The high-performance
packaged solution now
available with R-32
Compact and silent
Scroll compressors
High-efficiency brazed-plate heat exchangers Cooling capacity: 170 to 940 kW
Heating capacity: 160 to 520 kW
Self-adjusting electronic control
R-32
Cooling Hydraulic Heat
and module recovery
heating
Use
The new generation of AQUACIATPOWER ™ high-efficiency The optional variable-speed fan motors guarantee even better
air-to-water heat pumps and water chillers offers an optimal results.
solution for all heating and cooling applications used for the Thanks to their exceptional thermodynamic performance,
Healthcare, Office, and Hotel sectors. provided by radical selection of components, an electronic
These units are designed for outdoor installation and require expansion valve as standard, and a specific control function,
no special protection against adverse weather conditions. standard AQUACIATPOWER ™ units reach a high level of
AQUACIATPOWER ™ is optimised for R-32, the environmentally- seasonal efficiency in cooling mode (SEER) and in heating
responsible fluid with the lowest GWP. mode (SCOP).
This range guarantees compliance with the most demanding ■ Acoustic comfort
requirements for increased seasonal energy efficiency (SEER
With different levels of sound equipment available, the
and SCOP) and CO2 reduction to comply with the various
AQUACIATPOWER ™ range guarantees the acoustic comfort of
applicable European directives and regulations.
occupants and meets the needs of the most sensitive
■ Self-re gulating oper ation to adapt to environments, including hotels, offices and hospitals.
seasonal variations and requirements
■ Quick, simple installation
With exceptional SEER and SCOP seasonal energy efficiency
With a wide variety of connection accessories and equipment,
levels, the AQUACIATPOWER ™ range offers the best technology
the AQUACIATPOWER ™ range is quick and simple to install.
combined with savings throughout the year.
The advanced controller functions and different communication
Due to climatic variations and the different air-conditioning
protocols enable local control via CMS/BMS or remote control,
needs of tertiary buildings, most of the time water chillers and
providing building management with peace of mind.
heat pumps run at partial load.
Equipped with multiple compressors, AQUACIATPOWER ™ units
automatically adjust cooling capacity, anticipating variations in
load and starting only the number of compressors needed to
ensure optimum operation and energy efficiency.
1
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
COMFORT
UNITS WATER CHILLERS,
HEAT PUMPS
CIATCONTROL
DRYCOOLERS
SUPERVISION
FREE COOLING
HEAT EXCHANGERS
THERMAL ENERGY
STORAGE
Range
■ AQUACIATPOWER ™ LD/ILD series ■ Units equipped with variable-speed fans
In the LD water chiller & ILD standard reversible heat pump (option)
versions, AQUACIATPOWER ™ units are optimised to meet the High seasonal energy efficiency version.
most demanding technical and economic requirements.
In this configuration, the AQUACIATPOWER ™ unit is optimised
for partial load applications for which an optimum SEER and
■ Units with nominal high energy performance SCOP value is required. In this case, the machine is equipped
(option) with variable-speed fans, optimising the partial load efficiency
In this configuration, the AQUACIATPOWER ™ unit is optimised throughout the year.
for full-load applications for which an optimum EER and COP
value is required. In this case, the machine is equipped with
high-speed fans enabling nominal efficiency and a broader
application range.
2
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Description
AQUACIAT POWER ™ units are packaged machines supplied as The entire AQUACIAT POWER ™ range complies with the
standard with the following components: following EC directives and standards:
- Hermetic SCROLL compressors - Machinery directive 2006/42/EC.
- Brazed-plate condenser or evaporator water type heat - Electromagnetic compatibility directive 2014/30/EC
exchanger - Safety of machinery: Electrical equipment of machines EN
- All-aluminium micro-channel condenser (LD) or evaporator 60204-1
air-cooled exchanger, copper tube coil with aluminium fins - EMC immunity and emissions EN 61800-3 ‘C3’
(ILD) and axial fan motor assembly - Regulation (EC) No. 1907/2006 REACH
- Electrical power and remote control cabinet: Pressure equipment directive (PED) 2014/68/EU
• 400 V-3ph-50 Hz (+/-10%) mains power supply + earth - Refrigerating systems and heat pumps EN 378-2
• transformer fitted as standard on the machine for supplying - Regulation (EU) No. 813/2013 implementing Directive
the remote control circuit with 24 V 2009/125/EC with regard to ecodesign requirements (Heat
- Connect Touch electronic control module pump)
- Casing for outdoor installation - Regulation (EU) No. 2016/2281 implementing Directive
2009/125/EC with regard to ecodesign requirements (Chiller)
Configuration
Energy versions
3
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Customer benefits
Energy savings
We develop solutions to enable substantial savings while protecting the environment and guaranteeing user comfort.
Heat recovery options can be used to produce free additional hot water at a high temperature. This hot water can be used to
prepare domestic hot water for heating swimming pools, spas and hot tubs.
The free cooling option is used to provide significant energy savings for all for applications which require cooling all year round or
during the night, particularly in cold regions.
In these regions, free cooling is a very effective and environmentally-friendly means of meeting a large proportion of the cooling
requirements.
PROCESS application
Cooling capacity
Nominal
cooling
TO
TA
capacity
L
PA
FR
RT
FREE COOLING: The economical
EE
IA
LF Chiller
RE
CO
E cooling solution
CO
O
OL
LI
IN
N
G
G
Outdoor
temperature
* BluEdge® Digital is the new name for CIATM2M. The technology remains unchanged.
4
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Main components
FAN SPIGOT
(COMPOSITE)
OPTIMISED SCROLL
COMPRESSORS
R-32
ASYMMETRICAL BRAZED
PLATE HEAT EXCHANGER
ELECTRONIC
EXPANSION
VALVE
5
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
■ A
ir-cooled exchanger The electronic control module performs the following main
- Liquid chiller: air-cooled exchanger, all-aluminium, micro- functions:
channels - Regulation of the chilled water temperature (at the return or
- Heat pump: air-cooled exchanger, copper tube coil, at the outlet)
aluminium fins - Control of the water temperature based on the outdoor
- propeller fans with composite blades offering an optimised profile temperature (water law)
with fixed-speed or variable-speed according to the model, variable- - Control for low temperature energy storage
speed option using frequency inverter or EC motor - Management of a second setpoint
- motors – IP 54, class F - Complete management of the compressors with start-up
sequence, timer and runtime balancing
■ Refrigerating accessories - Self-adjusting and proactive functions with adjustment of
- ehumidifier filters with rechargeable cartridges
D settings on drift control
- hygroscopic sight glasses - In-series staged power control system on the compressors
- electronic expansion valves according to the thermal requirements
- service valves on the liquid line - Management of compressor short-cycle protection
- Four-way reverse cycle valve in cooling/heating mode - Frost protection (exchanger heater option)
- Phase reversal protection
■ Control and safety instruments - Optimised defrosting with free defrost function to optimise
- low and high pressure sensors part-load performance and the SCOP
- safety valves on refrigerant circuit - Management of occupied/unoccupied modes (according to
- water temperature control sensors the time schedule)
- evaporator antifreeze protection sensor - Compressor and pump runtime balancing
- factory-fitted evaporator water flow controller - Management of the machine operation limit according to
outdoor temperature
■ Electrical cabinet - Sound level reduction device (night mode according to the
- Electrical cabinet with IP 54 protection rating user programme) with limitation of compressor capacity and
- A connection point without neutral fan speed
- front-mounted main safety switch with handle - Diagnosis of fault and operating statuses
- control circuit transformer - Management of a fault memory allowing a log of the last 50
- 24 V control circuit incidents to be accessed, with an operating reading taken
- fan and compressor motor circuit breaker when the fault occurs
- fan and compressor motor contactors - Blackbox memory
- C o n n e c t To u c h - Master/slave management of the two machines in parallel
microprocessor-controlled with runtime balancing and automatic changeover if a fault
electronic control module occurs on one machine
- wire numbering - Weekly and hourly time schedule for the machine, including
- marking of the main electrical 16 periods of absence
components - Pump standby based on demand (energy saving)
- Calculation of the water flow rate and operating pressure
■ Casing (hydraulic module version)
Frame made from RAL 7035 - Electronic adjustment of the water pump speed and water
light grey & RAL 7024 graphite flow rate (variable-speed pump option)
grey painted panels - Display of all machine parameters (3 access levels, User/
Maintenance/Factory, password-protected): temperature,
setpoints, pressures, water flow rate (hydraulic version),
runtime.
- Display of trend curves for the main values
- Storage of maintenance manual, wiring diagram and spare
parts list.
- Innovative smart energy monitoring, providing users with
smart data such as real-time electrical energy consumption
and heating and cooling capacity, and instantaneous and
average energy efficiency rates.
6
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
■ Maintenance
Connect Touch has two maintenance reminder functions as - The scheduled maintenance reminder: when activated, this
standard, making users aware of the need to regularly perform function enables the period between two maintenance
maintenance operations and to guarantee the service life and inspections to be set. This period may be set by the operator
performance of the unit. These two functions can be activated in either days, months or operating hours, depending on the
independently. application.
A reminder message appears on the unit's HMI screen, and - The compulsory F-GAS sealing test maintenance reminder:
stays there until it is acknowledged by the maintenance operator. when activated, this function, which is the default factory
The information and alert relating to these functions are available setting, enables the period between two sealing tests to be
on the communication bus to be used on the CMS/BMS. selected, according to the unit's refrigerant charge, in
compliance with the F-GAS regulations.
7
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Peace of mind
Complete reliability thanks to state-of-the-art monitoring CLOUD
solutions: BluEdge® Digital
Data
■ BluEdge ® Digital, the CIAT monitoring analytics
4G
Advantages USERS
- Access to the operating trend curves for analysis
- Improved energy performance Customer BluEdge
technician
- Improved availability rate for the machines
ACTIONS
Functions
Digital
BluEdge® Digital will send data in real time to a supervision interface
website.
The machine operating data can be accessed from any PC,
smartphone or tablet.
Any event can be configured to trigger a mail alert.
Composition of the box (available in 230 V and
Parameters monitored:
400 V)
- Overview
- Control panel for the controllers - 1 GPRS / 4G LTE-M modem
- Events - 1 SMART SIM card
- Temperature curves - 1 power supply (24 VDC)
- 1 power protection device
Monthly and annual reports are available to analyse:
- 1 GSM antenna
- T h e p e r f o r m a n c e a n d o p e r a t i o n o f t h e m a c h i n e
- Rail mounting
Example: operating curves and time, number of compressor
- Enclosed casing to protect the equipment during transport
start-ups, events, preventive maintenance actions to be
- Packing box for cable routing (bus, power supply)
performed, etc.
