Combined Footing Excel File

This document provides the design of a combined footing, beam, and slab. The combined footing is designed to support a total load of 3850 kN from two columns spaced 2.725m apart. The footing size is increased from the required 18.82 sqm to a provided size of 19.2 sqm. A beam spanning the footing is then designed to carry a factored load of 725 kNm^2 with bottom and top reinforcement. Finally, the slab over the beam and footing is designed with minimum depth, main reinforcement, and shear check provided.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
228 views4 pages

Combined Footing Excel File

This document provides the design of a combined footing, beam, and slab. The combined footing is designed to support a total load of 3850 kN from two columns spaced 2.725m apart. The footing size is increased from the required 18.82 sqm to a provided size of 19.2 sqm. A beam spanning the footing is then designed to carry a factored load of 725 kNm^2 with bottom and top reinforcement. Finally, the slab over the beam and footing is designed with minimum depth, main reinforcement, and shear check provided.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 4

Combined Footing

1 Footing Size Design

Load 1 Pu1 2000 KN


Load 2 Pu2 1850 KN
Combine load Pcu 3850 KN
Design Load Pc 2823 KN

Moment in x dir Mux 40 KN-m


Moment in y dir Muy 40 KN-m

c/c dist b/w col in x dir 2.725 meters


c/c dist b/w col in y dir 0.000 meters

Col Dim x dir 0.20 meters


y dir 0.20 meters

SBC q 150 KNm2

Footing Size required A req 18.82 sqmm

L 6.00 meters
Footing Size Provided
B 3.20 meters
Area Provided A prvd 19.20 meters

x bar 1.309
y bar 0.000

Zx 10.24
Zx 19.20

Nup 151 KNm2

Increase the Footing Size


2 Beam Design

Total Load W 151 KNm2


Factored Load Wu 725 KNm2

1.691 meters 2.725 meters 1.584 meters

3.20 meters

6.00 meters

725 KNm2

1.69 meters 2.73 meters 1.58 meters

Beam Size width 600 mm


depth 900 mm

Moment Mb 898 KN-m

Design the beam from the BEAM DESIGN SHEET

Bottom Reinforcement
Type Bar dia Nos Area of Steel
Layer 1 25 mm 6 2945 sqmm
Layer 2 25 mm 6 2945 sqmm
Layer 3 -
Total Steel Provided 5890 sqmm
Percentage of Steel 1.148 %

Top Reinforcement
Type Bar dia Nos Area of Steel
Layer 1 25 mm 6 2945 sqmm
Layer 2 20 mm 6 1885 sqmm
Layer 3 -
Total Steel Provided 4830 sqmm
3 Slab Design

Net upward pressure Nup 151 KNm2


l 1.30 meters /=width of footing from col face

Bending Moment Ms 128 KN-m M=Nup*l2/2


Factored Moment Mus 191 KN-m 1.5*Ms

Concrete fck 20 MPa


Steel fy 415 MPa

Minimum Depth Required dmin 264 d=sqrt(Ms/Rumax*1000*b)

Depth Provided D 600 mm


Clear Cover c 50 mm
Effective Cover d' 56 mm
Effective Depth d' 544 mm

Area of Steel across x dir Spacing c/c in mm


12# 16# 20#
1014 sqmm 112 c/c 198 c/c 310 c/c

Ast across x direction 12 mm dia @ 100 mm c/c 1131 sqmm


Dist Ast across y direction 8 mm dia @ 175 mm c/c 287 sqmm

4 Shear Check for Slab

Vu1 171 KN
ζv 0.315 MPa

ζc 0.316 MPa

Shear Check OK
5
6.00 meters

3.20 meters 600 mm

1.7 meters 2.73 meters 1.6 meters

600 mm

6 - 25 mm dia
6 - 20 mm dia 6 - 25 mm dia
6 - 25 mm dia
900 mm

600 mm

250 mm

8 mm dia @ 175 mm c/c 12 mm dia @ 100 mm c/c

6 - 25 mm dia
6 - 20 mm dia

6 - 25 mm dia
6 - 25 mm dia