery
Signal output (contact free) for mains or Back-UP
Protection degree IP20 - DIN rail; Space saving

Technical features Frequency 47 ÷ 63 Hz


Thanks to the All In One units (DC-UPS), it will be possible to optimize power management. The Input Current (115 – 230 Vac) 2.8 – 1.3 A
available power is automatically allocated between load and battery, supplying power to the load is Internal fuse (not replaceable) 4A
the first priority of the unit thus it is not necessary to double the power, because also the power External Fuse (recommended) MCB curve B 10 A
going to the battery will go to the load if the load so requires. The maximum available current on the
load output is 2 times the value of the device rated current In. We call “Battery Care” the concept Output Data (internal power supply)
base on algorithms that implement rapid and automatic charging, battery charge optimization during Output Voltage (Vn) / Nominal Current (In) 24 Vdc / 5A
time, flat batteries recovery and real time diagnostic during installation and operation. The Real Time
Output Current In = Iload 5A
Auto-diagnostic system, monitoring battery faults such as, battery Sulfated, elements in short circuit,
accidental reverse polarity connection, disconnection of the battery, they can easily be detected and Efficiency (at 50% of rated current)  90 %
removed by help of Blink Code of Diagnosis Led; during the installation and after sell. The continuous Residual Ripple  60 mVpp
monitoring of battery efficiency, reduces battery damage risk and allows a safe operation in Turn-On delay after applying mains voltage 1 sec. (max)
permanent connection. Each device is suited for all battery types, by means of jumpers it is possible
Start up with Strong Load (capacitive load) Yes, Unlimited
setting predefined curves for Open Lead Acid, Sealed Lead Acid, Gel, Ni-Cd (option). They are
programmed for two charging levels, boost and charge, but they can be changed to single charging Dissipation power load max (W) 17
level by the user. A rugged casing with bracket for DIN rail mounting provides IP20 protection degree. Short-circuit protection) Yes
They are extremely compact and cost-effective. Over Load protection Yes
Over Voltage Output protection Yes (typ. 35 Vdc)
Overheating Thermal protection Yes
Battery Output
Boost charge (25 °C) (at In) 28.8 Vdc
Max.Time Boost–Bulk charge (Typ. at IN) 15 h
Min.Time Boost–Bulk charge (Typ. at IN) 1 min.
Float charge (25 °C) (at In) 27.5 Vdc
Jumper Configuration battery type 2.23;2,25;2,27;2,3;
(V/cell) NiCd:1,4; Li-ion 3.45
Recovery Charge 2 – 16 Vdc
Charging current max Ibatt 5 A  5%
Charging current limiting Iadj 20 ÷ 100 % / Ibat
Reverse battery protection Yes
Sulfated battery check Yes by Jumper
Short circuit Element Detection Yes
Detection of element in short circuit Yes
Norms and Certifications
Quiescent Current max.  100 mA
In Conformity to: EN60950 / UL60950-1 and CSA C22.2 No. 60950-1-07
Charging Curve automatic: IUoU 4 stage
(Information Technology Equipment) – Safety – Part1: General Requirement.
Electrical safety; EN54-4 Fire Detection and fire alarm systems; 89/336/EEC EMC Remote Input Control (RTCONN cable) Boost / Float
Directive; 2014/35/UE (Low Voltage); Safety EN IEC 62368-1: 2014/AC:2015; Load Output
DIN41773 (Charging cycle); Emission: IEC 61000-6-3; Immunity: IEC 61000-6-2. CE. Output voltage Vdc (at In) 22 - 28.8 V (31 Ni-Cd)
Climatic Data Nominal current Iload 1.1 x In A  5%
Ambient temperature (operation) -25 ÷ +70°C Continuous current (Without battery) Iload= In 5A
De Rating Ta > 50°C - 2.5%(In) / °C Continuous current (With battery) Iload= In+ Ibatt 10 A
Ambient temperature Storage -40 ÷ +85°C Max. current Output Load (Main) Iload (4 sec.) 15 A max.
Humidity at 25 °C no condensation 95% to 25°C Max. current Output Load (Back Up)I load (4 sec.) 10 A max.
Altitude: 0 to 2 000m - 0 to 6 560ft No restrictions Start From Battery Without Main (Remote Input Control) RTCONN (cable)
Altitude: 2 000 to 6 000m - 6 560 to 20 000ft De-rating 5°C/1000m Push Button
Cooling Auto convention Time Buffering; min (switch output off without main ∞: standard
input) 5 min.: Require SW
General Data
Threshold alarm Battery almost flat 20 – 21 Vdc batt
Insulation voltage (IN/OUT) 3000 Vac
LVD. (Protections against total Battery discharge) 19 – 20 Vdc batt
Insulation voltage (Input / Earth, PE) 2000 Vac
Insulation voltage (Out Load & Battery / Earth, PE) 500 Vac Signal Output (free switch contacts)
Insulation voltage (Out Load & Battery / Fault System & 500 Vac Main or Backup Input Power Yes
Main or Back Up terminal) Low Battery Yes
Protection Class (EN/IEC 60529) IP20 Fault Battery or system Yes
Reliability: MTBF IEC 61709 > 300.000 h Type of Signal Output Contact
Pollution Degree Environment 2 Dry Contact. Current can be switched (EN60947.4.1): Max: DC1: 30 Vdc 1 A; AC1: 60
Connection Terminal Blocks screw Type 2,5mm(24–14AWG) Vac 1A (Resistive load ) Min: 1mA at 5 Vdc (Min permissive load)
Protection class (PE Connected) I, with PE Fault System / Low Battery C NC NO
Dimensions (w-h-d) 65x115x135 mm Main or Back Up C NC NO
Weight 0.6 kg approx. Signal Input / Output (RJ45)
Input Data Temp. Comp. Battery (with external probe): Aux Out RJ Temp (cable)
Nominal Input Voltage Vac 115 – 230– 277 Remote monitoring LED from Front Device: Aux Out RJ 45 (cable)
Voltage range Vac 90 ÷ 305
Inrush Current (Vn – In nom. Load) I2t  11 A  5 msec.

1Can be adjusted via PC software mode


All specifications are subject to change without notice