Incidents such as a drift in the measurements on a temperature
Compatibility
sensor, incorrectly set control parameters, or even incorrect
settings between one compressor stage and the other, are Up to 5 machines per box
immediately detected, and the corrective actions put in place.
Equipment
This box can be used both on machines which are already in
use (existing inventory), and on new machines.
- 1 transportable cabinet
Overview Parameters
Curves Information
Events
(real time and archives) Reports
BluEdge® Digital
supervision platform
8
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
9
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
10
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Hydraulic module
■ The "ALL IN ONE" solution The components in the hydraulic system are carefully selected
and factory assembled and tested to make the installation of
The PLUG & COOL solution offered by the units simple and economical.
AQUACIATPOWER ™ This ensures conditioning times, implementation times and
space requirements are kept to a minimum.
The hydraulic module contains all the hydraulic circuit
components needed for the system to operate correctly: ■ Hydraulic module
- Buffer tank with 19-mm insulation, 550-litre capacity (option).
- Expansion vessel (option):
• 50 litres for models 602 to 900.
• 80 litres for models 902 to 3500.
- Wide choice of pumps:
• Single or dual pumps with operating time balancing and
backup.
• High- or low-pressure pumps.
• Fixed-speed or variable-speed pumps.
- Water temperature and pressure sensors.
- Water filter.
- Relief valve.
- Drain circuit.
- Air bleed valve.
- Frost protection (option).
11
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
■ Operating principle
- Full load operating
A regulator, with a direct display of the flow rate and pressure
on the Connect Touch screen, enables one pump (pump A in the
example below) to be adapted, by lowering its pressure P1 to
the requirements of system P2, to obtain the optimal water flow
rate setpoint. Electricity bills for the pump consumption are mWC
proportionally reduced, guaranteeing a return on investment
(ROI) in just a few years, compared to the same fixed-speed
pump equipped with a single flow rate adjustment valve. Pressure drop
pressure Va m
pA
P2 ri
puable
3-V
ariable flow rate: Constant regulation of the temperature m s
p pe
difference Pu "A e
m " d
p
The regulation maintains a constant temperature difference B
whatever the load rate of the unit by reducing the flow rate
to the minimum acceptable limit. This control mode is
Nominal flow rate m3/h
suitable for most comfort applications.
This provides energy savings of around 66% for the
pump in each of these last two operating modes
12
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
R-32
Environmental responsibility
The AQUACIATPOWER ™ contributes to sustainable development via an environmentally responsible approach, aimed at balancing
ecological and economic concerns. This enables it to meet the requirements of future European thermal regulations and to protect
our environment for future generations.
The impact of an air conditioning system on global warming of the planet is in large part caused by CO2 emissions released into
the atmosphere when the electricity required to power the unit is produced (indirect effect) and in small part by CO2 emissions
linked to uncontrolled emissions of refrigerant with global warming potential into the atmosphere (direct effect).
With AQUACIATPOWER ™, it's a win-win situation: its low charge of R-32 refrigerant with low GWP reduces the direct environmental
impact by 80% while reducing the indirect environmental impact thanks to its high energy performance.
To conclude, the potential direct impact of AQUACIATPOWER ™ on the environment with R-32 refrigerant is reduced by
77% compared to the previous generation R-410A.
90 33
13
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
R-32
Environmental responsibility
This performance is the result of the high-quality components used, which have all been rigorously selected:
- R-32 refrigerant with high energy performance,
- New generation of scroll compressors optimised for R-32 refrigerant
- Asymmetrical brazed-plate heat exchanger with extremely low water-side pressure drops enabling a reduction in pump electricity
consumption
- Optional variable-speed pump enabling automatic adjustment of the rated water flow rate (disposal of the control valve), during
operation and during unit shut down periods.
To conclude, the AQUACIATPOWER ™ unit with R-32 refrigerant and variable-speed pump greatly reduces the indirect
environmental impact compared to the previous generation R-410A.
■ EcoPassport®
The PEP ecopassport® programme provides an international reference framework for procedures enabling manufacturers to
report the environmental specifications of their products in the form of an environmental claim known as a Product Environmental
Profile (PEP).
The PEP ecopassport® programme guarantees that PEPs are correctly drawn up, verified and reported in line with the requirements
of the ISO 14025 and IEC/PAS 62545 standards.
The Life Cycle Analysis (LCA) PEP is the environmental identity card for an item of equipment which details the environmental
impacts of the product during its life cycle according to eight mandatory indicators:
1. Global Warming Potential
2. Impact on the ozone layer
3. Acidification of soil and water
4. Eutrophication of water
5. Photochemical ozone creation
6. Abiotic resource depletion
7. Fresh water consumption
8. Total use of primary energy during the life cycle
Products with certified environmental profiles are used to support methods to assess building sustainability such as BREEAM,
LEED. BREEAM, LEED gives additional recognition for materials with robust environmental product declaration types using
manufacturer data.
CIAT is the first HVAC manufacturer to provide the PEP for liquid chillers and heat pumps including not only the 8 mandatory
indicators, but all 27 indicators.
The AQUACIATPOWER ™ LD PEP can be downloaded from the PEP ecopassport® website: http://www.pep-ecopassport.org/fr/
14
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Available options
Corrosion
Fins made of pre-treated aluminium Improved corrosion resistance, recommended
protection,
(polyurethane and epoxy) for moderate marine and urban environments
No ●
traditional coils
Low temperature chilled water production
Low-temperature Covers specific applications such as ice
brine solution
down to -15 °C with ethylene glycol and
storage and industrial processes ● No
down to -12 °C with propylene glycol.
Unit equipped with specific variable-speed
fans: XtraFans (See specific chapter for Ducted fan discharge, optimised temperature
XtraFan maximum available static pressure according control, based on the operating conditions ● ●
to size), each fan equipped with a connection and system characteristics
flange and flexible sleeves
Acoustic compressor enclosure and
Very Low Noise
low-speed fans
Noise level reduction for sensitive sites ● ●
Acoustic compressor enclosure, low-speed
Ultra Low Noise fans and enhanced sound insulation of main Noise level reduction for sensitive sites ● ●
noise sources
High ambient Unit operating range extended to higher
temperature
Unit equipped with a higher speed fan
ambient temperatures ● ●
Protection grilles Metallic protection grilles Coil protection against possible impact ● ●
Soft starter per
compressor
Electronic starter on each compressor Reduced start-up current ● ●
Soft starter per Economical solution for reduced start-up
circuit
Soft starter on each circuit
current ● ●
All year round
Stable unit operation when the outdoor air
cooling operation Fanspeed control via frequency converter
temperature is between 0°C and -20°C ● ●
down to -20°C
Water type heat exchanger module frost
Water exchanger Electric heater on the water type heat
frost protection exchanger and the water duct
protection for an outdoor air temperature ● ●
between 0 °C and -20 °C
Exchanger and Electrical heaters on the water type heat Water type heat exchanger and hydraulic
hydraulic module exchanger, water pipes, hydraulic module module frost protection down to an outdoor ● ●
frost protection and expansion tank air temperature of -20 °C
Exchanger and Electrical heater on the water exchanger, Water type heat exchanger and hydraulic
hydraulic module water pipes, hydraulic module and optional module frost protection down to an outdoor ● ●
frost protection expansion tank & buffer tank air temperature of -20 °C
Production of free high-temperature hot-water
Partial heat Unit equipped with one desuperheater on
recovery each refrigerant circuit
simultaneously with chilled water production ● ●
(or hot water for Heat pump)
Unit equipped with additional heat exchanger Production of free hot water, adjustable on
Total heat recovery
in parallel with the condenser coils. demand ● No
● ALL MODELS
Refer to the selection tool to find out which options are not compatible.
15
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Available options
● ALL MODELS
Refer to the selection tool to find out which options are not compatible.
16
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Available options
● ALL MODELS
Refer to the selection tool to find out which options are not compatible.
