The document summarizes the BACnet interface of an Energy Valve. It includes a Protocol Implementation Conformance Statement that lists supported BACnet standards, objects, services, and properties. The valve can connect via MS/TP or BACnet/IP and supports common data sharing BIBBs. Configuration is possible through the Belimo Assistant app or an integrated web server.

Uploaded by

Bence Balogh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
104 views8 pages

Belimo BACnet Interface-Description Energy-Valve v4 01 En-Gb PDF

The document summarizes the BACnet interface of an Energy Valve. It includes a Protocol Implementation Conformance Statement that lists supported BACnet standards, objects, services, and properties. The valve can connect via MS/TP or BACnet/IP and supports common data sharing BIBBs. Configuration is possible through the Belimo Assistant app or an integrated web server.

Uploaded by

Bence Balogh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

BACnet Interface Description

Energy Valve

ket?
hern et soc
the Et nsor
Wher
e is e fl ow se
On th
ator
n t h e actu
O

nt
cume
ith this do
Stay w
iption )“
descr
„ M o dbus 1, V2 or V3 h EV V
4
See
y V a lve (V old EV wit s. V4“
Energ ing an 1, V2, V3 v
replac
id ance in ent Guide V
For gu Replacem

-> see

Energy Valve DN 15...50 (Version 4)

Contents
Protocol Implementation Conformance Statement – PICS 2
BACnet Object Description 4

www.belimo.com Energy Valve BACnet Interface Description • en-gb • 2022-08 • Subject to changes 1
Electronic pressure-independent characterised control valve
Energy Valve with energy monitoring

Protocol Implementation Conformance Statement – PICS


General information Date 15.01.2022
Vendor Name BELIMO Automation AG
Vendor ID 423
Product Name Energy Valve
Product Model Number EV..R2+(K)BAC (Version 4, DN 15...50)
EV..R2+MID (Version 4, DN 15...50)
Application Software Version 04.01.0000
Firmware Revision 14.10.0002
BACnet Protocol Revision 1.14
Product Description Electronic pressure-independent characterised
control valve with energy monitoring
BACnet Standard Device Profile BACnet Application Specific Controller (B-ASC)
Segmentation capability No
Data Link Layer Options MS/TP master
BACnet IP, (Annex J)
BACnet IP, (Annex J), Foreign Device
Device Address Binding No static device binding supported
Networking Options None
Character Sets Supported ISO 10646 (UTF-8)
Gateway Options None
Network Security Options Non-secure device
Conformance Listed by BTL
BACnet Interoperability Building Blocks Data sharing – ReadProperty-B (DS-RP-B)
supported BIBBs Data sharing – ReadPropertyMultiple-B (DS-RPM-B)
Data sharing – WriteProperty-B (DS-WP-B)
Data sharing – COV-B (DS-COV-B)
Device management – DynamicDeviceBinding-B (DM-DDB-B)
Device management – DynamicObjectBinding-B (DM-DOB-B)
Device management – DeviceCommunicationControl-B (DM-DCC-B)
BACnet MS/TP Baud rates 9’600, 19’200, 38’400, 76’800, 115’200
(Default: 38’400)
Address 0...127 (Default: 1)
Number of nodes Max 32 (without repeater), 1 full busload
Terminating resistor 120 Ω
BACnet IP Port open (Default: 47’808)
Parameterisation Tool Belimo Assistant App or integrated webserver

All writeable objects with instance number ≥ 90 are persistent and are not supposed to be written on a
! regular base.

