UPS Galaxy5500
UPS Galaxy5500
05/2016
www.schneider-electric.com
Legal Information
The Schneider Electric brand and any registered trademarks of Schneider Electric
Industries SAS referred to in this guide are the sole property of Schneider Electric
SA and its subsidiaries. They may not be used for any purpose without the owner's
permission, given in writing. This guide and its content are protected, within the
meaning of the French intellectual property code (Code de la propriété
intellectuelle français, referred to hereafter as "the Code"), under the laws of
copyright covering texts, drawings and models, as well as by trademark law. You
agree not to reproduce, other than for your own personal, noncommercial use as
defined in the Code, all or part of this guide on any medium whatsoever without
Schneider Electric's permission, given in writing. You also agree not to establish
any hypertext links to this guide or its content. Schneider Electric does not grant
any right or license for the personal and noncommercial use of the guide or its
content, except for a non-exclusive license to consult it on an "as is" basis, at your
own risk. All other rights are reserved.
Electrical equipment should be installed, operated, serviced, and maintained only
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
As standards, specifications, and designs change from time to time, please ask for
confirmation of the information given in this publication.
20 - 120 kVA 400 V
Table of Contents
Important Safety Instructions — SAVE THESE
INSTRUCTIONS .........................................................................................7
Safety Precautions .....................................................................................8
Electrical Safety..................................................................................10
Periodical Check................................................................................. 11
Battery Safety..................................................................................... 11
Electromagnetic Compatibility..............................................................12
Specifications ............................................................................................13
Input ........................................................................................................13
Power Supplied as a Function of Input Voltage ......................................13
Output .....................................................................................................13
Permissible UPS Overloads as a Function of Time ................................14
Bypass ....................................................................................................14
Environment .......................................................................................15
Batteries ..................................................................................................16
DC Power Levels for Battery Sizing with Output Power Factor =
0.9 .....................................................................................................16
DC Power Levels for Battery Sizing with Output Power Factor =
0.8 .....................................................................................................16
Maximum Current at End of Discharge .................................................16
Recommended Circuit Breakers and Cable Sizes .......................................17
Selection of Circuit Breakers................................................................17
Recommended Upstream Circuit Breaker .............................................18
Recommended Downstream Circuit Breaker.........................................18
Earth-Leakage Current........................................................................18
Fuses.................................................................................................19
Recommended Cable Sizes ................................................................19
Transformers............................................................................................21
Marine UPS Adaptation Voltage Transformer Specifications...................21
Isolation Transformer Specifications .....................................................21
Battery Circuit Breaker Enclosure ..............................................................23
Mechanical Assembly ..............................................................................25
Layout of Cabinets....................................................................................25
Remove Battery Protection........................................................................26
Remove Battery Protection from the UPS .............................................26
Remove Battery Protection from the External Battery Cabinet ................26
Install the Top Entry Option........................................................................27
Install the IP32 Option...............................................................................29
Floor Mounting ..........................................................................................30
Connect Input and PE Cables in Single Systems ................................31
Single Utility/Mains Systems......................................................................31
Dual Utility/Mains Systems ........................................................................31
Frequency Converter ................................................................................32
Connect Input and PE Cables in Parallel Systems ..............................34
Overview .................................................................................................34
Single Utility/Mains Systems......................................................................34
Dual Utility/Mains Systems ........................................................................35
990–5233D–001 3
20 - 120 kVA 400 V
4 990–5233D–001
20 - 120 kVA 400 V
990–5233D–001 5
Important Safety Instructions — SAVE
THESE INSTRUCTIONS 20 - 120 kVA 400 V
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
Failure to follow these instructions will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in
death or serious injury.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
Failure to follow these instructions can result in injury or equipment
damage.
NOTICE
NOTICE is used to address practices not related to physical injury. The safety
alert symbol shall not be used with this type of safety message.
Failure to follow these instructions can result in equipment damage.
Please Note
Electrical equipment should only be installed, operated, serviced, and maintained
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
990–5233D–001 7
Important Safety Instructions — SAVE
20 - 120 kVA 400 V THESE INSTRUCTIONS
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training
to recognize and avoid the hazards involved.
Safety Precautions
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
All safety instructions in this document must be read, understood and followed.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Read all instructions in the Installation Manual before installing or working on this
UPS system.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not install the UPS system until all construction work has been completed
and the installation room has been cleaned.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• The product must be installed according to the specifications and
requirements as defined by Schneider Electric. It concerns in particular the
external and internal protections (upstream breakers, battery breakers,
cabling, etc.) and environmental requirements. No responsibility is assumed
by Schneider Electric if these requirements are not respected.
• After the UPS system has been electrically wired, do not start up the system.
Start-up must only be performed by Schneider Electric.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS system must be installed according to local and national regulations.