17
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
AQUACIATPOWER ™ LD 0602R 0650R 0750R 0900R 1100R 1200R 1350R 1400R 1600R
Cooling
Standard unit Nominal capacity kW 165 180 198 217 256 296 328 361 394
CA1
Full load performances* EER kW/kW 3,05 3,24 3,04 3,02 2,81 2,96 2,86 2,94 2,86
SEER 12/7°C Comfort low temp. kWh/kWh 4,49 4,64 4,45 4,47 4,35 4,70 4,67 4,62 5,09
ηs cool 12/7°C % 169 181 178 176 171 185 183 183 201
Seasonal energy efficiency** SEER 23/18°C Comfort medium temp. kWh/kWh 5,27 5,52 5,22 5,26 4,99 5,66 5,55 5,43 5,95
SEPR 12/7°C Process high temp. kWh/kWh 5,27 5,42 5,34 5,19 5,14 5,44 5,47 5,60 6,34
SEPR -2/-8°C Process medium temp. kWh/kWh 3,06 3,11 3,08 3,00 3,04 3,09 3,14 3,09 3,44
Unit + Rated & Seasonal Nominal capacity kW 172 187 206 227 270 311 346 380 416
high performance
CA1
options EER kW/kW 3,20 3,36 3,21 3,16 3,03 3,15 3,09 3,14 3,09
Full load performances*
SEER 12/7°C Comfort low temp. kWh/kWh 4,82 5,02 4,84 4,94 4,79 5,25 5,15 5,09 5,11
ηs cool 12/7°C % 190 198 191 195 189 207 203 201 201
Seasonal energy efficiency** SEER 23/18°C Comfort medium temp. kWh/kWh 5,98 6,23 5,93 5,99 5,69 6,35 6,17 6,13 6,07
SEPR 12/7°C Process high temp. kWh/kWh 6,30 6,61 6,42 6,13 5,97 6,30 6,24 6,36 6,30
SEPR -2/-8°C Process medium temp. kWh/kWh 3,48 3,60 3,54 3,41 3,41 3,51 3,56 3,50 3,57
Part Load integrated values IPLV.SI kW/kW 5,06 5,16 5,04 5,16 5,08 5,25 5,23 5,21 5,52
Sound levels
Unit + High temperature option/Nominal high performance
Sound power(1) dB(A) 91,0 91,5 91,5 92,0 92,0 93,0 93,0 93,5 93,5
Sound pressure at 10 m(2) dB(A) 58,5 59,5 59,5 60,0 60,0 60,5 60,5 61,0 61,5
Standard unit
Sound power(1) dB(A) 88,5 89,0 89,0 89,5 89,5 90,5 90,5 91,0 91,0
Sound pressure at 10 m(2) dB(A) 56,5 57,0 57,0 57,5 57,5 58,5 58,5 59,0 58,5
Unit + Very Low Noise option
Sound power(1) dB(A) 85,5 85,5 85,5 86,5 86,5 87,5 87,5 88,0 88,0
Sound pressure at 10 m(2) dB(A) 53,0 53,5 53,5 54,5 54,5 55,5 55,5 55,5 56,0
Unit + Ultra Low Noise option
Sound power(1) dB(A) 83,5 83,5 83,5 84,5 84,5 85,5 85,5 86,0 86,0
Sound pressure at 10 m(2) dB(A) 51,5 51,5 51,5 52,5 52,5 53,5 53,5 53,5 53,5
18
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
AQUACIATPOWER ™ LD 0602R 0650R 0750R 0900R 1100R 1200R 1350R 1400R 1600R
Dimensions
Standard unit
Length mm 2410 2410 2410 2410 2410 3604 3604 3604 3604
Width mm 2253 2253 2253 2253 2253 2253 2253 2253 2253
Height mm 2324 2324 2324 2324 2324 2324 2324 2324 2324
Unit + water buffer tank module option
Length mm 3604 3604 3604 3604 3604 4798 4798 4798 4798
Operating weight (3)
Standard unit kg 1349 1397 1397 1521 1556 1995 2049 2211 2269
Unit + Ultra Low Noise option kg 1453 1501 1501 1656 1690 2153 2208 2394 2452
Unit + Ultra Low Noise + HP dual-pump hydraulic module
kg 1588 1636 1636 1791 1837 2302 2403 2589 2646
option
Unit + Ultra Low Noise + HP dual-pump hydraulic module
kg 2571 2619 2619 2774 2819 3288 3389 3575 3632
+ Water buffer tank module option
Compressors Hermetic Scroll 48.3 r/s
Circuit A 1 1 1 2 2 2 2 3 3
Circuit B 2 2 2 2 2 3 3 3 3
Number of power stages 3 3 3 4 4 5 5 6 6
Unit PED category III III III III III III III III III
Refrigerant(3) R-32 / A2L/ GWP= 675 in accordance with ARI4
kg 6,1 9,3 9,3 10,9 11,3 11,9 12,7 17,3 18,0
Circuit A
tCO2e 4,1 6,3 6,3 7,4 7,6 8,0 8,6 11,7 12,2
kg 10,9 10,9 10,9 10,9 11,3 16,7 17,5 17,3 18,0
Circuit B
tCO2e 7,4 7,4 7,4 7,4 7,6 11,3 11,8 11,7 12,2
Oil
Circuit A l 6,6 6,6 6,6 13,2 13,2 13,2 13,2 19,8 19,8
Circuit B l 13,2 13,2 13,2 13,2 13,2 19,8 19,8 19,8 19,8
Capacity control Connect'Touch
Minimum capacity % 33 33 25 25 25 20 20 17 17
Condenser All-aluminium micro-channel coils (MCHE)
Fans Axial with rotating impeller
Standard unit
Quantity 3 4 4 4 4 5 5 6 6
Maximum total air flow l/s 11790 15720 15720 15720 15720 19650 19650 23580 23580
Maximum rotation speed r/s 12 12 12 12 12 12 12 12 12
Evaporator Dual-circuit plate heat exchanger
Water volume l 15 15 15 19 27 27 35 44 44
Max. water-side operating pressure without hydraulic
kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000
module
Pump, Victaulic screen filter, relief valve, water and air vent valve,
Hydraulic module (option)
pressure sensors
Centrifugal pump, monocell, 48.3 r/s, low- or high-pressure (as
Pump
required), single or dual (as required)
Expansion tank volume (Option) l 50 50 50 50 50 80 80 80 80
Buffer tank volume (optional) l 550 550 550 550 550 550 550 550 550
Max. water-side operating pressure with hydraulic module kPa 400 400 400 400 400 400 400 400 400
Water connections with or without hydraulic module Victaulic ® type
Connections inches 3 3 3 3 3 4 4 4 4
External diameter mm 88,9 88,9 88,9 88,9 88,9 114,3 114,3 114,3 114,3
Casing paint colour Colour code RAL 7035 & 7024
(1) In dB ref=10-12 W, (A) weighting. Declared dual-number noise emission value in accordance with ISO 4871 with an uncertainty of +/-3 dB(A). Measured in
accordance with ISO 9614-1 and certified by Eurovent.
(2) In dB ref 20 µPa, (A) weighting. Declared dual-number noise emission value in accordance with ISO 4871 with an uncertainty of +/-3 dB(A). For information,
calculated from the sound power Lw(A).
(3) Values are guidelines only. Refer to the unit name plate.
19
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
AQUACIATPOWER ™ LD 1750R1800R2000R2200R2400R2650R2800R2950R3200R3500R
Cooling
Standard unit Nominal capacity kW 428 458 523 586 645 688 743 765 836 890
Full load CA1
performances* EER kW/kW 2,93 2,85 2,85 2,94 2,93 2,83 2,85 2,81 2,77 2,66
SEER 12/7°C Comfort low temp. kWh/kWh 5,37 5,30 5,21 5,24 5,35 5,20 5,43 5,38 5,22 5,07
ηs cool 12/7°C % 212 209 205 207 211 205 214 212 206 200
Seasonal energy
SEER 23/18°C Comfort medium temp. kWh/kWh 6,25 6,12 6,25 6,41 6,59 6,33 6,69 6,60 6,34 6,06
efficiency**
SEPR 12/7°C Process high temp. kWh/kWh 6,38 6,29 6,24 6,26 6,32 6,11 6,17 6,10 6,03 5,79
SEPR -2/-8°C Process medium temp. kWh/kWh 3,43 3,44 3,43 - 3,82 3,83 3,80 3,80 3,73 3,73
Unit + Rated & Nominal capacity kW 451 484 553 616 677 726 782 807 882 944
Seasonal high
performance options CA1
Full load
performances* EER kW/kW 3,14 3,09 3,08 3,15 3,14 3,06 3,07 3,04 3,00 2,92
SEER 12/7°C Comfort low temp. kWh/kWh 5,28 5,24 5,29 5,32 5,32 5,20 5,33 5,30 5,31 5,18
ηs cool 12/7°C % 208 207 209 210 210 205 210 209 209 204
Seasonal energy
SEER 23/18°C Comfort medium temp. kWh/kWh 6,33 6,23 6,32 6,56 6,51 6,28 6,54 6,47 6,56 6,32
efficiency**
SEPR 12/7°C Process high temp. kWh/kWh 6,41 6,32 6,27 6,27 6,33 6,14 6,25 6,18 6,07 5,86
SEPR -2/-8°C Process medium temp. kWh/kWh 3,55 3,55 3,55 - 3,82 3,83 3,79 3,80 3,74 3,74
Sound levels
Unit + High temperature option/Nominal high performance
Sound power(1) dB(A) 94,0 94,0 94,5 97,5 97,5 98,0 98,0 98,5 98,5 99,0
Sound pressure at 10 m(2) dB(A) 61,5 61,5 62,0 65,0 65,0 66,0 65,0 66,0 66,0 66,5
Standard unit
Sound power(1) dB(A) 91,5 91,5 92,0 96,5 96,5 97,0 97,0 97,5 97,5 98,0
Sound pressure at 10 m(2) dB(A) 59,5 59,0 60,0 64,0 64,0 64,5 65,0 65,0 65,0 65,5
Unit + Very Low Noise option
Sound power(1) dB(A) 88,5 88,5 89,0 92,5 92,5 93,0 93,0 93,5 93,5 94,5
Sound pressure at 10 m(2) dB(A) 56,0 56,5 57,0 60,5 60,0 60,5 60,0 61,0 60,5 61,5
Unit + Ultra Low Noise option
Sound power(1) dB(A) 86,5 86,5 87,0 90,0 90,0 90,5 90,5 90,5 90,5 91,0
Sound pressure at 10 m(2) dB(A) 54,5 54,0 55,0 57,5 57,5 58,0 58,0 57,5 58,0 58,5
20
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
AQUACIATPOWER ™ LD 1750R 1800R 2000R 2200R 2400R 2650R 2800R 2950R 3200R 3500R
Dimensions
Standard unit
Length mm 4798 4798 4798 5992 5992 5992 7186 7186 7186 7186
Width mm 2253 2253 2253 2253 2253 2253 2253 2253 2253 2253
Height mm 2324 2324 2324 2324 2324 2324 2324 2324 2324 2324
Unit + water buffer tank module option
Length mm 5992 5992 5992 7186 7186 7186 8380 8380 8380 8380
Operating weight (3)
Standard unit kg 2697 2722 2927 3265 3511 3511 4042 4042 4291 4291
Unit + Ultra Low Noise option kg 2904 2930 3158 3434 3703 3703 4260 4260 4535 4535
Unit + Ultra Low Noise + HP dual-pump hydraulic
kg 3138 3164 3430 3743 4013 4013 4650 4650 4925 4925
module option
Unit + Ultra Low Noise + HP dual-pump hydraulic
kg 4131 4156 4421 4750 5020 5020 5671 5671 5946 5946
module + Water buffer tank module option
Compressors Hermetic Scroll 48.3 r/s
Circuit A 3 3 4 2 3 3 3 3 4 4
Circuit B 4 4 4 3 3 3 4 4 4 4
Number of power stages 7 7 8 5 6 6 7 7 8 8
Unit PED category IV IV IV III III III IV IV IV IV
Refrigerant(3) R-32 / A2L/ GWP= 675 in accordance with ARI4
kg 18,3 18,6 22,8 21,8 23,2 23,2 24,9 24,9 29,5 29,5
Circuit A
tCO2e 12,4 12,6 15,4 14,7 15,7 15,7 16,8 16,8 19,9 19,9
kg 21,9 22,3 22,8 23,2 23,2 23,2 29,5 29,5 29,5 29,5
Circuit B
tCO2e 14,8 15,1 15,4 15,7 15,7 15,7 19,9 19,9 19,9 19,9
Oil
Circuit A l 19,8 19,8 26,4 13,2 19,8 19,8 19,8 19,8 26,4 26,4
Circuit B l 26,4 26,4 26,4 19,8 19,8 19,8 26,4 26,4 26,4 26,4
Capacity control Connect'Touch
Minimum capacity % 14 14 13 20 17 17 14 14 13 13
Condenser All-aluminium micro-channel coils (MCHE)
Fans Axial with rotating impeller
Standard unit
Quantity 7 7 8 9 10 10 11 11 12 12
Maximum total air flow l/s 27510 27510 31440 35370 39300 39300 43230 43230 47160 47160
Maximum rotation speed r/s 12 12 12 12 12 12 12 12 12 12
Evaporator Dual-circuit plate heat exchanger
Water volume l 44 47 53 73 73 73 84 84 84 84
Max. water-side operating pressure without hydraulic
kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
module
Pump, Victaulic screen filter, relief valve, water and air vent valve, pressure
Hydraulic module (option)
sensors
Centrifugal pump, monocell, 48.3 r/s, low- or high-pressure (as required),
Pump
single or dual (as required)
Expansion tank volume (Option) l 80 80 80 80 80 80 80 80 80 80
Buffer tank volume (optional) l 550 550 550 550 550 550 550 550 550 550
Max. water-side operating pressure with hydraulic
kPa 400 400 400 400 400 400 400 400 400 400
module
Water connections with or without hydraulic module Victaulic® type
Connections inches 4 4 4 5 5 5 5 5 5 5
External diameter mm 114,3 114,3 114,3 139,7 139,7 139,7 139,7 139,7 139,7 139,7
Casing paint colour Colour code RAL 7035 & 7024
(1) In dB ref=10-12 W, (A) weighting. Declared dual-number noise emission value in accordance with ISO 4871 with an uncertainty of +/-3 dB(A). Measured in
accordance with ISO 9614-1 and certified by Eurovent.
