AQUACIATPOWER™ LD/ILD

Water chiller &


heat pump

The high-performance
packaged solution now
available with R-32
Compact and silent
Scroll compressors
High-efficiency brazed-plate heat exchangers Cooling capacity: 170 to 940 kW
Heating capacity: 160 to 520 kW
Self-adjusting electronic control

R-32
Cooling Hydraulic Heat
and module recovery
heating

Use
The new generation of AQUACIATPOWER ™ high-efficiency The optional variable-speed fan motors guarantee even better
air-to-water heat pumps and water chillers offers an optimal results.
solution for all heating and cooling applications used for the Thanks to their exceptional thermodynamic performance,
Healthcare, Office, and Hotel sectors. provided by radical selection of components, an electronic
These units are designed for outdoor installation and require expansion valve as standard, and a specific control function,
no special protection against adverse weather conditions. standard AQUACIATPOWER ™ units reach a high level of
AQUACIATPOWER ™ is optimised for R-32, the environmentally- seasonal efficiency in cooling mode (SEER) and in heating
responsible fluid with the lowest GWP. mode (SCOP).
This range guarantees compliance with the most demanding ■ Acoustic comfort
requirements for increased seasonal energy efficiency (SEER
With different levels of sound equipment available, the
and SCOP) and CO2 reduction to comply with the various
AQUACIATPOWER ™ range guarantees the acoustic comfort of
applicable European directives and regulations.
occupants and meets the needs of the most sensitive
■ Self-re gulating oper ation to adapt to environments, including hotels, offices and hospitals.
seasonal variations and requirements
■ Quick, simple installation
With exceptional SEER and SCOP seasonal energy efficiency
With a wide variety of connection accessories and equipment,
levels, the AQUACIATPOWER ™ range offers the best technology
the AQUACIATPOWER ™ range is quick and simple to install.
combined with savings throughout the year.
The advanced controller functions and different communication
Due to climatic variations and the different air-conditioning
protocols enable local control via CMS/BMS or remote control,
needs of tertiary buildings, most of the time water chillers and
providing building management with peace of mind.
heat pumps run at partial load.
Equipped with multiple compressors, AQUACIATPOWER ™ units
automatically adjust cooling capacity, anticipating variations in
load and starting only the number of compressors needed to
ensure optimum operation and energy efficiency.

OFFICES HOTELS HEALTHCARE

1
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Global system solutions


As an expert on customised HVAC solutions, CIAT works to ■ Benefits of the water loop
improve the well-being of individuals in their living areas or - More competitive: equipment that is more cost effective and
places of work. Aware of the thermal, energy and air quality requires less maintenance than direct expansion systems.
issues faced today by every sector of activity, CIAT has - Greater comfort: flexible, precise control of occupant
responded by developing global systems based on an adapted comfort.
and efficient combination of products. The latest-generation - Greater energy efficiency: the homogeneity and the thermal
AQUACIATPOWER ™ with a low environmental footprint is part stability of water reduce the energy requirements for
of our sustainable development process. transferring heat.
- Environmentally sustainable: no refrigerant is required on
■ Global energy systems based on the water the premises and only a small amount is used in the heat
loop for heating, cooling and indoor air pump installed outside the building’s occupied spaces.
quality - Easy to install: no refrigerant specialists are required during
To comply with today’s thermal and environmental regulations, installation.
CIAT designs optimised energy systems based on the water loop - Flexibility: a water loop energy system adapts easily to the
comprised of comfort units, heat pumps such as AQUACIATPOWER configuration of buildings and the changes that may be made
™ and dual-flow air handling units. As a renewable resource and to spaces over time.
a highly effective heat-transfer fluid, water not only represents an
excellent alternative to direct expansion systems, it also meets
F-Gas regulations in terms of confinement and limitation of
refrigerants within buildings.

COMFORT
UNITS WATER CHILLERS,
HEAT PUMPS

CIATCONTROL

DRYCOOLERS
SUPERVISION
FREE COOLING

HEAT EXCHANGERS

AIR HANDLING UNITS

THERMAL ENERGY
STORAGE

Range
■ AQUACIATPOWER ™ LD/ILD series ■ Units equipped with variable-speed fans
In the LD water chiller & ILD standard reversible heat pump (option)
versions, AQUACIATPOWER ™ units are optimised to meet the High seasonal energy efficiency version.
most demanding technical and economic requirements.
In this configuration, the AQUACIATPOWER ™ unit is optimised
for partial load applications for which an optimum SEER and
■ Units with nominal high energy performance SCOP value is required. In this case, the machine is equipped
(option) with variable-speed fans, optimising the partial load efficiency
In this configuration, the AQUACIATPOWER ™ unit is optimised throughout the year.
for full-load applications for which an optimum EER and COP
value is required. In this case, the machine is equipped with
high-speed fans enabling nominal efficiency and a broader
application range.

2
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Description
AQUACIAT POWER ™ units are packaged machines supplied as The entire AQUACIAT POWER ™ range complies with the
standard with the following components: following EC directives and standards:
- Hermetic SCROLL compressors - Machinery directive 2006/42/EC.
- Brazed-plate condenser or evaporator water type heat - Electromagnetic compatibility directive 2014/30/EC
exchanger - Safety of machinery: Electrical equipment of machines EN
- All-aluminium micro-channel condenser (LD) or evaporator 60204-1
air-cooled exchanger, copper tube coil with aluminium fins - EMC immunity and emissions EN 61800-3 ‘C3’
(ILD) and axial fan motor assembly - Regulation (EC) No. 1907/2006 REACH
- Electrical power and remote control cabinet: Pressure equipment directive (PED) 2014/68/EU
• 400 V-3ph-50 Hz (+/-10%) mains power supply + earth - Refrigerating systems and heat pumps EN 378-2
• transformer fitted as standard on the machine for supplying - Regulation (EU) No. 813/2013 implementing Directive
the remote control circuit with 24 V 2009/125/EC with regard to ecodesign requirements (Heat
- Connect Touch electronic control module pump)
- Casing for outdoor installation - Regulation (EU) No. 2016/2281 implementing Directive
2009/125/EC with regard to ecodesign requirements (Chiller)

Configuration
Energy versions

High outdoor temperature option Nominal high performance option


AQUACIATPOWER ™
AQUACIATPOWER ™ Seasonal high-performance version
Acoustic Standard (Optional AC motor fans + Inverter
(AC motor fans) or
versions EC motor fans)
Very Low Noise option Very Low Noise option

Ultra Low Noise option Ultra Low Noise option

3
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Customer benefits

environmental responsibility Simplicity


We are committed to meeting your strictest To save you time, we guarantee easy installation and
environmental requirements. integration in the building management system.
We focus our energies on making our products ever ■ No machine room required for the pumps and other
more efficient and environmentally friendly. accessories thanks to the hydraulic module option.
AquaciatPOWER ™ R-32 exceeds the requirements of ■ Optimum use of the surface area for easy integration
Ecodesign 2021. into an existing building.
■ Quick, easy installation and system start-up.
■ Packaged solution for quick start-up and reliable
SEER UP
installation.
R-32 TO
5,33 ■ Communication with all types of building management
system (BMS) via Modbus protocol available as
standard, or optional LON or BACNET protocols.
User comfort
We guarantee acoustic comfort for your users.
Thanks to fans with low noise levels installed as standard
and the noise reduction technologies integrated into the
new AQUACIATPOWER ™ range, we can guarantee a Reliability
level of acoustic comfort which meets the expectations We use state-of-the-art monitoring solutions to
of your users, even in night mode. guarantee complete reliability for your equipment.
BluEdge® Digital* lets you track and monitor your CIAT
equipment.
ULTRA LOW NIGHT MODE ■ Data extraction in real time via customised access
NOISE LEVEL
to the BluEdge® Digital website (controller dashboard,
temperature/event curve, fault memory and alerts
Capacity
and parameter history).
-5 to -6 dB(A)
Noise Level

reinforced noise insulation on the compressors ■ Email alert.


and all of the components which generate noise
0 2 4 6 8 10 12 14 16 18 20 22 24 ■ Analysis and recommendations from CIAT experts

Energy savings
We develop solutions to enable substantial savings while protecting the environment and guaranteeing user comfort.
Heat recovery options can be used to produce free additional hot water at a high temperature. This hot water can be used to
prepare domestic hot water for heating swimming pools, spas and hot tubs.

100 % Chilled or hot water


production
+
30% 80 25 % Domestic hot water
production
energy or
65 100 % Hot water production

The free cooling option is used to provide significant energy savings for all for applications which require cooling all year round or
during the night, particularly in cold regions.
In these regions, free cooling is a very effective and environmentally-friendly means of meeting a large proportion of the cooling
requirements.
PROCESS application
Cooling capacity

Nominal
cooling
TO
TA

capacity
L

PA
FR

RT
FREE COOLING: The economical
EE

IA
LF Chiller
RE
CO

E cooling solution
CO
O

OL
LI

IN
N

G
G

Outdoor
temperature

* BluEdge® Digital is the new name for CIATM2M. The technology remains unchanged.

4
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Main components

MICRO-CHANNEL COIL, LD COOLING


ONLY VERSION
COPPER-ALUMINIUM COIL, ILD HEAT
PUMP VERSION

FAN SPIGOT
(COMPOSITE)

FIXED SPEED FANS (STANDARD)


VARIABLE-SPEED FANS (INVERTER
OR EC MOTOR OPTION)

HYDRAULIC MODULE OPTION WITH OR


WITHOUT BUFFER TANK

CONNECT TOUCH CONTROL VARIABLE OR FIXED


SPEED PUMP

OPTIMISED SCROLL
COMPRESSORS

R-32
ASYMMETRICAL BRAZED
PLATE HEAT EXCHANGER

ELECTRONIC
EXPANSION
VALVE

5
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Description of the main components


■ Compressors ■ Connect Touch control module
- Hermetic SCROLL type - U ser interface with 4.3-inch
- electronic motor overheating protection touch screen
- crankcase heater - I n t u i t i v e , u s e r - f r i e n d l y
- mounted on anti-vibration mounts navigation using icons
- Clear text display of
■ Water type heat exchanger information available in 7
- asymmetrical brazed-plate heat exchanger languages (FR-EN-DE-ES-I-
- plate patterns optimised for high efficiency PT-NL)
- 19 mm armaflex thermal insulation

■ A
 ir-cooled exchanger The electronic control module performs the following main
- Liquid chiller: air-cooled exchanger, all-aluminium, micro- functions:
channels - Regulation of the chilled water temperature (at the return or
- Heat pump: air-cooled exchanger, copper tube coil, at the outlet)
aluminium fins - Control of the water temperature based on the outdoor
- propeller fans with composite blades offering an optimised profile temperature (water law)
with fixed-speed or variable-speed according to the model, variable- - Control for low temperature energy storage
speed option using frequency inverter or EC motor - Management of a second setpoint
- motors – IP 54, class F - Complete management of the compressors with start-up
sequence, timer and runtime balancing
■ Refrigerating accessories - Self-adjusting and proactive functions with adjustment of
-  ehumidifier filters with rechargeable cartridges
D settings on drift control
- hygroscopic sight glasses - In-series staged power control system on the compressors
- electronic expansion valves according to the thermal requirements
- service valves on the liquid line - Management of compressor short-cycle protection
- Four-way reverse cycle valve in cooling/heating mode - Frost protection (exchanger heater option)
- Phase reversal protection
■ Control and safety instruments - Optimised defrosting with free defrost function to optimise
- low and high pressure sensors part-load performance and the SCOP
- safety valves on refrigerant circuit - Management of occupied/unoccupied modes (according to
- water temperature control sensors the time schedule)
- evaporator antifreeze protection sensor - Compressor and pump runtime balancing
- factory-fitted evaporator water flow controller - Management of the machine operation limit according to
outdoor temperature
■ Electrical cabinet - Sound level reduction device (night mode according to the
- Electrical cabinet with IP 54 protection rating user programme) with limitation of compressor capacity and
- A connection point without neutral fan speed
- front-mounted main safety switch with handle - Diagnosis of fault and operating statuses
- control circuit transformer - Management of a fault memory allowing a log of the last 50
- 24 V control circuit incidents to be accessed, with an operating reading taken
- fan and compressor motor circuit breaker when the fault occurs
- fan and compressor motor contactors - Blackbox memory
- C o n n e c t To u c h - Master/slave management of the two machines in parallel
microprocessor-controlled with runtime balancing and automatic changeover if a fault
electronic control module occurs on one machine
- wire numbering - Weekly and hourly time schedule for the machine, including
- marking of the main electrical 16 periods of absence
components - Pump standby based on demand (energy saving)
- Calculation of the water flow rate and operating pressure
■ Casing (hydraulic module version)
Frame made from RAL 7035 - Electronic adjustment of the water pump speed and water
light grey & RAL 7024 graphite flow rate (variable-speed pump option)
grey painted panels - Display of all machine parameters (3 access levels, User/
Maintenance/Factory, password-protected): temperature,
setpoints, pressures, water flow rate (hydraulic version),
runtime.
- Display of trend curves for the main values
- Storage of maintenance manual, wiring diagram and spare
parts list.
- Innovative smart energy monitoring, providing users with
smart data such as real-time electrical energy consumption
and heating and cooling capacity, and instantaneous and
average energy efficiency rates.

6
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Description of the main components


■ Remote management - u
 ser fault reporting, enables integration of a fault in the water
Connect Touch is equipped as standard with an RS485 port and loop
an ETHERNET (IP) connection, offering a range of options for - General fault reporting: this contact indicates that the unit
remote management, monitoring and diagnostics. has stopped completely
- alert reporting: this contact indicates the presence of a minor
Using the integrated Webserver, a simple internet connection fault which did not cause the refrigerant circuit in question to
uses the unit's IP address to access the Connect Touch interface stop.
on the PC, facilitating everyday management tasks and - End of storage signal: enables return to the second setpoint
maintenance operations. at the end of the storage cycle
A range of communication protocols are available: MODBUS/ - Schedule override: closing this contact cancels the time
JBUS RTU (RS485) or TC/IP as standard, LONWORKS – schedule.
BACNET IP (BTL certified) as an option, enabling most CMS/ - desuperheater activation control
BMS to be integrated - Desuperheater pump On/Off control.
Several contacts are available as standard, enabling the
machine to be controlled remotely by wired link:
- Automatic operation control: when this contact is open, the
machine stops
- Heating/cooling mode selection
- Setpoint 1/setpoint 2 selector: when this contact is closed, a
second cooling setpoint is activated (energy storage mode,
for example)
- Power limitation: closing the contact concerned allows the
power or refrigerating consumption of the machine to be
limited by stopping one or more compressors (this limit can
be set with a parameter) Web server IP address

- Fault reporting: this contact indicates the presence of a major


fault which has caused one or both refrigerant circuits to stop
- Operational status reporting indicates that the unit is in
production mode. Remote management via web server
Connection to RJ port
- Activation control for partial energy heat recovery unit using
Connection via IP address
the desuperheater. All the HMI functionalities
- Switch control for the customer pump, external to the machine available on the PC
(on/off). Simplified remote monitoring

Contacts available as an option:


- Setpoint adjustable via 4-20 mA signal: this input is used to
adjust the setpoint in COOLING mode
- On/off control for a boiler
- 4-stage on/off management for additional heaters
- Power limitation adjustable by 4-20 mA signal
E-mail alerts
- Second power limitation level
- Power indication: analogue output (0-10 V) providing an
indication of the unit's load rate.

■ Maintenance
Connect Touch has two maintenance reminder functions as - The scheduled maintenance reminder: when activated, this
standard, making users aware of the need to regularly perform function enables the period between two maintenance
maintenance operations and to guarantee the service life and inspections to be set. This period may be set by the operator
performance of the unit. These two functions can be activated in either days, months or operating hours, depending on the
independently. application.
A reminder message appears on the unit's HMI screen, and - The compulsory F-GAS sealing test maintenance reminder:
stays there until it is acknowledged by the maintenance operator. when activated, this function, which is the default factory
The information and alert relating to these functions are available setting, enables the period between two sealing tests to be
on the communication bus to be used on the CMS/BMS. selected, according to the unit's refrigerant charge, in
compliance with the F-GAS regulations.

7
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Peace of mind
Complete reliability thanks to state-of-the-art monitoring CLOUD
solutions: BluEdge® Digital
Data
■ BluEdge ® Digital, the CIAT monitoring analytics

solution Email alerts


and reports
BluEdge® Digital is a remote supervision solution dedicated to
Telecom
monitoring and controlling several CIAT machines in real time. operators

4G
Advantages USERS
- Access to the operating trend curves for analysis
- Improved energy performance Customer BluEdge
technician
- Improved availability rate for the machines
ACTIONS
Functions
Digital
BluEdge® Digital will send data in real time to a supervision interface

website.
The machine operating data can be accessed from any PC,
smartphone or tablet.
Any event can be configured to trigger a mail alert.
Composition of the box (available in 230 V and
Parameters monitored:
400 V)
- Overview
- Control panel for the controllers - 1 GPRS / 4G LTE-M modem
- Events - 1 SMART SIM card
- Temperature curves - 1 power supply (24 VDC)
- 1 power protection device
Monthly and annual reports are available to analyse:
- 1 GSM antenna
- T h e p e r f o r m a n c e a n d o p e r a t i o n o f t h e m a c h i n e
- Rail mounting
Example: operating curves and time, number of compressor
- Enclosed casing to protect the equipment during transport
start-ups, events, preventive maintenance actions to be
- Packing box for cable routing (bus, power supply)
performed, etc.
Incidents such as a drift in the measurements on a temperature
Compatibility
sensor, incorrectly set control parameters, or even incorrect
settings between one compressor stage and the other, are Up to 5 machines per box
immediately detected, and the corrective actions put in place.

Equipment
This box can be used both on machines which are already in
use (existing inventory), and on new machines.
- 1 transportable cabinet
Overview Parameters

Curves Information

Events
(real time and archives) Reports

BluEdge® Digital
supervision platform

8
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Seasonal performance in cooling mode


Analyses of installed systems show that the heat load varies The (Seasonal Energy Performance Ratio) (SEPR) measures
from season to season and that a water chiller operates at the seasonal energy efficiency of liquid chillers for process
reduced capacity for the majority of the time. applications by calculating the ratio between the annual
process cooling demand and the chiller's annual energy
Partial load efficiency is therefore essential when choosing a demand. It takes into account the energy efficiency at each
water chiller. It is with this in mind that the new AQUACIATPOWER outdoor temperature for the average European climate weighted
™ range was designed. In particular, the entire range uses R32 by the number of hours observed for each of these temperatures.
refrigerant which, thanks to its thermodynamic performance,
makes it possible to obtain much higher seasonal performance The SEPR is a new way of measuring the energy efficiency of
levels. liquid chillers for process applications over an entire year.
The new indicator provides a more realistic overview of the
As its compressors are connected in parallel on the refrigerating cooling system's energy efficiency and its actual impact on the
circuit, the AQUACIATPOWER ™ easily and efficiently adjusts environment (Ecodesign regulation 2015/1095 and 2016/2281).
the cooling capacity to the system's needs. The self-adjusting
Connect Touch control anticipates variations in load and starts MEPS(*) relating to EU ecodesign for
Level 1 Level 2
only the number of compressors needed. This ensures optimum (since (since
chillers with air cooled condensers
01/07/2016) 01/07/2018)
operation of the compressors and guarantees energy efficiency
SEPR for kWh/kWh < 300 kW kWh/
for the majority of the system's life. 2,24 2,58
medium temperature chillers kWh
In the high seasonal energy efficiency configuration, SEPR for kWh/kWh > 300 kW kWh/
2,80 3,22
medium temperature chillers kWh
AQUACIATPOWER ™ has variable-speed fan motor assemblies.
This technology enables the machine's part-load performance Level 1 Level
MEPS(*) relating to EU ecodesign for
to be improved, along with its seasonal performance (SEER, (since 2 (from
chillers with air cooled condensers
01/01/2018) 01/01/2021)
SEPR and SCOP).
SEPR for kWh/kWh < 400 kW
kWh/
process high temperature 4,50 5,00
kWh
chillers
The (Seasonal Energy Efficiency Ratio (SEER) measures the
seasonal energy efficiency of liquid chillers for comfort SEPR for kWh/kWh > 400 kW
kWh/
process high temperature 5,00 5,50
applications by calculating the ratio between the annual kWh
chillers
cooling demand of the building and the chiller's annual energy
(*) Minimum Efficiency Performance Standards: performance standards set by
demand. It takes into account the energy efficiency for each EU member states to comply with the EU Ecodesign directive. SCOP for
outdoor temperature weighted by the number of hours observed the comfort heat pump (as per EU ecodesign directive)
for each of these temperatures, using actual climate data.

The SEER is a new way of measuring the energy efficiency of


liquid chillers for comfort applications over an entire year.
The new indicator provides a more realistic overview of the
cooling system's energy efficiency and its actual impact on the
environment (Ecodesign regulation 2016/2281).

MEPS(*) relating to EU ecodesign


Level 1 (since Level 2 (from
for chillers with air cooled
01/01/2018) 01/01/2021)
condensers
SEER for comfort Chillers < kWh/
3,80 4,09
400 kW kWh
SEER for comfort Chillers > kWh/
4,09 4,55
400 kW kWh
(*) Minimum energy performance standards set by EU member states to comply
with the EU Ecodesign directive.

AQUACIATPOWER ™ LD comply with Ecodesign regulation


2016/2281

9
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Seasonal performance in heating mode


The (Seasonal Coefficient Of Performance) (SCOP) measures ■ Primary energy evaluation
the seasonal energy efficiency of heat pumps in heating mode. In order to compare the energy efficiency of products using
The European Ecodesign directive considers the product's different energy sources, the Ecodesign directive introduced a
environmental impact throughout its entire life cycle. It defines new seasonal energy efficiency calculation known as Ƞs (Greek
the mandatory energy efficiency requirements for water chillers letter eta followed by the letter "s" for seasonal) and expressed
and heat pumps. as a percentage. For heat pumps, the SCOP (final energy)
Products that do not meet the energy efficiency requirements value is transposed to Ƞs (primary energy) by taking into
set by the new directive will gradually be phased out of the account a conversion coefficient of 2.5 which corresponds to
market, forcing manufacturers to develop and offer more the average efficiency of the electrical production and various
efficient products. corrections for the responsiveness of the regulation system (i
= 3 for air-to-water heat pumps).
Like the SEER relating to water chillers, the new seasonal
SCOP(kW/kW)×100
coefficient of performance (SCOP) resulting from this new
European directive is used to evaluate the energy efficiency of
η s (%) = ∑ i corrections
2,5
heat pumps. Until now, only the COP has been used to measure
energy efficiency in heating mode.
The COP was exclusively calculated using a single measuring The minimum seasonal efficiency requirements to be met by
point, and only took into account operation at full load, which low temperature heat pumps, set by the standard, are as
did not represent the efficiency of the heat pump over an entire follows:
heating season.
Level 2 (since 09/2017)
The purpose of the SCOP is to characterise the seasonal MEPS(*) relating to EU ecodesign
efficiency of the heat pump by taking into account the efficiency for air-to-water heat pumps Space & Hot Space Heating
at partial load and full load established for several outdoor Water 47/55 °C 30/35 °C
temperatures. The SCOP is the ratio between the building's SCOP for heat kWh/
2,83 3,20
annual heating demand and the annual electricity consumption pump < 400 kW kWh
of the heating system. It is measured in accordance with the EtasS 110 125
EN14825 standard based on an average reference climate that
takes into account several reference temperatures between AQUACIAT POWER ™ ILD units comply with Ecodesign
-10 °C and +16 °C regulation 813/2013.