Install the UPS according to:
• IEC 60364 (including 60364–4–41- protection against electric shock, 60364–
4–42 - protection against thermal effect, and 60364–4–43 - protection against
overcurrent), or
• NEC NFPA 70, or
• Canadian Electrical Code (C22.1, Part 1)
depending on which one of the standards apply in your local area.
Failure to follow these instructions will result in death or serious injury.
8 990–5233D–001
Important Safety Instructions — SAVE
THESE INSTRUCTIONS 20 - 120 kVA 400 V
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Install the UPS system in a temperature controlled indoor environment free of
conductive contaminants and humidity.
• Install the UPS system on a non-flammable, level and solid surface (e.g.
concrete) that can support the weight of the system.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS is not designed for and must therefore not be installed in the following
unusual operating environments:
• Damaging fumes
• Explosive mixtures of dust or gases, corrosive gases, or conductive or radiant
heat from other sources
• Moisture, abrasive dust, steam or in an excessively damp environment
• Fungus, insects, vermin
• Salt-laden air or contaminated cooling refrigerant
• Pollution degree higher than 2 according to IEC 60664-1
• Exposure to abnormal vibrations, shocks, and tilting
• Exposure to direct sunlight, heat sources, or strong electromagnetic fields
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not drill or cut holes for cables or conduits with the gland plates installed and
do not drill or cut holes in close proximity to the UPS.
Failure to follow these instructions will result in death or serious injury.
WARNING
HAZARD OF ARC FLASH
Do not make mechanical changes to the product (including removal of cabinet
parts or drilling/cutting of holes) that are not described in the Installation Manual.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
NOTICE
RISK OF OVERHEATING
Respect the space requirements around the UPS system and do not cover the
product’s ventilation openings when the UPS system is in operation.
Failure to follow these instructions can result in equipment damage.
NOTICE
RISK OF EQUIPMENT DAMAGE
Do not connect the UPS output to regenerative load systems including
photovoltaic systems and speed drives.
Failure to follow these instructions can result in equipment damage.
990–5233D–001 9
Important Safety Instructions — SAVE
20 - 120 kVA 400 V THESE INSTRUCTIONS
Electrical Safety
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Electrical equipment must be installed, operated, serviced, and maintained
only by qualified personnel.
• The UPS system must be installed in a room with restricted access (qualified
personnel only).
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices.
• Turn off all power supplying the UPS system before working on or inside the
equipment.
• Before working on the UPS system, check for hazardous voltage between all
terminals including the protective earth.
• The UPS contains an internal energy source. Hazardous voltage can be
present even when disconnected from the utility/mains supply. Before
installing or servicing the UPS system, ensure that the units are OFF and that
utility/mains and batteries are disconnected. Wait five minutes before
opening the UPS to allow the capacitors to discharge.
• A disconnection device (e.g. disconnection circuit breaker or switch) must be
installed to enable isolation of the system from upstream power sources in
accordance with local regulations. This disconnection device must be easily
accessible and visible.
• The UPS must be properly earthed/grounded and due to a high leakage
current, the earthing/grounding conductor must be connected first.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
In systems where backfeed protection is not part of the standard design, an
automatic isolation device (backfeed protection option or other device meeting
the requirements of IEC/EN 62040–1 or UL1778 4th Edition – depending on
which of the two standards apply to your local area) must be installed to prevent
hazardous voltage or energy at the input terminals of the isolation device. The
device must open within 15 seconds after the upstream power supply fails and
must be rated according to the specifications.
Failure to follow these instructions will result in death or serious injury.
When the UPS input is connected through external isolators that, when opened,
isolate the neutral or when the automatic backfeed isolation is provided external to
the equipment or is connected to an IT power distribution system, a label must be
fitted at the UPS input terminals, and on all primary power isolators installed
remote from the UPS area and on external access points between such isolators
and the UPS, by the user, displaying the following text (or equivalent in a language
which is acceptable in the country in which the UPS system is installed):
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Risk of Voltage Backfeed. Before working on this circuit: Isolate the UPS and
check for hazardous voltage between all terminals including the protective earth.
Failure to follow these instructions will result in death or serious injury.
10 990–5233D–001
Important Safety Instructions — SAVE
THESE INSTRUCTIONS 20 - 120 kVA 400 V
Periodical Check
WARNING
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Limited lifetime components, such as capacitors, fans, electronic boards,
batteries, etc., must be checked periodically by qualified personnel.
• Battery trip control must be done periodically by qualified personnel.
This periodical check is recommended every 6 months and required every
12 months.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Battery Safety
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Battery circuit breakers must be installed according to the specifications and
requirements as defined by Schneider Electric.
• Servicing of batteries must only be performed or supervised by qualified
personnel knowledgeable of batteries and the required precautions. Keep
unqualified personnel away from batteries.