(2) In dB ref 20 µPa, (A) weighting. Declared dual-number noise emission value in accordance with ISO 4871 with an uncertainty of +/-3 dB(A). For information,
calculated from the sound power Lw(A).
(3) Values are guidelines only. Refer to the unit name plate.
21
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Heating
Nominal capacity kW 178 197 237 256 275 317
HA1
Standard unit COP kW/kW 3,88 3,80 3,84 3,84 3,82 3,82
Full load performances* Nominal capacity kW 173 192 231 250 269 310
HA2
COP kW/kW 3,16 3,09 3,14 3,12 3,11 3,10
SCOP30/35°C kWh/kWh 3,44 3,45 3,39 3,47 3,48 3,57
Seasonal energy
HA1 ηs heat 30/35°C % 135 135 133 136 136 140
efficiency**
Prated kW 139 155 186 200 217 250
Unit + Rated & Seasonal high Nominal capacity kW 178 197 237 256 275 317
performance options HA1
Full load performances* COP kW/kW 3,88 3,80 3,84 3,84 3,82 3,82
SCOP30/35°C kWh/kWh 3,67 3,66 3,74 3,77 3,80 3,87
Seasonal energy
HA1 ηs heat 30/35°C % 144 143 147 148 149 152
efficiency**
Prated kW 138 155 185 200 216 250
Cooling
Standard unit Nominal capacity kW 155 171 204 223 239 285
CA1
Full load performances* EER 2,73 2,55 2,73 2,63 2,56 2,66
Seasonal energy SEER 12/7°C Comfort low temp. kWh/kWh 4,17 4,01 4,18 4,08 4,04 4,48
efficiency** SEPR 12/7°C Process high temp. kWh/kWh 4,68 4,51 4,64 4,52 4,50 4,83
Unit + Rated & Seasonal high Nominal capacity kW 164 181 215 236 254 302
performance options CA1
Full load performances* EER kW/kW 2,87 2,72 2,86 2,80 2,76 2,85
Seasonal energy SEER 12/7°C Comfort low temp. kWh/kWh 4,41 4,23 4,48 4,41 4,34 4,78
efficiency** SEPR 12/7°C Process high temp. kWh/kWh 5,47 5,23 5,41 5,23 5,15 5,49
Sound levels
Unit + High temperature option/Nominal high performance
Sound power(1) dB(A) 90,5 91,0 91,5 92,0 92,0 93,0
Sound pressure at 10 m(2) dB(A) 58,5 59,0 59,5 60,0 60,0 61,0
Standard unit
Sound power(1) dB(A) 88,0 88,5 89,0 89,5 89,5 90,5
Sound pressure at 10 m(2) dB(A) 55,5 56,0 56,5 57,0 57,0 58,0
Unit + Very Low Noise option(3)
Sound power(1) dB(A) 85,0 86,0 86,5 87,0 87,0 88,0
Sound pressure at 10 m(2) dB(A) 53,0 53,5 54,0 54,5 54,5 55,5
Unit + Ultra Low Noise option(3)
Sound power(1) dB(A) 83,0 84,0 84,5 85,0 85,0 86,0
Sound pressure at 10 m(2) dB(A) 51,0 52,0 52,5 53,0 53,0 54,0
22
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Dimensions
Standard unit
Length mm 2410 2410 2410 2410 2410 3604
Width mm 2253 2253 2253 2253 2253 2253
Height mm 2324 2324 2324 2324 2324 2324
Unit + water buffer tank module option(3) mm 3604 3604 3604 3604 3604 4798
Length mm 3604 3604 3604 3604 3604 4798
Operating weight (3)
(3) Values are guidelines only. Refer to the unit name plate.
23
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Heating
Nominal capacity kW 336 387 406 441 467 537
HA1
Standard unit COP kW/kW 3,81 3,82 3,81 3,80 3,73 3,80
Full load performances* Nominal capacity kW 329 378 397 431 458 526
HA2
COP kW/kW 3,09 3,10 3,09 3,10 3,03 3,09
SCOP30/35°C kWh/kWh 3,58 3,55 3,57 3,54 3,53 3,57
Seasonal energy
HA1 ηs heat 30/35°C % 140 139 140 139 138 140
efficiency**
Prated kW 266 305 321 349 371 425
Unit + Rated & Seasonal high Nominal capacity kW 336 387 406 441 467 537
performance options HA1
Full load performances* COP kW/kW 3,81 3,82 3,81 3,80 3,73 3,80
SCOP30/35°C kWh/kWh 3,86 3,90 3,91 3,92 3,89 3,96
Seasonal energy
HA1 ηs heat 30/35°C % 151 153 153 154 153 155
efficiency**
Prated kW 265 305 320 348 370 424
Cooling
Standard unit Nominal capacity kW 305 341 358 389 414 470
CA1
Full load performances* EER 2,59 2,64 2,57 2,64 2,55 2,55
Seasonal energy SEER 12/7°C Comfort low temp. kWh/kWh 4,50 4,46 4,33 4,44 4,38 4,32
efficiency** SEPR 12/7°C Process high temp. kWh/kWh 4,76 4,93 4,79 4,94 4,82 4,83
Unit + Rated & Seasonal high Nominal capacity kW 324 362 381 413 439 500
performance options CA1
Full load performances* EER kW/kW 2,80 2,82 2,76 2,81 2,74 2,73
Seasonal energy SEER 12/7°C Comfort low temp. kWh/kWh 4,81 4,88 4,87 4,81 4,75 4,81
efficiency** SEPR 12/7°C Process high temp. kWh/kWh 5,34 5,60 5,40 5,60 5,43 5,47
Sound levels
Unit + High temperature option/Nominal high performance
Sound power(1) dB(A) 93,5 94,0 94,0 94,5 94,5 95,0
Sound pressure at 10 m(2) dB(A) 61,5 62,0 62,0 62,0 62,0 62,5
Standard unit
Sound power(1) dB(A) 91,0 91,5 91,5 92,0 92,5 93,0
Sound pressure at 10 m(2) dB(A) 58,5 59,5 59,5 60,0 60,0 60,5
Unit + Very Low Noise option(3)
Sound power(1) dB(A) 88,0 89,0 89,0 89,5 90,0 90,0
Sound pressure at 10 m(2) dB(A) 55,5 56,5 56,5 57,0 57,5 57,5
Unit + Ultra Low Noise option(3)
Sound power(1) dB(A) 86,0 86,5 87,0 87,5 87,5 88,0
Sound pressure at 10 m(2) dB(A) 54,0 54,5 55,0 55,5 55,5 56,0
24
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Dimensions
Standard unit
Length mm 3604 3604 3604 4798 4798 4798
Width mm 2253 2253 2253 2253 2253 2253
Height mm 2324 2324 2324 2324 2324 2324
Unit + water buffer tank module option(3) mm 4798 4798 4798 5992 5992 5992
Length mm 4798 4798 4798 5992 5992 5992
Operating weight (3)
(3) Values are guidelines only. Refer to the unit name plate.
25
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Caractéristiques électriques
■ Basic unit (excluding pump)
AQUACIATPOWER ™ LD 0602R 0650R 0750R 0900R 1100R 1200R 1350R 1400R 1600R 1750R
Standard unit A 300 347 364 341 411 436 461 485 510 535
Unit + Electronic soft starter option A 257 295 312 298 359 384 409 433 458 483
AQUACIATPOWER ™ LD 1800R 2000R 2200R 2400R 2650R 2800R 2950R 3200R 3500R
Standard unit A 560 609 763 815 848 893 906 971 1017
Unit + Electronic soft starter option A 508 557 680 732 765 811 824 889 934
AQUACIATPOWER ™ ILD 0602R 0700R 0800R 0900R 1000R 1150R 1250R 1400R 1500R 1600R 1750R 2000R
(1) Values at the unit's permanent maximum operating condition (as shown on the unit's nameplate).
(2) Values at the unit's maximum operating condition (as shown on the unit's nameplate).
(3) Maximum operating current of the smallest compressor(s) + fan current + locked rotor current of the largest compressor.
26
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Caractéristiques électriques
■ Short circuit current withstand capability (TN system(1))
AQUACIATPOWER ™ LD 0602R 0650R 0750R 0900R 1100R 1200R 1350R 1400R 1600R
AQUACIATPOWER ™ LD 1750R 1800R 2000R 2200R 2400R 2650R 2800R 2950R 3200R 3500R
(1) If another current limitation protection device is used, its time-current and thermal constraint (I²t) trip characteristics must be at least equivalent to those of the
recommended protection.
Note: The short-circuit withstand current capability values above have been established for the TN system.
