0% found this document useful (0 votes)
71 views23 pages

2022-10-28 BA S3C ES Komm en

This document provides installation and operating instructions for a Heat Meter Calculator. It includes information on the calculator's application and components, general technical specifications, installation procedures for temperature sensors and flow meters, and connection details. The calculator measures energy consumption in closed heating, cooling, or heating/cooling systems and must be installed according to relevant verification regulations.

Uploaded by

jan deman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
71 views23 pages

2022-10-28 BA S3C ES Komm en

This document provides installation and operating instructions for a Heat Meter Calculator. It includes information on the calculator's application and components, general technical specifications, installation procedures for temperature sensors and flow meters, and connection details. The calculator measures energy consumption in closed heating, cooling, or heating/cooling systems and must be installed according to relevant verification regulations.

Uploaded by

jan deman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 23

Installation and Operating Instructions

Heat Meter Calculator


Heat/Cooling Meter Calculator
Cooling Meter Calculator

SensoStar C
DE-18-MI004-PTB037 (MID heat)
DE-18-M-PTB-0049 (national German cooling)
CH-T2-18769-00 (national Swiss cooling)

1 Application and Function


The calculator SensoStar C is designed for the measurement of the consumed energy in a closed heating, cooling or
heating/cooling system.

2 Contents of the Package


- Calculator
- Installation kit
- Installation and Operating Instructions
- Operating Instructions „Communication Interfaces S3(C)“ (with meters with an optional interface)
- Declaration of Conformity

3 General Information
- Valid standards for the application of calculators for heat metering: EN 1434, parts 1 – 6; the Measuring
Instruments Directive 2014/32/EU, Annexes I and MI-004; and the relevant national verification
regulations.
- For the selection, installation, commissioning, monitoring and maintenance of the instrument observe the
standard EN 1434 part 6, as well as the verification regulations PTB TR K8 + K9 for Germany (and any
relevant national verification regulations in other countries).
- National regulations for the consumption measurement of cooling must be observed.
- The technical regulations for electrical installations must be observed.
- This product fulfils the requirements of the European Council Directive on Electromagnetic Compatibility
(EMC Directive) 2014/30/EU.
- The identification plate of the instrument and the seals must not be removed or damaged – otherwise the
guarantee and the approved application of the instrument are no longer valid!
- The calculator left the factory in conformance with all applicable safety regulations. All maintenance and
repair work is to be carried out only by qualified and authorized technical personnel.
- Instruments with activated radio function are not allowed on air freight.
- The correct installation point in the system must be chosen: inlet or outlet flow (see item 3.1 ’Pictograms
installation point’).
- To clean the calculator (only if necessary) use a slightly moist cloth.
- To protect against damage and dirt the calculator should only be removed from the packaging directly
before installation.
- All specifications and instructions listed on the data sheet and in the Application Notes must be adhered to.
Further information can be obtained at www.engelmann.de.
- The heat meter has a lithium-metal-battery. Do not open the batteries, do not bring the batteries into
contact with water or expose them to temperatures above 80 °C. Do not charge them or short-circuit them.
- Instruments which have been replaced or exchanged must be disposed of according to relevant
environmental regulations.
- The display is deactivated and can be activated for two minutes by pushing the button.
- Unit of energy and installation point (outlet flow / inlet flow) can be set on location, only once, before
start of operation by pushing the button or alternatively using the „Device Monitor“ software.
- Type and concentration of glycol in the medium of those calculator types designed to be used with glycol
can be set on location at any time using the „Device Monitor“ software (see item 8.1 for details).

Page 1 of 23 Article no.: 1080622201 2022_10_28 Subject to technical change! Errors excepted.
3.1 Pictograms installation point of calculator (in the information loops)
On the right in the calculator display in all information loops you will find one of the following two pictograms. The
pictogram indicates in which pipe the calculator is to be mounted.
Installation in outlet flow

Installation in inlet flow

3.2 Pictograms type of calculator (on type identification label)


Heat meter calculator

Cooling meter calculator

4 Wall Mounting the Calculator


You can open the calculator by pulling the clamping bracket at the upper housing´s leading edge up.
Before mounting, check to make sure that the cable lengths of the instruments to be connected are correct for the
individual installation situation.
The center to center drill hole separation for the direct screw mounting is in the following picture 131 mm.

With commonly available Direct screw mounting


mounting rail

5 Connecting the Components


Important: First mount the temperature sensors and then connect the flow meter to the calculator. This way
unnecessary error messages can be avoided.

At delivery, the display shows „H 05“ until temperature sensors have been attached. This message disappears as
soon as temperature sensors have been connected and the first temperature measurement is carried out (every 15
minutes without flow).
The calculator connections have been designed to meet the valid standard EN1434-2. All terminal strips have been
labelled according to this standard.
The terminal strips are located under the cover of the calculator housing.

5.1 Mounting the temperature sensors


Please note the following points:
- The temperature sensors must have the type of Pt suitable for the calculator (Pt 500). The calculator
identifies the temperature sensors automatically and shows the type of Pt in loop 2.
- The temperature sensors (up to DN 100) must be installed against the flow direction.
- The temperature sensors are not to be installed within the influence of other sources of heat.
- The temperature sensor cables must not be kinked, lengthened or shortened.

Page 2 of 23 Article no.: 1080622201 2022_10_28 Subject to technical change! Errors excepted.
- Sensor cables that are too long should not be rolled up tightly into an ‘air-core coil’. The cables should
either be laid out disordered, or rolled up loosely into a wide coil which can be turned and tied into an ‘8’.