• Disconnect charging source prior to connecting or disconnecting battery
terminals.
• Do not dispose of batteries in a fire as they can explode.
• Do not open, alter, or mutilate batteries. Released electrolyte is harmful to the
skin and eyes. It may be toxic.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Batteries can present a risk of electric shock and high short-circuit current. The
following precautions must be observed when working on batteries
• Remove watches, rings, or other metal objects.
• Use tools with insulated handles.
• Wear protective glasses, gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect the charging source prior to connecting or disconnecting battery
terminals.
• Determine if the battery is inadvertently grounded. If inadvertently grounded,
remove source from ground. Contact with any part of a grounded battery can
result in electric shock. The likelihood of such shock can be reduced if such
grounds are removed during installation and maintenance (applicable to
equipment and remote battery supplies not having a grounded supply circuit).
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
When replacing batteries, always replace with the same type and number of
batteries or battery packs.
Failure to follow these instructions will result in death or serious injury.
990–5233D–001 11
Important Safety Instructions — SAVE
20 - 120 kVA 400 V THESE INSTRUCTIONS
CAUTION
RISK OF EQUIPMENT DAMAGE
Batteries must not be stored more than six months due to the requirement of
recharging. If the UPS system remains de-energized for a long period, we
recommend that you energize the UPS system for a period of 24 hours at least
once every month. This charges the batteries, thus avoiding irreversible
damage.
Failure to follow these instructions can result in injury or equipment
damage.
Electromagnetic Compatibility
NOTICE
RISK OF ELECTROMAGNETIC DISTURBANCE
This is a product Category 3 according to IEC 62040-2 for commercial, industrial
and similar applications in the second environment - installation restrictions or
additional measures may be needed to prevent disturbances. The second
environment includes all commercial, light industry and industrial locations other
than residential, commercial and light industrial premises directly connected
without intermediate transformer to a public low-voltage mains supply. The
installation and cabling must follow the Electromagnetic compatibility rules, e.g.:
• the segregation of cables,
• the use of shielded or special cables when relevant,
• the use of grounded metallic cable tray and supports.
Failure to follow these instructions can result in equipment damage.
12 990–5233D–001
Specifications 20 - 120 kVA 400 V
Specifications
Input
UPS rating 20 kVA 30 kVA 40 kVA 60 kVA 80 kVA 100 kVA 120 kVA
Input voltage range permitted by the 250 to 470 for a standard UPS
standard according to the curve below 342 to 470 for a UPS with backfeed protection
(V)
Input current (A) for 400V, overload= 39 56 72 108 145 181 217
1.25 In limited to 10 min.
Input current (A) for 400V, overload=1.5 47 68 87 130 174 217 260
In limited to 1 min.
THDI < 6% at full load
< 8% at 25–75% load
Output
UPS rating 20 kVA 30 kVA 40 kVA 60 kVA 80 kVA 100 kVA 120 kVA
Output frequency 50 Hz or 60 Hz
1. Rated currents with battery float charging. normal AC input voltage = U, AC bypass input = U, load = 400 V / P
load = PN / load cos phi = 0.9
990–5233D–001 13
20 - 120 kVA 400 V Specifications
UPS rating 20 kVA 30 kVA 40 kVA 60 kVA 80 kVA 100 kVA 120 kVA
Bypass
UPS rating 20 kVA 30 kVA 40 kVA 60 kVA 80 kVA 100 kVA 120 kVA
14 990–5233D–001
Specifications 20 - 120 kVA 400 V
Environment
Operating Temperatures
The operating temperature range is 0 to 40 °C, however optimal operation is 20 to
25 °C.
Battery backup time is adversely affected by high and low temperatures. It is
significantly reduced at temperatures under 10 °C.
Above 25 °C, battery service life is reduced by 50% for every 10 °C temperature
increase. Above 40 °C, battery manufacturers no longer guarantee operation due
to the risk of thermal runaway.
Losses calculated with maximum current → V=380 and RL load; cosf: 0.9 @ 100%
load
Heat Dissipation
UPS rating 20 kVA 30 kVA 40 kVA 60 kVA 80 kVA 100 kVA 120 kVA
990–5233D–001 15
20 - 120 kVA 400 V Specifications
Batteries
Battery type: Sealed lead-acid or vented lead acid.