27
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
80°C
Partial recovery with desuperheater
The AQUACIATPOWER ™ range may be equipped as an option with an energy recovery function using a desuperheater.
Heat from gases released by the compressors is recovered directly by a type of heat exchanger called a desuperheater located
on the unit to produce free, additional hot water.
This optional configuration requires assembly in our factories and is by order only.
Suction C1 C2
HP
Water LP
Oil
Compressor 1
Water
Desuperheater HP Evaporator
LP
Compressor 2
C2
■ Operating limits
LD units
ILD units
28
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
80°C
Partial recovery with desuperheater
Cooling mode operating range Heating mode operating range
60
40
55
Part load, all sizes 35
50
DSH
30
°C
45 Partial load ILD only OFF
60
to
°C
40
45
25
70
°C
r=
°C
outside air temperature (°C)
to
80
te
35
60
ea
80
to
Inlet air temperature (°C)
rh
20
70
t=
pe
er
=
30
at
tle
su
r
te
e
De
ou
rh
ea
pe
rh
15
er
25
su
pe
at
De
su
w
De
T
20
W
10
rL
te
15
ea
rh
5
pe
10
su
g
in
De
st ing ad
0
e
5
cl
lo
cy
tia
g
in
n
te
0 -5
po
e
th
-5
-10
-10 Part load
-15
-15
-20 -20
40 45 50 55 60 65 70 75 80 85 15 20 25 30 35 40 45 50 55 60
Notes
1. Desuperheater water type heat exchanger ∆T = 10K.
2. The water type heat exchanger is protected against frost down to -20 °C (with Water exchanger frost protection option or water type heat exchanger and hydraulic
module frost protection option (if present) or water loop protected by antifreeze solution for outdoor temperatures < 0 °C)
The water loop on the desuperheater water type heat exchanger must be protected by the customer for outdoor temperatures below 0 °C
3. These ranges are guidelines only. Verify the operating range with the electronic catalogue.
Key
Extension of the operating range, LD 602 to 1400 unit: frost protection required (see note 2).
Heating mode: Part load at inlet air temperature between -10 and -15 °C.
Cooling mode: Partial load above 46 °C of inlet air temperature.
Limited desuperheater power.
operating range at part load for ILD only with limited desuperheater power.
Potential load shedding during the defrosting cycle at low outdoor temperatures (see operating range for ILD 602R - 2000R)
Limited desuperheater power. Please refer to the selection in the electronic catalogue.
Desuperheater not operational
29
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
80°C
Partial recovery with desuperheater
■ Technical specifications
AQUACIATPOWER ™ LD 0602R 0650R 0750R 0900R 1100R 1200R 1350R 1400R 1600R 1750R
Standard unit + desuperheater option kg 1409 1457 1457 1581 1616 2055 2109 2271 2329 2757
Unit + Ultra Low Noise + desuperheater option kg 1492 1540 1540 1690 1725 2182 2236 2416 2474 2920
Unit + Ultra Low Noise + HP dual-pump hydraulic
kg 1627 1675 1675 1825 1871 2331 2431 2611 2669 3154
module + desuperheater option
Unit + Ultra Low Noise + HP dual-pump hydraulic
module + Water buffer tank module + kg 2610 2658 2658 2808 2854 3318 3417 3597 3654 4146
desuperheater option
AQUACIATPOWER ™ LD 1800R 2000R 2200R 2400R 2650R 2800R 2950R 3200R 3500R
30
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
80°C
Partial recovery with desuperheater
■ Technical specifications
Standard unit + desuperheater option kg 1651 1657 1873 1900 1906 2500
Unit + Ultra Low Noise + desuperheater option kg 1735 1741 1981 2009 2015 2626
Unit + Ultra Low Noise + HP dual-pump hydraulic module +
kg 1870 1876 2128 2156 2162 2821
desuperheater option
Unit + Ultra Low Noise + HP dual-pump hydraulic module +
kg 2853 2859 3111 3138 3144 3831
Water buffer tank module + desuperheater option
Standard unit + desuperheater option kg 2558 2785 2791 3283 3309 3565
Unit + Ultra Low Noise + desuperheater option kg 2685 2930 2936 3446 3472 3746
Unit + Ultra Low Noise + HP dual-pump hydraulic module +
kg 2880 3164 3170 3681 3744 4018
desuperheater option
Unit + Ultra Low Noise + HP dual-pump hydraulic module +
kg 3889 4173 4179 4680 4743 5017
Water buffer tank module + desuperheater option
(1) Values are guidelines only. Refer to the unit name plate.
31
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
65°C
Total heat recovery
The AQUACIATPOWER ™ range can be equipped with a total heat recovery function as an option
The principle consists of producing free additional hot water at a high temperature of up to 65°C by adding a dual-circuit water-
cooled condenser which allows all the heat released by the machine to be recovered.
This optional configuration requires assembly in our factories and is by order only.
Operating principle
If hot water production is required, the compressor discharge gases are directed towards the heat recovery condenser. The
refrigerant releases its heat to the hot water that leaves the condenser at a temperature of up to 65 °C. In this way, 100% of the
heat rejected by the liquid chiller can be used to produce hot water. When the demand for heat is satisfied, the hot gas is again
directed towards the air condenser where the heat is rejected to the outside air by the fans.
The hot water temperature is controlled by the machine's Connect Touch control unit.
Note: Heat recovery is only possible if the machine produces cold water at the same time.
■ Operating limits
-10 -5 0 5 10 15 20 25
Key
Full load
Full load
Low temperature brine solution option
32
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
65°C
Total heat recovery
■ Technical specifications
AQUACIATPOWER ™ LD 0602R 0650R 0750R 0900R 1100R 1200R 1350R 1400R 1600R 1750R
Standard unit + total recovery kg 1490 1580 1580 1740 1775 2300 2354 4561 2620 3084
Unit + Ultra Low Noise + total recovery option kg 1573 1663 1663 1849 1884 2427 2481 4706 2765 3247
AQUACIATPOWER ™ LD 1800R 2000R 2200R 2400R 2650R 2800R 2950R 3200R 3500R
33
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
34
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
AQUACIATPOWER ™ LD 0602R 0650R 0750R 0900R 1100R 1200R 1350R 1400R 1600R
Cooling
Standard unit Nominal capacity kW 181 198 220 239 288 328 366 401 440
CA1
Full load performances* EER kW/kW 3,28 3,46 3,31 3,25 3,12 3,23 3,16 3,21 3,16
FREE COOLING
Nominal capacity kW 182 243 243 243 243 303 303 364 364
Free cooling EER kW/kW 28,02 27,56 27,56 27,56 27,92 27,92 28,11 27,69 27,86
Total free cooling option CFC1 Pressure drops kPa 94 112 112 112 102 107 101 117 112
Sound power(1) dB(A) 88,0 89,0 89,0 89,0 89,0 90,0 90,0 90,5 91,0
Sound pressure at 10 m(2) dB(A) 69,0 70,5 70,5 70,5 70,5 70,5 70,5 71,0 71,5
Nominal capacity kW 121 121 121 121 121 121 121 152 152
Free cooling EER kW/kW 27,94 27,94 27,94 27,94 28,04 28,15 28,18 23,78 23,76
Partial free cooling option CFC1 Pressure drops kPa 80 80 80 80 77 75 74 81 79
Sound power(1) dB(A) 86,0 86,0 86,0 86,0 86,0 86,0 86,0 87,5 88,0
Sound pressure at 10 m(2) dB(A) 67,5 67,5 67,5 67,5 67,5 66,5 66,5 68,0 68,5
Unit + ultra low noise level
Nominal capacity kW 171 189 208 226 270 309 343 377 413
option
CA1
Full load performances* EER kW/kW 3,06 3,29 3,08 3,03 2,82 2,96 2,85 2,94 2,86
FREE COOLING
Nominal capacity kW 148 197 197 197 197 247 247 296 296
Free cooling EER kW/kW 56,43 56,20 56,20 56,20 56,94 57,36 57,97 56,74 57,27
Total free cooling option CFC1 Pressure drops kPa 65 77 77 77 71 73 70 80 77
Sound power(1) dB(A) 79,5 80,5 80,5 80,5 81,0 82,0 82,0 82,0 82,5
Sound pressure at 10 m(2) dB(A) 60,5 62,0 62,0 62,0 62,5 63,0 63,0 62,5 63,0
Nominal capacity kW 99 99 99 99 99 99 99 123 123
Free cooling EER kW/kW 57,60 57,60 57,60 57,60 58,06 58,51 58,67 48,12 48,32
Partial free cooling option CFC1 Pressure drops kPa 55 55 55 55 54 52 51 56 55
Sound power(1) dB(A) 77,5 77,5 77,5 77,5 78,0 78,0 78,0 79,0 79,5
Sound pressure at 10 m(2) dB(A) 59,0 59,0 59,0 59,0 59,5 59,0 59,0 59,5 60,0
35
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
AQUACIATPOWER ™ LD 0602R 0650R 0750R 0900R 1100R 1200R 1350R 1400R 1600R
(3) Values are guidelines only. Refer to the unit name plate.