10
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Hydraulic module
■ The "ALL IN ONE" solution The components in the hydraulic system are carefully selected
and factory assembled and tested to make the installation of
The PLUG & COOL solution offered by the units simple and economical.
AQUACIATPOWER ™ This ensures conditioning times, implementation times and
space requirements are kept to a minimum.
The hydraulic module contains all the hydraulic circuit
components needed for the system to operate correctly: ■ Hydraulic module
- Buffer tank with 19-mm insulation, 550-litre capacity (option).
- Expansion vessel (option):
• 50 litres for models 602 to 900.
• 80 litres for models 902 to 3500.
- Wide choice of pumps:
• Single or dual pumps with operating time balancing and
backup.
• High- or low-pressure pumps.
• Fixed-speed or variable-speed pumps.
- Water temperature and pressure sensors.
- Water filter.
- Relief valve.
- Drain circuit.
- Air bleed valve.
- Frost protection (option).

■ AQUACIATPOWER ™ hydraulic module diagram

Components of the hydraulic module and the unit Installation components


1 Screen filter 16 Pocket
2 Expansion tank 17 Air vent
3 Relief valve 18 Flexible connection
4 Circulating pump (single or dual) 19 Shut-off valve
5 Air vent 20 800 µm screen filter (Option - mandatory in the case of a unit without hydraulic
6 Water drain tap module/included on the hydraulic version)
7 Pressure sensor 2 Pressure gauge
Note: provides pressure information from the pump inlet 22 Water flow control valve
8 Temperature sensor Note: not required if hydraulic module with variable-speed pump
Note: provides temperature information from the heat exchanger outlet 23 Charging valve
9 Temperature sensor 24 Bypass valve for frost protection (if shut-off valves are closed (item 19) during
Note: provides temperature information from the heat exchanger inlet winter)
10 Pressure sensor 25 Buffer tank (if required)
Note: provides pressure information from the heat exchanger outlet - - - - - Hydraulic module (unit with hydraulic module option)
11 Check valve (If dual-pump) Notes:
12 Plate heat exchanger - The installation must be protected against frost.
13 Heater or heat trace cable for frost protection - The unit's hydraulic module and the water type heat exchanger may be
14 Water type heat exchanger flow rate sensor protected (factory-fitted option) against freezing using electric heaters and
15 Water buffer tank module heat trace cables (13)
- The pressure sensors are assembled on connections without Schrader.
Option Depressurise and drain the system before any work.

11
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Variable flow pump


■ Description ■ SOFT START
The AQUACIATPOWER ™ may be equipped with one or two A SOFT START function prevents any current peaks when the
variable-speed pumps which save you energy by adjusting the pump is started up to protect the electrical system, thereby
electrical consumption of one pump to the actual requirements limiting the building's electricity use at peak times and ensuring
of a hydraulic system, in particular for oversized installations. the smooth operation of the pipework

■ Simple to use ■ STANDBY function


The "variable-speed pump" option is fully protected and fully Lowering the speed when the compressors are on standby
built into the machine, which is installed outdoors to avoid the reduces the water flow rate to ensure the water loop is perfectly
need for machine room work. homogenised and the control temperature sensors are well
The assembly is factory-fitted and pre-set on the unit; it is irrigated. This reduces the pump's electricity consumption by
therefore quick to install and reduces the cost of work, in around 80% during standby periods, which represents a
particular because there is no water flow control valve on the significant proportion of the machine's normal operating time,
unit's outlet. in particular for air conditioning applications.
The ability to adjust the water flow to your requirements means
that the pump pressure can be adapted precisely to the actual
pressure drop on the system when it is started up on-site.

■ Operating principle
- Full load operating
A regulator, with a direct display of the flow rate and pressure
on the Connect Touch screen, enables one pump (pump A in the
example below) to be adapted, by lowering its pressure P1 to
the requirements of system P2, to obtain the optimal water flow
rate setpoint. Electricity bills for the pump consumption are mWC
proportionally reduced, guaranteeing a return on investment
(ROI) in just a few years, compared to the same fixed-speed
pump equipped with a single flow rate adjustment valve. Pressure drop

- Part load operation


Three part load operating modes are available: P2
1 - Fixed speed
The control ensures the pump continuously runs at a
constant speed, based on the capacity of the compressor(s).
When the compressor is powered off, the Connect Touch Nominal flow rate m3/h
"standby" function manages the electrical power consumed
by the pump by reducing its speed to the minimum.
This provides energy savings of around 33%.
2-V
 ariable flow rate: Constant regulation of the pressure
difference
The control continuously acts on the pump speed to ensure mWC
a constant pressure difference. This solution is suitable for
installations with two-way valves. This control mode is used
to ensure a uniform supply in each hydraulic circuit to make
sure that each terminal unit operates at a satisfactory P1
Pu
ΔP

pressure Va m
pA
P2 ri
puable
3-V
 ariable flow rate: Constant regulation of the temperature m s
p pe
difference Pu "A e
m " d
p
The regulation maintains a constant temperature difference B
whatever the load rate of the unit by reducing the flow rate
to the minimum acceptable limit. This control mode is
Nominal flow rate m3/h
suitable for most comfort applications.
This provides energy savings of around 66% for the
pump in each of these last two operating modes

12
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

R-32
Environmental responsibility
The AQUACIATPOWER ™ contributes to sustainable development via an environmentally responsible approach, aimed at balancing
ecological and economic concerns. This enables it to meet the requirements of future European thermal regulations and to protect
our environment for future generations.
The impact of an air conditioning system on global warming of the planet is in large part caused by CO2 emissions released into
the atmosphere when the electricity required to power the unit is produced (indirect effect) and in small part by CO2 emissions
linked to uncontrolled emissions of refrigerant with global warming potential into the atmosphere (direct effect).
With AQUACIATPOWER ™, it's a win-win situation: its low charge of R-32 refrigerant with low GWP reduces the direct environmental
impact by 80% while reducing the indirect environmental impact thanks to its high energy performance.

■ 77% reduction in the direct environmental impact (refrigerant)


This performance is the result of the high-quality components used, which have all been rigorously selected:
- R-32 refrigerant with low environmental impact (Ozone depletion potential =0, Global warming potential =675)
- Aluminium micro-channel coil on LD chiller versions with a 40% reduction in refrigerant charge compared to a conventional
coil
- New generation of copper tube coil-aluminium fins on ILD heat pump versions with a 30% reduction in refrigerant charge
compared to a conventional coil
- Asymmetrical brazed-plate heat exchanger (BPHE) with a reduction in the refrigerant charge compared to a shell and tube
heat exchanger
- Systematic tightness check of units in leak detection cabinets at end of line production

Refrigerant GWP Refrigerant Environmental impact


(CO2 eq.) charge* (kg) (kg.CO2 eq.)

-68 -30 -77


2088
% % %
100
70 2088
675
473

R-410A R-32 R-410A R-32 R-410A R-32

To conclude, the potential direct impact of AQUACIATPOWER ™ on the environment with R-32 refrigerant is reduced by
77% compared to the previous generation R-410A.

■ Reduced indirect environmental impact (Energy)


The high energy performance offered by AQUACIATPOWER ™ R-32 enables energy consumption to be greatly reduced, therefore
reducing energy bills for the user whilst reducing the unit's carbon footprint.
The seasonal efficiency of AQUACIATPOWER ™ R-32 in cooling mode is 10% greater than the previous version with R-410A and
6% greater in heating mode.
In addition, the AQUACIATPOWER ™ unit with R-32 refrigerant can be equipped with a variable-speed pump with constant or
variable water flow control to significantly reduce pumping energy costs.
Energy consumption level during Pump energy consumption
operation (kWh index) (kWh index)

100 100 100 -33


-8% %
-10 -66
% 66 %
93

90 33

AQUACIATPOWER ™AQUACIATPOWER ™AQUACIATPOWER ™AQUACIATPOWER ™ AQUACIATPOWER ™ AQUACIATPOWER ™ AQUACIATPOWER ™ R-32


R-410a R-32 R-410a R-32 R-32 R-32 Variable-speed pump,
Cooling mode Cooling mode Heating mode Heating mode Fixed-speed pump, Variable-speed pump, variable flow
constant flow constant flow

13
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

R-32
Environmental responsibility
This performance is the result of the high-quality components used, which have all been rigorously selected:
- R-32 refrigerant with high energy performance,
- New generation of scroll compressors optimised for R-32 refrigerant
- Asymmetrical brazed-plate heat exchanger with extremely low water-side pressure drops enabling a reduction in pump electricity
consumption
- Optional variable-speed pump enabling automatic adjustment of the rated water flow rate (disposal of the control valve), during
operation and during unit shut down periods.
To conclude, the AQUACIATPOWER ™ unit with R-32 refrigerant and variable-speed pump greatly reduces the indirect
environmental impact compared to the previous generation R-410A.

■ EcoPassport®
The PEP ecopassport® programme provides an international reference framework for procedures enabling manufacturers to
report the environmental specifications of their products in the form of an environmental claim known as a Product Environmental
Profile (PEP).
The PEP ecopassport® programme guarantees that PEPs are correctly drawn up, verified and reported in line with the requirements
of the ISO 14025 and IEC/PAS 62545 standards.
The Life Cycle Analysis (LCA) PEP is the environmental identity card for an item of equipment which details the environmental
impacts of the product during its life cycle according to eight mandatory indicators:
1. Global Warming Potential
2. Impact on the ozone layer
3. Acidification of soil and water
4. Eutrophication of water
5. Photochemical ozone creation
6. Abiotic resource depletion
7. Fresh water consumption
8. Total use of primary energy during the life cycle
Products with certified environmental profiles are used to support methods to assess building sustainability such as BREEAM,
LEED. BREEAM, LEED gives additional recognition for materials with robust environmental product declaration types using
manufacturer data.
CIAT is the first HVAC manufacturer to provide the PEP for liquid chillers and heat pumps including not only the 8 mandatory
indicators, but all 27 indicators.
The AQUACIATPOWER ™ LD PEP can be downloaded from the PEP ecopassport® website: http://www.pep-ecopassport.org/fr/

14
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Available options

Options Description Advantages LD ILD

Corrosion
Fins made of pre-treated aluminium Improved corrosion resistance, recommended
protection,
(polyurethane and epoxy) for moderate marine and urban environments
No ●
traditional coils
Low temperature chilled water production
Low-temperature Covers specific applications such as ice
brine solution
down to -15 °C with ethylene glycol and
storage and industrial processes ● No
down to -12 °C with propylene glycol.
Unit equipped with specific variable-speed
fans: XtraFans (See specific chapter for Ducted fan discharge, optimised temperature
XtraFan maximum available static pressure according control, based on the operating conditions ● ●
to size), each fan equipped with a connection and system characteristics
flange and flexible sleeves
Acoustic compressor enclosure and
Very Low Noise
low-speed fans
Noise level reduction for sensitive sites ● ●
Acoustic compressor enclosure, low-speed
Ultra Low Noise fans and enhanced sound insulation of main Noise level reduction for sensitive sites ● ●
noise sources
High ambient Unit operating range extended to higher
temperature
Unit equipped with a higher speed fan
ambient temperatures ● ●
Protection grilles Metallic protection grilles Coil protection against possible impact ● ●
Soft starter per
compressor
Electronic starter on each compressor Reduced start-up current ● ●
Soft starter per Economical solution for reduced start-up
circuit
Soft starter on each circuit
current ● ●
All year round
Stable unit operation when the outdoor air
cooling operation Fanspeed control via frequency converter
temperature is between 0°C and -20°C ● ●
down to -20°C
Water type heat exchanger module frost
Water exchanger Electric heater on the water type heat
frost protection exchanger and the water duct
protection for an outdoor air temperature ● ●
between 0 °C and -20 °C
Exchanger and Electrical heaters on the water type heat Water type heat exchanger and hydraulic
hydraulic module exchanger, water pipes, hydraulic module module frost protection down to an outdoor ● ●
frost protection and expansion tank air temperature of -20 °C
Exchanger and Electrical heater on the water exchanger, Water type heat exchanger and hydraulic
hydraulic module water pipes, hydraulic module and optional module frost protection down to an outdoor ● ●
frost protection expansion tank & buffer tank air temperature of -20 °C
Production of free high-temperature hot-water
Partial heat Unit equipped with one desuperheater on
recovery each refrigerant circuit
simultaneously with chilled water production ● ●
(or hot water for Heat pump)
Unit equipped with additional heat exchanger Production of free hot water, adjustable on
Total heat recovery
in parallel with the condenser coils. demand ● No

Unit equipped with supplementary water


Master/slave outlet temperature sensor kit (to be field Optimised operation of two units connected in
operation installed) allowing master/slave operation of parallel operation with runtime balancing ● ●
two units connected in parallel
Compressor Simplified maintenance. Possibility to store
Shut-off valves on the common compressor
suction and
suction and discharge pipes
the refrigerant charge in the cooler or ● ●
discharge valves condenser side during servicing
Evaporator hydraulic module equipped with
high pressure fixed-speed pump, drain valve,
air vent and pressure sensors. For more
Evaporator single
HP pump
details, refer to the dedicated chapter Quick and easy installation (plug & play) 0602R-1400R ●
(expansion tank not included; option with
built-in hydraulic safety components
available)

● ALL MODELS
Refer to the selection tool to find out which options are not compatible.

15
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Available options

Options Description Advantages LD ILD

Dual high pressure water pump, water filter,


electronic water flow rate control, pressure
sensors.
HP dual-pump
hydraulic module
For more details, refer to the dedicated Quick and easy installation (plug & play) 0602R-1400R ●
chapter (expansion tank not included; option
with built-in hydraulic safety components
available)
Single low pressure water pump, water filter,
electronic water flow rate control, pressure
LP single-pump sensors. For more details, refer to the
hydraulic module dedicated chapter (expansion tank not
Quick and easy installation (plug & play) 0602R-1400R ●
included; option with built-in hydraulic safety
components)
Dual low-pressure water pump, water filter,
electronic water flow control, pressure
LP dual-pump sensors. For more details, refer to the
hydraulic module dedicated chapter (expansion tank not
Quick and easy installation (plug & play) 0602R-1400R ●
included; option with built-in hydraulic safety
components)
Evaporator hydraulic module equipped with
high-pressure variable-speed pump, drain Quick and easy installation (plug & play),
valve, air vent and pressure sensors. For significant reduction in pumping energy
HP evap. variable-
speed single-pump
more details, refer to the dedicated chapter consumption level (more than two-thirds), ● ●
(expansion tank not included; option with precise water flow control, improved system
built-in safety hydraulic components reliability
available.)
Quick and easy installation (plug & play),
Dual high pressure water pump with speed
Variable-speed significant reduction in pumping energy
regulator, pressure sensors. Multiple water
dual high-pressure
flow rate control options. For more details,
consumption level (more than two-thirds), ● ●
pump precise water flow control, improved system
refer to the dedicated section.
reliability
Higher air flow through the condenser coils Energy cost reduction and extended
High nominal
energy efficiency
improving heat exchange efficiency on the operating envelope (full load operation at ● ●
condenser higher air temperature)
High seasonal Enhances the unit seasonal energy efficiency
Unit equipped with variable-speed fans
energy efficiency
(VSD)
performance and reduces the noise emission 0602R-1400R ●
(VSD) thanks to a smooth fan speed variation.
High seasonal Enhances the unit seasonal energy efficiency
energy efficiency Variable-speed fans with EC motors performance and reduces the noise emission ● ●
(EC) thanks to a smooth fan speed variation.
High energy
efficiency Improvement of performances and reduction
Optimisation of the refrigerant circuit for the
underfloor heating/
underfloor heating/cooling system application
of energy costs for the underfloor heating/ No ●
cooling system cooling system application
application
Lon communication Two-directional communication board Connects the unit by communication BUS to
gateway complying with Lon Talk protocol a centralised building management system ● ●
Two-directional high-speed communication Easy and high-speed connection by ethernet
Bacnet over IP using BACnet protocol over Ethernet network line to a building management system. Allows ● ●
(IP) access to multiple unit parameters
Energy EMM Control board with additional inputs/ Extended remote control capabilities
Management outputs. See Energy Management Module (Set-point reset, ice storage end, demand ● ●
Module option chapter limits, boiler on/off command...)
Contact for 0-10 V signal to report any refrigerant Immediate customer notification of refrigerant
refrigerant leak leakage in the unit directly (the leak detector losses to the atmosphere, allowing timely ● ●
detection itself must be supplied by the customer) corrective actions
Compliance with
Russian EAC certification Compliance with Russian regulations ● ●
regulations

● ALL MODELS
Refer to the selection tool to find out which options are not compatible.

16
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Available options

Options Description Advantages LD ILD

Prevents frost formation on the coils;


Coil defrost Electric heaters under the coils and the
resistance heaters condensate pans
compulsory in heating mode if the outdoor No ●
temperature is below 0 °C
Insulation of the
Thermal insulation of the evaporator inlet/
evaporator inlet/ Prevents condensation on the evaporator
outlet refrigerant
outlet refrigerant lines, with UV-resistant
inlet/outlet refrigerant lines ● ●
flexible connection and insulation
lines
Coating applied using a conversion process
which modifies the surface of the aluminium
MCHE anti- producing a coating that is integral to the Protect2 Improved corrosion resistance of the
corrosion coil. Complete immersion in a bath to ensure MCHE coils by 2, recommended for use in ● No
protection Protect2 100% coverage. No heat transfer variation, moderately corrosive environments
tested to withstand more than 4000 hours of
salt spray as per ASTM B117
Extremely durable and flexible epoxy
polymer coating applied on micro channel
coils by electro coating process, final UV
Protect4 anti- Protect4 Improved corrosion resistance of the
protective topcoat. Minimal heat transfer
corrosion
variation, tested to withstand more than
MCHE coils by 4, recommended for use in ● No
protection corrosive environments
6000 hours of constant neutral salt spray as
per ASTM B117, improved impact resistance
as per ASTM D2794
Flanged
Victaulic piping connections with flanged
evaporator water
joints
Easy installation ● ●
connection kit
Improved aesthetics, compressor protection
Compressor
enclosure
Compressor with enclosure  against external elements (dust, sand, ● ●
water…)
Enables connection of a laptop or an
230 V electrical 230 VAC power source provided with plug
plug socket and transformer (180 VA, 0.8 A)
electrical device during system start-up or ● ●
maintenance
Easy and fast installation (plug & play), &
6-bar expansion tank built into the hydraulic
Expansion tank
module (requires hydraulic module option)
protection of closed water systems from ● ●
excessive pressure
Screwed water
DSH connections with screw connection Easy to install. Allows unit connection to a
connection sleeves
sleeves screw connector ● ●
for desuperheater
Water buffer tank Avoids short cycle on compressors and
module
Built-in water buffer tank module
ensures stable water in the loop ● ●
Isolate the unit from the building, prevent the
Elastomer anti-vibration mounts to be placed transmission of vibrations and associated
Anti-vibration
mounts
under the unit (material classified as fire noise to the building. Must be used in ● ●
class B2 according to DIN 4102). conjunction with a flexible connection on the
water side
Exchangers flexible
Flexible connections on the exchanger water Easy to install. Limits the transmission of
coupling
side vibrations to the water network ● ●
connection
Exchanger water
filter
Water filter Prevents dust entering the water network ● ●
Free cooling mode Control and connections to a free cooling Easy system management, extended control
drycooler drycooler Opera or Vextra fitted with optional capabilities to a drycooler used in free cooling ● ●
management FC control box mode
Desuperheater Flexible connections on the desuperheater Easy to install. Limits the transmission of
flexible couplings water side vibrations to the water network ● ●
Installation or
Permits non-standard option compatibility for
application process Specific management of option compatibility
HVAC application in the EU ● No
outside Europe
Compliance with
Moroccan Specific regulatory documentation Compliance with Moroccan regulations ● ●
regulations
Unit wrapped in a plastic cover and strapped Protects against dust and external soiling of
Plastic cover
onto a wooden pallet. the unit during storage and transport. ● ●
Energy savings for applications which require
Free cooling hydraulic coils on the two
Free cooling (total)
refrigerant circuits
cooling all year round (e.g.: industrial ● No
processes, data centres)
Energy savings for applications with reduced
Free cooling Free cooling hydraulic coils on a refrigerant
(partial) circuit
demand for cooling in the winter (e.g. office ● No
space with computer room, meeting rooms)

● ALL MODELS
Refer to the selection tool to find out which options are not compatible.