DC Power Levels for Battery Sizing with Output Power Factor = 0.9
UPS rating 20 kVA 30 kVA 40 kVA 60 kVA 80 kVA 100 kVA 120 kVA
DC Power Levels for Battery Sizing with Output Power Factor = 0.8
UPS rating 20 kVA 30 kVA 40 kVA 60 kVA 80 kVA 100 kVA 120 kVA
UPS rating 20 kVA 30 kVA 40 kVA 60 kVA 80 kVA 100 kVA 120 kVA
16 990–5233D–001
Specifications 20 - 120 kVA 400 V
990–5233D–001 17
20 - 120 kVA 400 V Specifications
UPS Rating 20 kVA 30 kVA 40 kVA 60 kVA 80 kVA 100 kVA 120 kVA
Dual utility/ C60L - 50A C60L - 63A NSX 100F 3P- NSX 160F 3P- NSX 160F 3P- NSX 250F 3P- NSX 250F 3P-
mains TM80D TM125D TM160D TM200D TM250D
system –
Input
Dual utility/ NSX 100F 4P- NSX 100F 4P- NSX 100F 4P- NSX 160F 4P- NSX 160F 4P- NSX 250F 4P- NSX 250F 4P-
mains TM100D TM100D TM100D TM125D TM160D TM250D TM250D
system –
Bypass
Single utility/ NSX 100F 4P- NSX 100F 4P- NSX 100F 4P- NSX 160F 4P- NSX 160F 4P- NSX 250F 4P- NSX 250F 4P-
mains TM100D TM100D TM100D TM125D TM160D TM250D TM250D
system
WARNING
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Place a label with the following text on each upstream circuit breaker: “Isolate
the Uninterruptible Power Supply (UPS) before working on this circuit”.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
NOTICE
RISK OF EXPLOSION, ARC FLASH OR VOLTAGE OUTAGE
For Installation design, consider:
• the above recommended upstream circuit breaker for discrimination with the
UPS internal fuses.
• Icw = 20 kA for 20 to 60 kVA UPS when using the recommended upstream
circuit breaker.
• Icw = 30 kA for 80 to 120 kVA UPS when using the recommended upstream
circuit breaker.
Failure to follow these instructions can result in equipment damage.
N type curve for the downstream circuit breaker can be replaced by H or L type
curve, depending on the installation. The indicated protection ensures
discrimination for each output circuit downstream of the UPS, whether supplied via
the input or the bypass source.
NOTE: If these downstream protection recommendations are not followed, it can
result in a break in power longer than 20 ms in all the output circuits if a short circuit
occurs on an output circuit.
Earth-Leakage Current
UPS earth-leakage current is 1A.
18 990–5233D–001
Specifications 20 - 120 kVA 400 V
Fuses
Time/Current Curves for UPS Input and Output Fuses
UPS rating 20 kVA 30 kVA 40 kVA 60 kVA 80 kVA 100 kVA 120 kVA
Dual utility/ 10 16 16 25 50 50 70
mains
system –
Input (mm²)
Dual utility/ 16 16 16 25 50 70 70
mains
system –
Bypass
(mm²)
Single utility/ 16 16 16 25 50 70 70
mains
system –
Input &
bypass (mm²)
Output (mm²) 16 16 16 25 50 70 70
Battery (<15 16 25 35 70 95 2 x 50 2 x 70
m) (mm²)
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Use power cables of equal resistance, equal length, and equal size for the same
function.
Failure to follow these instructions will result in death or serious injury.
990–5233D–001 19
20 - 120 kVA 400 V Specifications
NOTE: Cable sizes are determined for copper conductors (for aluminium
conductors, increase the size by 30%). Size calculations also take into account a
voltage of 400 V and grouping of four cables.
Terminal hole diameter: 6.5 mm (8.5 mm for 120 kVA).
PE cables (Protective Earth) cables connect to the earthing terminal. Hole
diameter: 6.5 mm (8.5 mm for 120 kVA).
20 990–5233D–001
Specifications 20 - 120 kVA 400 V
Transformers
Marine UPS Adaptation Voltage Transformer Specifications
Primary Voltage (V) 440 +/- 5% 690 +/- 5% 440 +/- 5% 690 +/- 440 +/- 5% 690 +/- 5%
5%
Frequency (Hz) 50
2. The suggested cable sizes are for 1000R02V type copper cables less than 100 meters long and for a voltage
drop of less than 3%.
3. Full load
990–5233D–001 21
20 - 120 kVA 400 V Specifications
NOTE: The current values given in the table below are for nominal utility/mains
voltages and rated load.
The transforming ratio is equal to 1.
4. The suggested cable sizes are for 1000R02V type copper cables less than 100 meters long and for a voltage
drop of less than 3%.
22 990–5233D–001
Specifications 20 - 120 kVA 400 V
WARNING
HAZARD OF FIRE
• Protect the battery circuit with a DC circuit breaker equipped with an
undervoltage coil (MN 24 VDC).