36
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
AQUACIATPOWER ™ LD 1750R 1800R 2000R 2200R 2400R 2650R 2800R 2950R 3200R 3500R
Cooling
Standard unit Nominal capacity kW 475 512 585 652 718 767 827 852 932 994
CA1
Full load performances* EER kW/kW 3,22 3,16 3,15 3,23 3,22 3,12 3,14 3,10 3,06 2,96
FREE COOLING
Nominal capacity kW 425 425 485 546 607 607 667 667 728 728
Free cooling EER kW/kW 28,26 28,31 28,13 28,17 27,93 27,93 27,80 27,80 27,54 27,54
Total free cooling option CFC1 Pressure drops kPa 103 102 110 111 120 120 126 126 136 136
Sound power(1) dB(A) 91,0 91,0 91,5 92,5 93,0 93,0 93,0 93,0 93,5 94,0
Sound pressure at 10 m(2) dB(A) 71,0 71,0 71,5 72,0 72,5 72,5 72,0 72,0 72,5 73,0
Nominal capacity kW 182 182 243 212 273 273 303 303 364 364
Free cooling EER kW/kW 28,67 28,68 28,81 25,28 25,96 25,96 28,89 28,89 28,80 28,80
Partial free cooling
CFC1 Pressure drops kPa 75 75 79 77 82 82 80 80 86 86
option
Sound power(1) dB(A) 87,5 87,5 88,5 89,0 90,0 90,0 89,5 89,5 90,5 91,0
Sound pressure at 10 m(2) dB(A) 67,5 67,5 68,5 68,5 69,5 69,5 68,5 68,5 69,5 70,0
Unit + ultra low noise
Nominal capacity kW 447 481 549 613 677 719 777 798 873 925
level option
CA1
Full load performances* EER kW/kW 2,94 2,85 2,85 2,94 2,94 2,82 2,84 2,79 2,76 2,63
FREE COOLING
Nominal capacity kW 346 346 395 444 494 494 543 543 592 592
Free cooling EER kW/kW 58,50 58,65 58,15 58,28 57,57 57,57 57,20 57,20 56,43 56,43
Total free cooling option CFC1 Pressure drops kPa 71 70 75 76 82 82 86 86 93 93
Sound power(1) dB(A) 82,5 83,0 83,5 85,0 85,0 85,0 85,5 84,5 85,5 86,0
Sound pressure at 10 m(2) dB(A) 62,5 63,0 63,5 64,0 64,5 64,5 64,5 63,5 64,5 65,0
Nominal capacity kW 148 148 197 173 222 222 247 247 296 296
Free cooling EER kW/kW 58,71 58,76 59,31 52,08 53,94 53,94 60,06 60,06 60,16 60,16
Partial free cooling
CFC1 Pressure drops kPa 52 52 55 53 56 56 56 56 59 59
option
Sound power(1) dB(A) 79,0 79,5 80,5 81,0 82,0 82,0 82,0 81,0 82,5 83,0
Sound pressure at 10 m(2) dB(A) 59,0 59,5 60,5 60,5 61,5 61,5 61,0 60,0 61,5 62,0
37
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
AQUACIATPOWER ™ LD 1750R 1800R 2000R 2200R 2400R 2650R 2800R 2950R 3200R 3500R
(3) Values are guidelines only. Refer to the unit name plate.
(1) For an application requiring start-up at less than 8 °C, contact the manufacturer to select a unit using the electronic catalogue.
(2) For applications requiring operation above a water outlet temperature of 20 °C, contact the manufacturer to select a unit using the electronic catalogue.
(3) Part load operation permitted above an outdoor air temperature of 47 °C. Contact the manufacturer to select a unit using the electronic catalogue.
All the free cooling units must be protected against freezing with 30% ethylene glycol in the cooling loop circuit (recommended
value).
38
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
39
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
combination, the result of many hours of study of the thermal Sound level reduction
and acoustic properties in our Research and Innovation
Centre, to ensure a linear flow of air without turbulence, to
0 2 4 6 8 10 12 14 16 18 20 22 24
limit noise to an acceptable acoustic spectrum.
- Even with the basic version, the fans rotate at low speed to
guarantee maximum comfort
- The Connect Touch controller automatically adjusts the fan ■ Acoustic signature
air flow rate according to the outdoor air temperature and As important as the sound power level, the acoustic signature
the unit's load rate which enables the sound level to be reflects the noise disturbance generated by the unit.
significantly reduced, particularly at night, mid-season, dB
morning and evening, which totals more than 75% of the Acoustic discomfort
time the unit is used
dB
Without Variable-speed
-3 to -4 dB(A)
Thanks to the With Variable-speed
compressor enclosure
With all these benefits and its three acoustic finish levels, the AQUACIATPOWER ™ range can be integrated into any site, ensuring
any constraints in terms of the sound environment can be met, while guaranteeing optimal comfort for both users and their
neighbours, allowing customers in the hotel industry to enjoy their rest, and promoting rest and recovery for users in the hospital
sector.
40
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
0602R dB 51,0 45,0 49,0 54,0 53,0 49,0 41,0 38,0 dB(A) 56,5
0650R dB 53,0 48,5 51,0 54,5 52,5 50,5 41,0 38,5 dB(A) 57,0
0750R dB 53,0 48,5 51,0 54,5 52,5 50,5 41,0 38,5 dB(A) 57,0
0900R dB 51,5 45,5 50,0 54,5 53,5 50,0 42,0 38,5 dB(A) 57,5
1100R dB 52,5 49,0 52,0 55,0 53,0 51,0 41,5 39,0 dB(A) 57,5
1200R dB 53,5 49,5 53,0 56,0 54,0 52,0 42,5 40,0 dB(A) 58,5
1350R dB 53,5 49,5 53,0 56,0 54,0 52,0 42,5 40,0 dB(A) 58,5
1400R dB 53,5 47,5 52,0 56,5 55,5 51,5 43,5 40,5 dB(A) 59,0
1600R dB 54,0 50,0 53,0 56,0 54,5 52,5 42,5 40,5 dB(A) 58,5
1750R dB 53,5 47,5 52,0 56,5 55,5 52,0 44,0 40,5 dB(A) 59,5
1800R dB 54,0 50,0 53,5 56,0 54,5 52,5 43,0 40,5 dB(A) 59,0
2000R dB 54,5 51,0 54,0 57,0 55,0 53,0 43,5 41,0 dB(A) 60,0
2200R dB 64,5 67,0 65,5 58,0 54,5 59,5 51,0 45,0 dB(A) 64,0
2400R dB 58,0 53,0 56,0 60,0 56,5 60,5 49,5 47,0 dB(A) 64,0
2650R dB 65,0 67,5 66,0 58,0 54,5 60,0 51,0 45,0 dB(A) 64,5
2800R dB 58,5 54,0 57,0 61,0 57,0 61,0 50,0 47,5 dB(A) 65,0
2950R dB 65,5 68,0 66,5 58,5 55,0 60,5 52,0 46,0 dB(A) 65,0
3200R dB 58,5 54,0 57,0 61,0 57,0 61,0 50,0 47,5 dB(A) 65,0
3500R dB 59,0 54,5 57,5 61,5 57,5 61,5 50,5 48,0 dB(A) 65,5
(1) In dB ref=2x10-5 Pa, as a guideline.
(2) In dB ref=2x10-5 Pa, (A) weighting with an uncertainty of +/-3 dB.
41
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
42
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
0602R dB 53,0 45,5 47,5 52,5 48,5 44,0 37,5 33,5 dB(A) 53,0
0650R dB 54,0 48,0 49,0 52,5 48,5 45,0 37,0 34,0 dB(A) 53,5
0750R dB 54,0 48,0 49,0 52,5 48,5 45,0 37,0 34,0 dB(A) 53,5
0900R dB 54,5 47,0 48,5 54,0 50,0 45,0 38,5 35,0 dB(A) 54,5
1100R dB 55,5 49,5 50,5 54,0 49,5 46,5 38,5 35,5 dB(A) 54,5
1200R dB 56,5 50,5 51,5 55,0 50,5 47,5 39,5 36,5 dB(A) 55,5
1350R dB 56,5 50,5 51,5 55,0 50,5 47,5 39,5 36,5 dB(A) 55,5
1400R dB 55,5 48,0 50,0 55,0 51,0 46,5 40,0 36,0 dB(A) 55,5
1600R dB 56,5 50,5 51,5 55,0 51,0 48,0 40,0 36,5 dB(A) 56,0
1750R dB 56,0 48,5 50,0 55,5 51,5 46,5 40,0 36,0 dB(A) 56,0
1800R dB 57,0 51,0 52,0 55,5 51,0 48,0 40,0 37,0 dB(A) 56,5
2000R dB 57,5 51,5 52,5 56,0 51,5 48,5 40,5 37,5 dB(A) 57,0
2200R dB 71,5 65,5 63,0 55,5 50,5 53,5 47,0 41,0 dB(A) 60,5
2400R dB 62,5 55,5 54,0 58,0 53,0 55,0 46,0 43,5 dB(A) 60,0
2650R dB 72,0 65,5 63,0 55,5 50,5 54,0 47,0 41,5 dB(A) 60,5
2800R dB 62,5 55,5 54,0 58,5 53,0 55,0 46,0 43,5 dB(A) 60,0
2950R dB 72,5 66,5 64,0 56,0 51,0 54,5 48,0 42,0 dB(A) 61,0
3200R dB 63,0 56,0 54,5 59,0 53,5 55,5 46,5 44,5 dB(A) 60,5
3500R dB 64,0 57,0 55,5 60,0 54,5 56,5 47,5 45,5 dB(A) 61,5
(1) In dB ref=2x10-5 Pa, as a guideline.
(2) In dB ref=2x10-5 Pa, (A) weighting with an uncertainty of +/-3 dB.
43
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
0602R dB 50,5 44,5 45,5 49,5 48,0 42,0 34,5 31,0 dB(A) 51,5
0650R dB 51,0 47,5 48,0 50,5 47,0 42,5 35,0 31,5 dB(A) 51,5
0750R dB 51,0 47,5 48,0 50,5 47,0 42,5 35,0 31,5 dB(A) 51,5
0900R dB 51,5 46,0 47,0 51,0 49,5 43,5 35,5 32,0 dB(A) 52,5
1100R dB 51,5 48,5 49,5 51,5 48,0 44,0 36,5 33,0 dB(A) 52,5
1200R dB 52,5 49,5 50,5 52,5 49,0 45,0 37,5 34,0 dB(A) 53,5
1350R dB 52,5 49,5 50,5 52,5 49,0 45,0 37,5 34,0 dB(A) 53,5
1400R dB 53,0 47,0 48,0 52,0 50,5 44,5 37,0 33,5 dB(A) 53,5
1600R dB 52,5 50,0 50,5 53,0 49,0 45,0 38,0 34,5 dB(A) 53,5
1750R dB 53,0 47,5 48,0 52,5 51,0 44,5 37,0 33,5 dB(A) 54,5
1800R dB 53,0 50,0 51,0 53,0 49,5 45,5 38,0 34,5 dB(A) 54,0
2000R dB 53,5 50,5 51,5 53,5 50,0 46,0 38,5 35,0 dB(A) 55,0
2200R dB 54,5 51,5 52,0 53,5 52,0 51,0 48,5 43,5 dB(A) 57,5
2400R dB 57,5 52,5 55,0 55,0 52,5 49,5 43,0 41,0 dB(A) 57,5
2650R dB 55,0 52,0 52,5 54,5 52,5 51,5 49,5 44,5 dB(A) 58,0
2800R dB 58,5 53,0 55,5 55,5 53,0 50,0 43,5 41,5 dB(A) 58,0
2950R dB 54,5 51,5 52,0 54,0 52,0 51,0 49,0 44,0 dB(A) 57,5
3200R dB 58,5 53,5 55,5 55,5 53,0 50,0 44,0 41,5 dB(A) 58,0
3500R dB 59,0 54,0 56,0 56,0 53,5 50,5 44,5 42,0 dB(A) 58,5
(1) In dB ref=2x10-5 Pa, as a guideline.