Mounting
- Loosen the two cable glands without blind plugs and glide them over the sensor cables.
- Feed the temperature sensors through the appropriate openings of the cable glands into the terminal box.
- Clamp the wires (see identification label temperature sensors) as shown in the illustration:
The inlet flow temperature sensor must always be connected to clamp 5 and 6 (inlet).
The outlet flow temperature sensor must always be connected to clamp 7 and 8 (outlet).
The color of the wires does not matter.

- Check that the connections are tight.


- Screw the cable glands tight by hand.

5.2 Mounting the flow meter


The pulse output of the flow meter to be connected to the calculator must be identical to the calculator input pulse
value. Check the technical data of the flow meter and compare it to the specifications on the calculator.

Mounting
- Loosen the middle cable gland and glide it over the flow meter cable.
- Remove the blind plug in the cable gland opening. Feed the pulse cable of the flow meter through the
opening into the terminal box.
- Clamp 10 and 11 are used for the connection to the flow meter.
- Clamp on the wires as shown in the illustration.
Note: For flow meters with open collector connections (electronic outputs) make sure the polarity is correct.

- Check that the connections are tight.


- Screw the cable gland tight by hand.

Please check the unused cable glands to make sure that the necessary blind plugs are inserted and then tighten
the cable glands by hand.

Page 3 of 23 Article no.: 1080622201 2022_10_28 Subject to technical change! Errors excepted.
5.2.1 Special features when connecting to a Diehl VMT „Sharky FS 473“
For the correct connection of the cables, please note the polarity described in the following drawing:

white  Clamp 10

Useful pulse
brown
 Clamp 11

Important note: The colored marking of the cables corresponds to the scheme shown above.
The white cable (+) is connected to clamp 10, the brown cable (-) to clamp 11.

5.2.2 Calculators with TX version


TX version instruments can be recognized by a special display as long as the pulse value has not been set yet:

Important note: The pulse value will be set permanently after the first input pulses and cannot be changed
afterwards. Pay special attention that the flow meter does not register a flow before the correct pulse value has
been chosen (factory setting 1 l/pulse).

Set up of pulse value


If the pulse value has not yet been set, follow these steps:
- Choose the desired pulse value by pressing the push-button briefly.
- Confirm the selected pulse value by pressing the push-button longer than 4 seconds. After this the pulse
value cannot be changed any longer.
The display format is automatically determined by the pulse value that has been set:
Pulse value Display format Display format Display format Display format
[l/pulse] energy volume flow power
1 0 kWh 0,000 MWh 0,000 GJ 0,000 m³ 0,000 m³/h 0,000 kW
2,5 - 0,000 MWh 0,000 GJ 0,000 m³ 0,000 m³/h 0,000 kW
10 - 0,00 MWh 0,00 GJ 0,00 m³ 0,00 m³/h 0,00 kW

Page 4 of 23 Article no.: 1080622201 2022_10_28 Subject to technical change! Errors excepted.
25 - 0,00 MWh 0,00 GJ 0,00 m³ 0,00 m³/h 0,00 kW
100 - 0,0 MWh 0,0 GJ 0,0 m³ 0,0 m³/h 0,0 kW
250 - 0,0 MWh 0,0 GJ 0,0 m³ 0,0 m³/h 0,0 kW
1000 - 0 MWh 0 GJ 0 m³ 0 m³/h 0 kW
2500 - 0 MWh 0 GJ 0 m³ 0 m³/h 0 kW

6 Start of Operation
- Slowly open the shut-off valves.
Check the following points:
- Is the flow meter of the right size?
- Does the directional arrow on the flow meter match the actual direction of flow?
- Check that there are no leaks.
- Is a flow volume displayed?
- Are all shut-off valves open?
- Is the heating (heating/cooling) system clear (dirt filters not clogged)?
- Is a plausible temperature difference displayed?
When the components are functioning properly, attach the seals to the temperature sensors and the flow meter.
Protect the calculator against unauthorized opening using the numbered adhesive seal enclosed. The added bar
code label can be used for the purpose of documentation.

7 Interfaces and Options


7.1 Optical (infrared) interface
For communication with the optical interface an optocoupler and the “Device Monitor” software are necessary.
The optocoupler and “Device Monitor” are available as accessory equipment.
The optical infrared interface will be activated by automatically sending a header (according to EN 13757-3). Baud
rate: 2400 baud. Then you can communicate with the calculator for 4 seconds. After every valid communication the
calculator is open for another 4 seconds. Afterwards the display is deactivated.
The number of read-outs per day via the optical interface is limited. During daily read-out at least 4
communications are possible. If read-outs are carried out more rarely, the possible number of communications will
increase.

7.2 Retrofitting with an additional communication interface


To our calculator further communication interfaces can be added later. You will find the description of our optional
interfaces in the operating instructions „Communication Interfaces S3(C)“.

During installation of the retrofitting module observe the ESD requirements according to EN 61340-5-1.
This means that on location an antistatic wrist strap with an integrated 1 MΩ resistor has to be used which must be
connected to a proper spot: This is either a grounded pipe or – only with an appropriate adapter! – a Schuko plug
grounding socket. The antistatic wrist strap must be worn tightly on the skin of the wrist.

Open the calculator by pulling the clamping bracket at the upper housing´s leading edge up.
Plug the interface module on the right side of the PC board. If there are module cables you have to loosen the
needed number of cable glands and to glide them over the cables. Remove the blind plugs from the cable gland
openings and feed the cables into the calculator.
Protect the calculator against unauthorized opening using one of the numbered adhesive seals enclosed to the
modules. The added bar code label can be used for the purpose of documentation.