• The DC breaker must be rated. The undervoltage coil must be wired to the
UPS as shown in the connection diagrams below.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
QF1 Type NSX160S NSX160- NSX400S NSX160- NSX400S NSX160S NSX400S DC NSX400S
circuit DC 3P S DC 3P DC 3P S DC 3P DC 3P DC 3P 3P DC 3P
breaker
Trip unit TM100D TM100D MP1 TM250D MP1 TM250D MP1 MP1
Thermal 1 1 - 1 - 1 - -
setting
5. For other values, consult the after sales department at Schneider Electric or your local agency.
6. All In One Box – batteries and the circuit breaker are stored in the UPS cabinet.
990–5233D–001 23
20 - 120 kVA 400 V Specifications
UPS rating 20 kVA 30 kVA 40 kVA 60 kVA 80 kVA 100 kVA 120 kVA
Maximum Magnetic current setting (lsd) must be less than 50% of maximum battery short circuit current8
magnetic
current
Minimum 95.2 141.1 187.6 281.4 375.2 473.2 562.8
magnetic
setting (A)9
NOTE: Due to discharge time limited to battery backup time, circuit breaker can be
overloaded according to battery supplier specifications.
7. Rated discharge battery current based on nominal load with a power factor of 0.9
8. According to circuit breaker supplier specifications.
9. Including 20% of circuit breaker trip uncertainty. Magnetic must trip below 40 ms for 50% of maximum battery
short circuit current.
24 990–5233D–001
Mechanical Assembly 20 - 120 kVA 400 V
Mechanical Assembly
NOTE: Not applicable for Galaxy 5500 Marine, see Galaxy 5500 Marine receiving
and unpacking manual.
Layout of Cabinets
NOTE: The clearance dimensions given above are published for airflow and
service access only. Consult with the local safety codes and standards for
additional requirements in your local area.
990–5233D–001 25
20 - 120 kVA 400 V Mechanical Assembly
26 990–5233D–001
Mechanical Assembly 20 - 120 kVA 400 V
1. Remove the two screws on the top edges of the UPS left side panel.
2. Install the cable fastening bar using the M5 spacers, the washers, and the M5
screws.
3. Install the panel brackets and spacers.
990–5233D–001 27
20 - 120 kVA 400 V Mechanical Assembly
4. Install four clip nuts on each sides of the left side panel.
5. Install the left side panel using M6 screws.
6. Install the front and back panels using the remaining M6 screws.
28 990–5233D–001
Mechanical Assembly 20 - 120 kVA 400 V
2. Install the posts. The longer posts must be positioned in the front.
990–5233D–001 29
20 - 120 kVA 400 V Floor Mounting
Floor Mounting
WARNING
HAZARD OF OVERHEATING
Do not remove the cabinet feet as they are required to ensure sufficient
ventilation.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
30 990–5233D–001
Connect Input and PE Cables in Single
Systems 20 - 120 kVA 400 V
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
PE cables must be connected first.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
PE cables must be connected first.
Failure to follow these instructions will result in death or serious injury.
990–5233D–001 31
Connect Input and PE Cables in Single
20 - 120 kVA 400 V Systems
Frequency Converter
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
PE cables must be connected first.
Failure to follow these instructions will result in death or serious injury.
32 990–5233D–001
Connect Input and PE Cables in Single
Systems 20 - 120 kVA 400 V
8. Reinstall the protection cover for power terminals. Tightening torque is 2 Nm.
9. Unfold the dust protection cover.
990–5233D–001 33
Connect Input and PE Cables in Parallel
20 - 120 kVA 400 V Systems
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
PE cables must be connected first.
Failure to follow these instructions will result in death or serious injury.
34 990–5233D–001
Connect Input and PE Cables in Parallel
Systems 20 - 120 kVA 400 V
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
PE cables must be connected first.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
PE cables must be connected first.
Failure to follow these instructions will result in death or serious injury.
990–5233D–001 35
Connect Input and PE Cables in Parallel
20 - 120 kVA 400 V Systems
7. Connect the output terminals of the UPSs to the output terminals of the external
bypass using cables with equal lengths and sizes.
8. Fasten the cables to the cabinet.
9. Reinstall the protection covers for power terminals. Tightening torque is 2 Nm.
10.Unfold the dust protection cover.
36 990–5233D–001
Connect Input and PE Cables in Parallel
Systems 20 - 120 kVA 400 V
Frequency Converter
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
PE cables must be connected first.
Failure to follow these instructions will result in death or serious injury.
990–5233D–001 37
20 - 120 kVA 400 V Connect PE Cable in TNC System
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
PE cables must be connected for single UPSs, parallel UPSs and external
bypasses.
Failure to follow these instructions will result in death or serious injury.
38 990–5233D–001
Connect the Communication Cables 20 - 120 kVA 400 V
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Run the communication cables separately from the power cables to ensure
sufficient isolation. If any risk of contact with the power cables exists, reinforce
the insulation of the communication cables.
Failure to follow these instructions will result in death or serious injury.
990–5233D–001 39
20 - 120 kVA 400 V Connect the Communication Cables
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Run the communication cables separately from the power cables to ensure
sufficient isolation. If any risk of contact with the power cables exists, reinforce
the insulation of the communication cables.