(2) In dB ref=2x10-5 Pa, (A) weighting with an uncertainty of +/-3 dB.
44
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
45
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
46
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
47
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
48
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
AQUACIATPOWER ™ LD 0602R 0650R 0750R 0900R 1100R 1200R 1350R 1400R 1600R
AQUACIATPOWER ™ LD 1750R 1800R 2000R 2200R 2400R 2650R 2800R 2950R 3200R 3500R
(1) Minimum flow rate for maximum permitted water temperature difference conditions (10° C)
(2) Maximum flow rate for a pressure drop of 100 kPa in the plate heat exchanger
(3) Minimum factory flow rate setting according to the type of pump
49
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
AQUACIATPOWER ™ ILD 0602R 0700R 0800R 0900R 1000R 1150R 1250R 1400R 1500R 1600R 1750R 2000R
(1) Minimum flow rate for maximum permitted water temperature difference conditions (10° C)
(2) Maximum flow rate for a pressure drop of 100 kPa in the plate heat exchanger
(3) Minimum factory flow rate setting according to the type of pump
50
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Operating range
AQUACIATPOWER ™ devices have a broad field of application, enabling them to meet a range of heating and cooling requirements
in the most varied of climates.
Multi-climate:
Cooling mode from -20 °C to +44 °C (option +48 °C)
The AQUACIATPOWER ™ series is equipped as standard with all the management devices and algorithms to enable all-season
operation in all climates. The AQUACIATPOWER ™ equipped with optional all-season operation and/or variable-speed fans is able
to operate in conditions ranging from the heat of the Mediterranean basin to the cold of Scandinavia, the humid Atlantic coast to
the dry climate of Central Europe.
Heating mode from -10 °C to +35 °C
The design of the AQUACIATPOWER ™ makes it suitable for the majority of heating and air conditioning applications, regardless
of the climate. Water heated to +45 °C is guaranteed, even for outdoor temperatures of -10 °C.
Multi-application: air conditioning, industrial processes
The AQUACIATPOWER ™ can be used for all traditional air conditioning applications in sectors as varied as collective housing,
hotels, shopping centres and offices.
35 35
30 30
Inlet air temperature (°C)
25 25
Low-temperature Low-temperature
20 brine solution option 20 brine solution option
15 15
10 10
5 5
0 0
Sizes 602-1400
operation option
operation option
Variable-speed
602 -
Variable speed
-5 -5
All-season
All-season
fan option
fan option
1400
-10 -10
Sizes
-15 -15
-20 -20
-25 -25
-10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Key
Full load
All-season operation option or variable-speed fans option for units LD 602 to 1400 (see note 2)
Part load
Extension of the operating range for units with low-temperature brine solution option
51
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Operating range
ILD 602R - 2000R units
52
50
35
part load
46
45
Options: Rated high performance or extended application range
42 30
Basic unit or VLN/ULN acoustic version option
40
35 25
30
25
15
20
15 10
10
5
g
cle rin
5
cy du
0
ng ng
0
sti adi
fro fflo
th ial o
variable speed
All seasons or
-5 -5
operating
nt
e
option
te
fans
po
-10
-10
-15 Partial load
-15
-20
-25
3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
-20
15 20 25 30 35 40 45 50 55 60
Full load operating range for AQUACIATPOWER ™ ILD units with Rated High performance or Extended application range options
Extended operating range in cooling mode: ILD unit with Winter operation option for outdoor air temperatures down to -20 °C.
The water type heat exchanger must be protected against freezing.
Part load or potential load shedding during the frosting cycle depending on the humidity conditions. Refer to the manufacturer's electronic catalogue.
Heating mode: Partial load at inlet air temperature between -10 and -15 °C
Cooling mode: Partial load above 46 °C of inlet air temperature.
Part load operation outside of an inlet air temperature of 42 °C for Basic ILD units or units with the Low noise level option
For operation in pure water at an inlet air temperature below 0 °C, the frost protection option must be provided
52
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Hydraulic specifications
■ Water pressure drop in the evaporator
Data applicable for pure water at 20 °C.
LD 602R - 1400R
B C D FE
Pressure drop, kPa
LD 1600R - 3500R
GHIJ K L
Pressure drop, kPa
53
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Hydraulic specifications
ILD 602R-1400R
B C DE
Pressure drop, kPa
ILD 1500R-2000R
FGH
Pressure drop, kPa
54
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Hydraulic specifications
■ Water pressure drop in the filter
Screen filter (800 µm)
12
10
5,0
Pressure drops (mWC)
1,0
1
2
0,1
10 20 100 150
Qv (m3/h)
1 LD 602R - 650R and ILD 602R - 700R (DN80 filter)
2 LD 750R - 1200R and ILD 800R - 1250R (DN100 filter)
3 LD 1350R - 3500R and ILD 1400R - 2000R (DN125 filter)
55
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Hydraulic specifications
■ Available static system pressure
Data applicable for:
- Pure water at 20 °C
- Refer to the section "Exchanger water flow rate" for the minimum and maximum water flow rate values
- If a brine solution is used, the maximum water flow rate is reduced
Single pumps
1 LD 602R - 900R
2 LD 1100R
3 LD 1200R
4 LD 1350R
5 LD 1400R
6 LD 1600R
B C D EF G
Water flow rate, l/s
7 LD 1750R
8 LD 1800R
9 LD 2000R
56
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Hydraulic specifications
Dual pumps
1 LD 602R - 900R
2 LD 1100R
3 LD 1200R
4 LD 1350R
5 LD 1400R
6 LD 1600R
B C D F EG
Water flow rate, l/s
7 LD 1750R
8 LD 1800R
9 LD 2000R
10 LD 2200R - 2650R
11 LD 2800R - 3500R
57
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Hydraulic specifications
■ Low pressure pumps (fixed speed)
Single pumps
Dual pumps
240
Available static pressure, kPa
200
220
180 200
160 180
160
140
140
120
120
100 100
80 80
60
60
40
40
20
20 5,0 10,0 15,0 20,0 25,0 30,0
0,0 5,0 10,0 15,0 20,0 25,0
Water flow rate, l/s K IJ
B C D E FG H
8 LD 1750R
Water flow rate, l/s 9 LD 1800R
1 LD 602R - 650R 10 LD 2000R
2 LD 750R - 900R
3 LD 1100R
4 LD 1200R
5 LD 1350R
6 LD 1400R
7 LD 1600R
58
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Hydraulic specifications
■ Available static system pressure
Data applicable for:
- Pure water at 20 °C
- Refer to the section "Exchanger water flow rate" for the minimum and maximum water flow rate values
- If a brine solution is used, the maximum water flow rate is reduced
Single pumps
270 330
310
250
Available static pressure, kPa
190 230
210
170
190
150
170
130 150
110 130
110
90
90
70
70
50 50
0,0 5,0 10,0 15,0 20,0 0,0 5,0 10,0 15,0 20,0 25,0 30,0 35,0 40,0
Dual pumps
270
Available static pressure, kPa
230
250
210 230
190 210
190
170
170
150
150
130 130
110 110
90
90
70
70
50
50 0,0 5,0 10,0 15,0 20,0 25,0 30,0 35,0 40,0
0,0 5,0 10,0 15,0 20,0 25,0 FG H IJ
B C DE Water flow rate, l/s
Water flow rate, l/s
5 ILD 1150R
1 ILD 602R - 700R 6 ILD 1250R
2 ILD 800R 7 ILD 1400R
3 ILD 900R 8 ILD 1500R - 1600R
4 ILD 1000R 9 ILD 1750R - 2000R
59
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Hydraulic specifications
■ ILD low-pressure pumps (fixed-speed)
Single pumps
170 200
160
150 180
140
160
130
120 140
110
100 120
90
100
80
70 80
60
50 60
40 40
30
20 20
0,0 5,0 10,0 15,0 20,0 0,0 5,0 10,0 15,0 20,0 25,0 30,0
B C D Water flow rate, l/s E F G
Water flow rate, l/s
4 ILD 1150R
1 ILD 602R - 700R 5 ILD 1250R - 1600R
2 ILD 800R 6 ILD 1750R - 2000R
3 ILD 900R - 1000R
Dual pumps
240
Available static pressure, kPa
200
220
180 200
160 180
160
140
140
120
120
100 100
80 80
60
60
40
40
20
20 0,0 5,0 10,0 15,0 20,0 25,0 30,0
0,0 5,0 10,0 15,0 20,0
Water flow rate, l/sF HG I
B C DE
Water flow rate, l/s 5 ILD 1150R
6 ILD 1250R - 1600R
1 ILD 602R 7 ILD 1750R
2 ILD 700R 8 ILD 2000R
3 ILD 800R
4 ILD 900R - 1000R
60
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Dimensions
■ AQUACIATPOWER ™ LD 602R to 1100R/ILD 602R to 1000R Without buffer tank
Key Notes:
All dimensions in mm
Non-contractual drawings.
B Clearance required for maintenance and air flow
C Clearance recommended for coil removal When designing a system, refer to the certified dimensional
drawings provided with the unit or available on request.
Water inlet
Please refer to the certified dimensional drawings for the
Water outlet
positioning of the fixing points, weight distribution points
Air outlet, do not obstruct
and centre of gravity coordinates.
Electrical cabinet
61
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Dimensions
■ AQUACIATPOWER ™ LD 602R to 1100R/ILD 602R to 1000R With buffer tank
Key Notes:
All dimensions in mm
Non-contractual drawings.
B Clearance required for maintenance and air flow
C Clearance recommended for coil removal When designing a system, refer to the certified dimensional
drawings provided with the unit or available on request.
Water inlet
Please refer to the certified dimensional drawings for the
Water outlet
positioning of the fixing points, weight distribution points
Air outlet, do not obstruct
and centre of gravity coordinates.
Electrical cabinet
62
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Dimensions
■ AQUACIATPOWER ™ LD 1200R to 1600R/ILD 1150R to 1500R Without buffer tank
Key Notes:
All dimensions in mm
Non-contractual drawings.
B Clearance required for maintenance and air flow
C Clearance recommended for coil removal When designing a system, refer to the certified dimensional
drawings provided with the unit or available on request.