7.3 Exchanging the battery


The calculator´s battery is easy to exchange by authorized technical personnel (our replacements only). Replaced
batteries must be disposed of according to relevant environmental regulations.
Open the calculator by pulling the clamping bracket at the upper housing´s leading edge up. Afterwards protect the
calculator against unauthorized opening using one of the numbered adhesive seals enclosed to the batteries (stick
it upon the seal destroyed). The added bar code label can be used for the purpose of documentation.

Page 5 of 23 Article no.: 1080622201 2022_10_28 Subject to technical change! Errors excepted.
7.4 Mounting a power pack
If an external power supply is needed, only the power pack designed for our calculator may be used.
To connect it to the calculator, please open the calculator. First remove the battery from the calculator and plug it
into the battery connector in the power pack. Protect the power pack against unauthorized opening using one of
the numbered adhesive seals enclosed. The added bar code label can be used for the purpose of documentation.
(The battery is a backup in case of a power outage.)
Remove the left blind grommet in the calculator housing and feed the power pack cable (A) through the cable
feedthrough. Press the cable grommet into the cable feedthrough. Connect the black service plug with the contact
fingers on the left hand side of the calculator’s PC board under the display. Plug the white connector into the
battery connector on the PC board.
Only authorized technical personnel may connect the power pack to 230 V / 24 V and check it.
When the calculator detects external power supply the pictogram of a mains plug appears in the display.
Protect the calculator against unauthorized opening using one of the numbered adhesive seals enclosed to the
power pack. The added bar code label can be used for the purpose of documentation.

A
Page 6 of 23 Article no.: 1080622201 2022_10_28 Subject to technical change! Errors excepted.
8 Display
The calculator has a liquid crystal display with 8 digits and special characters. The values that can be shown are
divided into five display loops. All data is retrieved using the push-button next to the display.
At the start you are automatically in the main loop (1st level). By pressing the push-button longer than 4 seconds
you change to the next display loop. Keep the push-button pressed until you reach the desired information loop. By
pressing the push-button briefly each time you can scan all the information within a loop.
After 2 minutes of non-use of the push-button, the display will automatically be deactivated.

Level 1 / Main Loop:

2) Segment test on / off 4) Total flow volume in m³


(all segments triggered
simultaneously)

1) Total heat energy


since start of operation
(standard display);
alternating display:
total cooling energy (for
heat/cooling calculators);
information message (if an
error was detected)
3) Last reading date
alternating with
heat energy
(cooling energy),
volume,
value tariff register 1,
value tariff register 2
at last reading date.1)
(If the calculator has 3
pulse inputs, their values
follow.2))

5) Current date 6) Information message 7) Tariff register 1: 8) Tariff register 2:


alternating with (alternating binary and value alternating with value alternating with
time hexadecimal display) tariff register no. and tariff register no. and
criteria criteria

9) Pulse counter 1: 10) Pulse counter 2: 11) Pulse counter 3:


pulse value pulse value pulse value
alternating with alternating with alternating with
reading2) reading2) reading2)

Page 7 of 23 Article no.: 1080622201 2022_10_28 Subject to technical change! Errors excepted.
1)
Up to the end of the month / the 15th of the month (for the semimonthly values) the consumption and date will be
shown as 0.
2)
Three pulse inputs are an option. They can be set using the software „Device Monitor“.

Level 2 / Technician’s Loop:

1) Current power in kW 2) Current flow in m³/h 3) Inlet flow temperature 4) Outlet flow
in °C temperature in °C

5) Temperature difference 6) Before start of 7) M-bus address 8) Serial number


in K. operation:
(Cooling energy: Value is days since manufacture
displayed negative.)

After start of operation:


days since manufacture
alternating with
days of operation after
reaching an energy value >
10 kWh

9) Firmware version 10) Type of Pt 11) Pulse value

Level 3 / Statistics Loop:


1) – 30) Semimonthly pulse inputs, their values
values: follow.2))
date alternating with
heat energy,
cooling energy,
volume,
value tariff register 1,
value tariff register 2.1)
(If the calculator has 3

Level 4 / Maximum Values Loop:

1) Maximum power 3) Maximum inlet flow 4) Maximum outlet flow


2) Maximum flow
alternating with date temperature temperature
alternating with date
and time alternating with date alternating with date
and time
and time and time

Page 8 of 23 Article no.: 1080622201 2022_10_28 Subject to technical change! Errors excepted.
5) Maximum temperature
difference
alternating with date
and time

Level 5 / Parametrizing Loop:

1) Parametrizing 2) Parametrizing
„unit of energy“ „installation point“

8.1 Parametrizing loop


a) The following characteristics of the calculators can be set on location, only once, by pushing the button or
alternatively using the „Device Monitor“ software:
- unit of energy (kWh (only with 1 liter / pulse); MWh; GJ)
- installation point (inlet flow; outlet flow).

These parametrizing options are only available when the amount of energy is still <= 10 kWh. Make sure that
these characteristics are set as needed before starting up the system.
Setup by pushing the button: In order to start the editing mode for parametrizing you must select the respective
item in the parametrizing loop and then push the button once again for 2-3 seconds. As an aid, after 2 seconds the
„editing pen“ will be displayed bottom left in the LCD (see below picture). As soon as it appears you have to let go
of the button. Then the current display will start blinking.

By pressing the push-button briefly you can switch to the next option. By pressing the push-button longer the
currently displayed option will be set. If no option is chosen there will be no change and as soon as the LCD goes
out the edit mode will end automatically.

b) The following characteristic of those calculator types designed to be used with glycol can be set on location at
any time using the „Device Monitor“ software:
- type and concentration of glycol in the medium (propylene glycol; ethylene glycol; 20 %; 30 %; 40 %; 50%).