2 Energy Valve BACnet Interface Description • en-gb • 2022-08 • Subject to changes www.belimo.com
Electronic pressure-independent characterised control valve
Energy Valve with energy monitoring

Protocol Implementation Conformance Statement - PICS


Standard Object Types Supported Object type Optional properties Writeable properties
Device Description Object Identifier
Location Object Name
Active COV Subscriptions Location
Max Master Description
Max Info Frames APDU Timeout (1’000…60’000)
Profile Name Number of APDU Retries (0...10)
Max Master (1...127)
Max Info Frames (1...255)
Analog Input [AI] Description COV Increment
COV Increment
Analog Output [AO] Description Present Value
COV Increment COV Increment
Relinquish Default
Analog Value [AV] Description Present Value
COV Increment COV Increment
Binary Input [BI] Description
Active text
Inactive Text
Multi-state Input [MI] Description
State Text
Multi-state Output [MO] Description Present Value
State Text Relinquish Default
Multi-state Value [MV] Description Present Value
State Text
Positive Integer Value Description
[PIV]

The device does not support the services CreateObject and DeleteObject.
The specified maximum length of writable strings is based on single-byte characters.
• Object name 32 char
• Location 64 char
• Description 64 char

Service processing The device supports the DeviceCommunicationControl and ReinitializeDevice services. No
password is required.
A maximum of 6 active COV subscriptions with a lifetime of 1…28‘800 sec. (max. 8 hours) are
supported.

www.belimo.com Energy Valve BACnet Interface Description • en-gb • 2022-08 • Subject to changes 3
Electronic pressure-independent characterised control valve
Energy Valve with energy monitoring

BACnet Object Description


Object Name Object Type Description Values COV Increment Access
[Instance] Comment
Status_Flags
Device Device 0…4’194’302 – W
[Inst.Nr] Default: 1
RelPos AI[1] Relative Position in % 0...100 0.01...100 R
Overridden = true, if the gear is disengaged Default: 1
SpAnalog AI[6] If SetpointSource MV[122] is not 1: Analog then Out_Of_Service is 0...100 0.01...100
TRUE Default: 1
Overridden = true, if forced control (bus, tool and analog forced
control) is active
Sens1Active_Volt AI[20] Sensor 1 as Voltage in V 0...15 0.01...15 R
If Sens1Type MV[220] is not 2: Active then Out_Of_Service is TRUE Default: 1
Sens1Passive_ AI[21] Sensor 1 as Resistor in Ohm 0.1...1‘000‘000 0.1...1‘000‘000 R
Ohm If Sens1Type MV[220] is not 4: Passive then Out_Of_Service is Default: 1
TRUE
T1_UnitSel AI[22] Temperature 1 (remote) in selected unit -20…120 0.01…252 R
Unit can be selected with object MV[127] Default: 1
T2_UnitSel AI[23] Temperature 2 (Flow Body) in selected unit -20…120 0.01…252 R
Unit can be selected with object MV[127] Default: 1
SpRel AO[1] Setpoint Relative in % 0...100 0.01…100 C
The set point is related to either the position, the flow (of V`min, Default: 0 Default: 1
Vmax) or the power (of Pmax).
See also AV[90], AV[94], MV[100], AV[110]
Overridden = true, if forced control (bus MV[1], tool and analog
forced control) is active
RelFlow AV[10] Relative Flow in % 0…150 0.01…150 R
Default: 1
SpAbsFlow_ AV [17] Setpoint Absolute Flow in selected unit 0…1,5*Vnom 0…1,5*Vnom R
UnitSel Unit can be selected with object MV[123]
Overridden = true, if forced control (bus, tool and analog forced
control) is active
AbsFlow_UnitSel AV[19] Absolute Flow in selected unit 0…1,5*Vnom 0…1,5*Vnom R
Unit can be selected with object MV[123]
Sens1Temp_ AV [20] Sensor 1 as Temperature in selected unit -20…248 0.01...252 R
UnitSel Unit can be selected with object MV[127] Default: 1
If Sens1PassiveType MV[221] is 1: None or Sens1Type MV[220] is
not 3: Passive then Out_Of_Service is TRUE
DeltaT_UnitSel AV[22] Delta Temperature in selected unit 0...140 0.01…810 R
Unit can be selected with object MV[128] Default: 1
RelPower AV[40] Relative Power in % 0...300 0.01…300 R
Default: 1
CoolingPower_ AV[45] Cooling Power in selected unit 0…74‘150‘000 0.1…73‘361‘050 R
UnitSel Unit can be selected with object MV[124] Default: 1
HeatingPower_ AV[46] Heating Power in selected unit 0…74‘150‘000 0.1…73‘361‘050 R
UnitSel Unit can be selected with object MV[124] Default: 1
CoolingEnergy_ AV[47] Cooling Energy in selected unit 0…2‘147‘483‘641 1…1.35E12 R
UnitSel Unit can be selected with object MV[125]. See also MV[200] Default: 1
HeatingEnergy_ AV[48] Heating Energy in selected unit 0…2‘147‘483‘641 1…1.35E12 R
UnitSel Unit can be selected with object MV[125]. See also MV[200] Default: 1
VolumeDecimal_ AV[50] Decimal Number of the Volume_m3 Object 0.01-0.99 0.01-0.99‬‬ R
UnitSel Resolution of 0.01m3 of the Object PIV[50]. See also MV[200] Default: 0.1
Volume_UnitSel AV[52] Accumulated Volume in selected unit 0…2‘147‘483‘641 1…4.2E10 R
Unit can be selected with object MV[126]. See also MV[200] Default: 1
GlycolConcentration AV[60] Glycol concentration in % 0…100 0.01…100 R
Measured value or override value in settings Default: 1
Vmin AV[90] Minimum Flow Limit in % 0…100 0.01…100 W
Default: 1
Vmin_UnitSel AV[93] Minimum Flow Limit in selected unit 0…360‘000 0…360‘000 W
Unit can be selected with object MV[123] Default: 1