17
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Technical characteristics - cooling only

AQUACIATPOWER ™ LD 0602R 0650R 0750R 0900R 1100R 1200R 1350R 1400R 1600R

Cooling
Standard unit Nominal capacity kW 165 180 198 217 256 296 328 361 394
CA1
Full load performances* EER kW/kW 3,05 3,24 3,04 3,02 2,81 2,96 2,86 2,94 2,86
SEER 12/7°C Comfort low temp. kWh/kWh 4,49 4,64 4,45 4,47 4,35 4,70 4,67 4,62 5,09
ηs cool 12/7°C % 169 181 178 176 171 185 183 183 201
Seasonal energy efficiency** SEER 23/18°C Comfort medium temp. kWh/kWh 5,27 5,52 5,22 5,26 4,99 5,66 5,55 5,43 5,95
SEPR 12/7°C Process high temp. kWh/kWh 5,27 5,42 5,34 5,19 5,14 5,44 5,47 5,60 6,34
SEPR -2/-8°C Process medium temp. kWh/kWh 3,06 3,11 3,08 3,00 3,04 3,09 3,14 3,09 3,44
Unit + Rated & Seasonal Nominal capacity kW 172 187 206 227 270 311 346 380 416
high performance
CA1
options EER kW/kW 3,20 3,36 3,21 3,16 3,03 3,15 3,09 3,14 3,09
Full load performances*
SEER 12/7°C Comfort low temp. kWh/kWh 4,82 5,02 4,84 4,94 4,79 5,25 5,15 5,09 5,11
ηs cool 12/7°C % 190 198 191 195 189 207 203 201 201
Seasonal energy efficiency** SEER 23/18°C Comfort medium temp. kWh/kWh 5,98 6,23 5,93 5,99 5,69 6,35 6,17 6,13 6,07
SEPR 12/7°C Process high temp. kWh/kWh 6,30 6,61 6,42 6,13 5,97 6,30 6,24 6,36 6,30
SEPR -2/-8°C Process medium temp. kWh/kWh 3,48 3,60 3,54 3,41 3,41 3,51 3,56 3,50 3,57
Part Load integrated values IPLV.SI kW/kW 5,06 5,16 5,04 5,16 5,08 5,25 5,23 5,21 5,52
Sound levels
Unit + High temperature option/Nominal high performance
Sound power(1) dB(A) 91,0 91,5 91,5 92,0 92,0 93,0 93,0 93,5 93,5
Sound pressure at 10 m(2) dB(A) 58,5 59,5 59,5 60,0 60,0 60,5 60,5 61,0 61,5
Standard unit
Sound power(1) dB(A) 88,5 89,0 89,0 89,5 89,5 90,5 90,5 91,0 91,0
Sound pressure at 10 m(2) dB(A) 56,5 57,0 57,0 57,5 57,5 58,5 58,5 59,0 58,5
Unit + Very Low Noise option
Sound power(1) dB(A) 85,5 85,5 85,5 86,5 86,5 87,5 87,5 88,0 88,0
Sound pressure at 10 m(2) dB(A) 53,0 53,5 53,5 54,5 54,5 55,5 55,5 55,5 56,0
Unit + Ultra Low Noise option
Sound power(1) dB(A) 83,5 83,5 83,5 84,5 84,5 85,5 85,5 86,0 86,0
Sound pressure at 10 m(2) dB(A) 51,5 51,5 51,5 52,5 52,5 53,5 53,5 53,5 53,5

* In accordance with EN14511-3:2018.


** In accordance with EN14825:2018, average climate conditions
CA1 Cooling mode conditions: evaporator water inlet/outlet temperature 12 °C/7 °C, outdoor air temperature 35 °C, evaporator fouling
factor 0 m2. k/W
Ƞs cool12/7°C & SEER 12/7°C Values in bold comply with Ecodesign Regulation (EU) No. 2016/2281 for Comfort applications
SEER 23/18 °C Values in bold comply with Ecodesign Regulation (EU) No. 2016/2281 for Comfort applications
SEPR 12/7 °C Values calculated in accordance with EN 14825:2016
SEPR -2/-8 °C Values calculated in accordance with EN 14825:2016
IPLV.SI Calculated as per AHRI standard 551-591.
(1) In dB ref=10-12 W, (A) weighting. Declared dual-number noise emission value in accordance with ISO 4871 with an uncertainty of
+/-3 dB(A). Measured in accordance with ISO 9614-1 and certified by Eurovent.
(2) In dB ref 20 µPa, (A) weighting. Declared dual-number noise emission value in accordance with ISO 4871 with an uncertainty of +/-3
dB(A). For information, calculated from the sound power Lw(A).

Eurovent certified values

18
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Technical characteristics - cooling only

AQUACIATPOWER ™ LD 0602R 0650R 0750R 0900R 1100R 1200R 1350R 1400R 1600R

Dimensions
Standard unit
Length mm 2410 2410 2410 2410 2410 3604 3604 3604 3604
Width mm 2253 2253 2253 2253 2253 2253 2253 2253 2253
Height mm 2324 2324 2324 2324 2324 2324 2324 2324 2324
Unit + water buffer tank module option
Length mm 3604 3604 3604 3604 3604 4798 4798 4798 4798
Operating weight (3)

Standard unit kg 1349 1397 1397 1521 1556 1995 2049 2211 2269
Unit + Ultra Low Noise option kg 1453 1501 1501 1656 1690 2153 2208 2394 2452
Unit + Ultra Low Noise + HP dual-pump hydraulic module
kg 1588 1636 1636 1791 1837 2302 2403 2589 2646
option
Unit + Ultra Low Noise + HP dual-pump hydraulic module
kg 2571 2619 2619 2774 2819 3288 3389 3575 3632
+ Water buffer tank module option
Compressors Hermetic Scroll 48.3 r/s
Circuit A 1 1 1 2 2 2 2 3 3
Circuit B 2 2 2 2 2 3 3 3 3
Number of power stages 3 3 3 4 4 5 5 6 6
Unit PED category III III III III III III III III III
Refrigerant(3) R-32 / A2L/ GWP= 675 in accordance with ARI4
kg 6,1 9,3 9,3 10,9 11,3 11,9 12,7 17,3 18,0
Circuit A
tCO2e 4,1 6,3 6,3 7,4 7,6 8,0 8,6 11,7 12,2
kg 10,9 10,9 10,9 10,9 11,3 16,7 17,5 17,3 18,0
Circuit B
tCO2e 7,4 7,4 7,4 7,4 7,6 11,3 11,8 11,7 12,2
Oil
Circuit A l 6,6 6,6 6,6 13,2 13,2 13,2 13,2 19,8 19,8
Circuit B l 13,2 13,2 13,2 13,2 13,2 19,8 19,8 19,8 19,8
Capacity control Connect'Touch
Minimum capacity % 33 33 25 25 25 20 20 17 17
Condenser All-aluminium micro-channel coils (MCHE)
Fans Axial with rotating impeller
Standard unit
Quantity 3 4 4 4 4 5 5 6 6
Maximum total air flow l/s 11790 15720 15720 15720 15720 19650 19650 23580 23580
Maximum rotation speed r/s 12 12 12 12 12 12 12 12 12
Evaporator Dual-circuit plate heat exchanger
Water volume l 15 15 15 19 27 27 35 44 44
Max. water-side operating pressure without hydraulic
kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000
module
Pump, Victaulic screen filter, relief valve, water and air vent valve,
Hydraulic module (option)
pressure sensors
Centrifugal pump, monocell, 48.3 r/s, low- or high-pressure (as
Pump
required), single or dual (as required)
Expansion tank volume (Option) l 50 50 50 50 50 80 80 80 80
Buffer tank volume (optional) l 550 550 550 550 550 550 550 550 550
Max. water-side operating pressure with hydraulic module kPa 400 400 400 400 400 400 400 400 400
Water connections with or without hydraulic module Victaulic ® type
Connections inches 3 3 3 3 3 4 4 4 4
External diameter mm 88,9 88,9 88,9 88,9 88,9 114,3 114,3 114,3 114,3
Casing paint colour Colour code RAL 7035 & 7024

(1) In dB ref=10-12 W, (A) weighting. Declared dual-number noise emission value in accordance with ISO 4871 with an uncertainty of +/-3 dB(A). Measured in
accordance with ISO 9614-1 and certified by Eurovent.
(2) In dB ref 20 µPa, (A) weighting. Declared dual-number noise emission value in accordance with ISO 4871 with an uncertainty of +/-3 dB(A). For information,
calculated from the sound power Lw(A).
(3) Values are guidelines only. Refer to the unit name plate.

19
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Technical characteristics - cooling only

AQUACIATPOWER ™ LD 1750R1800R2000R2200R2400R2650R2800R2950R3200R3500R

Cooling
Standard unit Nominal capacity kW 428 458 523 586 645 688 743 765 836 890
Full load CA1
performances* EER kW/kW 2,93 2,85 2,85 2,94 2,93 2,83 2,85 2,81 2,77 2,66
SEER 12/7°C Comfort low temp. kWh/kWh 5,37 5,30 5,21 5,24 5,35 5,20 5,43 5,38 5,22 5,07
ηs cool 12/7°C % 212 209 205 207 211 205 214 212 206 200
Seasonal energy
SEER 23/18°C Comfort medium temp. kWh/kWh 6,25 6,12 6,25 6,41 6,59 6,33 6,69 6,60 6,34 6,06
efficiency**
SEPR 12/7°C Process high temp. kWh/kWh 6,38 6,29 6,24 6,26 6,32 6,11 6,17 6,10 6,03 5,79
SEPR -2/-8°C Process medium temp. kWh/kWh 3,43 3,44 3,43 - 3,82 3,83 3,80 3,80 3,73 3,73

Unit + Rated & Nominal capacity kW 451 484 553 616 677 726 782 807 882 944
Seasonal high
performance options CA1
Full load
performances* EER kW/kW 3,14 3,09 3,08 3,15 3,14 3,06 3,07 3,04 3,00 2,92

SEER 12/7°C Comfort low temp. kWh/kWh 5,28 5,24 5,29 5,32 5,32 5,20 5,33 5,30 5,31 5,18
ηs cool 12/7°C % 208 207 209 210 210 205 210 209 209 204
Seasonal energy
SEER 23/18°C Comfort medium temp. kWh/kWh 6,33 6,23 6,32 6,56 6,51 6,28 6,54 6,47 6,56 6,32
efficiency**
SEPR 12/7°C Process high temp. kWh/kWh 6,41 6,32 6,27 6,27 6,33 6,14 6,25 6,18 6,07 5,86
SEPR -2/-8°C Process medium temp. kWh/kWh 3,55 3,55 3,55 - 3,82 3,83 3,79 3,80 3,74 3,74
Sound levels
Unit + High temperature option/Nominal high performance
Sound power(1) dB(A) 94,0 94,0 94,5 97,5 97,5 98,0 98,0 98,5 98,5 99,0
Sound pressure at 10 m(2) dB(A) 61,5 61,5 62,0 65,0 65,0 66,0 65,0 66,0 66,0 66,5
Standard unit
Sound power(1) dB(A) 91,5 91,5 92,0 96,5 96,5 97,0 97,0 97,5 97,5 98,0
Sound pressure at 10 m(2) dB(A) 59,5 59,0 60,0 64,0 64,0 64,5 65,0 65,0 65,0 65,5
Unit + Very Low Noise option
Sound power(1) dB(A) 88,5 88,5 89,0 92,5 92,5 93,0 93,0 93,5 93,5 94,5
Sound pressure at 10 m(2) dB(A) 56,0 56,5 57,0 60,5 60,0 60,5 60,0 61,0 60,5 61,5
Unit + Ultra Low Noise option
Sound power(1) dB(A) 86,5 86,5 87,0 90,0 90,0 90,5 90,5 90,5 90,5 91,0
Sound pressure at 10 m(2) dB(A) 54,5 54,0 55,0 57,5 57,5 58,0 58,0 57,5 58,0 58,5

* In accordance with EN14511-3:2018.


** In accordance with EN14825:2018, average climate conditions
CA1 Cooling mode conditions: evaporator water inlet/outlet temperature 12 °C/7 °C, outdoor air temperature 35 °C, evaporator fouling
factor 0 m2. k/W
Ƞs cool12/7°C & SEER 12/7°C Values in bold comply with Ecodesign Regulation (EU) No. 2016/2281 for Comfort applications
SEER 23/18 °C Values in bold comply with Ecodesign Regulation (EU) No. 2016/2281 for Comfort applications
SEPR 12/7 °C Values calculated in accordance with EN 14825:2016
SEPR -2/-8 °C Values calculated in accordance with EN 14825:2016
IPLV.SI Calculated as per AHRI standard 551-591.
(1) In dB ref=10-12 W, (A) weighting. Declared dual-number noise emission value in accordance with ISO 4871 with an uncertainty of
+/-3 dB(A). Measured in accordance with ISO 9614-1 and certified by Eurovent.
(2) In dB ref 20 µPa, (A) weighting. Declared dual-number noise emission value in accordance with ISO 4871 with an uncertainty of +/-3
dB(A). For information, calculated from the sound power Lw(A).

Eurovent certified values

20
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Technical characteristics - cooling only

AQUACIATPOWER ™ LD 1750R 1800R 2000R 2200R 2400R 2650R 2800R 2950R 3200R 3500R

Dimensions
Standard unit
Length mm 4798 4798 4798 5992 5992 5992 7186 7186 7186 7186
Width mm 2253 2253 2253 2253 2253 2253 2253 2253 2253 2253
Height mm 2324 2324 2324 2324 2324 2324 2324 2324 2324 2324
Unit + water buffer tank module option
Length mm 5992 5992 5992 7186 7186 7186 8380 8380 8380 8380
Operating weight (3)

Standard unit kg 2697 2722 2927 3265 3511 3511 4042 4042 4291 4291
Unit + Ultra Low Noise option kg 2904 2930 3158 3434 3703 3703 4260 4260 4535 4535
Unit + Ultra Low Noise + HP dual-pump hydraulic
kg 3138 3164 3430 3743 4013 4013 4650 4650 4925 4925
module option
Unit + Ultra Low Noise + HP dual-pump hydraulic
kg 4131 4156 4421 4750 5020 5020 5671 5671 5946 5946
module + Water buffer tank module option
Compressors Hermetic Scroll 48.3 r/s
Circuit A 3 3 4 2 3 3 3 3 4 4
Circuit B 4 4 4 3 3 3 4 4 4 4
Number of power stages 7 7 8 5 6 6 7 7 8 8
Unit PED category IV IV IV III III III IV IV IV IV
Refrigerant(3) R-32 / A2L/ GWP= 675 in accordance with ARI4
kg 18,3 18,6 22,8 21,8 23,2 23,2 24,9 24,9 29,5 29,5
Circuit A
tCO2e 12,4 12,6 15,4 14,7 15,7 15,7 16,8 16,8 19,9 19,9
kg 21,9 22,3 22,8 23,2 23,2 23,2 29,5 29,5 29,5 29,5
Circuit B
tCO2e 14,8 15,1 15,4 15,7 15,7 15,7 19,9 19,9 19,9 19,9
Oil
Circuit A l 19,8 19,8 26,4 13,2 19,8 19,8 19,8 19,8 26,4 26,4
Circuit B l 26,4 26,4 26,4 19,8 19,8 19,8 26,4 26,4 26,4 26,4
Capacity control Connect'Touch
Minimum capacity % 14 14 13 20 17 17 14 14 13 13
Condenser All-aluminium micro-channel coils (MCHE)
Fans Axial with rotating impeller
Standard unit
Quantity 7 7 8 9 10 10 11 11 12 12
Maximum total air flow l/s 27510 27510 31440 35370 39300 39300 43230 43230 47160 47160
Maximum rotation speed r/s 12 12 12 12 12 12 12 12 12 12
Evaporator Dual-circuit plate heat exchanger
Water volume l 44 47 53 73 73 73 84 84 84 84
Max. water-side operating pressure without hydraulic
kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
module
Pump, Victaulic screen filter, relief valve, water and air vent valve, pressure
Hydraulic module (option)
sensors
Centrifugal pump, monocell, 48.3 r/s, low- or high-pressure (as required),
Pump
single or dual (as required)
Expansion tank volume (Option) l 80 80 80 80 80 80 80 80 80 80
Buffer tank volume (optional) l 550 550 550 550 550 550 550 550 550 550
Max. water-side operating pressure with hydraulic
kPa 400 400 400 400 400 400 400 400 400 400
module
Water connections with or without hydraulic module Victaulic® type
Connections inches 4 4 4 5 5 5 5 5 5 5
External diameter mm 114,3 114,3 114,3 139,7 139,7 139,7 139,7 139,7 139,7 139,7
Casing paint colour Colour code RAL 7035 & 7024

(1) In dB ref=10-12 W, (A) weighting. Declared dual-number noise emission value in accordance with ISO 4871 with an uncertainty of +/-3 dB(A). Measured in
accordance with ISO 9614-1 and certified by Eurovent.
(2) In dB ref 20 µPa, (A) weighting. Declared dual-number noise emission value in accordance with ISO 4871 with an uncertainty of +/-3 dB(A). For information,
calculated from the sound power Lw(A).
(3) Values are guidelines only. Refer to the unit name plate.

21
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Technical characteristics - reversible heat pump

AQUACIATPOWER ™ ILD 0602R 0700R 0800R 0900R 1000R 1150R

Heating
Nominal capacity kW 178 197 237 256 275 317
HA1
Standard unit COP kW/kW 3,88 3,80 3,84 3,84 3,82 3,82
Full load performances* Nominal capacity kW 173 192 231 250 269 310
HA2
COP kW/kW 3,16 3,09 3,14 3,12 3,11 3,10
SCOP30/35°C kWh/kWh 3,44 3,45 3,39 3,47 3,48 3,57
Seasonal energy
HA1 ηs heat 30/35°C % 135 135 133 136 136 140
efficiency**
Prated kW 139 155 186 200 217 250
Unit + Rated & Seasonal high Nominal capacity kW 178 197 237 256 275 317
performance options HA1
Full load performances* COP kW/kW 3,88 3,80 3,84 3,84 3,82 3,82
SCOP30/35°C kWh/kWh 3,67 3,66 3,74 3,77 3,80 3,87
Seasonal energy
HA1 ηs heat 30/35°C % 144 143 147 148 149 152
efficiency**
Prated kW 138 155 185 200 216 250
Cooling
Standard unit Nominal capacity kW 155 171 204 223 239 285
CA1
Full load performances* EER 2,73 2,55 2,73 2,63 2,56 2,66
Seasonal energy SEER 12/7°C Comfort low temp. kWh/kWh 4,17 4,01 4,18 4,08 4,04 4,48
efficiency** SEPR 12/7°C Process high temp. kWh/kWh 4,68 4,51 4,64 4,52 4,50 4,83
Unit + Rated & Seasonal high Nominal capacity kW 164 181 215 236 254 302
performance options CA1
Full load performances* EER kW/kW 2,87 2,72 2,86 2,80 2,76 2,85

Seasonal energy SEER 12/7°C Comfort low temp. kWh/kWh 4,41 4,23 4,48 4,41 4,34 4,78
efficiency** SEPR 12/7°C Process high temp. kWh/kWh 5,47 5,23 5,41 5,23 5,15 5,49
Sound levels
Unit + High temperature option/Nominal high performance
Sound power(1) dB(A) 90,5 91,0 91,5 92,0 92,0 93,0
Sound pressure at 10 m(2) dB(A) 58,5 59,0 59,5 60,0 60,0 61,0
Standard unit
Sound power(1) dB(A) 88,0 88,5 89,0 89,5 89,5 90,5
Sound pressure at 10 m(2) dB(A) 55,5 56,0 56,5 57,0 57,0 58,0
Unit + Very Low Noise option(3)
Sound power(1) dB(A) 85,0 86,0 86,5 87,0 87,0 88,0
Sound pressure at 10 m(2) dB(A) 53,0 53,5 54,0 54,5 54,5 55,5
Unit + Ultra Low Noise option(3)
Sound power(1) dB(A) 83,0 84,0 84,5 85,0 85,0 86,0
Sound pressure at 10 m(2) dB(A) 51,0 52,0 52,5 53,0 53,0 54,0

* In accordance with EN14511-3:2018.


** In accordance with EN14825:2018, average climate conditions
HA1 Heating mode conditions: Water type heat exchanger water inlet/outlet temperature 30 °C/35 °C, outdoor air temperature tdb/twb = 7 °C
db/6 °C wb, evaporator fouling factor 0 m2. k/W
HA2 Heating mode conditions: Water type heat exchanger water inlet/outlet temperature 40 °C/45 °C, outdoor air temperature tdb/twb = 7 °C
db/6 °C wb, evaporator fouling factor 0 m2. k/W
CA1 Cooling mode conditions: evaporator water inlet/outlet temperature 12 °C/7 °C, outdoor air temperature 35 °C, evaporator fouling factor
0 m2. k/W
Ƞs heat 30/35°C & SCOP 30/35°C Values in bold comply with Ecodesign Regulation (EU) No. 813/2013 for Heating applications
SEER 12/7 °C & SEPR 12/7 °C Applicable Ecodesign regulation (EU) No. 2016/2281
(1) In dB ref=10-12 W, (A) weighting. Declared dual-number noise emission value in accordance with ISO 4871 with an uncertainty of +/-3
dB(A). Measured in accordance with ISO 9614-1 and certified by Eurovent.
(2) In dB ref 20 µPa, (A) weighting. Declared dual-number noise emission value in accordance with ISO 4871 with an uncertainty of +/-3
dB(A). For information, calculated from the sound power Lw(A).

Eurovent certified values

22
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Technical characteristics - reversible heat pump

AQUACIATPOWER ™ ILD 0602R 0700R 0800R 0900R 1000R 1150R

Dimensions
Standard unit
Length mm 2410 2410 2410 2410 2410 3604
Width mm 2253 2253 2253 2253 2253 2253
Height mm 2324 2324 2324 2324 2324 2324
Unit + water buffer tank module option(3) mm 3604 3604 3604 3604 3604 4798
Length mm 3604 3604 3604 3604 3604 4798
Operating weight (3)

Standard unit kg 1569 1575 1784 1811 1817 2394


Unit + Ultra Low Noise option kg 1672 1678 1918 1946 1952 2552
Unit + Ultra Low Noise + HP dual-pump hydraulic module option kg 1808 1814 2065 2092 2098 2747
Unit + Ultra Low Noise + HP dual-pump hydraulic module + Water 2791 2797 3048 3075 3081 3756
kg
buffer tank module option
Compressors Hermetic Scroll 48.3 r/s
Circuit A 1 1 2 2 2 2
Circuit B 2 2 2 2 2 3
Number of power stages 3 3 4 4 4 5
Unit PED category III III III III III III
Refrigerant(3) R-32 / A2L/ GWP= 675 in accordance with ARI4
kg 10,5 10,5 16,0 16,0 16,0 16,0
Circuit A
tCO2e 7,1 7,1 10,8 10,8 10,8 10,8
kg 16,0 16,0 16,0 16,0 16,0 28,5
Circuit B
tCO2e 10,8 10,8 10,8 10,8 10,8 19,2
Oil
Circuit A l 6,6 6,6 13,2 13,2 13,2 13,2
Circuit B l 13,2 13,2 13,2 13,2 13,2 19,8
Capacity control Connect'Touch
Minimum capacity % 33 33 25 25 25 20
Condenser Grooved copper tubes and aluminium fins
Fans Axial with rotating impeller
Standard unit
Quantity 3 3 4 4 4 5
Maximum total air flow (cooling mode) l/s 11790 11790 15720 15720 15720 19650
Maximum rotation speed (heating mode) r/s 12 12 12 12 12 12
Maximum total air flow (heating mode) l/s 14460 14460 19280 19280 19280 24100
Maximum rotation speed (heating mode) r/s 16 16 16 16 16 16
Evaporator Dual-circuit plate heat exchanger
Water volume l 16,2 16,2 16,2 20,7 20,7 38,7
Max. water-side operating pressure without hydraulic module kPa 1000 1000 1000 1000 1000 1000
Pump, Victaulic screen filter, relief valve, water and air vent valve,
Hydraulic module (option) pressure sensors
Centrifugal pump, monocell, 48.3 r/s, low- or high-pressure (as
Pump required), single or dual (as required)
Expansion tank volume (Option) l 50 50 50 50 50 80
Buffer tank volume (optional) l 550 550 550 550 550 550
Max. water-side operating pressure with hydraulic module kPa 400 400 400 400 400 400
Water connections with or without hydraulic module Victaulic® type
Connections inches 3 3 3 3 3 4
External diameter mm 88,5 88,6 88,7 88,8 88,9 114,3
Casing paint colour Colour code RAL 7035 & 7024

(3) Values are guidelines only. Refer to the unit name plate.