8.2 Detection of flow


As long as the calculator detects some flow the following pictogram will be displayed bottom right in the LCD:
flow detected

8.3 Volume pulses


When a volume pulse is received via the calculator input the following pictogram will be displayed bottom right in
the LCD for 1 second:
volume pulse

Page 9 of 23 Article no.: 1080622201 2022_10_28 Subject to technical change! Errors excepted.
9 Application Conditions
Calculator
Temperature range medium °C 0 – 150
heat
Temperature range medium °C 0 – 50
cooling
Mechanical class M2
Electromagnetic class E2
Protection class IP54
Ambient temperature in the °C 5 – 55 at 95 % relative humidity
field
Transport temperature °C -25 – 70 (for maximal 168 h)
Storage temperature °C -25 – 55
Pulse input interface microcontroller CMOS input class IB according to EN 1434-2: 2015
Pulse values standard see type identification label
TX versions adjustable pulse values will be shown in the display: 1; 2,5; 10; 25;
100; 250; 1000; 2500

Flow meter requirements


Pulse output device class OA (reed contact) according to EN 1434-2: 2015;
class OC (open collector) according to EN 1434-2: 2015
Point of installation outlet flow (standard) / inlet flow;
calculator can be set on location, only once, before start of
operation by pushing the button or alternatively using the „Device
Monitor“ software
Maximum input frequency Hz 10
Pulse length ms ≥ 25
Pulse pause ms ≥ 50

Temperature sensor requirements


Platinum precision resistor Pt 500
Cable length (unshielded) m up to 10 in 2-wire technique
Installation direct mounted; in temperature pockets
Application heat metering EU (MID) identification on the temperature sensors
Application cooling metering national approval as a temperature sensor for cooling meters*)
Application heat/cooling metering EU (MID) identification and separate national approval as a
temperature sensor for cooling meters*)
*) Requirements in countries other than Germany may be different.

10 Information Messages
When the instrument has detected an information message, the message symbol is displayed:
The specific message can be found at menu item 6 ‘Information message’ in level 1 / main loop (see section 8,
Display). The message code is displayed alternately in binary and hexadecimal form.
The instrument recognizes seven message causes, which can also occur in combination with each other.

Hexadecimal display Description Binary display


H 80 Low battery 1 at first place
H 40 Instrument has been reset 1 at second place
H 20 Electronics defective 1 at third place
H 08 Temperature sensor outlet flow short circuit 1 at fifth place
H 04 Temperature sensor outlet flow cable break 1 at sixth place
H 02 Temperature sensor inlet flow short circuit 1 at seventh place
H 01 Temperature sensor inlet flow cable break 1 at eighth place

Page 10 of 23 Article no.: 1080622201 2022_10_28 Subject to technical change! Errors excepted.
Example: Temperature sensor inlet cable break
Message

outlet flow short circuit

outlet flow cable break

inlet flow short circuit

inlet flow cable break


(Bit will not be used.)
Electronics defective

Temperature sensor

Temperature sensor

Temperature sensor

Temperature sensor
Low battery

Bit 7 Reset
6 5 4 3 2 1 0
Alternating hexadecimal
Display location 1 2 3 4 5 6 7 8 message displayed (LCD)

Alternating binary
message
displayed (LCD)

When a message appears in the standard display (total heat energy), with the exception of the messages
- Low battery (H 80)
- Reset (H 40),
the instrument must be exchanged and sent to the supplier for examination.

10.1 Message description


Display Message Effect Possible cause
H 80 Low battery No influence on the Adverse environmental
calculation conditions; long operating time
H 40 Reset No influence on the EMC, electromagnetic
calculation interference
H 20 Electronics defective No energy calculations are Defective component, defect on
carried out. The register for the calculator PC board
energy is not being updated.
H 08 / H 04 / Temperature sensor outlet As for message „Electronics Sensor cable damaged
H 02 / H 01 or inlet flow: short circuit / defective“
cable break

11 Manufacturer
Engelmann Sensor GmbH
Rudolf-Diesel-Str. 24-28
69168 Wiesloch-Baiertal
Germany

Tel: +49 (0)6222-9800-0


Fax:+49 (0)6222-9800-50
E-Mail: [email protected]
www.engelmann.de

Page 11 of 23 Article no.: 1080622201 2022_10_28 Subject to technical change! Errors excepted.
Operating Instructions

Communication Interfaces S3(C)

1 Interfaces and Options


1.1 Optical (infrared) interface
For communication with the optical interface an optocoupler and the “Device Monitor” software are necessary.
The optocoupler and “Device Monitor” are available as accessory equipment.
The optical infrared interface will be activated by automatically sending a header (according to EN 13757-3). Baud
rate: 2400 baud.
Then you can communicate with the meter for 4 seconds. After every valid communication the meter is open for
another 4 seconds. Afterwards the display is deactivated.
The number of read-outs per day via the optical interface is limited. During daily read-out at least 4
communications are possible. If read-outs are carried out more rarely, the possible number of communications will
increase.

1.2 M-Bus (optional)


The M-Bus is a galvanically isolated interface for the transmission of meter data
(absolute values).

General information about the M-Bus interface:


It is important to note that the acknowledged state of the art technology rules
and the relevant legal restraints (international and local; see “Relevant Norms /
Standards / Literature M-Bus”) are to be observed.
The installation has to be performed by authorized, skilled persons.
If the regulations and the information in the installation and operating instruction
manuals are not strictly followed, or if the installation is shown to be faulty, any
resulting expenses will be charged to the company responsible for the installation.

