VESDA Tech Tip
Manual Back Flush & Water
Trap
Overview
The diagrams below shows the recommended pipe configuration for a manual back flushing and
water trap application.
Inverted VESDA
(for example VLI) Manual Back Flush Port for
compressed air injection.
Pipe Back Flush Valve
1 mtr
Approx.
500 mm
Sampling Pipe
Typical overflow 500 mm
water trap with water
Doc 24000_01
AUTHORISED DISTRIBUTOR OF VESDA
www.flamestop.com.au |
[email protected]Back Flush Compressed Air Connection Arrangements
Xtralis recommends the use of counter-sinking holes in environments with high levels of ambient
particulates to mitigate the blockage of sample holes.
Sampling hole to size (3.5mm min)
Pipe Joiner
Countersink
System
Sampling Pipe
Doc 24000_01
AUTHORISED DISTRIBUTOR OF VESDA
www.flamestop.com.au |
[email protected] Additional Support For further information and support please contact your nearest Xtralis office,
or email your local technical support.
AUTHORISED DISTRIBUTOR OF VESDA
www.flamestop.com.au |
[email protected]The contents of this document are provided on an “as is” basis. No representation or warranty (either express or implied) is made as to the
completeness, accuracy or reliability of the contents of this document. The manufacturer reserves the right to change designs or specifications
without obligation and without further notice. Except as otherwise provided, all warranties, express or implied, including without limitation any implied
warranties of merchantability and fitness for a particular purpose are expressly excluded.
This document includes registered and unregistered trademarks. All trademarks displayed are the trademarks of their respective owners. Your use of
this document does not constitute or create a licence or any other right to use the name and/or trademark and/or label.
This document is subject to copyright owned by Xtralis AG (“Xtralis”). You agree not to copy, communicate to the public, adapt, distribute, transfer,
sell, modify or publish any contents of this document without the express prior written consent of Xtralis.
Doc. 24000_00