23
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Technical characteristics - reversible heat pump

AQUACIATPOWER ™ ILD 1250R 1400R 1500R 1600R 1750R 2000R

Heating
Nominal capacity kW 336 387 406 441 467 537
HA1
Standard unit COP kW/kW 3,81 3,82 3,81 3,80 3,73 3,80
Full load performances* Nominal capacity kW 329 378 397 431 458 526
HA2
COP kW/kW 3,09 3,10 3,09 3,10 3,03 3,09
SCOP30/35°C kWh/kWh 3,58 3,55 3,57 3,54 3,53 3,57
Seasonal energy
HA1 ηs heat 30/35°C % 140 139 140 139 138 140
efficiency**
Prated kW 266 305 321 349 371 425
Unit + Rated & Seasonal high Nominal capacity kW 336 387 406 441 467 537
performance options HA1
Full load performances* COP kW/kW 3,81 3,82 3,81 3,80 3,73 3,80
SCOP30/35°C kWh/kWh 3,86 3,90 3,91 3,92 3,89 3,96
Seasonal energy
HA1 ηs heat 30/35°C % 151 153 153 154 153 155
efficiency**
Prated kW 265 305 320 348 370 424
Cooling
Standard unit Nominal capacity kW 305 341 358 389 414 470
CA1
Full load performances* EER 2,59 2,64 2,57 2,64 2,55 2,55
Seasonal energy SEER 12/7°C Comfort low temp. kWh/kWh 4,50 4,46 4,33 4,44 4,38 4,32
efficiency** SEPR 12/7°C Process high temp. kWh/kWh 4,76 4,93 4,79 4,94 4,82 4,83
Unit + Rated & Seasonal high Nominal capacity kW 324 362 381 413 439 500
performance options CA1
Full load performances* EER kW/kW 2,80 2,82 2,76 2,81 2,74 2,73

Seasonal energy SEER 12/7°C Comfort low temp. kWh/kWh 4,81 4,88 4,87 4,81 4,75 4,81
efficiency** SEPR 12/7°C Process high temp. kWh/kWh 5,34 5,60 5,40 5,60 5,43 5,47
Sound levels
Unit + High temperature option/Nominal high performance
Sound power(1) dB(A) 93,5 94,0 94,0 94,5 94,5 95,0
Sound pressure at 10 m(2) dB(A) 61,5 62,0 62,0 62,0 62,0 62,5
Standard unit
Sound power(1) dB(A) 91,0 91,5 91,5 92,0 92,5 93,0
Sound pressure at 10 m(2) dB(A) 58,5 59,5 59,5 60,0 60,0 60,5
Unit + Very Low Noise option(3)
Sound power(1) dB(A) 88,0 89,0 89,0 89,5 90,0 90,0
Sound pressure at 10 m(2) dB(A) 55,5 56,5 56,5 57,0 57,5 57,5
Unit + Ultra Low Noise option(3)
Sound power(1) dB(A) 86,0 86,5 87,0 87,5 87,5 88,0
Sound pressure at 10 m(2) dB(A) 54,0 54,5 55,0 55,5 55,5 56,0

* In accordance with EN14511-3:2018.


** In accordance with EN14825:2018, average climate conditions
HA1 Heating mode conditions: Water type heat exchanger water inlet/outlet temperature 30 °C/35 °C, outdoor air temperature tdb/twb = 7 °C
db/6 °C wb, evaporator fouling factor 0 m2. k/W
HA2 Heating mode conditions: Water type heat exchanger water inlet/outlet temperature 40 °C/45 °C, outdoor air temperature tdb/twb = 7 °C
db/6 °C wb, evaporator fouling factor 0 m2. k/W
CA1 Cooling mode conditions: evaporator water inlet/outlet temperature 12 °C/7 °C, outdoor air temperature 35 °C, evaporator fouling factor
0 m2. k/W
Ƞs heat 30/35°C & SCOP 30/35°C Values in bold comply with Ecodesign Regulation (EU) No. 813/2013 for Heating applications
SEER 12/7 °C & SEPR 12/7 °C Applicable Ecodesign regulation (EU) No. 2016/2281
(1) In dB ref=10-12 W, (A) weighting. Declared dual-number noise emission value in accordance with ISO 4871 with an uncertainty of +/-3
dB(A). Measured in accordance with ISO 9614-1 and certified by Eurovent.
(2) In dB ref 20 µPa, (A) weighting. Declared dual-number noise emission value in accordance with ISO 4871 with an uncertainty of +/-3
dB(A). For information, calculated from the sound power Lw(A).

Eurovent certified values

24
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Technical characteristics - reversible heat pump

AQUACIATPOWER ™ ILD 1250R 1400R 1500R 1600R 1750R 2000R

Dimensions
Standard unit
Length mm 3604 3604 3604 4798 4798 4798
Width mm 2253 2253 2253 2253 2253 2253
Height mm 2324 2324 2324 2324 2324 2324
Unit + water buffer tank module option(3) mm 4798 4798 4798 5992 5992 5992
Length mm 4798 4798 4798 5992 5992 5992
Operating weight (3)

Standard unit kg 2452 2672 2678 3154 3180 3430


Unit + Ultra Low Noise option kg 2611 2855 2861 3361 3387 3661
Unit + Ultra Low Noise + HP dual-pump hydraulic module option kg 2806 3089 3095 3595 3658 3932
Unit + Ultra Low Noise + HP dual-pump hydraulic module + Water 3815 4098 4104 4595 4658 4932
kg
buffer tank module option
Compressors Hermetic Scroll 48.3 r/s
Circuit A 2 2 2 3 3 4
Circuit B 3 4 4 4 4 4
Number of power stages 5 6 6 7 7 8
Unit PED category IV IV IV IV IV IV
Refrigerant(3) R-32 / A2L/ GWP= 675 in accordance with ARI4
kg 18,0 18,0 18,0 29,0 29,0 35,0
Circuit A
tCO2e 12,2 12,2 12,2 19,6 19,6 23,6
kg 28,5 34,0 34,0 34,5 35,0 35,0
Circuit B
tCO2e 19,2 23,0 23,0 23,3 23,6 23,6
Oil
Circuit A l 13,2 13,2 13,2 19,8 19,8 26,4
Circuit B l 19,8 26,4 26,4 26,4 26,4 26,4
Capacity control Connect'Touch
Minimum capacity % 20 17 17 14 14 13
Condenser Grooved copper tubes and aluminium fins
Fans Axial with rotating impeller
Standard unit
Quantity 5 6 6 7 7 8
Maximum total air flow (cooling mode) l/s 19650 23580 23580 27510 27510 31440
Maximum rotation speed (heating mode) r/s 12 12 12 12 12 12
Maximum total air flow (heating mode) l/s 24100 28920 28920 33740 33740 38560
Maximum rotation speed (heating mode) r/s 16 16 16 16 16 16
Evaporator Dual-circuit plate heat exchanger
Water volume l 48,6 48,6 48,6 48,6 52,2 58,5
Max. water-side operating pressure without hydraulic module kPa 1000 1000 1000 1000 1000 1000
Pump, Victaulic screen filter, relief valve, water and air vent valve,
Hydraulic module (option) pressure sensors
Centrifugal pump, monocell, 48.3 r/s, low- or high-pressure (as
Pump required), single or dual (as required)
Expansion tank volume (Option) l 80 80 80 80 80 80
Buffer tank volume (optional) l 550 550 550 550 550 550
Max. water-side operating pressure with hydraulic module kPa 400 400 400 400 400 400
Water connections with or without hydraulic module Victaulic® type
Connections inches 4 4 4 4 4 4
External diameter mm 114,4 114,5 114,6 114,7 114,8 114,9
Casing paint colour Colour code RAL 7035 & 7024

(3) Values are guidelines only. Refer to the unit name plate.

25
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Caractéristiques électriques
■ Basic unit (excluding pump)

AQUACIATPOWER ™ LD 0602R 0650R 0750R 0900R 1100R 1200R 1350R 1400R 1600R 1750R

Power circuit supply


Nominal voltage V-ph-Hz 400-3-50
Voltage range V 360-440
Control circuit supply 24 V via internal transformer
Maximum operating input power(1) or (2)
Circuit A&B kW 71,6 77,2 86,8 95,4 114,6 128,9 143,3 157,5 171,9 186,2
Power factor at maximum power(1) or (2)
Displacement Power Factor (Cos Phi), standard unit 0,83 0,83 0,83 0,83 0,83 0,83 0,83 0,83 0,83 0,83
Maximum operating current draw (Un)(1) or (2)
Standard unit A 123,9 134,4 151,0 165,2 198,4 223,1 248,0 272,7 297,6 322,3
Maximum current (Un-10%)(1) or (2)
Standard unit A 132,6 143,8 161,8 176,8 212,8 239 266 292,2 319,2 345,4
Maximum start-up current (Un) (2) + (3)

Standard unit A 300 347 364 341 411 436 461 485 510 535
Unit + Electronic soft starter option A 257 295 312 298 359 384 409 433 458 483

AQUACIATPOWER ™ LD 1800R 2000R 2200R 2400R 2650R 2800R 2950R 3200R 3500R

Power circuit supply


Nominal voltage V-ph-Hz 400-3-50
Voltage range V 360-440
Control circuit supply 24 V via internal transformer
Maximum operating input power(1) or (2)
Circuit A&B kW 200,6 229,2 246,7 271,9 295,3 316,7 328,4 361,4 392,6
Power factor at maximum power(1) or (2)
Displacement Power Factor (Cos Phi), standard unit 0,83 0,83 0,83 0,83 0,83 0,83 0,83 0,83 0,83
Maximum operating current draw (Un)(1) or (2)
Standard unit A 347,2 396,8 432,3 478,0 517,0 556,2 575,7 634,4 686,4
Maximum current (Un-10%)(1) or (2)
Standard unit A 372,4 425,6 464,8 514 556 598,2 619,2 682,4 738,4
Maximum start-up current (Un) (2) + (3)

Standard unit A 560 609 763 815 848 893 906 971 1017
Unit + Electronic soft starter option A 508 557 680 732 765 811 824 889 934

AQUACIATPOWER ™ ILD 0602R 0700R 0800R 0900R 1000R 1150R 1250R 1400R 1500R 1600R 1750R 2000R

Power circuit supply


Nominal voltage V-ph-Hz 400-3-50
Voltage range V 360-440
Control circuit supply 24 V via internal transformer
Maximum operating input power(1) or (2)
Circuit A&B kW 71,6 81,2 95,4 105,0 114,6 133,7 143,3 162,3 171,9 186,2 200,6 229,2
Power factor at maximum power(1) or (2)
Displacement Power Factor (Cos Phi), standard unit 0,83 0,83 0,83 0,83 0,83 0,83 0,83 0,83 0,83 0,83 0,83 0,83
Maximum operating current draw (Un)(1) or (2)
Standard unit A 129,0 145,6 172,0 188,6 205,2 239,9 256,5 291,2 307,8 334,2 359,1 410,4
Maximum current (Un-10%)(1) or (2)
Standard unit A 135,6 151,6 180,8 196,8 212,8 250 266 303,2 319,2 348,4 372,4 425,6
Maximum start-up current (Un) (2) + (3)
Standard unit A 300 355 341 394 411 444 461 494 510 535 560 609
Unit + Electronic soft starter option A 257 303 298 342 359 392 409 442 458 483 508 557

(1) Values at the unit's permanent maximum operating condition (as shown on the unit's nameplate).
(2) Values at the unit's maximum operating condition (as shown on the unit's nameplate).
(3) Maximum operating current of the smallest compressor(s) + fan current + locked rotor current of the largest compressor.

26
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Caractéristiques électriques
■ Short circuit current withstand capability (TN system(1))

AQUACIATPOWER ™ LD 0602R 0650R 0750R 0900R 1100R 1200R 1350R 1400R 1600R

Rated short-circuit withstand currents


Rated short time (1s) current - Icw kA eff 8,5 8,5 8,5 8,5 8,5 20 20 20 20
Rated peak current - Ipk kA pk 330 330 330 330 330 330 330 330 330
Value with upstream protection (1)

Rated conditional short circuit current Icc kA eff 50 50 50 50 50 50 50 50 50


Associated protection - type INS250 INS250 INS250 INS250 INS250 INS400 INS400 INS400 INS400
Micrologic Micrologic Micrologic
TM160D / TM200D / TM200D / TM250D / TM250D / TM250D /
Associated protection - rating/reference 2.3 400 A / 2.3 400 A / 2.3 400 A /
LV430840 LV431831 LV431831 LV431831 LV431831 LV431831
LV432693 LV432693 LV432693

AQUACIATPOWER ™ LD 1750R 1800R 2000R 2200R 2400R 2650R 2800R 2950R 3200R 3500R

Rated short-circuit withstand


currents
Rated short time (1s) current -
kA eff 20 20 20 20 20 20 35 35 35 35
Icw
Rated peak current - Ipk kA pk 330 330 330 330 330 330 330 330 330 330
Value with upstream protection (1)

Rated conditional short circuit


kA eff 50 50 50 50 50 50 50 50 50 50
current Icc
Associated protection - type INS400 INS500 INS500 INS630 INS630 INS630 INS800 INS800 INS800 INS800
Micrologic Micrologic Micrologic Micrologic Micrologic Micrologic Micrologic Micrologic Micrologic Micrologic
Associated protection - rating/
2.3 400 A / 2.3 630 A / 2.3 630 A / 2.3 630 A / 2.3 630 A / 2.3 630 A / 5.0 800 A 5.0 800 A 5.0 800 A 5.0 800 A
reference
LV432693 LV432893 LV432893 LV432893 LV432893 LV432893 /34426 /34426 /34426 /34426

AQUACIATPOWER ™ ILD 0602R 0700R 0800R 0900R 1000R 1150R

Rated short-circuit withstand currents


Rated short time (1s) current - Icw kA eff 8,5 8,5 8,5 8,5 8,5 20
Rated peak current - Ipk kA pk 330 330 330 330 330 330
Value with upstream protection (1)

Rated conditional short circuit current Icc kA eff 50 50 50 50 50 50


Associated protection - type INS250 INS250 INS250 INS250 INS250 INS400
Micrologic
TM160D / TM200D / TM250D / TM250D / TM250D /
Associated protection - rating/reference 2.3 400 A /
LV430840 LV431831 LV431831 LV431831 LV431831
LV432693

AQUACIATPOWER ™ ILD 1250R 1400R 1500R 1600R 1750R 2000R

Rated short-circuit withstand currents


Rated short time (1s) current - Icw kA eff 20 20 20 20 20 20
Rated peak current - Ipk kA pk 330 330 330 330 330 330
Value with upstream protection (1)

Rated conditional short circuit current Icc kA eff 50 50 50 50 50 50


Associated protection - type INS400 INS400 INS400 INS400 INS500 INS500
Micrologic Micrologic Micrologic Micrologic Micrologic Micrologic
Associated protection - rating/reference 2.3 400 A / 2.3 400 A / 2.3 400 A / 2.3 400 A / 2.3 630 A / 2.3 630 A /
LV432693 LV432693 LV432693 LV432693 LV432893 LV432893

(1) If another current limitation protection device is used, its time-current and thermal constraint (I²t) trip characteristics must be at least equivalent to those of the
recommended protection.
Note: The short-circuit withstand current capability values above have been established for the TN system.

27
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

80°C
Partial recovery with desuperheater
The AQUACIATPOWER ™ range may be equipped as an option with an energy recovery function using a desuperheater.
Heat from gases released by the compressors is recovered directly by a type of heat exchanger called a desuperheater located
on the unit to produce free, additional hot water.
This optional configuration requires assembly in our factories and is by order only.

■ Refrigeration circuit diagram


This refrigeration diagram illustrates a unit with a desuperheater on each refrigerating circuit. For heat recovery to be possible,
the unit must be operating. For the same cooling capacity, the desuperheater provides a source of free hot water and lowers the
unit's electrical power consumption.
Discharge C1

Suction C1 C2

HP

Water LP
Oil

Compressor 1
Water
Desuperheater HP Evaporator
LP

Compressor 2

C2

Air-cooled condenser C1: Refrigerant circuit No. 1


C2: Refrigerant circuit No. 2

■ Hydraulic connections: configuration and precautions


The hydraulic supply for each desuperheater is delivered in parallel. In order to ensure that the unit can start and operate under
the correct conditions, the desuperheater circuit water loop must be as short as possible and be able to increase quickly in
temperature. The minimum desuperheater water inlet temperature is 30 °C. It may require the use of a three-way valve with its
controller and a sensor controlling the minimum water inlet temperature.
Note:
The water loop for the desuperheater circuit must include an expansion vessel and a valve. Special attention should be paid when
selecting the expansion vessel as the recovery water circuit can reach 120°C if the pump is turned off or if no hot water is consumed

■ Operating limits

LD units

Desuperheater Minimum Maximum

Water inlet temperature at start-up °C 30 (1) 75


Water outlet temperature during operation °C 45 80
Water inlet temperature on shut-down °C 3 75

ILD units

Desuperheater Minimum Maximum

Water inlet temperature at start-up °C 30 (1) 60


Water outlet temperature during operation °C 45 80
Water inlet temperature on shut-down °C 3 60
Note: Do not exceed the maximum operating temperature.
(1) On start-up, the water inlet temperature must not be below 25 °C. On lower temperature installations, a 3-way valve is required until the desuperheater water
outlet reaches 45 °C.

28
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

80°C
Partial recovery with desuperheater
Cooling mode operating range Heating mode operating range
60
40
55
Part load, all sizes 35
50
DSH
30

°C
45 Partial load ILD only OFF

60
to

°C
40

45
25

70

°C
r=

°C
outside air temperature (°C)

to

80
te
35

60
ea

80
to
Inlet air temperature (°C)

rh
20

70

t=
pe

er

=
30

at

tle
su

r
te
e
De

ou
rh

ea
pe

rh
15

er
25

su

pe

at
De

su

w
De

T
20

W
10

rL
te
15

ea
rh
5

pe
10

su

g
in
De

st ing ad
0

fro dur fflo

e
5

cl
lo

cy
tia

g
in
n
te
0 -5

po

e
th
-5
-10
-10 Part load

-15
-15

-20 -20
40 45 50 55 60 65 70 75 80 85 15 20 25 30 35 40 45 50 55 60

Desuperheater water outlet temperature (°C) Leaving water temperature (°C)

Notes
1. Desuperheater water type heat exchanger ∆T = 10K.
2. The water type heat exchanger is protected against frost down to -20 °C (with Water exchanger frost protection option or water type heat exchanger and hydraulic
module frost protection option (if present) or water loop protected by antifreeze solution for outdoor temperatures < 0 °C)
The water loop on the desuperheater water type heat exchanger must be protected by the customer for outdoor temperatures below 0 °C
3. These ranges are guidelines only. Verify the operating range with the electronic catalogue.
Key

Operating range at full load

Extension of the operating range, LD 602 to 1400 unit: frost protection required (see note 2).
Heating mode: Part load at inlet air temperature between -10 and -15 °C.
Cooling mode: Partial load above 46 °C of inlet air temperature.
Limited desuperheater power.
operating range at part load for ILD only with limited desuperheater power.
Potential load shedding during the defrosting cycle at low outdoor temperatures (see operating range for ILD 602R - 2000R)
Limited desuperheater power. Please refer to the selection in the electronic catalogue.
Desuperheater not operational

Limited desuperheater water outlet temperature

29
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

80°C
Partial recovery with desuperheater
■ Technical specifications

AQUACIATPOWER ™ LD 0602R 0650R 0750R 0900R 1100R 1200R 1350R 1400R 1600R 1750R

Desuperheater in circuits A/B Brazed-plate heat exchanger


2/ 2/ 3,75 / 3,75 / 3,75 / 3,75 / 3,75 / 5,5 / 5,5 / 5,5 /
Water volume circuits A/B l
3,75 3,75 3,75 3,75 3,75 5,5 5,5 5,5 5,5 7,5
Maximum operating pressure, water side kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Hydraulic connections Victaulic
Connection in 2" 2" 2" 2" 2" 2" 2" 2" 2" 2"
External diameter mm 60,3 60,3 60,3 60,3 60,3 60,3 60,3 60,3 60,3 60,3
Operating weight (1)

Standard unit + desuperheater option kg 1409 1457 1457 1581 1616 2055 2109 2271 2329 2757
Unit + Ultra Low Noise + desuperheater option kg 1492 1540 1540 1690 1725 2182 2236 2416 2474 2920
Unit + Ultra Low Noise + HP dual-pump hydraulic
kg 1627 1675 1675 1825 1871 2331 2431 2611 2669 3154
module + desuperheater option
Unit + Ultra Low Noise + HP dual-pump hydraulic
module + Water buffer tank module + kg 2610 2658 2658 2808 2854 3318 3417 3597 3654 4146
desuperheater option

AQUACIATPOWER ™ LD 1800R 2000R 2200R 2400R 2650R 2800R 2950R 3200R 3500R

Desuperheater in circuits A/B Brazed-plate heat exchanger


5,5 / 7,5 / 7,5 / 11 / 11 / 11 / 11 / 15 / 15 /
Water volume circuits A/B l
7,5 7,5 11 11 11 15 15 15 15
Maximum operating pressure, water side kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000
Hydraulic connections Victaulic
Connection in 2" 2" 2" 2" 2" 2" 2" 2" 2"
External diameter mm 60,3 60,3 60,3 60,3 60,3 60,3 60,3 60,3 60,3
Operating weight (1)
Standard unit + desuperheater option kg 2782 2987 3325 3571 3571 4102 4102 4351 4351
Unit + Ultra Low Noise + desuperheater option kg 2945 3168 3458 3724 3724 4276 4276 4545 4545
Unit + Ultra Low Noise + HP dual-pump hydraulic
kg 3179 3439 3768 4034 4034 4665 4665 4934 4934
module + desuperheater option
Unit + Ultra Low Noise + HP dual-pump hydraulic
module + Water buffer tank module + kg 4171 4431 4775 5041 5041 5686 5686 5955 5955
desuperheater option
(1) Weights are guidelines only. Refer to the unit name plate.