Recommended type of cable: Telephone cable J-Y(ST)Y 2x2x0.8mm².


It is important to make sure that the topology of the M-Bus network (cable lengths and cross-sections) is suitable
for the baud rate (2400 Bd) of the end instruments.

1.2.1 Relevant norms / standards / literature M-Bus


IEC 60364-4-41 (2005-12) Low-voltage electrical installations - Part 4-41: Protection for safety -
Protection against electric shock
IEC 60364-4-44 (2007-08) Low-voltage electrical installations - Part 4-44: Protection for safety -
Protection against voltage disturbances and electromagnetic disturbances
IEC 60364-5-51 (2005-04) Electrical installations of buildings - Part 5-51: Selection and erection of
electrical equipment - Common rules
IEC 60364-5-54 (2011-03) Low-voltage electrical installations - Part 5-54: Selection and erection of
electrical equipment - Earthing arrangements and protective conductors
EN 50310 (2011) Application of equipotential bonding and earthing in buildings with
information technology equipment
EN 13757-1_2015, -2_2004, Communication systems for meters and remote reading of meters
-3_2013
The M-Bus A Documentation, Version 4.8, M-Bus User group

1.2.2 Additional technical specifications


The installation has to fulfill the requirements of the relevant norms / standards / literature (see paragraph 2.1) and
the specifications as follows:
Maximum voltage M-Bus 42 V
Minimum voltage M-Bus 24 V
Page 12 of 23 Article no.: 1080622201 2022_10_28 Subject to technical change! Errors excepted.
Maximum ripple voltage 200 mV; EN 13757-2_2004; 4.3.3.6
Maximum voltage potential 2V
differences

1.2.3 Technical data M-Bus


Primary address 0 (factory setting); 1 - 250 (configurable)
Baud rate 2400; 300
Connecting cable length 1m
Number of possible read-outs unlimited
Refresh of data 120 s; using a power pack: 2 s

1.3 Modbus RTU (optional)


The Modbus RTU Module is a galvanically isolated interface for the transmission of meter data (absolute values). It
is designed for use with S3 heat meter and S3C calculator to connect them to Modbus RTU network using EIA-485
channel.

1.3.1 Technical data Modbus


Connector A PowerSupply 12 V – 24V DC ± 10% (SELV power supply only)
Connector B Modbus Network
Maximum power consumption 500 mW
Communication protocol Modbus RTU
Channel EIA-485 (galvanically isolated)
Baud rate 1200, 2400, 4800, 9600, 14400, 19200, 38400, 56000, 57600, 115200

1.3.2 Default factory settings


Communication parameters 9600 bps, 8N1 data format (8 data bits, none parity, 1 stop bit)
Update Rate Data from Meter 600 s
Modbus Slave ID* 1
Automatic Slave ID** 0 (deactivated)
* Acceptable values: 1 … 247
** If the automatic Slave ID is activated (set to = 1), the M-Bus address which is set in the meter is used for
communication.

1.4 Wireless Interfaces


Engelmann offers the following radio interfaces:
- wireless M-Bus interface EN 13757-3, -4 (see chapter 1.4.1)
- LoRaWAN communication interface (see chapter 1.4.2)

General information about the radio interface:


Installation of radio components between or behind heating pipes, or the presence of other bulky metallic
obstacles directly over or in front of the housing must be avoided.
The transmission quality (range, telegram processing) of radio components can be negatively influenced by
instruments or equipment with electromagnetic emissions, such as telephones (particularly LTE mobile radio
standard), wi-fi routers, baby monitors, remote control units, electric motors, etc.
In addition, the construction of the building has a strong influence on the transmission range and coverage.
Furthermore, when using installation boxes (substations) they must be equipped with non-metallic covers or doors.

The factory-setting of the clock in the meter is standard (winter) Central European Time (GMT +1). There is no
automatic changeover to daylight savings (summer) time.

The radio function is deactivated upon delivery (factory-setting). See chapter 1.4.1.3 & 1.4.2.3 regarding the
activation of the radio interface.

Page 13 of 23 Article no.: 1080622201 2022_10_28 Subject to technical change! Errors excepted.
1.4.1 Radio interface wireless M-Bus EN 13757-3, -4 (optional)
The radio interface transmits meter data (absolute values).

1.4.1.1 Technical data radio


Frequency 868 MHz
Transmission power up to 12 dBm
Protocol wireless M-Bus based on EN 13757-3, -4
Selectable modes S1 / T1 (Frame Format A)
C1 (Frame Format B)
Telegrams - short telegram in conformity to AMR (OMS-Spec_Vol2_Primary_v301 and _v402):
energy (heat/cooling energy, pulse input 1 to pulse input 3), total volume, flow,
power, information message, outlet flow temperature, temperature difference
- long telegram for walk-by read-out: energy (heat/cooling energy, pulse input 1 to
pulse input 3), total volume, information message, 15 monthly or 30 semimonthly
values (compact mode)
Encryption AES: Advanced Encryption Standard; key length: 128 bits

1.4.1.2 Radio configuration


Parameter Possible settings
Mode S1 / T1 / C1; unidirectional
Transmission period 00:00 - 24:00; any time period in the day
Transmission interval 10 seconds - 240 minutes
Weekdays Monday – Sunday (any weekday)
Weeks in a month 1 – 4 (4: uninterrupted, incl. a possible 5th week)
Months 1 - 12
Radio activation date 01.01. - 31.12. (day. month)
AES-128-Encryption - not encrypted;
- encrypted according to MODE 5 or MODE 7:
- Master Key
- key per instrument
Type of telegram - short telegram in conformity to AMR (OMS-Spec_Vol2_Primary_v301 and _v402)
- long telegram for walk-by read-out

1.4.1.3 Activation of the radio interface


The radio interface leaves the factory deactivated. It can be activated as follows:

a) The radio function can be activated by pressing the push-button.