Failure to follow these instructions will result in death or serious injury.
40 990–5233D–001
Connect the Communication Cables 20 - 120 kVA 400 V
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Isolate and tagout/lockout all power sources for the dry contact communication
card (also known as SECI) before making connections. Never connect SELV
(safety extra low voltage) and non-SELV circuits to the different outputs of the
same card.
Failure to follow these instructions will result in death or serious injury.
NOTE: Only one dry contact communication card can be installed in a UPS.
Pin Description
3 Load on UPS
2 Battery inoperable
1 General alarm
Pin Description
A UPS OFF
B UPS ON
990–5233D–001 41
20 - 120 kVA 400 V Connect the Communication Cables
42 990–5233D–001
Connect the Communication Cables 20 - 120 kVA 400 V
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
If a SELV source is used, isolate the communication card from the power source
to ensure the safety of personnel working on the installation.
Failure to follow these instructions will result in death or serious injury.
1. Open the UPS door. The cardholder for optional communication cards is placed
on the inside of the door.
2. Remove the four screws from the cardholder.
990–5233D–001 43
20 - 120 kVA 400 V Connect the Communication Cables
44 990–5233D–001
Connect the Communication Cables 20 - 120 kVA 400 V
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
De-energize the UPSs before connecting the cables.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
A maximum of two UPSs can be installed in parallel.
Failure to follow these instructions will result in death or serious injury.
NOTE: The supplied cables (10 m) limit the distance between the two UPSs to
approximately six meters.
To locate the terminals in the cabinet, see Overview of the Communication Cables,
page 39
990–5233D–001 45
20 - 120 kVA 400 V Connect the Communication Cables
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
De-energize the UPSs before connecting the cables.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
A maximum of two UPSs can be installed in parallel. (Four UPSs can be present
in redundancy parallel system).
Failure to follow these instructions will result in death or serious injury.
NOTE: The supplied cables (10 m) limit the distance between the two UPSs to
approximately six meters.
To locate the terminals in the cabinet, see Overview of the Communication Cables,
page 39
46 990–5233D–001
Connect the Communication Cables 20 - 120 kVA 400 V
990–5233D–001 47
20 - 120 kVA 400 V Install an External Battery
CAUTION
FOR INSTALLATION ON SHIP – RISK OF ELECTRICAL DISCONNECTION
Install wedges as shown below.
Failure to follow these instructions can result in injury or equipment
damage.
1. Install the battery cells on the shelves according to the documentation supplied
by the battery vendor.
2. Mount the back wedge (20 - 30 kVA only).
3. Mount the sides wedges.
4. Mount the front wedges.
48 990–5233D–001
Install an External Battery 20 - 120 kVA 400 V
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect PE cables to the battery cabinet and the UPS first.
Failure to follow these instructions will result in death or serious injury.
990–5233D–001 49
20 - 120 kVA 400 V Install an External Battery
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• It is mandatory to protect the battery circuit with a circuit breaker equipped
with an undervoltage coil (MN 24V DC).
• Circuit breaker type and rated must be compliant with specifications given.
See Battery Circuit Breaker Enclosure, page 23
Failure to follow these instructions will result in death or serious injury.
NOTE: Please contact Schneider Electric when selecting the battery circuit
breaker. In systems with several battery cabinets, only one circuit breaker is
necessary. Temperature sensors must be installed to obtain the battery warranty
and to optimize battery lifetime.
50 990–5233D–001
Install an External Battery 20 - 120 kVA 400 V
990–5233D–001 51
20 - 120 kVA 400 V Install an External Battery
WARNING
RISK OF EQUIPMENT DAMAGE
The maximum size for the communication cables (SELV) is 2.5 mm² and the
total length must be less than 100 meters.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
1. Connect the external battery cabinet connector XR1 to UPS connector XMB07,
as shown.
52 990–5233D–001
Install an External Battery 20 - 120 kVA 400 V
2. Connect the external battery cabinet connector XR1 to UPS connector XMD3,
and pass the cable through the ferrite three times.
990–5233D–001 53
Install a Battery Circuit Breaker Kit for
20 - 120 kVA 400 V Third Party Battery Cabinets (Option)
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
This battery circuit breaker kit contains an undervoltage coil (MN 24 VDC) which
is mandatory for all external battery cabinets. This battery circuit breaker is for
installations with third party batteries.
Failure to follow these instructions will result in death or serious injury.
54 990–5233D–001
Install a Battery Circuit Breaker Kit for
Third Party Battery Cabinets (Option) 20 - 120 kVA 400 V
5. Connect the battery circuit breaker to XR1. The connecting cables (2.5 m) are
supplied (N° 51031630).