30
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

80°C
Partial recovery with desuperheater
■ Technical specifications

AQUACIATPOWER ™ ILD 0602R 0700R 0800R 0900R 1000R 1150R

Desuperheater in circuits A/B Brazed-plate heat exchanger


3,75 / 3,75 / 3,75 /
Water volume circuits A/B l 2 / 3,75 2 / 3,75 3,75 / 5,5
3,75 3,75 3,75
Maximum operating pressure, water side kPa 1000 1000 1000 1000 1000 1000
Hydraulic connections Victaulic
Connection in 2" 2" 2" 2" 2" 2"
External diameter mm 60,3 60,3 60,3 60,3 60,3 60,3
Operating weight (1)

Standard unit + desuperheater option kg 1651 1657 1873 1900 1906 2500
Unit + Ultra Low Noise + desuperheater option kg 1735 1741 1981 2009 2015 2626
Unit + Ultra Low Noise + HP dual-pump hydraulic module +
kg 1870 1876 2128 2156 2162 2821
desuperheater option
Unit + Ultra Low Noise + HP dual-pump hydraulic module +
kg 2853 2859 3111 3138 3144 3831
Water buffer tank module + desuperheater option

AQUACIATPOWER ™ ILD 1250R 1400R 1500R 1600R 1750R 2000R

Desuperheater in circuits A/B Brazed-plate heat exchanger


Water volume circuits A/B l 3,75 / 5,5 3,75 / 7,5 3,75 / 7,5 5,5 / 7,5 5,5 / 7,5 7,5 / 7,5
Maximum operating pressure, water side kPa 1000 1000 1000 1000 1000 1000
Hydraulic connections Victaulic
Connection in 2" 2" 2" 2" 2" 2"
External diameter mm 60,3 60,3 60,3 60,3 60,3 60,3
Operating weight (1)

Standard unit + desuperheater option kg 2558 2785 2791 3283 3309 3565
Unit + Ultra Low Noise + desuperheater option kg 2685 2930 2936 3446 3472 3746
Unit + Ultra Low Noise + HP dual-pump hydraulic module +
kg 2880 3164 3170 3681 3744 4018
desuperheater option
Unit + Ultra Low Noise + HP dual-pump hydraulic module +
kg 3889 4173 4179 4680 4743 5017
Water buffer tank module + desuperheater option
(1) Values are guidelines only. Refer to the unit name plate.

31
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

65°C
Total heat recovery
The AQUACIATPOWER ™ range can be equipped with a total heat recovery function as an option
The principle consists of producing free additional hot water at a high temperature of up to 65°C by adding a dual-circuit water-
cooled condenser which allows all the heat released by the machine to be recovered.
This optional configuration requires assembly in our factories and is by order only.

Operating principle
If hot water production is required, the compressor discharge gases are directed towards the heat recovery condenser. The
refrigerant releases its heat to the hot water that leaves the condenser at a temperature of up to 65 °C. In this way, 100% of the
heat rejected by the liquid chiller can be used to produce hot water. When the demand for heat is satisfied, the hot gas is again
directed towards the air condenser where the heat is rejected to the outside air by the fans.
The hot water temperature is controlled by the machine's Connect Touch control unit.
Note: Heat recovery is only possible if the machine produces cold water at the same time.

■ Operating limits

LD units Operating range in heat recovery mode


70

Heat recovery water outlet temperature (°C)


Total recovery exchanger Min. Max. 65
63

Water inlet temperature at start-up °C 25 (1) 60 60

Water outlet temperature during operation °C 30 65 55


54
Water inlet temperature on shut-down °C 3 70 °C
50 0
e
Note: Do not exceed the maximum operating temperature. tur °C
ra 0
(1) On start-up, the water inlet temperature must not be below 25 °C. For 45 pe -1
m re
installations with a lower temperature, a three-way valve is necessary. te tu
nt era
e
40 bi p
Am em
Operating range in cooling mode tt
ien
35 b
Am
30
Partial load for LD
2600-3200
25
For LD 3500
20
Outdoor air temperature (°C)

-10 -5 0 5 10 15 20 25

Evaporator water outlet temperature (°C)

Key

Full load

Low temperature brine solution option


Limitation to a part load of 50% below an ambient air
temperature of -10 °C
Limitation to a part load of 50 % below an ambient air
temperature of 0 °C
Notes
- Evaporator ∆T = 5K
- Condenser ∆T = 5K up to 30RBP550 and 8K for sizes 610R to 950R
- These ranges are guidelines only. Verify the operating range with the electronic
catalogue.
Evaporator water outlet temperature (°C)
Key

Full load
Low temperature brine solution option

Partial load for LD 2600-3200

Partial load for LD 3500


Notes
1. Evaporator ∆T = 5K
2. The unit must be either equipped with antifreeze protection options for the water
type heat exchangers (evaporator and heat recovery) and the hydraulic module
(if used), or the water loop must be protected against freezing by the installer with
an antifreeze solution
3. These ranges are guidelines only. Verify the operating range with the electronic
catalogue.

32
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

65°C
Total heat recovery
■ Technical specifications

AQUACIATPOWER ™ LD 0602R 0650R 0750R 0900R 1100R 1200R 1350R 1400R 1600R 1750R

Total recovery exchanger Brazed-plate heat exchanger


Water volume circuits A/B l 20 24 24 29 29 31 31 31 31 44
Maximum operating pressure, water side kPa 600 600 600 600 600 600 600 600 600 600
Hydraulic connections Victaulic
Connection in 3" 3" 3" 3" 3" 4" 4" 4" 4" 4"
External diameter mm 88,9 88,9 88,9 88,9 88,9 114,3 114,3 114,3 114,3 114,3
Operating weight (1)

Standard unit + total recovery kg 1490 1580 1580 1740 1775 2300 2354 4561 2620 3084
Unit + Ultra Low Noise + total recovery option kg 1573 1663 1663 1849 1884 2427 2481 4706 2765 3247

AQUACIATPOWER ™ LD 1800R 2000R 2200R 2400R 2650R 2800R 2950R 3200R 3500R

Total recovery exchanger Brazed-plate heat exchanger


Water volume circuits A/B l 44 44 61 61 61 61 61 61 61
Maximum operating pressure, water side kPa 600 600 600 600 600 600 600 600 600
Hydraulic connections Victaulic
Connection in 4" 4" 5" 5" 5" 5" 5" 5" 5"
External diameter mm 114,3 114,3 139,7 139,7 139,7 139,7 139,7 139,7 139,7
Operating weight (1)
Standard unit + total recovery kg 3110 3315 3848 4093 4093 4627 4627 4876 4876
Unit + Ultra Low Noise + total recovery option kg 3273 3496 3981 4246 4246 4801 4801 5070 5070
(1) Weights are guidelines only. Refer to the unit name plate.

33
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Free cooling system


Reducing operating costs and protecting the environment have Adaptations to requirements
become the key concerns, both for air conditioning applications,
and for industrial processes and cooling data centres. Depending on the requirements of the user, the AQUACIATPOWER
™ LD free cooling is available with 2 performance levels:
The free cooling option allows significant energy savings to be
- Total hydraulic free cooling on the 2 circuits, specifically
made in all applications that require cooling throughout the
designed for installations which have major cooling
year, particularly when used in colder climates. In these regions,
requirements all year round (industrial processes, data
free cooling can be used to fulfil a large proportion of the cooling
centres)
requirements both economically and in a way that respects the
- Partial hydraulic free cooling on 1 circuit, designed for
environment
installations which have limited cooling requirements during
In free cooling mode, the compressors are stopped, and only the winter (offices, hospitals, etc.)
the fans are in operation. The Connect Touch control
automatically switches from compressor cooling mode to free Advantages of the built-in free
cooling mode depending on the cooler heat load and the cooling system
temperature differential between the chilled water outlet and - The free cooling function is independent of the refrigerant
the ambient air. circuit, which increases reliability and facilitates maintenance
Important: to optimise cooler performance, you are compared to free cooling built into the refrigerant circuit (DX
recommended to use the leaving water temperature FC).
setpoint offset function. - The Hydraulic Free Cooling design is intended to expand
the scope of application compared to the Free Cooling
Operating principle refrigerant concept (DX FC) by enabling Free Cooling mode
The unit's Connect Touch control maximises the use of the free to be activated by a higher outdoor temperature, thereby
cooling based on the needs of the application and the climate allowing for greater energy savings.
conditions. Once the chilled water/ambient air temperature - The built-in Hydraulic Free Cooling version developed based
differential exceeds the threshold value by 1K, the Connect on the AQUACIAT POWER ™ range allows all of the
Touch control activates free cooling and adjusts the air flow advantages of a free cooling solution to be combined with
rate to optimise the unit's energy performance. If the operating the compact design of the base units.
conditions permit the free cooling to operate on its own to meet
the requirements, the compressors are stopped. Two motorised
valves direct the chilled water to the free cooling coils.

Three operating modes are possible:


Summer (warm weather season): Mechanical cooling mode
The liquid chiller meets the needs traditionally using the
refrigerant circuit. The fluid bypasses the free cooling coils and
is cooled by the evaporator.
Mid-season: Combination mode
It is possible to operate in combination free cooling and
mechanical cooling mode. This helps optimise free cooling
operations while covering the system's cooling requirements.
The fluid is pre-cooled by the free cooling coils positioned in
series with the refrigerant circuit evaporator which finalises
cooling of the fluid.
Winter (cold weather season): Free cooling mode
Depending on the capacity requested and the setpoint, all of
the requirements may be fulfilled by the free cooling in this
operating mode without the fans running, thereby ensuring
optimum energy efficiency.

34
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Free cooling system


Physical characteristics of AQUACIATPOWER ™ LD units with free cooling
option

AQUACIATPOWER ™ LD 0602R 0650R 0750R 0900R 1100R 1200R 1350R 1400R 1600R

Cooling
Standard unit Nominal capacity kW 181 198 220 239 288 328 366 401 440
CA1
Full load performances* EER kW/kW 3,28 3,46 3,31 3,25 3,12 3,23 3,16 3,21 3,16
FREE COOLING
Nominal capacity kW 182 243 243 243 243 303 303 364 364
Free cooling EER kW/kW 28,02 27,56 27,56 27,56 27,92 27,92 28,11 27,69 27,86
Total free cooling option CFC1 Pressure drops kPa 94 112 112 112 102 107 101 117 112
Sound power(1) dB(A) 88,0 89,0 89,0 89,0 89,0 90,0 90,0 90,5 91,0
Sound pressure at 10 m(2) dB(A) 69,0 70,5 70,5 70,5 70,5 70,5 70,5 71,0 71,5
Nominal capacity kW 121 121 121 121 121 121 121 152 152
Free cooling EER kW/kW 27,94 27,94 27,94 27,94 28,04 28,15 28,18 23,78 23,76
Partial free cooling option CFC1 Pressure drops kPa 80 80 80 80 77 75 74 81 79
Sound power(1) dB(A) 86,0 86,0 86,0 86,0 86,0 86,0 86,0 87,5 88,0
Sound pressure at 10 m(2) dB(A) 67,5 67,5 67,5 67,5 67,5 66,5 66,5 68,0 68,5
Unit + ultra low noise level
Nominal capacity kW 171 189 208 226 270 309 343 377 413
option
CA1
Full load performances* EER kW/kW 3,06 3,29 3,08 3,03 2,82 2,96 2,85 2,94 2,86

FREE COOLING
Nominal capacity kW 148 197 197 197 197 247 247 296 296
Free cooling EER kW/kW 56,43 56,20 56,20 56,20 56,94 57,36 57,97 56,74 57,27
Total free cooling option CFC1 Pressure drops kPa 65 77 77 77 71 73 70 80 77
Sound power(1) dB(A) 79,5 80,5 80,5 80,5 81,0 82,0 82,0 82,0 82,5
Sound pressure at 10 m(2) dB(A) 60,5 62,0 62,0 62,0 62,5 63,0 63,0 62,5 63,0
Nominal capacity kW 99 99 99 99 99 99 99 123 123
Free cooling EER kW/kW 57,60 57,60 57,60 57,60 58,06 58,51 58,67 48,12 48,32
Partial free cooling option CFC1 Pressure drops kPa 55 55 55 55 54 52 51 56 55
Sound power(1) dB(A) 77,5 77,5 77,5 77,5 78,0 78,0 78,0 79,0 79,5
Sound pressure at 10 m(2) dB(A) 59,0 59,0 59,0 59,0 59,5 59,0 59,0 59,5 60,0

* In accordance with EN14511-3:2018.


CA1 Cooling mode conditions: evaporator water inlet/outlet temperature 17 °C/10 °C, outdoor air temperature at 35 °C, 30% Mono-
Ethylene-Glycol, evaporator fouling factor 0 m2. k/W
CFC1 Free cooling mode conditions: evaporator water inlet/outlet temperature 17 °C/10 °C, outdoor air temperature at 0 °C, 30% Mono-
Ethylene-Glycol, evaporator fouling factor 0 m2. k/W
(1) In dB ref=10-12 W, (A) weighting. Declared dual-number noise emission value in accordance with ISO 4871 with an uncertainty of
+/-3 dB(A). Measured in accordance with ISO 9614-1 and certified by Eurovent.
(2) In dB ref 20 µPa, (A) weighting. Declared dual-number noise emission value in accordance with ISO 4871 with an uncertainty of +/-3
dB(A). For information, calculated from the sound power Lw(A).

35
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Free cooling system

AQUACIATPOWER ™ LD 0602R 0650R 0750R 0900R 1100R 1200R 1350R 1400R 1600R

Total free cooling


Free cooling coil All-aluminium micro-channel coils (MCHE)
Quantity 3 4 4 4 4 5 5 6 6
Hydraulic connection
Connection in 3" 3" 3" 3" 3" 4" 4" 4" 4"
External diameter mm 88,9 88,9 88,9 88,9 88,9 114,3 114,3 114,3 114,3
Additional water volume l 60 72 72 72 72 113 113 126 126
Weight (3)
Additional weight (without water) kg 225 266 266 266 266 357 359 395 397
Additional weight (during operation) kg 287 341 341 341 341 475 477 526 528
Operation
Max. operating pressure, water side bar 6 6 6 6 6 6 6 6 6
Partial free cooling
Free cooling coil All-aluminium micro-channel coils (MCHE)
Quantity 2 2 2 2 2 2 2 3 3
Hydraulic connection
Connection in 3" 3" 3" 3" 3" 4" 4" 4" 4"
External diameter mm 88,9 88,9 88,9 88,9 88,9 114,3 114,3 114,3 114,3
Additional water volume l 48 48 48 48 48 58 58 75 75
Weight (3)
Additional weight (without water) kg 179 179 179 179 179 210 212 249 251
Additional weight (during operation) kg 228 228 228 228 228 271 273 327 329
Operation
Max. operating pressure, water side bar 6 6 6 6 6 6 6 6 6

(3) Values are guidelines only. Refer to the unit name plate.

36
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Free cooling system

AQUACIATPOWER ™ LD 1750R 1800R 2000R 2200R 2400R 2650R 2800R 2950R 3200R 3500R

Cooling

Standard unit Nominal capacity kW 475 512 585 652 718 767 827 852 932 994
CA1
Full load performances* EER kW/kW 3,22 3,16 3,15 3,23 3,22 3,12 3,14 3,10 3,06 2,96

FREE COOLING
Nominal capacity kW 425 425 485 546 607 607 667 667 728 728
Free cooling EER kW/kW 28,26 28,31 28,13 28,17 27,93 27,93 27,80 27,80 27,54 27,54
Total free cooling option CFC1 Pressure drops kPa 103 102 110 111 120 120 126 126 136 136
Sound power(1) dB(A) 91,0 91,0 91,5 92,5 93,0 93,0 93,0 93,0 93,5 94,0
Sound pressure at 10 m(2) dB(A) 71,0 71,0 71,5 72,0 72,5 72,5 72,0 72,0 72,5 73,0
Nominal capacity kW 182 182 243 212 273 273 303 303 364 364
Free cooling EER kW/kW 28,67 28,68 28,81 25,28 25,96 25,96 28,89 28,89 28,80 28,80
Partial free cooling
CFC1 Pressure drops kPa 75 75 79 77 82 82 80 80 86 86
option
Sound power(1) dB(A) 87,5 87,5 88,5 89,0 90,0 90,0 89,5 89,5 90,5 91,0
Sound pressure at 10 m(2) dB(A) 67,5 67,5 68,5 68,5 69,5 69,5 68,5 68,5 69,5 70,0
Unit + ultra low noise
Nominal capacity kW 447 481 549 613 677 719 777 798 873 925
level option
CA1
Full load performances* EER kW/kW 2,94 2,85 2,85 2,94 2,94 2,82 2,84 2,79 2,76 2,63

FREE COOLING
Nominal capacity kW 346 346 395 444 494 494 543 543 592 592
Free cooling EER kW/kW 58,50 58,65 58,15 58,28 57,57 57,57 57,20 57,20 56,43 56,43
Total free cooling option CFC1 Pressure drops kPa 71 70 75 76 82 82 86 86 93 93
Sound power(1) dB(A) 82,5 83,0 83,5 85,0 85,0 85,0 85,5 84,5 85,5 86,0
Sound pressure at 10 m(2) dB(A) 62,5 63,0 63,5 64,0 64,5 64,5 64,5 63,5 64,5 65,0
Nominal capacity kW 148 148 197 173 222 222 247 247 296 296
Free cooling EER kW/kW 58,71 58,76 59,31 52,08 53,94 53,94 60,06 60,06 60,16 60,16
Partial free cooling
CFC1 Pressure drops kPa 52 52 55 53 56 56 56 56 59 59
option
Sound power(1) dB(A) 79,0 79,5 80,5 81,0 82,0 82,0 82,0 81,0 82,5 83,0
Sound pressure at 10 m(2) dB(A) 59,0 59,5 60,5 60,5 61,5 61,5 61,0 60,0 61,5 62,0

* In accordance with EN14511-3:2018.


CA1 Cooling mode conditions: evaporator water inlet/outlet temperature 17 °C/10 °C, outdoor air temperature at 35 °C, 30% Mono-
Ethylene-Glycol, evaporator fouling factor 0 m2. k/W
CFC1 Free cooling mode conditions: evaporator water inlet/outlet temperature 17 °C/10 °C, outdoor air temperature at 0 °C, 30% Mono-
Ethylene-Glycol, evaporator fouling factor 0 m2. k/W
(1) In dB ref=10-12 W, (A) weighting. Declared dual-number noise emission value in accordance with ISO 4871 with an uncertainty of
+/-3 dB(A). Measured in accordance with ISO 9614-1 and certified by Eurovent.
(2) In dB ref 20 µPa, (A) weighting. Declared dual-number noise emission value in accordance with ISO 4871 with an uncertainty of +/-3
dB(A). For information, calculated from the sound power Lw(A).

37
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Free cooling system

AQUACIATPOWER ™ LD 1750R 1800R 2000R 2200R 2400R 2650R 2800R 2950R 3200R 3500R

Total free cooling


Free cooling coil All-aluminium micro-channel coils (MCHE)
Quantity 7 7 8 9 10 10 11 11 12 12
Hydraulic connection
Connection in 4" 4" 4" 5'' 5'' 5'' 5'' 5'' 5'' 5''
External diameter mm 114,3 114,3 114,3 139,7 139,7 139,7 139,7 139,7 139,7 139,7
Additional water volume l 200 200 213 298 310 310 351 351 364 364
Weight (3)
Additional weight (without water) kg 516 516 556 663 697 697 772 772 810 810
Additional weight (during operation) kg 725 725 778 973 1020 1020 1138 1138 1189 1189
Operation
Max. operating pressure, water side bar 6 6 6 6 6 6 6 6 6 6
Partial free cooling
Free cooling coil All-aluminium micro-channel coils (MCHE)
Quantity 3 3 4 4 5 5 5 5 6 6
Hydraulic connection
Connection in 4" 4" 4" 5'' 5'' 5'' 5'' 5'' 5'' 5''
External diameter mm 114,3 114,3 114,3 139,7 139,7 139,7 139,7 139,7 139,7 139,7
Additional water volume l 101 101 120 186 198 198 205 205 224 224
Weight (3)
Additional weight (without water) kg 304 304 346 412 449 449 457 457 494 494
Additional weight (during operation) kg 409 409 471 606 656 656 671 671 728 728
Operation
Max. operating pressure, water side bar 6 6 6 6 6 6 6 6 6 6

(3) Values are guidelines only. Refer to the unit name plate.

Free cooling operating limits


LD 602R to 3500R units

Water-cooled heat exchanger Minimum Maximum

Water inlet temperature at start-up °C 8 (1) 40


Water outlet temperature during operation °C 5 20 (2)

Air-cooled exchanger Minimum Maximum

Outdoor ambient operating temperature


LD units - Full load °C -20 47
LD units - Part load °C -20 52 (3)

(1) For an application requiring start-up at less than 8 °C, contact the manufacturer to select a unit using the electronic catalogue.
(2) For applications requiring operation above a water outlet temperature of 20 °C, contact the manufacturer to select a unit using the electronic catalogue.
(3) Part load operation permitted above an outdoor air temperature of 47 °C. Contact the manufacturer to select a unit using the electronic catalogue.

All the free cooling units must be protected against freezing with 30% ethylene glycol in the cooling loop circuit (recommended
value).

38
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

xtra fan operating pressure ventilation


The AQUACIATPOWER ™ range can be equipped as an option with the XTRAFAN operating pressure ventilation.