Press the push-button until you change to the display loop “6” (module loop). Then change with a brief keystroke
to the 2nd item “rad(io) off“ (see picture).
In order to start the editing mode you afterwards must press the push-button
once again for 2-3 seconds. As an aid, after 2 seconds the “editing pen“ will be
displayed bottom left in the LCD. As soon as it appears you have to let go of
the button. Now the display shows “rad(io) on“ and in all display loops a black
triangle (see picture).

b) The radio function can also be activated using the software “Device Monitor”.

Page 14 of 23 Article no.: 1080622201 2022_10_28 Subject to technical change! Errors excepted.
This software can be ordered separately as an option.

The radio function can only be deactivated using the software “Device Monitor”.

After activation of the radio function or modification of the radio parameters the meter remains in installation
mode for 60 minutes. During this time he sends telegrams in a 36-seconds-interval.

If using the compact mode, after activation the meter transmits during installation mode format telegrams and
compact telegrams alternately.
During installation mode at least one meter of the version being installed (inlet or outlet flow, heat or heat/cooling,
pulse inputs, display units) must be read out with the Engelmann “Read-out Software walk-by”. The format of the
telegram will be stored locally in the PC in an .xml file.
After completion of the installation mode only compact telegrams will be transmitted.

1.4.1.4 Later activation of the radio encryption


The AES encryption can also be activated later. It can be activated as follows:
a) The encryption can be activated by pressing the push-button.
Press the push-button until you change to the display loop “6” (module loop). Then
change with a brief keystroke to the 3rd item “AES off“ (see picture).
In order to start the editing mode you afterwards must press the push-button
once again for 2-3 seconds. As an aid, after 2 seconds the “editing pen“ will be
displayed bottom left in the LCD. As soon as it appears you have to let go of
the button. Now the display shows “AES on“ (see picture).

b) The encryption can also be activated using the software “Device Monitor”. This software can be ordered
separately as an option.
The encryption can only be deactivated using the software “Device Monitor”.

1.4.2 LoRaWAN interface


The LoRaWAN interface transmits meter data (absolute values).

1.4.2.1 Technical data

Radio characteristics
Frequency 868 MHz Frequency 868 MHz
Output power 14 dBm Output power 14 dBm
Receiver sensitivity -135 dBm Receiver sensitivity -135 dBm

LoRaWAN characteristics
Device class Class A, Bi-directional
LoRa version 1.0.2 Rev B
Activation OTAA* or ABP*
Data rate DR0-DR5 (250 bit/s-5470 bit/s)
*OTAA = Over-the-air activation
** ABP = Activation by personalization

Page 15 of 23 Article no.: 1080622201 2022_10_28 Subject to technical change! Errors excepted.
1.4.2.2 LoRa module configuration
The module can be configurated by using the Device Monitors or the OTC App.
Parameter Possible settings Factory setting
Power mode Active Inactive
Inactive
Configuration Lock Open Open
Locked
Synchronize meter time on off
off
Activation type OTAA OTAA
ABP
EcoMode off EcoMode 10 years
6 years
10 years
Transmit interval *[Min.] 5 … 1440 60
Message format** Standard Standard
Engelmann
Compact
JSON
Scheduled - daily redundant
Scheduled - extended
Combined heat/cooling
Pulse input selection Choice between 0-3 pulse inputs 0

* The actual transmission interval depends on the type of telegram and the current data rate. The transmission
interval is adjusted accordingly in order to guarantee the set battery life (Eco Mode 10 or 6 years). You can find
more information in the „Manual LoRa Module“.
** For pulse input option, the telegram type „Engelmann“ must be selected.

1.4.2.3 Activation of the radio interface


The radio interface is deactivated by default and can be activated in one of the three following ways:

a) NTC interface - via Elvaco OTC App; further information is available in the operating instructions of the Elvaco
OTC App: https://www.elvaco.se/Image/GetDocument/en/269/elvaco-otc-app-manual-english.pdf
b) Optical interface - via the Engelmann configuration software Device Monitor – from version 2.22; further
information is available in the operating instructions of the Device Monitor. The software can be ordered
separately.
c) Via the heat meter menu;
Press and hold the button to switch to display loop "6" (= module loop; see Chapter
3 Display in the Module Loop (Optional)). Then switch to the second loop with a
short press of the button – 6-02 – „EnA oFF“ (see image).
In order to start the edit mode, you must then press the key
press once more for 2-3 seconds. As an aid, an “editing pen” symbol appears in the
lower left corner of the LCD after 2 seconds. As soon as it can be seen, you must
release the button. The display now shows „EnA on“ and a black triangle in all
display loops (see image).

1.4.2.3 Connection to the LoRaWAN Network


To check whether the meter has already connected to the LoRaWAN network, change
from loop 6-02 to loop 6-03 by briefly pressing the button. As long as the meter is
searching for the LoRaWAN network, „LorA Pen“ appears in the LCD; the time between
each connection attempt is gradually reduced to at least once a day.

Page 16 of 23 Article no.: 1080622201 2022_10_28 Subject to technical change! Errors excepted.
As soon as the meter has connected to the LoRaWAN network, “LorA Con” appears in
the LCD.