6. Connect XR1 to the ATIZ board.
7. The terminals 1 to 4 of the XR1 terminal block must be connected to the UPS to
provide the functions for automatic opening of battery circuit breaker QF1 (in
case of emergency shutdown) and detection of the battery circuit breaker
position for the UPS. Details of these connections are given in the installation
manuals of these units.
8. Place the QF1 protection cover over the circuit breaker and its connections.
990–5233D–001 55
Install a Battery Circuit Breaker Kit for
20 - 120 kVA 400 V Third Party Battery Cabinets (Option)
9. Fasten the protection cover to the frame with the two screws. Tightening torque
is 6.5 Nm.
56 990–5233D–001
Battery Circuit Breaker Enclosure
(Option) 20 - 120 kVA 400 V
990–5233D–001 57
Battery Circuit Breaker Enclosure
20 - 120 kVA 400 V (Option)
100–120 kVA Battery Circuit Breaker Enclosure with More Than 10 Minutes
Runtime
Connection Diagrams
• The size of the power cables is given in the tables above.
• The recommended size of auxiliary cables is 1 mm2 (terminal acceptance
capacity: 2.5 mm2 ).
• Make sure that the auxiliary cables and power cables do not follow the same
path.
• Power cables and auxiliary cables are not supplied.
58 990–5233D–001
Battery Circuit Breaker Enclosure
(Option) 20 - 120 kVA 400 V
Connection Points
UPS rating 20 – 120 kVA 100 – 120 kVA
990–5233D–001 59
Battery Circuit Breaker Enclosure
20 - 120 kVA 400 V (Option)
60 990–5233D–001
Install the Battery Temperature Monitor
(Option) 20 - 120 kVA 400 V
2. Connect the temperature monitor to the XMD3 connector in the UPS, and pass
the cable through the ferrite three times.
990–5233D–001 61
Install the Synchronization Module
20 - 120 kVA 400 V (Option)
62 990–5233D–001
Install the Synchronization Module
(Option) 20 - 120 kVA 400 V
1. Mark the four mounting hole locations on the wall. You can either use the
horizontal or the vertical mounting brackets. Drill holes in each of the four
marked locations and install plugs.
2. Place the synchronization module enclosure against the wall lining up with the
holes and fasten the synchronization module enclosure to the wall with four
screws.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The synchronization module must be earthed at one point only.
Failure to follow these instructions will result in death or serious injury.
990–5233D–001 63
Install the Synchronization Module
20 - 120 kVA 400 V (Option)
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The synchronization module must be earthed at one point only.
Failure to follow these instructions will result in death or serious injury.
64 990–5233D–001
Install the Synchronization Module
(Option) 20 - 120 kVA 400 V
1. Connect power cables between all UPS units in Group 1 and connect them to
the synchronization module.
2. Connect the supplied 12 m Sub D9/Sub D15 cables between the SYNIN boards
in the UPS units, and connect Sub D9/Sub D15 cable from the last UPS in the
row to the COSS board in the synchronization module.
3. Connect Group 2 to the synchronization module according to the procedures in
step 1 and 2 above.
990–5233D–001 65
Install the Synchronization Module
20 - 120 kVA 400 V (Option)
Outputs
Inputs
66 990–5233D–001
Install an External Bypass 20 - 120 kVA 400 V
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The combined UPS power of all the installed UPS cabinets must not exceed the
available bypass power.
Failure to follow these instructions will result in death or serious injury.
1. Prepare the external bypass cabinet for cables by clearing the cable running
entries.
2. Connect the external bypass cabinet to earth.
3. Connect the bypass cables from the terminals (N, L1, L2, L3) in the external
bypass cabinet to the bypass terminals (N, L1, L2, L3) on the UPSs.
4. Connect the bypass cables from the AC bypass source to the terminals (N, L1,
L2, L3) in the external bypass cabinet.
5. Connect the load cables from the load to the terminals (N, L1, L2, L3) in the
external bypass cabinet.
990–5233D–001 67
20 - 120 kVA 400 V Install an External Bypass
6. Connect the AC output cables from output terminals (N, L1, L2, L3) in the UPSs
to the terminals (N, L1, L2, L3) in the external bypass cabinet.
NOTE: Connection of the communication cables is shown in Parallel System
with External Bypass, page 35.
TNC
1. Prepare the external bypass cabinet for cables by clearing the cable running
entries.
2. Connect the external bypass cabinet to earth and neutral (PEN).
3. Connect the bypass cables from the terminals (L1, L2, L3) in the external
bypass cabinet to the bypass terminals (L1, L2, L3) on the UPSs.
4. Connect the bypass cables from the AC bypass source to the terminals (L1, L2,
L3) in the external bypass cabinet.
5. Connect the load cables from the load to the terminals (L1, L2, L3) in the
external bypass cabinet.