■ Functions ■ Precautions for installation


The XTRAFAN offers a wide range of functions, making a whole On-site installation of a packaged reversible air-to-water unit
host of flexible installation conditions possible, such as: requires some safety measures to be taken, particularly if it is
- The option of installation in a confined space, for example installed in a machine room. For example, the evacuation of
on a terrace surrounded by walls, where only an air supply condensates specific to these units, including at very low
with static pressure of between 100 and 200 pascals within outdoor temperatures.
a duct enables use without recirculation or mixing of air at During defrosting cycles, reversible units are liable to discharge
the condenser intake, a large amount of water onto the ground, which must be drained,
- Installation in an urban area in which noise is a particular as well as steam from the fan discharge which can damage the
issue, where operation is only possible by adapting a sound air discharge ducts. The ground supporting the unit must be
trap to the supply air, perfectly watertight and capable of collecting and draining the
- A self-adjusting variable speed function which allows "all- defrosted water, including during freezing periods. It is
season" cooling, fully secured for industrial processes, recommended that the unit is raised by approximately 300 mm.
including during harsh winter conditions with an external
If an air discharge duct is installed on site, its weight must not
temperature of -20 °C,
be supported by the roof of the unit. Each fan must be connected
- The freedom to precisely adjust the ventilation speed on-site
independently.
to what is "strictly necessary" to obtain the optimum air
supply pressure, or the maximum acceptable noise level for The duct must be connected to the unit using a flexible supply
the site on which the unit is located, air sleeve, included in the option
- An improvement in the EER and electrical consumption for
the unit, in direct proportion to the load required by the
installation.
The various performances (cooling capacity, heating capacity,
input power, energy efficiency) depend on the rotation speed
of the fans, and therefore on the desired operating pressure in
the duct:
- At an operating pressure of between 0 and 100 Pa, the
machine performances are barely affected
- At an operating pressure of between 100 and 200 Pa, the
machine performances may be significantly affected,
particularly according to the air and water temperature
conditions.
The sound level at the duct outlet and the level radiated around
the machine depend on the operating pressure.
Refer to the selection tool to evaluate the estimated impact of
the ducting system on the machine's operating conditions.

39
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Intelligently designed acoustics


To comply with the various restrictions on integration, the AQUACIATPOWER ™ has two sound finish levels, enabling it to be easily
integrated into a number of zones without causing disruption to users or their neighbours.

■ Basic version ■ Night mode


The distinguishing feature of the AQUACIAT range is its rigorous The AQUACIATPOWER ™ has a Night Mode function enabling
design incorporating "noiseless" assembly techniques to reduce the sound level to be limited at night or when the building is
vibrations and sources of noise: unoccupied (according to the user programming) by controlling
- New-generation scroll compressors with a continuous the output and the fan rotation speed.
scrolling motion to lessen vibrations
- Compressor structure separated from the unit by anti- NIGHT MODE
vibration mounts
- Pipes separated from the unit structure
- Fans made from a synthetic material, with aerodynamic Capacity
blades offering an optimised profile. Optimised coil-fan Noise Level

combination, the result of many hours of study of the thermal Sound level reduction
and acoustic properties in our Research and Innovation
Centre, to ensure a linear flow of air without turbulence, to
0 2 4 6 8 10 12 14 16 18 20 22 24
limit noise to an acceptable acoustic spectrum.
- Even with the basic version, the fans rotate at low speed to
guarantee maximum comfort
- The Connect Touch controller automatically adjusts the fan ■ Acoustic signature
air flow rate according to the outdoor air temperature and As important as the sound power level, the acoustic signature
the unit's load rate which enables the sound level to be reflects the noise disturbance generated by the unit.
significantly reduced, particularly at night, mid-season, dB
morning and evening, which totals more than 75% of the Acoustic discomfort
time the unit is used

■ Very Low Noise option


In this version, the compressors are fitted inside an insulated
soundproof box, and the rotation speed of the fans is kept to a
minimum, but the output power and thermal performance
remains the same as the basic version.
Disruption of the cooling cycle

VERY LOW NOISE t

dB
Without Variable-speed
-3 to -4 dB(A)
Thanks to the With Variable-speed
compressor enclosure

■ Ultra Low Noise option


In this version, the compressor soundproof box and all sources t
of vibration which generate noise have had a special coating
applied, and the rotation speed of the fans is kept to a minimum,
but the output power and thermal performance remains the The AQUACIATPOWER ™ can be equipped as an option with a
same as the basic version. variable-speed motor, enabling a soft start of the fan (all-season
operation).
ULTRA LOW NOISE
It avoids the increases in noise linked to the on/off sequences,
thereby improving the unit's acoustic signature.
Installing a variable-speed pump also reduces the noise level
-5 to -6 dB(A) of the pumping function by adjusting the pump speed to the
Thanks to a specific exact requirements. The soft start improves the signature and
soundproof box and an
acoustic and vibration
reduces nuisance noise.
treatment on the structure

With all these benefits and its three acoustic finish levels, the AQUACIATPOWER ™ range can be integrated into any site, ensuring
any constraints in terms of the sound environment can be met, while guaranteeing optimal comfort for both users and their
neighbours, allowing customers in the hotel industry to enjoy their rest, and promoting rest and recovery for users in the hospital
sector.

OFFICES HOTELS HEALTHCARE

40
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Sound levels - cooling only


Standard unit
■ Sound power level (LW)

AQUACIATPOWER ™ LD Power level spectrum (1)


Global sound
Standard unit 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz power level (2)
0602R dB 83,0 77,0 81,0 86,0 85,0 81,0 73,0 70,0 dB(A) 88,5
0650R dB 85,0 80,5 83,0 86,5 84,5 82,5 73,0 70,5 dB(A) 89,0
0750R dB 85,0 80,5 83,0 86,5 84,5 82,5 73,0 70,5 dB(A) 89,0
0900R dB 83,5 77,5 82,0 86,5 85,5 82,0 74,0 70,5 dB(A) 89,5
1100R dB 84,5 81,0 84,0 87,0 85,0 83,0 73,5 71,0 dB(A) 89,5
1200R dB 85,5 81,5 85,0 88,0 86,0 84,0 74,5 72,0 dB(A) 90,5
1350R dB 85,5 81,5 85,0 88,0 86,0 84,0 74,5 72,0 dB(A) 90,5
1400R dB 85,5 79,5 84,0 88,5 87,5 83,5 75,5 72,5 dB(A) 91,0
1600R dB 86,0 82,0 85,0 88,0 86,5 84,5 74,5 72,5 dB(A) 91,0
1750R dB 86,0 80,0 84,5 89,0 88,0 84,5 76,5 73,0 dB(A) 91,5
1800R dB 86,5 82,5 86,0 88,5 87,0 85,0 75,5 73,0 dB(A) 91,5
2000R dB 87,0 83,5 86,5 89,5 87,5 85,5 76,0 73,5 dB(A) 92,0
2200R dB 97,0 99,5 98,0 90,5 87,0 92,0 83,5 77,5 dB(A) 96,5
2400R dB 90,5 85,5 88,5 92,5 89,0 93,0 82,0 79,5 dB(A) 96,5
2650R dB 97,5 100,0 98,5 90,5 87,0 92,5 83,5 77,5 dB(A) 97,0
2800R dB 91,0 86,5 89,5 93,5 89,5 93,5 82,5 80,0 dB(A) 97,0
2950R dB 98,0 100,5 99,0 91,0 87,5 93,0 84,5 78,5 dB(A) 97,5
3200R dB 91,0 86,5 89,5 93,5 89,5 93,5 82,5 80,0 dB(A) 97,5
3500R dB 91,5 87,0 90,0 94,0 90,0 94,0 83,0 80,5 dB(A) 98,0
(1) In dB ref=10-12 W, as a guideline. Measured in accordance with ISO 9614-1.
(2) In dB ref=10-12 W, (A) weighting, with an uncertainty of +/-3 dB. Measured in accordance with ISO 9614-1 and certified by Eurovent.

■ Sound pressure level (Lp)


Measurement conditions: Free field, 10 metres from machine, 1.5 metres above floor level, directivity 2
Note: the sound pressure levels depend on the installation conditions of each system. As such, the levels listed here are given
for information only. Only the sound power levels are comparable and certified.

Sound pressure spectrum (1) Global sound


AQUACIATPOWER ™ LD
pressure spectrum
Standard unit 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz (2)

0602R dB 51,0 45,0 49,0 54,0 53,0 49,0 41,0 38,0 dB(A) 56,5
0650R dB 53,0 48,5 51,0 54,5 52,5 50,5 41,0 38,5 dB(A) 57,0
0750R dB 53,0 48,5 51,0 54,5 52,5 50,5 41,0 38,5 dB(A) 57,0
0900R dB 51,5 45,5 50,0 54,5 53,5 50,0 42,0 38,5 dB(A) 57,5
1100R dB 52,5 49,0 52,0 55,0 53,0 51,0 41,5 39,0 dB(A) 57,5
1200R dB 53,5 49,5 53,0 56,0 54,0 52,0 42,5 40,0 dB(A) 58,5
1350R dB 53,5 49,5 53,0 56,0 54,0 52,0 42,5 40,0 dB(A) 58,5
1400R dB 53,5 47,5 52,0 56,5 55,5 51,5 43,5 40,5 dB(A) 59,0
1600R dB 54,0 50,0 53,0 56,0 54,5 52,5 42,5 40,5 dB(A) 58,5
1750R dB 53,5 47,5 52,0 56,5 55,5 52,0 44,0 40,5 dB(A) 59,5
1800R dB 54,0 50,0 53,5 56,0 54,5 52,5 43,0 40,5 dB(A) 59,0
2000R dB 54,5 51,0 54,0 57,0 55,0 53,0 43,5 41,0 dB(A) 60,0
2200R dB 64,5 67,0 65,5 58,0 54,5 59,5 51,0 45,0 dB(A) 64,0
2400R dB 58,0 53,0 56,0 60,0 56,5 60,5 49,5 47,0 dB(A) 64,0
2650R dB 65,0 67,5 66,0 58,0 54,5 60,0 51,0 45,0 dB(A) 64,5
2800R dB 58,5 54,0 57,0 61,0 57,0 61,0 50,0 47,5 dB(A) 65,0
2950R dB 65,5 68,0 66,5 58,5 55,0 60,5 52,0 46,0 dB(A) 65,0
3200R dB 58,5 54,0 57,0 61,0 57,0 61,0 50,0 47,5 dB(A) 65,0
3500R dB 59,0 54,5 57,5 61,5 57,5 61,5 50,5 48,0 dB(A) 65,5
(1) In dB ref=2x10-5 Pa, as a guideline.
(2) In dB ref=2x10-5 Pa, (A) weighting with an uncertainty of +/-3 dB.

41
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Sound levels - cooling only


Unit + High temperature option/Nominal high performance
■ Sound power level (LW)

AQUACIATPOWER ™ LD Power level spectrum (1)


Unit + High temperature Global sound
option/Nominal high 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz power level (2)
performance
0602R dB 82,5 83,5 83,5 87,0 87,5 83,0 75,5 73,5 dB(A) 91,0
0650R dB 84,0 85,0 85,0 87,5 88,0 84,0 75,5 74,0 dB(A) 90,5
0750R dB 84,0 85,0 85,0 87,5 88,0 84,0 75,5 74,0 dB(A) 90,5
0900R dB 83,5 84,5 85,0 88,5 89,0 84,5 76,5 74,5 dB(A) 92,0
1100R dB 84,0 85,0 85,5 88,0 88,5 85,0 76,0 74,5 dB(A) 92,0
1200R dB 85,0 86,0 86,5 89,0 89,5 85,5 77,0 75,5 dB(A) 93,0
1350R dB 85,0 86,0 86,5 89,0 89,5 85,5 77,0 75,5 dB(A) 93,0
1400R dB 85,0 86,0 86,0 89,5 90,0 85,5 78,0 76,0 dB(A) 93,5
1600R dB 86,0 87,0 87,5 90,0 90,0 86,5 77,5 76,0 dB(A) 93,5
1750R dB 85,5 86,5 87,0 90,0 91,0 86,0 78,5 76,5 dB(A) 94,0
1800R dB 86,0 87,0 87,5 90,0 90,5 86,5 78,0 76,5 dB(A) 94,0
2000R dB 86,5 87,5 88,0 90,5 91,0 87,5 78,5 77,0 dB(A) 94,5
2200R dB 96,5 99,5 98,0 92,0 91,5 92,0 84,0 79,5 dB(A) 97,5
2400R dB 90,0 89,5 90,0 93,5 92,5 93,0 83,0 81,0 dB(A) 97,5
2650R dB 97,5 100,5 98,5 92,5 92,0 93,0 84,5 80,0 dB(A) 98,0
2800R dB 90,0 89,5 90,0 93,5 92,5 93,0 83,0 81,0 dB(A) 98,0
2950R dB 97,5 100,5 99,0 92,5 92,0 93,0 84,5 80,0 dB(A) 98,5
3200R dB 90,5 90,0 90,5 94,0 93,0 94,0 83,5 81,5 dB(A) 98,5
3500R dB 91,0 90,5 91,0 94,5 93,5 94,5 84,0 82,0 dB(A) 99,0
(1) In dB ref=10-12 W, as a guideline. Measured in accordance with ISO 9614-1.
(2) In dB ref=10-12 W, (A) weighting, with an uncertainty of +/-3 dB. Measured in accordance with ISO 9614-1 and certified by Eurovent.

■ Sound pressure level (Lp)


Measurement conditions: Free field, 10 metres from machine, 1.5 metres above floor level, directivity 2
Note: the sound pressure levels depend on the installation conditions of each system. As such, the levels listed here are given
for information only. Only the sound power levels are comparable and certified.

AQUACIATPOWER ™ LD Sound pressure spectrum (1)


Global sound
Unit + High temperature
pressure spectrum
option/Nominal high 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz (2)
performance
0602R dB 50,5 51,5 51,5 55,0 55,5 51,0 43,5 41,5 dB(A) 58,5
0650R dB 52,0 53,0 53,0 55,5 56,0 52,0 43,5 42,0 dB(A) 59,5
0750R dB 52,0 53,0 53,0 55,5 56,0 52,0 43,5 42,0 dB(A) 59,5
0900R dB 51,5 52,5 53,0 56,5 57,0 52,5 44,5 42,5 dB(A) 60,0
1100R dB 52,0 53,0 53,5 56,0 56,5 53,0 44,0 42,5 dB(A) 60,0
1200R dB 53,0 54,0 54,5 57,0 57,5 53,5 45,0 43,5 dB(A) 60,5
1350R dB 53,0 54,0 54,5 57,0 57,5 53,5 45,0 43,5 dB(A) 60,5
1400R dB 53,0 54,0 54,0 57,5 58,0 53,5 46,0 44,0 dB(A) 61,0
1600R dB 54,0 55,0 55,5 58,0 58,0 54,5 45,5 44,0 dB(A) 61,5
1750R dB 53,0 54,0 54,5 57,5 58,5 53,5 46,0 44,0 dB(A) 61,5
1800R dB 53,5 54,5 55,0 57,5 58,0 54,0 45,5 44,0 dB(A) 61,5
2000R dB 54,0 55,0 55,5 58,0 58,5 55,0 46,0 44,5 dB(A) 62,0
2200R dB 64,0 67,0 65,5 59,5 59,0 59,5 51,5 47,0 dB(A) 65,0
2400R dB 57,5 57,0 57,5 61,0 60,0 60,5 50,5 48,5 dB(A) 65,0
2650R dB 65,0 68,0 66,0 60,0 59,5 60,5 52,0 47,5 dB(A) 66,0
2800R dB 57,5 57,0 57,5 61,0 60,0 60,5 50,5 48,5 dB(A) 65,0
2950R dB 65,0 68,0 66,5 60,0 59,5 60,5 52,0 47,5 dB(A) 66,0
3200R dB 58,0 57,5 58,0 61,5 60,5 61,5 51,0 49,0 dB(A) 66,0
3500R dB 58,5 58,0 58,5 62,0 61,0 62,0 51,5 49,5 dB(A) 66,5
(1) In dB ref=2x10-5 Pa, as a guideline.
(2) In dB ref=2x10-5 Pa, (A) weighting with an uncertainty of +/-3 dB.

42
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Sound levels - cooling only


Unit + Very Low Noise option
■ Sound power level (LW)

AQUACIATPOWER ™ LD Power level spectrum (1)


Global sound
Unit + Very Low Noise
63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz power level (2)
option
0602R dB 75,5 80 83 85 80 75 69 74 dB(A) 85,0
0700R dB 76,5 81 84 86 81 76 70 75 dB(A) 86,0
0800R dB 77 82 85 86 82 77 71 75 dB(A) 86,5
0900R dB 77,5 82 85 87 82 77 71 76 dB(A) 87,0
1000R dB 78 82 85 87 81 78 71 75 dB(A) 87,0
1150R dB 78,5 83 86 88 83 79 72 77 dB(A) 88,0
1250R dB 79 83 86 88 82 79 72 76 dB(A) 88,0
1400R dB 79,5 84 87 89 84 79 73 78 dB(A) 89,0
1500R dB 80 84 87 89 83 80 73 77 dB(A) 89,0
1600R dB 80 85 87 89 84 80 73 78 dB(A) 89,5
1750R dB 81 85 88 90 84 81 74 78 dB(A) 90,0
2000R dB 81 85 88 90 84 81 74 78 dB(A) 90,0
(1) In dB ref=10-12 W, as a guideline. Measured in accordance with ISO 9614-1.
(2) In dB ref=10-12 W, (A) weighting, with an uncertainty of +/-3 dB. Measured in accordance with ISO 9614-1 and certified by Eurovent.

■ Sound pressure level (Lp)


Measurement conditions: Free field, 10 metres from machine, 1.5 metres above floor level, directivity 2
Note: the sound pressure levels depend on the installation conditions of each system. As such, the levels listed here are given
for information only. Only the sound power levels are comparable and certified.

AQUACIATPOWER ™ LD Sound pressure spectrum (1) Global sound


Unit + Very Low Noise pressure spectrum
option 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz (2)

0602R dB 53,0 45,5 47,5 52,5 48,5 44,0 37,5 33,5 dB(A) 53,0
0650R dB 54,0 48,0 49,0 52,5 48,5 45,0 37,0 34,0 dB(A) 53,5
0750R dB 54,0 48,0 49,0 52,5 48,5 45,0 37,0 34,0 dB(A) 53,5
0900R dB 54,5 47,0 48,5 54,0 50,0 45,0 38,5 35,0 dB(A) 54,5
1100R dB 55,5 49,5 50,5 54,0 49,5 46,5 38,5 35,5 dB(A) 54,5
1200R dB 56,5 50,5 51,5 55,0 50,5 47,5 39,5 36,5 dB(A) 55,5
1350R dB 56,5 50,5 51,5 55,0 50,5 47,5 39,5 36,5 dB(A) 55,5
1400R dB 55,5 48,0 50,0 55,0 51,0 46,5 40,0 36,0 dB(A) 55,5
1600R dB 56,5 50,5 51,5 55,0 51,0 48,0 40,0 36,5 dB(A) 56,0
1750R dB 56,0 48,5 50,0 55,5 51,5 46,5 40,0 36,0 dB(A) 56,0
1800R dB 57,0 51,0 52,0 55,5 51,0 48,0 40,0 37,0 dB(A) 56,5
2000R dB 57,5 51,5 52,5 56,0 51,5 48,5 40,5 37,5 dB(A) 57,0
2200R dB 71,5 65,5 63,0 55,5 50,5 53,5 47,0 41,0 dB(A) 60,5
2400R dB 62,5 55,5 54,0 58,0 53,0 55,0 46,0 43,5 dB(A) 60,0
2650R dB 72,0 65,5 63,0 55,5 50,5 54,0 47,0 41,5 dB(A) 60,5
2800R dB 62,5 55,5 54,0 58,5 53,0 55,0 46,0 43,5 dB(A) 60,0
2950R dB 72,5 66,5 64,0 56,0 51,0 54,5 48,0 42,0 dB(A) 61,0
3200R dB 63,0 56,0 54,5 59,0 53,5 55,5 46,5 44,5 dB(A) 60,5
3500R dB 64,0 57,0 55,5 60,0 54,5 56,5 47,5 45,5 dB(A) 61,5
(1) In dB ref=2x10-5 Pa, as a guideline.
(2) In dB ref=2x10-5 Pa, (A) weighting with an uncertainty of +/-3 dB.

43
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Sound levels - cooling only


Unit + Ultra Low Noise option
■ Sound power level (LW)

AQUACIATPOWER ™ LD Power level spectrum (1)


Global sound
Unit + Ultra Low Noise
63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz power level (2)
option
0602R dB 82,5 76,5 77,5 81,5 80,0 74,0 66,5 63,0 dB(A) 83,5
0650R dB 83,0 79,5 80,0 82,5 79,0 74,5 67,0 63,5 dB(A) 83,5
0750R dB 83,0 79,5 80,0 82,5 79,0 74,5 67,0 63,5 dB(A) 83,5
0900R dB 83,5 78,0 79,0 83,0 81,5 75,5 67,5 64,0 dB(A) 84,5
1100R dB 83,5 80,5 81,5 83,5 80,0 76,0 68,5 65,0 dB(A) 84,5
1200R dB 84,5 81,5 82,5 84,5 81,0 77,0 69,5 66,0 dB(A) 85,5
1350R dB 84,5 81,5 82,5 84,5 81,0 77,0 69,5 66,0 dB(A) 85,5
1400R dB 85,0 79,0 80,0 84,0 82,5 76,5 69,0 65,5 dB(A) 86,0
1600R dB 84,5 82,0 82,5 85,0 81,0 77,0 70,0 66,5 dB(A) 86,0
1750R dB 85,5 80,0 80,5 85,0 83,5 77,0 69,5 66,0 dB(A) 86,5
1800R dB 85,5 82,5 83,5 85,5 82,0 78,0 70,5 67,0 dB(A) 86,5
2000R dB 86,0 83,0 84,0 86,0 82,5 78,5 71,0 67,5 dB(A) 87,0
2200R dB 87,0 84,0 84,5 86,0 84,5 83,5 81,0 76,0 dB(A) 90,0
2400R dB 90,0 85,0 87,5 87,5 85,0 82,0 75,5 73,5 dB(A) 90,0
2650R dB 87,5 84,5 85,0 87,0 85,0 84,0 82,0 77,0 dB(A) 90,5
2800R dB 91,0 85,5 88,0 88,0 85,5 82,5 76,0 74,0 dB(A) 90,5
2950R dB 87,0 84,0 84,5 86,5 84,5 83,5 81,5 76,5 dB(A) 90,5
3200R dB 91,0 86,0 88,0 88,0 85,5 82,5 76,5 74,0 dB(A) 90,5
3500R dB 91,5 86,5 88,5 88,5 86,0 83,0 77,0 74,5 dB(A) 91,0
(1) In dB ref=10-12 W, as a guideline. Measured in accordance with ISO 9614-1.
(2) In dB ref=10-12 W, (A) weighting, with an uncertainty of +/-3 dB. Measured in accordance with ISO 9614-1 and certified by Eurovent.