1.5 Three additional pulse inputs (optional; only in conjunction with M-Bus or radio)
With this option, additional instruments with pulse outputs can be read out via optical interface, M-Bus or radio.
General information about pulse inputs:
It is important to note that the acknowledged state of the art technology rules and the relevant legal restraints
(international and local; see “Relevant Norms / Standards / Literature Pulse Inputs”) are to be observed.
The installation has to be performed by authorized, skilled persons.
If the regulations and the information in the installation and operating instruction manuals are not strictly followed,
or if the installation is shown to be faulty, any resulting expenses will be charged to the company responsible for
the installation.

1.5.1 Relevant norms / standards / literature pulse inputs


IEC 60364-4-41 (2005-12) Low-voltage electrical installations – Part 4-41: Protection for safety – Protection
against electric shock
IEC 60364-4-44 (2007-08) Low-voltage electrical installations – Part 4-44: Protection for safety – Protection
against voltage disturbances and electromagnetic disturbances
IEC 60364-5-51 (2005-04) Electrical installations of buildings – Part 5-51: Selection and erection of
electrical equipment – Common rules
IEC 60364-5-54 (2011-03) Low-voltage electrical installations – Part 5-54: Selection and erection of
electrical equipment – Earthing arrangements and protective conductors
EN 50310 (2011) Application of equipotential bonding and earthing in buildings with information
technology equipment
EN 1434-2 (2016) Heat Meters – Part 2: Constructional requirements

1.5.2 Technical data pulse inputs


Pulse input class IB according to EN 1434-2:2016
Connecting cable length 1m
Voltage supply + 3 V DC
Source current = 1,5 µA
High level input threshold U≥2V
Low level input threshold U ≤ 0,5 V
Pull-up resistor 2 MΩ
Pulse length ≥ 100 ms
Pulse frequency ≤ 5 Hz

1.5.3 Possible combinations of the different input (class IB) and output (class OA) devices
Class IA Class IB Class IC Class ID Class IE
Class OA yes yes no yes no
Class OB yes no no yes yes
Class OC no yes yes no no
Class OD no no yes no no
Class OE no no no no yes

1.5.4 Setting up the three additional pulse inputs


The optional pulse inputs 1 + 2 + 3 for external meters can be set up using the “Device Monitor” configuration
software. You can configure serial number, manufacturer, version (0 … 255), medium code, input pulse value, unit
and starting value of the external meters.

Page 17 of 23 Article no.: 1080622201 2022_10_28 Subject to technical change! Errors excepted.
1.5.5 Set-up possibilities
Pulse value Units
1 liters / kWh / pulse without unit
2,5 liters / kWh / pulse without unit
10 liters / kWh / pulse without unit
25 liters / kWh / pulse without unit
100 liters / kWh / pulse without unit
250 liters / kWh / pulse without unit
1000 liters / kWh / pulse without unit

Installation notes for pulse inputs:


It is important that the pulse cables not be affected by (or exposed to) an external voltage!
Check the polarity of pulse generators with “open collector“ outputs.
The cable wires must not touch each other during installation, otherwise pulses will be counted in the instrument.
When setting up the meter it may be necessary to adjust the meter reading of the instruments connected and the
pulse value using the “Device Monitor” software.

For transmitting the values of the pulse inputs via radio, transmission must be set using the “Device Monitor”
software, if the meters were not already ordered with the transmission of these values set.
Select the menu item „Parameterization of the module“ in the software. Set the radio transmission in the menu
item „Transmission of values for the pulse inputs“. (The transmission of these values via M-Bus is always set in the
factory setting.)

1.5.6 Pin assignments 6-wire cable


Color Connection
Pink IE1+
Grey IE1┴
Yellow IE2+
Green IE2┴
Brown IE3+
White IE3┴

1.6 One potential-free pulse output (optional)


Important note: This module can be used for the compact heat meter S3 from
firmware version 1.03 on, for the calculator S3C from firmware version 1.00 on.
The potential-free pulse output provides counting pulses of the meter.
The pulse output closes corresponding to the pulse value, see item „pulse value
pulse output 1“ in display loop “6” (module loop).

Heat meter Cooling meter Heat/cooling meter


Possible settings heat energy cooling energy heat energy
pulse output 1 (factory setting) (factory setting) (factory setting)
or volume or volume or volume

From firmware version 1.03 (S3) and 1.00 (S3C) on the meter recognizes nominal size and unit of energy and
autonomously sets the pulse values for energy and volume according to the following notes.

Page 18 of 23 Article no.: 1080622201 2022_10_28 Subject to technical change! Errors excepted.
S3 - pulse output for energy:
Display shows Display shows Display shows Display shows
kWh / MWh Gcal GJ MMBTU
qp 0,6 m3/h 1 kWh/pulse 1 Mcal/pulse 10 MJ/pulse 10 MMBTU/pulse
qp 1,5 m3/h 1 kWh/pulse 1 Mcal/pulse 10 MJ/pulse 10 MMBTU/pulse
qp 2,5 m3/h 1 kWh/pulse 1 Mcal/pulse 10 MJ/pulse 10 MMBTU/pulse
qp 3,5 m3/h 10 kWh/pulse 10 Mcal/pulse 10 MJ/pulse 10 MMBTU/pulse
qp 6 m3/h 10 kWh/pulse 10 Mcal/pulse 10 MJ/pulse 10 MMBTU/pulse

qp 10 m3/h 10 kWh/pulse 10 Mcal/pulse 10 MJ/pulse 10 MMBTU/pulse

S3 - pulse output for volume:


The pulse value for volume is always determined as follows: Display shows m³ -> pulse value: 100 l/pulse
(0,1 m³/pulse).

S3C - pulse output for energy:


The pulse value for energy is always determined by the second-to-last place of the energy display.
Examples:
Display: 0 kWh -> pulse value: 10 kWh/pulse
Display: 0,000 MWh -> pulse value: 0,01 MWh/pulse
Display: 0,000 GJ -> pulse value: 0,01 GJ/pulse.