6. Connect the AC output cables from the output terminals (L1, L2, L3) in the
UPSs to the terminals (L1, L2, L3) in the external bypass cabinet.
NOTE: Connection of the communication cables is shown in Parallel System
with External Bypass, page 35.
68 990–5233D–001
Install an External Bypass 20 - 120 kVA 400 V
1. Prepare the external bypass cabinet for cables by clearing the cable running
entries.
2. Connect the external bypass to earth.
3. Connect the bypass cables from the terminals (N, L1, L2, L3) in the external
bypass cabinet to the bypass terminals (N, L1, L2, L3) on the UPSs through the
top cable entry.
4. Connect the bypass cables from the AC bypass source to the terminals (N, L1,
L2, L3) in the external bypass cabinet.
5. Connect the load cables from the load to the terminals (N, L1, L2, L3) in the
external bypass cabinet.
6. Connect the AC output cable from output terminals (N, L1, L2, L3) in the UPSs
to the terminals (N, L1, L2, L3) in the external bypass cabinet.
NOTE: Connection of the communication cables is shown in Parallel System
with External Bypass, page 35.
990–5233D–001 69
20 - 120 kVA 400 V Install an External Bypass
TNC
1. Prepare the external bypass cabinet for cables by clearing the cable running
entries.
2. Connect the external bypass cabinet to earth.
3. Connect the bypass cables from the terminals (PEN, L1, L2, L3) in the external
bypass cabinet to the bypass terminals (PEN, L1, L2, L3) on the UPSs through
the top cable entry.
4. Connect the bypass cables from the AC bypass source to the terminals (PEN,
L1, L2, L3) in the external bypass cabinet.
5. Connect the load cables from the load to the terminals (PEN, L1, L2, L3) in the
external bypass cabinet.
6. Connect the AC output cables from output terminals (PEN, L1, L2, L3) in the
UPSs to the terminals (N, L1, L2, L3) in the external bypass cabinet.
NOTE: Connection of the communication cables is shown in Parallel System
with External Bypass, page 35.
70 990–5233D–001
Install Marine UPS Adaptation Voltage
Transformer 20 - 120 kVA 400 V
WARNING
HAZARD OF OVERHEATING
• Do not cover the transformer ventilation openings when the transformer is in
operation.
• Do not remove the transformer feet.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
990–5233D–001 71
20 - 120 kVA 400 V Install Isolation Transformer (Option)
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Do not install different transformer sizes that belong to different vector groups in
the same UPS installation.
Failure to follow these instructions will result in death or serious injury.
72 990–5233D–001
Install Isolation Transformer (Option) 20 - 120 kVA 400 V
990–5233D–001 73
20 - 120 kVA 400 V Install Isolation Transformer (Option)
74 990–5233D–001
Install Isolation Transformer (Option) 20 - 120 kVA 400 V
WARNING
RISK OF EQUIPMENT DAMAGE
Before turning on the UPS system, make sure that N on the UPSs are parallel
connected and that the output of the UPSs are parallel connected as shown in
the diagram below. This requires extra cables which are not provided by
Schneider Electric.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
A maximum of four UPSs plus transformers can be connected in parallel.
Transformers must be earthed correctly.
• Use power cables of equal resistance, equal length and equal size for the
same function.
• To choose the correct upstream circuit breaker, see the table in Install
Isolation Transformer (Option), page 72.
Failure to follow these instructions will result in death or serious injury.
990–5233D–001 75
20 - 120 kVA 400 V Install Isolation Transformer (Option)
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect PE cables to the transformer first.
Failure to follow these instructions will result in death or serious injury.
76 990–5233D–001
Install Isolation Transformer (Option) 20 - 120 kVA 400 V
1. Connect a cable from the transformer input terminals (L1, L2, L3) to the utility/
mains supply.
990–5233D–001 77
20 - 120 kVA 400 V Install Isolation Transformer (Option)
78 990–5233D–001
Install Isolation Transformer (Option) 20 - 120 kVA 400 V
990–5233D–001 79
20 - 120 kVA 400 V Install Isolation Transformer (Option)
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Connect PE cables to the transformer first.
Failure to follow these instructions will result in death or serious injury.
80 990–5233D–001
Install Isolation Transformer (Option) 20 - 120 kVA 400 V
1. Connect a cable from the transformer input terminals (L1, L2, L3) to the UPS
output terminals (L1, L2, L3) and to PE. Remove N if connected.
990–5233D–001 81
20 - 120 kVA 400 V Install Isolation Transformer (Option)
82 990–5233D–001
Install Isolation Transformer (Option) 20 - 120 kVA 400 V
3. Connect a cable from the transformer output terminals (L1, L2, L3, N) to the
load.
990–5233D–001 83
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmason
France
+ 33 (0) 1 41 29 70 00
www.schneider-electric.com