■ Sound pressure level (Lp)


Measurement conditions: Free field, 10 metres from machine, 1.5 metres above floor level, directivity 2
Note: the sound pressure levels depend on the installation conditions of each system. As such, the levels listed here are given
for information only. Only the sound power levels are comparable and certified.

AQUACIATPOWER ™ LD Sound pressure spectrum (1) Global sound


Unit + Ultra Low Noise pressure spectrum
option 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz (2)

0602R dB 50,5 44,5 45,5 49,5 48,0 42,0 34,5 31,0 dB(A) 51,5
0650R dB 51,0 47,5 48,0 50,5 47,0 42,5 35,0 31,5 dB(A) 51,5
0750R dB 51,0 47,5 48,0 50,5 47,0 42,5 35,0 31,5 dB(A) 51,5
0900R dB 51,5 46,0 47,0 51,0 49,5 43,5 35,5 32,0 dB(A) 52,5
1100R dB 51,5 48,5 49,5 51,5 48,0 44,0 36,5 33,0 dB(A) 52,5
1200R dB 52,5 49,5 50,5 52,5 49,0 45,0 37,5 34,0 dB(A) 53,5
1350R dB 52,5 49,5 50,5 52,5 49,0 45,0 37,5 34,0 dB(A) 53,5
1400R dB 53,0 47,0 48,0 52,0 50,5 44,5 37,0 33,5 dB(A) 53,5
1600R dB 52,5 50,0 50,5 53,0 49,0 45,0 38,0 34,5 dB(A) 53,5
1750R dB 53,0 47,5 48,0 52,5 51,0 44,5 37,0 33,5 dB(A) 54,5
1800R dB 53,0 50,0 51,0 53,0 49,5 45,5 38,0 34,5 dB(A) 54,0
2000R dB 53,5 50,5 51,5 53,5 50,0 46,0 38,5 35,0 dB(A) 55,0
2200R dB 54,5 51,5 52,0 53,5 52,0 51,0 48,5 43,5 dB(A) 57,5
2400R dB 57,5 52,5 55,0 55,0 52,5 49,5 43,0 41,0 dB(A) 57,5
2650R dB 55,0 52,0 52,5 54,5 52,5 51,5 49,5 44,5 dB(A) 58,0
2800R dB 58,5 53,0 55,5 55,5 53,0 50,0 43,5 41,5 dB(A) 58,0
2950R dB 54,5 51,5 52,0 54,0 52,0 51,0 49,0 44,0 dB(A) 57,5
3200R dB 58,5 53,5 55,5 55,5 53,0 50,0 44,0 41,5 dB(A) 58,0
3500R dB 59,0 54,0 56,0 56,0 53,5 50,5 44,5 42,0 dB(A) 58,5
(1) In dB ref=2x10-5 Pa, as a guideline.
(2) In dB ref=2x10-5 Pa, (A) weighting with an uncertainty of +/-3 dB.

44
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Sound levels - reversible heat pump


Standard unit
■ Sound power level (LW) - Cooling mode

AQUACIATPOWER Power level spectrum (1)


Global sound
™ ILD
63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz power level (2)
Standard unit
0602R dB 75 81 84 86 85 81 72 76 dB(A) 88,0
0700R dB 75 82 84 87 84 81 73 76 dB(A) 88,5
0800R dB 76 82 85 87 85 81 73 76 dB(A) 89,0
0900R dB 76 83 85 88 86 82 74 77 dB(A) 89,5
1000R dB 76 82 85 88 85 82 73 77 dB(A) 89,5
1150R dB 77 84 86 89 86 83 75 78 dB(A) 90,5
1250R dB 77 84 86 90 87 84 75 78 dB(A) 91,0
1400R dB 78 85 87 90 87 84 76 79 dB(A) 91,5
1500R dB 78 84 87 90 87 84 75 79 dB(A) 91,5
1600R dB 78 85 88 90 88 85 76 79 dB(A) 92,0
1750R dB 79 85 88 91 88 85 76 79 dB(A) 92,5
2000R dB 79 86 88 91 89 86 77 80 dB(A) 93,0
(1) In dB ref=10-12 W, as a guideline. Measured in accordance with ISO 9614-1.
(2) In dB ref=10-12 W, (A) weighting, with an uncertainty of +/-3 dB. Measured in accordance with ISO 9614-1 and certified by Eurovent.

■ Sound pressure level (Lp) - Cooling mode


Measurement conditions: Free field, 10 metres from machine, 1.5 metres above floor level, directivity 2
Note: the sound pressure levels depend on the installation conditions of each system. As such, the levels listed here are given
for information only. Only the sound power levels are comparable and certified.

AQUACIATPOWER Sound pressure spectrum (1) Global sound


™ ILD pressure spectrum
Standard unit 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz (2)

0602R dB 43 49 52 54 53 49 40 44 dB(A) 56,0


0700R dB 43 50 52 55 52 49 41 44 dB(A) 56,5
0800R dB 44 50 53 55 53 49 41 44 dB(A) 57,0
0900R dB 44 51 53 56 54 50 42 45 dB(A) 57,5
1000R dB 44 50 53 56 53 50 41 45 dB(A) 57,5
1150R dB 45 52 54 57 54 51 43 46 dB(A) 58,5
1250R dB 45 52 54 58 55 52 43 46 dB(A) 59,0
1400R dB 46 53 55 58 55 52 44 47 dB(A) 59,5
1500R dB 46 52 55 58 55 52 43 47 dB(A) 59,5
1600R dB 46 52 55 58 55 52 44 47 dB(A) 60,0
1750R dB 46 53 55 58 56 53 44 47 dB(A) 60,0
2000R dB 47 53 56 59 56 53 44 47 dB(A) 60,5
(1) In dB ref=2x10-5 Pa, as a guideline.
(2) In dB ref=2x10-5 Pa, (A) weighting with an uncertainty of +/-3 dB.

45
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Sound levels - reversible heat pump


Unit + High temperature option/Nominal high performance
■ Sound power level (LW) - Cooling mode

AQUACIATPOWER ™ ILD Power level spectrum (1)


Unit + High
Global sound
temperature option/
63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz power level (2)
Nominal high
performance
0602R dB 81 88 92 88 86 82 74 75 dB(A) 90,5
0650R dB 81 88 92 89 87 83 75 75 dB(A) 91,0
0800R dB 82 88 93 89 87 83 75 75 dB(A) 91,5
0900R dB 83 89 93 90 88 84 76 76 dB(A) 92,0
1000R dB 82 89 93 90 87 84 76 76 dB(A) 92,0
1150R dB 84 90 94 91 89 85 77 77 dB(A) 93,0
1250R dB 84 90 94 92 89 86 77 78 dB(A) 93,5
1350R dB 84 91 95 92 90 86 78 78 dB(A) 94,0
1500R dB 84 91 95 92 89 86 78 78 dB(A) 94,0
1750R dB 85 91 95 92 90 86 78 78 dB(A) 94,5
1800R dB 85 91 95 93 90 87 78 78 dB(A) 94,5
2000R dB 85 91 96 93 90 87 79 79 dB(A) 95,0
(1) In dB ref=10-12 W, as a guideline. Measured in accordance with ISO 9614-1.
(2) In dB ref=10-12 W, (A) weighting, with an uncertainty of +/-3 dB. Measured in accordance with ISO 9614-1 and certified by Eurovent.

■ Sound pressure level (Lp) - Cooling mode


Measurement conditions: Free field, 10 metres from machine, 1.5 metres above floor level, directivity 2
Note: the sound pressure levels depend on the installation conditions of each system. As such, the levels listed here are given
for information only. Only the sound power levels are comparable and certified.

AQUACIATPOWER ™ ILD Sound pressure spectrum (1)


Unit + High Global sound
temperature option/ pressure
Nominal high 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz spectrum (2)
performance
0602R dB 49 56 60 56 54 50 42 43 dB(A) 58,5
0700R dB 49 56 60 57 55 51 43 43 dB(A) 59,0
0800R dB 50 56 61 57 55 51 43 43 dB(A) 59,5
0900R dB 51 57 61 58 56 52 44 44 dB(A) 60,0
1000R dB 50 57 61 58 55 52 44 44 dB(A) 60,0
1150R dB 52 58 62 59 57 53 45 45 dB(A) 61,0
1250R dB 52 58 62 60 57 54 45 46 dB(A) 61,5
1400R dB 52 59 63 60 58 54 46 46 dB(A) 62,0
1500R dB 52 59 63 60 57 54 46 46 dB(A) 62,0
1600R dB 52 59 63 60 57 54 46 46 dB(A) 62,0
1750R dB 52 59 63 60 57 54 46 46 dB(A) 62,5
2000R dB 53 59 63 61 58 55 46 46 dB(A) 63,0
(1) In dB ref=2x10-5 Pa, as a guideline.
(2) In dB ref=2x10-5 Pa, (A) weighting with an uncertainty of +/-3 dB.

46
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Sound levels - reversible heat pump


Unit + Very Low Noise option
■ Sound power level (LW) - Cooling mode

AQUACIATPOWER Power level spectrum (1)


™ ILD Global sound
Unit + Very Low 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz power level (2)
Noise option
0602R dB 75,5 80 83 85 80 75 69 74 dB(A) 85,0
0700R dB 76,5 81 84 86 81 76 70 75 dB(A) 86,0
0800R dB 77 82 85 86 82 77 71 75 dB(A) 86,5
0900R dB 77,5 82 85 87 82 77 71 76 dB(A) 87,0
1000R dB 78 82 85 87 81 78 71 75 dB(A) 87,0
1150R dB 78,5 83 86 88 83 79 72 77 dB(A) 88,0
1250R dB 79 83 86 88 82 79 72 76 dB(A) 88,0
1400R dB 79,5 84 87 89 84 79 73 78 dB(A) 89,0
1500R dB 80 84 87 89 83 80 73 77 dB(A) 89,0
1600R dB 80 85 87 89 84 80 73 78 dB(A) 89,5
1750R dB 81 85 88 90 84 81 74 78 dB(A) 90,0
2000R dB 81 85 88 90 84 81 74 78 dB(A) 90,0
(1) In dB ref=10-12 W, as a guideline. Measured in accordance with ISO 9614-1.
(2) In dB ref=10-12 W, (A) weighting, with an uncertainty of +/-3 dB. Measured in accordance with ISO 9614-1 and certified by Eurovent.

■ Sound pressure level (Lp) - Cooling mode


Measurement conditions: Free field, 10 metres from machine, 1.5 metres above floor level, directivity 2
Note: the sound pressure levels depend on the installation conditions of each system. As such, the levels listed here are given
for information only. Only the sound power levels are comparable and certified.

AQUACIATPOWER Sound pressure spectrum (1)


Global sound
™ ILD
pressure
Unit + Very Low 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz spectrum (2)
Noise option
0602R dB 44 48 51 53 48 43 37 42 dB(A) 53,0
0700R dB 45 49 52 54 49 44 38 43 dB(A) 54,0
0800R dB 45 50 53 54 50 45 39 43 dB(A) 54,5
0900R dB 46 50 53 55 50 45 39 44 dB(A) 55,0
1000R dB 46 50 53 55 49 46 39 43 dB(A) 55,0
1150R dB 47 51 54 56 51 47 40 45 dB(A) 56,0
1250R dB 47 51 54 56 50 47 40 44 dB(A) 56,0
1400R dB 48 52 55 57 52 47 41 46 dB(A) 57,0
1500R dB 48 52 55 57 51 48 41 45 dB(A) 57,0
1600R dB 48 52 55 57 52 47 41 46 dB(A) 57,0
1750R dB 49 53 55 58 52 48 41 46 dB(A) 57,5
2000R dB 49 53 55 58 52 48 41 46 dB(A) 57,5
(1) In dB ref=2x10-5 Pa, as a guideline.
(2) In dB ref=2x10-5 Pa, (A) weighting with an uncertainty of +/-3 dB.

47
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Sound levels - reversible heat pump


Unit + Ultra Low Noise option
■ Sound power level (LW) - Cooling mode

AQUACIATPOWER Power level spectrum (1)


™ ILD Global sound
Unit + Ultra Low 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz power level (2)
Noise option
0602R dB 79 80 83 81 78 73 67 74 dB(A) 83
0700R dB 80 82 84 83 79 74 69 75 dB(A) 84
0800R dB 80 82 85 83 80 74 69 76 dB(A) 85
0900R dB 81 83 85 84 80 75 70 76 dB(A) 85
1000R dB 81 82 85 84 80 75 70 76 dB(A) 85
1150R dB 82 84 86 85 81 76 71 77 dB(A) 86
1250R dB 82 83 86 85 81 76 71 77 dB(A) 86
1400R dB 82 84 87 85 81 77 71 78 dB(A) 87
1500R dB 83 84 87 86 82 77 72 78 dB(A) 87
1600R dB 83 85 88 86 83 78 72 79 dB(A) 88
1750R dB 83 85 88 86 82 78 72 79 dB(A) 88
2000R dB 84 85 88 87 83 78 73 79 dB(A) 88
(1) In dB ref=10-12 W, as a guideline. Measured in accordance with ISO 9614-1.
(2) In dB ref=10-12 W, (A) weighting, with an uncertainty of +/-3 dB. Measured in accordance with ISO 9614-1 and certified by Eurovent.

■ Sound pressure level (Lp) - Cooling mode


Measurement conditions: Free field, 10 metres from machine, 1.5 metres above floor level, directivity 2
Note: the sound pressure levels depend on the installation conditions of each system. As such, the levels listed here are given
for information only. Only the sound power levels are comparable and certified.

AQUACIATPOWER Sound pressure spectrum (1)


Global sound
™ ILD
pressure
Unit + Ultra Low 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz spectrum (2)
Noise option
0602R dB 47 48 51 49 46 41 35 42 dB(A) 51
0700R dB 48 50 52 51 47 42 37 43 dB(A) 52
0800R dB 48 50 53 51 48 42 37 44 dB(A) 53
0900R dB 49 51 53 52 48 43 38 44 dB(A) 53
1000R dB 49 50 53 52 48 43 38 44 dB(A) 53
1150R dB 50 52 54 53 49 44 39 45 dB(A) 54
1250R dB 50 51 54 53 49 44 39 45 dB(A) 54
1400R dB 50 52 55 53 49 45 39 46 dB(A) 55
1500R dB 51 52 55 54 50 45 40 46 dB(A) 55
1600R dB 51 53 55 54 50 45 40 46 dB(A) 56
1750R dB 51 52 55 54 50 45 40 46 dB(A) 56
2000R dB 51 53 56 54 50 46 40 47 dB(A) 56
(1) In dB ref=2x10-5 Pa, as a guideline.
(2) In dB ref=2x10-5 Pa, (A) weighting with an uncertainty of +/-3 dB.

48
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Installation water volume - exchanger water flow rate


The Connect Touch control is equipped with anticipation logic Heating mode
making it highly flexible in adjusting operation to parameter - hot water temperature = 40 °C/45 °C
drift, particularly on hydraulic systems with low water volumes. - outdoor air temperature = 7 °C
By adjusting compressor running times, it prevents short-cycle
This value is applicable for most air conditioning applications
protection cycles from starting and, in most cases, eliminates
(unit with fan coil units).
the need for a buffer tank.
Note:
Note: The minimum volumes of chilled water are calculated for
EUROVENT rated conditions: For installations running with a low volume of water (assembly
with air handling unit) or for industrial processes, the buffer tank
Cooling mode is a required component.
- chilled water temperature = 12 °C/7 °C
- outdoor air temperature = 35 °C

AQUACIATPOWER ™ LD 0602R 0650R 0750R 0900R 1100R 1200R 1350R 1400R 1600R

Minimum system water volume, air


(litres) 431 468 516 568 676 777 864 949 1039
conditioning application
Minimum system water volume, industrial
(litres) 1121 1217 1342 1476 1758 2021 2247 2467 2702
process application
Water type heat exchanger flow rate without 3,1 / 3,1 / 3,7 / 3,1 / 3,8 / 3,5 / 4,6 / 4,3 / 5,4 /
(l/s)
hydraulic module Min(1)/Max(2) 17,5 17,5 17,5 17,5 21,8 29,8 35,2 33,8 38,9
Single min(3)/
3,1 / 12 3,1 / 12 3,7 / 12 3,1 / 12 3,8 / 15 3,5 / 19 4,6 / 20 4,3 / 20 5,4 / 28
Water type heat exchanger flow rate with Max (l/s)
low-pressure hydraulic module Dual min(3)/
3,1 / 11 3,1 / 11 3,7 / 12 3,1 / 12 3,8 / 15 3,5 / 19 4,6 / 20 4,3 / 20 5,4 / 23
Max (l/s)
Single
3,1 / 14 3,1 / 14 3,7 / 3,1 / 14 3,8 / 16 3,5 / 18 4,6 / 25 4,3 / 25 5,4 / 25
Water type heat exchanger with high-pressure min(3)/Max (l/s)
hydraulic module Dual
3,1 / 14 3,1 / 14 3,7 / 14 3,1 / 14 3,8 / 17 3,5 / 19 4,6 / 24 4,3 / 24 5,4 /25
min(3)/Max (l/s)

AQUACIATPOWER ™ LD 1750R 1800R 2000R 2200R 2400R 2650R 2800R 2950R 3200R 3500R

Minimum system water volume, air


(litres) 1126 1209 1381 1542 1694 1816 1955 2017 2204 2359
conditioning application
Minimum system water volume, industrial
(litres) 2928 3144 3590 4009 4405 4723 5083 5245 5730 6132
process application
Water type heat exchanger flow rate without 5,8 / 6,2 / 6,9 / 7,3 / 7,3 / 7,3 / 8,3 / 8,3 / 8,3 / 8,3 /
(l/s)
hydraulic module Min(1)/Max(2) 40,4 41,6 43,4 57,3 57,3 57,3 62,7 62,7 62,7 62,7
Single min(3)/ 5,8 / 6,2 / 6,9 /
- - - - - - -
Water type heat exchanger flow rate with Max (l/s) 29 29 27
low-pressure hydraulic module Dual min(3)/ 5,8 / 6,2 / 6,9 /
- - - - - - -
Max (l/s) 28 29 27
Single 5,8 / 6,2 / 6,9 /
- - - - - - -
Water type heat exchanger with high- min(3)/Max (l/s) 29 29 29
pressure hydraulic module Dual 5,8 / 6,2 / 6,9 / 7,3 / 7,3 / 7,3 / 8,3 / 8,3 / 8,3 / 8,3 /
min(3)/Max (l/s) 28 28 34 42,4 42,4 42,4 50,4 50,4 50,4 50,4

(1) Minimum flow rate for maximum permitted water temperature difference conditions (10° C)
(2) Maximum flow rate for a pressure drop of 100 kPa in the plate heat exchanger
(3) Minimum factory flow rate setting according to the type of pump

49
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Installation water volume - exchanger water flow rate

AQUACIATPOWER ™ ILD 0602R 0700R 0800R 0900R 1000R 1150R 1250R 1400R 1500R 1600R 1750R 2000R

Minimum system water volume, air


(litres) 388 425 488 550 588 700 763 863 900 975 1050 1213
conditioning application - cooling
Minimum system water volume, air
(litres) 1360 1520 1840 2000 2080 2480 2640 2960 3120 3400 3600 4160
conditioning application - heating
Minimum system water volume,
(litres) 1008 1105 1268 1430 1528 1820 1983 2243 2340 2535 2730 3153
industrial process application
Water type heat exchanger flow rate 3,1 / 3,7 / 3,1 / 3,8 / 3,8 / 4,6 / 5,8 / 5,8 / 5,8 / 5,8 / 6,2 / 6,9 /
(l/s)
without hydraulic module Min(1)/Max(2) 17,5 17,5 17,5 21,8 21,8 35,2 40,4 40,4 40,4 40,4 41,6 43,4
Single min(3)/ 3,1 / 3,7 / 3,1 / 3,8 / 3,8 / 4,6 / 5,8 / 5,8 / 5,8 / 5,8 / 6,2 / 6,9 /
Water type heat exchanger flow rate Max (l/s) 12,0 12,0 13,6 14,7 14,7 20,1 28,8 28,8 28,9 28,10 29,7 30,1
with low-pressure hydraulic module Dual min(3)/ 3,1 / 3,7 / 3,1 / 3,8 / 3,8 / 4,6 / 5,8 / 5,8 / 5,8 / 5,8 / 6,2 / 6,9 /
Max (l/s) 10,5 13,2 13,9 14,7 14,7 20,0 27,8 27,8 27,8 27,8 26,8 29,3
Single 3,1 / 3,7 / 3,1 / 3,8 / 3,8 / 4,6 / 5,8 / 5,8 / 5,8 / 5,8 / 6,2 / 6,9 /
Water type heat exchanger with min(3)/Max (l/s) 14,1 14,1 15,2 16,0 16,0 25,0 25,5 25,6 25,7 28,5 28,6 34,9
high-pressure hydraulic module Dual 3,1 / 3,7 / 3,1 / 3,8 / 3,8 / 4,6 / 5,8 / 5,8 / 5,8 / 5,8 / 6,2 / 6,9 /
min(3)/Max (l/s) 13,7 13,7 15,6 16,6 16,6 24,4 25,0 28,2 28,2 28,2 33,3 33,7

(1) Minimum flow rate for maximum permitted water temperature difference conditions (10° C)
(2) Maximum flow rate for a pressure drop of 100 kPa in the plate heat exchanger
(3) Minimum factory flow rate setting according to the type of pump

50
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Operating range
AQUACIATPOWER ™ devices have a broad field of application, enabling them to meet a range of heating and cooling requirements
in the most varied of climates.

Multi-climate:
Cooling mode from -20 °C to +44 °C (option +48 °C)
The AQUACIATPOWER ™ series is equipped as standard with all the management devices and algorithms to enable all-season
operation in all climates. The AQUACIATPOWER ™ equipped with optional all-season operation and/or variable-speed fans is able
to operate in conditions ranging from the heat of the Mediterranean basin to the cold of Scandinavia, the humid Atlantic coast to
the dry climate of Central Europe.
Heating mode from -10 °C to +35 °C
The design of the AQUACIATPOWER ™ makes it suitable for the majority of heating and air conditioning applications, regardless
of the climate. Water heated to +45 °C is guaranteed, even for outdoor temperatures of -10 °C.
Multi-application: air conditioning, industrial processes
The AQUACIATPOWER ™ can be used for all traditional air conditioning applications in sectors as varied as collective housing,
hotels, shopping centres and offices.