S3C - pulse output for volume:


The pulse value for volume is always determined by the third-to-last place of the volume display. Examples:
Display: 0,000 m³ -> pulse value: 100 l/pulse (0,1 m³/pulse)
Display: 0 m³ -> pulse value: 100 m³/pulse.

1.6.1 Pin assignments 4-wire cable


Color Connection
Yellow IA1
Green IA1
Brown / White not reserved

1.6.2 Technical data for one pulse output and two pulse outputs
Pulse outputs class OA (electronic switch) according to EN 1434-2:2016
Connecting cable length 1m
Switching voltage, maximum 30 V
Switching current, maximum 27 mA
Contact resistance (on) max. 74 Ω
Contact resistance (off) min. 6 MΩ
Closure time 100 ms
Interval between pulses 100 ms

1.7 Two potential-free pulse outputs (optional)


The potential-free pulse outputs provide counting pulses of the meter.
The pulse outputs close corresponding to the pulse value, see items „pulse value pulse
output 1“ and „pulse value pulse output 2“ in display loop “6” (module loop).

Heat meter Cooling meter Heat/cooling meter


Pulse output 1 heat energy cooling energy heat energy
Pulse output 2 volume volume cooling energy

Page 19 of 23 Article no.: 1080622201 2022_10_28 Subject to technical change! Errors excepted.
Pulse outputs for energy:
The pulse value for energy is always determined by the last place of the energy display.
Examples:
Display: 0 kWh -> pulse value: 1 kWh/pulse
Display: 0,000 MWh -> pulse value: 0,001 MWh/pulse
Display: 0,000 GJ -> pulse value: 0,001 GJ/pulse

Pulse outputs for volume:


The pulse value for volume is always determined by the second-to-last place of the volume display.
Example:
Display: 0,000 m³ -> pulse value: 10 l/pulse (0,01 m³/pulse)

1.7.1 Pin assignments 4-wire cable


Color Connection
Yellow IA1
Green IA1
Brown IA2
White IA2

2 Retrofitting with an Additional Communication Interface


During installation of the retrofitting module observe the ESD requirements according to EN 61340-5-1.
This means that on location an antistatic wrist strap with an integrated 1 MΩ resistor has to be used which must be
connected to a proper spot: This is either a grounded pipe or – only with an appropriate adapter! – a Schuko plug
grounding socket. The antistatic wrist strap must be worn tightly on the skin of the wrist.

2.1 Retrofitting S3 with an additional communication interface (optional)


We also offer a retrofittable meter to which communication interfaces can be added later.

To retrofit such a meter with an additional communication interface the calculator´s adhesive seal has to be
destroyed and the device´s calculator to be opened. Use a screwdriver with a wide tip (4 - 5 mm) and carefully
press in the two round predetermined breaking points above the cable feedthroughs (see picture 1).

Then insert the screwdriver into one of the two openings at an angle of approx. 45° and carefully lift the handle up
to approx. 90° (see picture 2). The upper housing piece of the calculator is then no longer latched on this side.
Repeat this with the other opening. Now the upper housing piece can be taken off.

Page 20 of 23 Article no.: 1080622201 2022_10_28 Subject to technical change! Errors excepted.
Plug the interface module on the right side of the PC board (see picture 3). The cables are to be fed through the
rightmost cable feedthroughs into the calculator after removing the blind grommets. Close the calculator.
Protect the calculator against unauthorized opening using one of the numbered adhesive seals enclosed to the
modules (stick it upon the seal destroyed). The added bar code label can be used for the purpose of
documentation.

To remove a module the upper housing piece must be carefully pressed against the rear panel of the lower housing
piece during opening the calculator. Thus the two rear snap-fits of the upper housing piece lever out the module of
the PC board (see picture 4).

Page 21 of 23 Article no.: 1080622201 2022_10_28 Subject to technical change! Errors excepted.
2.2 Retrofitting S3C with an additional communication interface
To our calculator further communication interfaces can be added later.

Open the calculator by pulling the clamping bracket at the upper housing´s leading edge up.
Plug the interface module on the right side of the PC board. If there are module cables you have to loosen the
needed number of cable glands and to glide them over the cables. Remove the blind plugs from the cable gland
openings and feed the cables into the calculator.
Protect the calculator against unauthorized opening using one of the numbered adhesive seals enclosed to the
modules (stick it upon the seal destroyed). The added bar code label can be used for the purpose of
documentation.

Page 22 of 23 Article no.: 1080622201 2022_10_28 Subject to technical change! Errors excepted.
3 Display in the Module Loop (Optional)

Level 6 / Module Loop:

or: or:

1) Display of plugged 2) Display depending on 3) Display depending on


module (alternatively): plugged module and plugged module and
setup: setup:
5 = 1 pulse output
wireless M-Bus (radio) off/ radio encryption (AES) off;
8 = wireless M-Bus + 3
wireless M-Bus (radio) on; radio encryption (AES) on;
pulse inputs
LoRa on/ LoRa off LoRa pending/
LoRa connected
9 = M-Bus + 3 pulse
inputs;
9 = Modbus
pulse value / pulse value /
10 = 2 pulse outputs
pulse output 1 pulse output 2

4 Imprint
Engelmann Sensor GmbH
Rudolf-Diesel-Str. 24-28
69168 Wiesloch-Baiertal
Germany

E-Mail: [email protected]
www.engelmann.de

Page 23 of 23 Article no.: 1080622201 2022_10_28 Subject to technical change! Errors excepted.

You might also like