Water inlet
Please refer to the certified dimensional drawings for the
Water outlet
positioning of the fixing points, weight distribution points
Air outlet, do not obstruct
and centre of gravity coordinates.
Electrical cabinet
63
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Dimensions
■ AQUACIATPOWER ™ LD 1200R to 1600R/ILD 1150R to 1500R With buffer tank
Key Notes:
All dimensions in mm
Non-contractual drawings.
B Clearance required for maintenance and air flow
C Clearance recommended for coil removal When designing a system, refer to the certified dimensional
drawings provided with the unit or available on request.
Water inlet
Please refer to the certified dimensional drawings for the
Water outlet
positioning of the fixing points, weight distribution points
Air outlet, do not obstruct
and centre of gravity coordinates.
Electrical cabinet
64
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Dimensions
■ AQUACIATPOWER ™ LD 1750R to 2000R/ILD 1600R to 2000R Without buffer tank
Key Notes:
All dimensions in mm
Non-contractual drawings.
B Clearance required for maintenance and air flow
C Clearance recommended for coil removal When designing a system, refer to the certified dimensional
drawings provided with the unit or available on request.
Water inlet
Please refer to the certified dimensional drawings for the
Water outlet
positioning of the fixing points, weight distribution points
Air outlet, do not obstruct
and centre of gravity coordinates.
Electrical cabinet
65
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Dimensions
■ AQUACIATPOWER ™ LD 1750R to 2000R/ILD 1600R to 2000R With buffer tank
Key Notes:
All dimensions in mm
Non-contractual drawings.
B Clearance required for maintenance and air flow
C Clearance recommended for coil removal When designing a system, refer to the certified dimensional
drawings provided with the unit or available on request.
Water inlet
Please refer to the certified dimensional drawings for the
Water outlet
positioning of the fixing points, weight distribution points
Air outlet, do not obstruct
and centre of gravity coordinates.
Electrical cabinet
66
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Dimensions
■ AQUACIATPOWER ™ LD 2200R to 2650R/Without buffer tank
Key Notes:
All dimensions in mm
Non-contractual drawings.
B Clearance required for maintenance and air flow
C Clearance recommended for coil removal When designing a system, refer to the certified dimensional
drawings provided with the unit or available on request.
Water inlet
Please refer to the certified dimensional drawings for the
Water outlet
positioning of the fixing points, weight distribution points
Air outlet, do not obstruct
and centre of gravity coordinates.
Electrical cabinet
67
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Dimensions
■ AQUACIATPOWER ™ LD 2200R to 2650R/With buffer tank
Key Notes:
All dimensions in mm
Non-contractual drawings.
B Clearance required for maintenance and air flow
C Clearance recommended for coil removal When designing a system, refer to the certified dimensional
drawings provided with the unit or available on request.
Water inlet
Please refer to the certified dimensional drawings for the
Water outlet
positioning of the fixing points, weight distribution points
Air outlet, do not obstruct
and centre of gravity coordinates.
Electrical cabinet
68
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Dimensions
■ AQUACIATPOWER ™ LD 2800R to 3500R/Without buffer tank
Key Notes:
All dimensions in mm
Non-contractual drawings.
B Clearance required for maintenance and air flow
C Clearance recommended for coil removal When designing a system, refer to the certified dimensional
drawings provided with the unit or available on request.
Water inlet
Please refer to the certified dimensional drawings for the
Water outlet
positioning of the fixing points, weight distribution points
Air outlet, do not obstruct
and centre of gravity coordinates.
Electrical cabinet
69
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Dimensions
■ AQUACIATPOWER ™ LD 2800R to 3500R/With buffer tank
Key Notes:
All dimensions in mm
Non-contractual drawings.
B Clearance required for maintenance and air flow
C Clearance recommended for coil removal When designing a system, refer to the certified dimensional
drawings provided with the unit or available on request.
Water inlet
Please refer to the certified dimensional drawings for the
Water outlet
positioning of the fixing points, weight distribution points
Air outlet, do not obstruct
and centre of gravity coordinates.
Electrical cabinet
70
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Installation recommendations
■ Water quality criteria to be respected Electrical connections must be made in accordance with best
Warning: It is essential that an 800-micron water filter be current practices and applicable standards and regulations.
placed on the unit's water inlet during installation. The Electrical cable connections to be made on-site:
quality of the water used has a direct impact on the correct - electrical power supply to the unit
and compliant operation of the machine and its service life. - contacts available as standard enabling the machine to be
This is particularly true if the water used clogs or corrodes controlled remotely (optional)
components or promotes the growth of algae or micro- It should be noted that the unit's electrical system is not protected
organisms. The water must be tested to determine whether against lightning strikes.
it is suitable for the unit. It is also tested to determine Therefore devices to protect against transient voltage surges
whether chemical treatment is necessary and will suffice must be installed on the system and inside the power supply
to make it of acceptable quality. This analysis should unit.
confirm whether or not the various machine components
are compatible with the water they come into contact with ■ Pipe connections
on-site. You must follow the instructions in the manual. All pipes must
WARNING: failure to follow these instructions will result in be correctly aligned and slope towards the system's drain valve.
the immediate voiding of the unit's warranty. Pipes must be installed to allow sufficient access to the panels
for maintenance, and must be fitted with heat insulation.
■ Lifting and handling
Pipe fixings and brackets must be separate to avoid vibrations
The utmost safety precautions must be taken when lifting and and ensure no pressure is placed on the unit. Water flow shut-
handling the unit. off and control valves must be fitted when the unit is installed.
Always follow the lifting diagram on the unit and in the instruction Pipe connections to be made on site:
manual. - Water supply with pressure-reducing valve
Before attempting to lift the unit, make sure the path leading to - Evaporator, condenser and drain
its intended location is free from obstacles. Always keep the unit Accessories essential to any hydraulic circuit must also be
vertical when moving it. Never tip it or lie it on its side. installed, such as:
- Water expansion tank
■ Choosing a location for the unit - Drain nozzles at pipe low points
AQUACIATPOWER ™ units are designed for outdoor installation. - Exchanger shut-off valves equipped with filters
Precautions should be taken to protect the unit from freezing - Air vents at pipe high points
temperatures. Special attention should be paid to ensure - Check the system's water capacity (install a buffer water tank
sufficient free space (including at the top) to allow maintenance. if necessary)
The unit must be placed on a perfectly level, fireproof surface - Flexible couplings on exchanger inlets and outlets
strong enough to support it when ready for operation. Noise Warning:
pollution from auxiliary equipment such as pumps should be - Pressure in the hydraulic circuits below 4 bar for units
studied thoroughly. equipped with the hydraulic module
Potential noise transmission routes should be studied, with - Place the expansion tank before the pump.
assistance from an acoustical engineer if necessary, before - Do not place any valves on the expansion tank.
installing the unit. It is strongly recommended that flexible - Make sure the water circulation pumps are placed
couplings are placed over pipes and anti-vibration mounts are directly at the exchanger inlets.
fitted underneath the unit (equipment available as an option) to - Make sure the pressure of the water drawn in by the
reduce vibrations, and the noise this causes, as much as circulation pumps is greater than or equal to the required
possible. minimum NPSH, particularly if the hydraulic circuits are
open.
■ Fitting accessories supplied separately - Test the water quality in accordance with the relevant
A number of optional accessories may be delivered separately technical specifications.
and installed on the unit on site. - Take the necessary precautions to protect the unit and
You must follow the instructions in the manual. hydraulic system from freezing temperatures (e.g. allow
for the possibility of draining the unit). If glycol is added
■ Electrical connections to prevent freezing, check its type and concentration
before system start-up.
You must follow the instructions in the manual. All information
- Before making any final hydraulic connections, flush the
concerning electrical connections is stated on the wiring
pipes with clean water to remove any debris in the
diagrams provided with the unit. Always follow this information
network.
to the letter.
71
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Installation recommendations
■ System start-up ■ Maintenance operations
System start-up for these machines must be performed by CIAT Specific preventive maintenance operations are required at
or a CIAT-authorised firm. regular intervals and should be performed by CIAT-approved
You must follow the instructions in the manual. contractors.
List of system start-up checks (non-exhaustive): The operating parameters are read and noted on a "CHECK
- Correct positioning of unit LIST" form to be returned to CIAT.
- Power supply protections To do this, you must refer to and comply with the instruction
- Phases and direction of rotation manual.
- Wiring connections on unit You must take out a maintenance contract with a CIAT-approved
- Direction of water flow in unit refrigeration equipment specialist. Such a contract is required
- Cleanliness of hydraulic circuit even during the warranty period.
- Water flow rate at specified value
- Pressure in the refrigerating circuit
- Direction of rotation of compressors
- Water pressure drops and flow rates
- Operating readings
72
AQUACIATPOWER™ LD/ILD
Water chiller & heat pump
Control
USER-FRIENDLY INTERFACE CONSOLE BluEdge® Digital REMOTE MACHINE
- User-friendly 4.3-inch touch screen. SUPERVISION
- Information displayed in a choice of languages. 2 years of services with:
- Temperature and pressure readings. - Monitoring of machine operation (operation overviews and
- Operating and fault status diagnostics. curves, alarm logs).
- Master/slave control of two machines in parallel. - E-mail alerts for alarms (optional SMS alerts).
- Fault memory management. - Remote updates for BluEdge® Digital.
- Pump management.
- Access to a log of machine operation data.
- Time schedule.
- Remote advice on using BluEdge® Digital.
- IP web server
- System start-up and operating readings.
- Programmable maintenance
- Preventive maintenance
- F-Gas maintenance
- E-mail alert
- Indication of energy supplied and consumed instantly (kW)
and integrally (kWh)
PRODUCT FUNCTIONALITY
POTENTIAL-FREE (DRY) CONTACTS AVAILABLE
AS STANDARD
Inputs:
- Automatic operation control
- Heating/cooling mode selection
- Selection of setpoints 1 / 2
Via dry contact
- Power limitation.
Outputs:
- General fault reporting
- Operational status reporting
Additional inputs available as options:
- Setpoint adjustment by 4-20 mA signal
- Power limitation adjustable by 4-20 mA signal
- Second power limitation level
- End of storage signal
Customer CMS - User fault display
COMMUNICATION - Contact for refrigerant leak detector
Additional outputs available as options:
- Indication of the power level by 0-10 V signal
- Minor alert reporting
- Unit shut-down general fault reporting
- Desuperheater pump On/Off control
- On/off control for a boiler
- 4-stage on/off management for additional heaters
73