LD 602R - 3500R units

Operating range Operating range


Options: Rated high performance Standard unit basic version
or Extended application range VLN/ULN acoustic version
52
50 Part load 50
pa
LD 18 rt load
45
00R -
3500R
45 Part load
pa
LD 18 rt load
00R-35
00R
40 40

35 35

30 30
Inlet air temperature (°C)

Inlet air temperature (°C)

25 25
Low-temperature Low-temperature
20 brine solution option 20 brine solution option
15 15

10 10

5 5

0 0
Sizes 602-1400
operation option

operation option
Variable-speed

602 -
Variable speed

-5 -5
All-season

All-season
fan option

fan option

1400

-10 -10
Sizes

-15 -15

-20 -20

-25 -25
-10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

Water outlet temperature (°C) Water outlet temperature (°C)

1. Water type heat exchanger ∆T = 5K


2. The water type heat exchanger is protected against frost down to -20 °C (with Water exchanger frost protection option or water type heat exchanger and hydraulic
module frost protection option (if present) or water loop protected by antifreeze solution for outdoor temperatures < 0 °C)
3. These ranges are guidelines only. The operating range must be checked with the Selection software.

Key

Full load

All-season operation option or variable-speed fans option for units LD 602 to 1400 (see note 2)

Part load

Extension of the operating range for units with low-temperature brine solution option

51
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Operating range
ILD 602R - 2000R units

Cooling mode Heating mode


40

52
50
35
part load
46
45
Options: Rated high performance or extended application range
42 30
Basic unit or VLN/ULN acoustic version option
40

35 25

30

Inlet air temperature (°C)


20
Inlet air temperature (°C)

25

15
20

15 10

10
5

g
cle rin
5

cy du
0

ng ng
0

sti adi
fro fflo
th ial o
variable speed
All seasons or

-5 -5
operating

nt
e
option

te
fans

po
-10
-10
-15 Partial load
-15
-20

-25
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
-20
15 20 25 30 35 40 45 50 55 60

Water outlet temperature (°C) Water outlet temperature (°C)

Full load operating range for AQUACIATPOWER ™ ILD units with Rated High performance or Extended application range options

Extended operating range in cooling mode: ILD unit with Winter operation option for outdoor air temperatures down to -20 °C.
The water type heat exchanger must be protected against freezing.

Part load or potential load shedding during the frosting cycle depending on the humidity conditions. Refer to the manufacturer's electronic catalogue.

Heating mode: Partial load at inlet air temperature between -10 and -15 °C
Cooling mode: Partial load above 46 °C of inlet air temperature.

Part load operation outside of an inlet air temperature of 42 °C for Basic ILD units or units with the Low noise level option

For operation in pure water at an inlet air temperature below 0 °C, the frost protection option must be provided

52
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Hydraulic specifications
■ Water pressure drop in the evaporator
Data applicable for pure water at 20 °C.

LD 602R - 1400R

B C D FE
Pressure drop, kPa

Water flow rate, l/s


1 LD 602R - 900R
2 LD 1100R
3 LD 1200R
4 LD 1350R
5 LD 1400R

LD 1600R - 3500R

GHIJ K L
Pressure drop, kPa

Water flow rate, l/s


6 LD 1600R
7 LD 1750R
8 LD 1800R
9 LD 2000R
10 LD 2200R - 2650R
11 LD 2800R - 3500R

53
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Hydraulic specifications
ILD 602R-1400R

B C DE
Pressure drop, kPa

Water flow rate, l/s


1 ILD 602R - 800R
2 ILD 900R - 1000R
3 ILD 1150R - 1250R
4 ILD 1400R

ILD 1500R-2000R

FGH
Pressure drop, kPa

Water flow rate, l/s


5 ILD 1500R - 1600R
6 ILD 1750R
7 ILD 2000R

54
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Hydraulic specifications
■ Water pressure drop in the filter
Screen filter (800 µm)

12
10

5,0
Pressure drops (mWC)

1,0

1
2

0,1
10 20 100 150
Qv (m3/h)
1 LD 602R - 650R and ILD 602R - 700R (DN80 filter)
2 LD 750R - 1200R and ILD 800R - 1250R (DN100 filter)
3 LD 1350R - 3500R and ILD 1400R - 2000R (DN125 filter)

55
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Hydraulic specifications
■ Available static system pressure
Data applicable for:
- Pure water at 20 °C
- Refer to the section "Exchanger water flow rate" for the minimum and maximum water flow rate values
- If a brine solution is used, the maximum water flow rate is reduced

■ LD high pressure pumps (fixed speed or variable speed)

Single pumps

Sizes 602R - 1600R


Available static pressure, kPa

1 LD 602R - 900R
2 LD 1100R
3 LD 1200R
4 LD 1350R
5 LD 1400R
6 LD 1600R

B C D EF G
Water flow rate, l/s

Sizes 1750R - 2000R


Available static pressure, kPa

7 LD 1750R
8 LD 1800R
9 LD 2000R

Water flow rate, l/s HI J

56
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Hydraulic specifications
Dual pumps

Sizes 602R - 1600R


Available static pressure, kPa

1 LD 602R - 900R
2 LD 1100R
3 LD 1200R
4 LD 1350R
5 LD 1400R
6 LD 1600R

B C D F EG
Water flow rate, l/s

Sizes 1750R - 2000R


Available static pressure, kPa

7 LD 1750R
8 LD 1800R
9 LD 2000R

Water flow rate, l/s HI J

Sizes 2200R - 3500R


Available static pressure, kPa

10 LD 2200R - 2650R
11 LD 2800R - 3500R

Water flow rate, l/s K L

57
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Hydraulic specifications
■ Low pressure pumps (fixed speed)

Single pumps

Sizes 602R - 1400R Sizes 1600R - 2000R

Available static pressure, kPa


Available static pressure, kPa

B C D EF Water flow rate, l/s J G HI


Water flow rate, l/s
6 LD 1600R
1 LD 602R - 900R 7 LD 1750R
2 LD 1100R 8 LD 1800R
3 LD 1200R 9 LD 2000R
4 LD 1350R
5 LD 1400R

Dual pumps

Sizes 602R - 1600R Sizes 1750R - 2000R


240 280
260
220
Available static pressure, kPa

240
Available static pressure, kPa

200
220
180 200

160 180
160
140
140
120
120
100 100

80 80
60
60
40
40
20
20 5,0 10,0 15,0 20,0 25,0 30,0
0,0 5,0 10,0 15,0 20,0 25,0
Water flow rate, l/s K IJ
B C D E FG H
8 LD 1750R
Water flow rate, l/s 9 LD 1800R
1 LD 602R - 650R 10 LD 2000R
2 LD 750R - 900R
3 LD 1100R
4 LD 1200R
5 LD 1350R
6 LD 1400R
7 LD 1600R

58
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Hydraulic specifications
■ Available static system pressure
Data applicable for:
- Pure water at 20 °C
- Refer to the section "Exchanger water flow rate" for the minimum and maximum water flow rate values
- If a brine solution is used, the maximum water flow rate is reduced

■ ILD high pressure pumps (fixed speed or variable speed)

Single pumps

Sizes 602R - 1000R Sizes 1150R - 2000R

270 330
310
250
Available static pressure, kPa

Available static pressure, kPa


290
230 270
210 250

190 230
210
170
190
150
170
130 150

110 130
110
90
90
70
70
50 50
0,0 5,0 10,0 15,0 20,0 0,0 5,0 10,0 15,0 20,0 25,0 30,0 35,0 40,0

Water flow rate, l/s B C


D FG H I
Water flow rate, l/s
1 ILD 602R - 700R
5 ILD 1150R
2 ILD 800R
6 ILD 1250R - 1500R
3 ILD 900R - 1000R
7 ILD 1600R - 1750R
8 ILD 2000R

Dual pumps

Sizes 602R - 1000R Sizes 1150R - 2000R


270 310
290
250
Available static pressure, kPa

270
Available static pressure, kPa

230
250
210 230

190 210
190
170
170
150
150
130 130

110 110
90
90
70
70
50
50 0,0 5,0 10,0 15,0 20,0 25,0 30,0 35,0 40,0
0,0 5,0 10,0 15,0 20,0 25,0 FG H IJ
B C DE Water flow rate, l/s
Water flow rate, l/s
5 ILD 1150R
1 ILD 602R - 700R 6 ILD 1250R
2 ILD 800R 7 ILD 1400R
3 ILD 900R 8 ILD 1500R - 1600R
4 ILD 1000R 9 ILD 1750R - 2000R

59
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Hydraulic specifications
■ ILD low-pressure pumps (fixed-speed)

Single pumps

Sizes 602R - 1000R Sizes 1150R - 2000R


200 240
190
180 220

Available static pressure, kPa


Available static pressure, kPa

170 200
160
150 180
140
160
130
120 140
110
100 120
90
100
80
70 80
60
50 60
40 40
30
20 20
0,0 5,0 10,0 15,0 20,0 0,0 5,0 10,0 15,0 20,0 25,0 30,0
B C D Water flow rate, l/s E F G
Water flow rate, l/s
4 ILD 1150R
1 ILD 602R - 700R 5 ILD 1250R - 1600R
2 ILD 800R 6 ILD 1750R - 2000R
3 ILD 900R - 1000R

Dual pumps

Sizes 602R - 1000R Sizes 1150R - 2000R


240 280
260
220
Available static pressure, kPa

240
Available static pressure, kPa

200
220
180 200
160 180
160
140
140
120
120
100 100

80 80
60
60
40
40
20
20 0,0 5,0 10,0 15,0 20,0 25,0 30,0
0,0 5,0 10,0 15,0 20,0
Water flow rate, l/sF HG I
B C DE
Water flow rate, l/s 5 ILD 1150R
6 ILD 1250R - 1600R
1 ILD 602R 7 ILD 1750R
2 ILD 700R 8 ILD 2000R
3 ILD 800R
4 ILD 900R - 1000R

60
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Dimensions
■ AQUACIATPOWER ™ LD 602R to 1100R/ILD 602R to 1000R Without buffer tank

Electrical power connection

Key Notes:
All dimensions in mm
Non-contractual drawings.
B Clearance required for maintenance and air flow
C Clearance recommended for coil removal When designing a system, refer to the certified dimensional
drawings provided with the unit or available on request.
Water inlet
Please refer to the certified dimensional drawings for the
Water outlet
positioning of the fixing points, weight distribution points
Air outlet, do not obstruct
and centre of gravity coordinates.
Electrical cabinet

61
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Dimensions
■ AQUACIATPOWER ™ LD 602R to 1100R/ILD 602R to 1000R With buffer tank

Electrical power connection

Key Notes:
All dimensions in mm
Non-contractual drawings.
B Clearance required for maintenance and air flow
C Clearance recommended for coil removal When designing a system, refer to the certified dimensional
drawings provided with the unit or available on request.
Water inlet
Please refer to the certified dimensional drawings for the
Water outlet
positioning of the fixing points, weight distribution points
Air outlet, do not obstruct
and centre of gravity coordinates.
Electrical cabinet

62
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Dimensions
■ AQUACIATPOWER ™ LD 1200R to 1600R/ILD 1150R to 1500R Without buffer tank

Electrical power connection

Key Notes:
All dimensions in mm
Non-contractual drawings.
B Clearance required for maintenance and air flow
C Clearance recommended for coil removal When designing a system, refer to the certified dimensional
drawings provided with the unit or available on request.
Water inlet
Please refer to the certified dimensional drawings for the
Water outlet
positioning of the fixing points, weight distribution points
Air outlet, do not obstruct
and centre of gravity coordinates.
Electrical cabinet

63
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Dimensions
■ AQUACIATPOWER ™ LD 1200R to 1600R/ILD 1150R to 1500R With buffer tank

Electrical power connection

Key Notes:
All dimensions in mm
Non-contractual drawings.
B Clearance required for maintenance and air flow
C Clearance recommended for coil removal When designing a system, refer to the certified dimensional
drawings provided with the unit or available on request.
Water inlet
Please refer to the certified dimensional drawings for the
Water outlet
positioning of the fixing points, weight distribution points
Air outlet, do not obstruct
and centre of gravity coordinates.
Electrical cabinet

64
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Dimensions
■ AQUACIATPOWER ™ LD 1750R to 2000R/ILD 1600R to 2000R Without buffer tank

Electrical power connection

Key Notes:
All dimensions in mm
Non-contractual drawings.
B Clearance required for maintenance and air flow
C Clearance recommended for coil removal When designing a system, refer to the certified dimensional
drawings provided with the unit or available on request.
Water inlet
Please refer to the certified dimensional drawings for the
Water outlet
positioning of the fixing points, weight distribution points
Air outlet, do not obstruct
and centre of gravity coordinates.
Electrical cabinet

65
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Dimensions
■ AQUACIATPOWER ™ LD 1750R to 2000R/ILD 1600R to 2000R With buffer tank

Electrical power connection

Key Notes:
All dimensions in mm
Non-contractual drawings.
B Clearance required for maintenance and air flow
C Clearance recommended for coil removal When designing a system, refer to the certified dimensional
drawings provided with the unit or available on request.
Water inlet
Please refer to the certified dimensional drawings for the
Water outlet
positioning of the fixing points, weight distribution points
Air outlet, do not obstruct
and centre of gravity coordinates.
Electrical cabinet

66
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Dimensions
■ AQUACIATPOWER ™ LD 2200R to 2650R/Without buffer tank

Main hydraulic connection

Key Notes:
All dimensions in mm
Non-contractual drawings.
B Clearance required for maintenance and air flow
C Clearance recommended for coil removal When designing a system, refer to the certified dimensional
drawings provided with the unit or available on request.
Water inlet
Please refer to the certified dimensional drawings for the
Water outlet
positioning of the fixing points, weight distribution points
Air outlet, do not obstruct
and centre of gravity coordinates.
Electrical cabinet

67
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Dimensions
■ AQUACIATPOWER ™ LD 2200R to 2650R/With buffer tank

Electrical power connection

Key Notes:
All dimensions in mm
Non-contractual drawings.
B Clearance required for maintenance and air flow
C Clearance recommended for coil removal When designing a system, refer to the certified dimensional
drawings provided with the unit or available on request.
Water inlet
Please refer to the certified dimensional drawings for the
Water outlet
positioning of the fixing points, weight distribution points
Air outlet, do not obstruct
and centre of gravity coordinates.
Electrical cabinet

68
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Dimensions
■ AQUACIATPOWER ™ LD 2800R to 3500R/Without buffer tank

Electrical power connection

Key Notes:
All dimensions in mm
Non-contractual drawings.
B Clearance required for maintenance and air flow
C Clearance recommended for coil removal When designing a system, refer to the certified dimensional
drawings provided with the unit or available on request.
Water inlet
Please refer to the certified dimensional drawings for the
Water outlet
positioning of the fixing points, weight distribution points
Air outlet, do not obstruct
and centre of gravity coordinates.
Electrical cabinet

69
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Dimensions
■ AQUACIATPOWER ™ LD 2800R to 3500R/With buffer tank

Electrical power connection

Key Notes:
All dimensions in mm
Non-contractual drawings.
B Clearance required for maintenance and air flow
C Clearance recommended for coil removal When designing a system, refer to the certified dimensional
drawings provided with the unit or available on request.
Water inlet
Please refer to the certified dimensional drawings for the
Water outlet
positioning of the fixing points, weight distribution points
Air outlet, do not obstruct
and centre of gravity coordinates.
Electrical cabinet

70
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Installation recommendations
■ Water quality criteria to be respected Electrical connections must be made in accordance with best
Warning: It is essential that an 800-micron water filter be current practices and applicable standards and regulations.
placed on the unit's water inlet during installation. The Electrical cable connections to be made on-site:
quality of the water used has a direct impact on the correct - electrical power supply to the unit
and compliant operation of the machine and its service life. - contacts available as standard enabling the machine to be
This is particularly true if the water used clogs or corrodes controlled remotely (optional)
components or promotes the growth of algae or micro- It should be noted that the unit's electrical system is not protected
organisms. The water must be tested to determine whether against lightning strikes.
it is suitable for the unit. It is also tested to determine Therefore devices to protect against transient voltage surges
whether chemical treatment is necessary and will suffice must be installed on the system and inside the power supply
to make it of acceptable quality. This analysis should unit.
confirm whether or not the various machine components
are compatible with the water they come into contact with ■ Pipe connections
on-site. You must follow the instructions in the manual. All pipes must
WARNING: failure to follow these instructions will result in be correctly aligned and slope towards the system's drain valve.
the immediate voiding of the unit's warranty. Pipes must be installed to allow sufficient access to the panels
for maintenance, and must be fitted with heat insulation.
■ Lifting and handling
Pipe fixings and brackets must be separate to avoid vibrations
The utmost safety precautions must be taken when lifting and and ensure no pressure is placed on the unit. Water flow shut-
handling the unit. off and control valves must be fitted when the unit is installed.
Always follow the lifting diagram on the unit and in the instruction Pipe connections to be made on site:
manual. - Water supply with pressure-reducing valve
Before attempting to lift the unit, make sure the path leading to - Evaporator, condenser and drain
its intended location is free from obstacles. Always keep the unit Accessories essential to any hydraulic circuit must also be
vertical when moving it. Never tip it or lie it on its side. installed, such as:
- Water expansion tank
■ Choosing a location for the unit - Drain nozzles at pipe low points
AQUACIATPOWER ™ units are designed for outdoor installation. - Exchanger shut-off valves equipped with filters
Precautions should be taken to protect the unit from freezing - Air vents at pipe high points
temperatures. Special attention should be paid to ensure - Check the system's water capacity (install a buffer water tank
sufficient free space (including at the top) to allow maintenance. if necessary)
The unit must be placed on a perfectly level, fireproof surface - Flexible couplings on exchanger inlets and outlets
strong enough to support it when ready for operation. Noise Warning:
pollution from auxiliary equipment such as pumps should be - Pressure in the hydraulic circuits below 4 bar for units
studied thoroughly. equipped with the hydraulic module
Potential noise transmission routes should be studied, with - Place the expansion tank before the pump.
assistance from an acoustical engineer if necessary, before - Do not place any valves on the expansion tank.
installing the unit. It is strongly recommended that flexible - Make sure the water circulation pumps are placed
couplings are placed over pipes and anti-vibration mounts are directly at the exchanger inlets.
fitted underneath the unit (equipment available as an option) to - Make sure the pressure of the water drawn in by the
reduce vibrations, and the noise this causes, as much as circulation pumps is greater than or equal to the required
possible. minimum NPSH, particularly if the hydraulic circuits are
open.
■ Fitting accessories supplied separately - Test the water quality in accordance with the relevant
A number of optional accessories may be delivered separately technical specifications.
and installed on the unit on site. - Take the necessary precautions to protect the unit and
You must follow the instructions in the manual. hydraulic system from freezing temperatures (e.g. allow
for the possibility of draining the unit). If glycol is added
■ Electrical connections to prevent freezing, check its type and concentration
before system start-up.
You must follow the instructions in the manual. All information
- Before making any final hydraulic connections, flush the
concerning electrical connections is stated on the wiring
pipes with clean water to remove any debris in the
diagrams provided with the unit. Always follow this information
network.
to the letter.

71
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Installation recommendations
■ System start-up ■ Maintenance operations
System start-up for these machines must be performed by CIAT Specific preventive maintenance operations are required at
or a CIAT-authorised firm. regular intervals and should be performed by CIAT-approved
You must follow the instructions in the manual. contractors.
List of system start-up checks (non-exhaustive): The operating parameters are read and noted on a "CHECK
- Correct positioning of unit LIST" form to be returned to CIAT.
- Power supply protections To do this, you must refer to and comply with the instruction
- Phases and direction of rotation manual.
- Wiring connections on unit You must take out a maintenance contract with a CIAT-approved
- Direction of water flow in unit refrigeration equipment specialist. Such a contract is required
- Cleanliness of hydraulic circuit even during the warranty period.
- Water flow rate at specified value
- Pressure in the refrigerating circuit
- Direction of rotation of compressors
- Water pressure drops and flow rates
- Operating readings

72
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump

Control
USER-FRIENDLY INTERFACE CONSOLE BluEdge® Digital REMOTE MACHINE
- User-friendly 4.3-inch touch screen. SUPERVISION
- Information displayed in a choice of languages. 2 years of services with:
- Temperature and pressure readings. - Monitoring of machine operation (operation overviews and
- Operating and fault status diagnostics. curves, alarm logs).
- Master/slave control of two machines in parallel. - E-mail alerts for alarms (optional SMS alerts).
- Fault memory management. - Remote updates for BluEdge® Digital.
- Pump management.
- Access to a log of machine operation data.
- Time schedule.
- Remote advice on using BluEdge® Digital.
- IP web server
- System start-up and operating readings.
- Programmable maintenance
- Preventive maintenance
- F-Gas maintenance
- E-mail alert
- Indication of energy supplied and consumed instantly (kW)
and integrally (kWh)

PRODUCT FUNCTIONALITY
POTENTIAL-FREE (DRY) CONTACTS AVAILABLE
AS STANDARD
Inputs:
- Automatic operation control
- Heating/cooling mode selection
- Selection of setpoints 1 / 2
Via dry contact
- Power limitation.
Outputs:
- General fault reporting
- Operational status reporting
Additional inputs available as options:
- Setpoint adjustment by 4-20 mA signal
- Power limitation adjustable by 4-20 mA signal
- Second power limitation level
- End of storage signal
Customer CMS - User fault display
COMMUNICATION - Contact for refrigerant leak detector
Additional outputs available as options:
- Indication of the power level by 0-10 V signal
- Minor alert reporting
- Unit shut-down general fault reporting
- Desuperheater pump On/Off control
- On/off control for a boiler
- 4-stage on/off management for additional heaters

Via BUS AVAILABLE OUTPUTS


communication - MODBUS-JBUS RTU (RS485) or TC/IP (standard) open
protocol
- LONWORKS protocol (option)
- BTL certified BACNET IP protocol (option)

CIAT SYSTEM FUNCTIONALITY


Communication with CIAT Energy pool controlled by
PowerCTRL.
Integrated PowerCTRL:
- Energy optimisation of refrigeration and heating using
several generators,
- Manages free cooling capacity
- Uses heat recovery to supply
- domestic hot water.

73
Order No.: NA22.769A. Supersedes Order No.: NA21.769B. Manufactured by: Carrier SCS, Montluel, France.
The manufacturer reserves the right to make any changes, without notice.
The illustrations contained in this document are for information only and do not form part of any sales or contract proposal. The manufacturer reserves the right to
make changes to the model design, at any time and without notice.