Submittal Ref.
#: SQJKW002717_1
long-coupled horizontal base-mounted end suction pump
Model: Series 4030 - 6x4x13H - 4p - 60 hp - (Factory Choice Motor)
Project name: MELIA RETROFIT Representative: Oscar Perez
Location: Phone number:
Date submitted: 2/22/2022 2:19 PM e-mail:
[email protected] Engineer: Submitted by: Perez , Oscar
Application design data
Tag number: BAH-1/2 Configuration: Single + Standby
Service: Suction pressure: 0 ft
Location: Fluid: Non-Potable Fluid - Water
Qty: 2 Operating temperature: 60 °F
Total system flow: 1000 USgpm Duty flow per pump: 1000 USgpm
System head: 46 m Viscosity: 31 SSU
Total dissolved solids: 0 ppm Specific gravity: 1.0000
NPSHR: 3.34 m Absorbed Power/BHP: 47.26 hp
%Mtr Safety*: 26.95% Efficiency at Design: 80.62 %
Outlet velocity: 25.2 ft/s Impeller diameter: 12.71 in
PEIcl: Not applicable ERcl: Not applicable
Standby qty: 1 Pump/motor run qty: 1
*Motor safety factor above duty point.
Materials of construction
Construction: Ductile Bronze Fitted Impeller: Bronze
Rating: ANSI-250 Pump shaft: Carbon Steel
Connections: Inlet: 6 in, Outlet: 4 in Shaft sleeve:ea 304 SS
Casing (volute): Ductile Iron Flexible coupling: Sureflex
Bearings: Anti-Friction Grease Lubricated Casing gasket: Confined Non-Asbestos Fiber
Drip pan: No
Mechanical seal data
Seal type: Inside Single Spring Rotating face: Resin Bonded Carbon
Manufacturer code: C-ssc L EPSS 2A Stationary seat: Sintered Silicon Carbide
Springs: Stainless Steel Secondary seal: EPDM
Rotating hardware: Stainless Steel Maximum total dissolved 2000 PPM
solids (TDS)*:
*Note: Please ensure proper seal is selected by inputting Total Dissolved Solids (TDS) in PPM in ADEPT if water quality is
poor at site. Also select Flush Line Filter or Cyclone Separator if there are other contaminants in the fluid.
Electrical data
Supplier: Factory Choice Insulation class: Class F Insulation
Frame size: 364TC Motor type: Induction
Speed: 1790 rpm Size: 60 hp
Enclosure: ODP Efficiency: NEMA Premium 12.12
Power supply: 460/3/60
www.armstrongfluidtechnology.com 2/22/2022 2:19:36 PM, Ref. #SQJKW002717_1 Page 1 of 3
Operating limits (temperature - pressure)
Maximum pressure: 300 psi
Maximum temperature: 250 F
All Pump casings are hydrostatically tested to requirements of ANSI/HI 14.6 standard.
Performance curve
----Admin Data—-
Tag Num: BAH-1/2
Service:
Series 4030 Location:
6x4x13H @ 1790 rpm ----Motor Data----
60 Motor Size: 60 hp
63 68 *PT-631-1-0
13.188 in 72 75 ANSI/HI 14.6
78 ----Design Duty Points---
12.714 in 80 Flow: 1000 USgpm
81 Head: 46 m
50 Impeller: 12.71 in
82
75 hp
81 ----Performance Data---
80 NPSHR: 3.34 m
40 60 hp Eff. @ Design: 80.62 %
Absorbed Power/BHP @
50 hp Design: 47.26 hp
Mtr Capability @ Rated Spd: 60
Head (m)
30 10 in 40 hp hp
Motor safety factor: 26.95%
78 BEP @ Design Imp: 81.3 % @
30 hp 1126.12 USgpm
25 hp %maximp.range: 85.12%
20
Outlet velocity: 25.2 ft/s
20 hp
15 hp
10 System
0 250 500 750 1000 1250 1500 1750
Water, spgr=1.0000 Flow (USgpm)
www.armstrongfluidtechnology.com 2/22/2022 2:19:36 PM, Ref. #SQJKW002717_1 Page 2 of 3
Dimensional data (not for construction)
Side view Top view
Inverter motor type: Inverter duty
Weight: 1288 lb [584.23 kg], Units of measure: inches [millimeters]
• Not to scale
• Tolerance of ± 0.125 inch (± 3 mm) should be used
• For certified dimensions, please contact your Armstrong representative
• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports
Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 6 ANSI-250 12.50 12 10.63 0.75
Outlet 4 ANSI-250 10.00 8 7.88 0.75
*Equally spaced straddling centreline
Special instructions
Reference Motor Specification AES 05007.
Selected options
Testing: No Test Certification Required
Seal Environment Accessories: None
Couplings: Sureflex
Space Heater: No
Motor Thermistor: No Thermistors
Wye-Delta Starting: No
Drip Pan: No
www.armstrongfluidtechnology.com 2/22/2022 2:19:36 PM, Ref. #SQJKW002717_1 Page 3 of 3