4 Energy Valve BACnet Interface Description • en-gb • 2022-08 • Subject to changes www.belimo.com
Electronic pressure-independent characterised control valve
Energy Valve with energy monitoring

BACnet Object Description


Object Name Object Type Description Values COV Increment Access
[Instance] Comment
Status_Flags
Vmax AV[94] Maximum Flow Limit in % 0…100 0.01…100 W
Default: 1
Vmax_UnitSel AV[97] Maximum Flow Limit in selected unit 0…360‘000 0…360‘000 W
Unit can be selected with object MV[123] Default: 1
Vnom_UnitSel R AV[100] Nominal Flow in selected unit 0…360‘000 0…360‘000 R
Unit can be selected with object MV[123] Default: 1

Pmax AV[110] Maximum Power Limit in % 0…100 0.01…100 W


Default: 1
Pmax_UnitSel AV[113] Maximum Power Limit in selected unit 0...74‘150‘000 0.01…73‘361‘050 W
Unit can be selected with object MV[124] Default: 1
Pnom_ UnitSel AV[116] Nominal Power in selected unit 0…21‘500 0.01…73‘361‘050 R
Unit can be selected with object MV[124] Default: 1
SpDeltaT_UnitSel AV[120] Setpoint Delta Temperature in selected unit 0…99 0.01…99 W
Unit can be selected with object MV[128] Default: 1
SpAbsFlowDeltaT_ AV[127] Setpoint Absolute Flow at Delta T in selected unit 0…360‘000 0…360‘000 W
UnitSel
Unit can be selected with object MV[123] Default: 1
BusWatchdog AV[130] Timeout for Bus Watchdog in s 0…3600 0.01…120 W
Non functional. Reserved for future extension Default: 0 Default: 1
ErrorState AV[140] Error State Bit 0: No communication 1…16‘383 R
to actuator Default: 1
No communication to actuator: Communication with actuator not
Bit 1: Gear disengaged
possible.
Bit 2: Actuator cannot
Gear disengagement: Gear disengaged button is pressed move
Actuator cannot move: Mechanical overload due to blocked valve, Bit 3: Reverse flow
etc. Bit 4: Flow setpoint not
(only available for EV..R+KBAC) reached
Reverse flow: Reverse flow is detected Bit 5: Flow with closed
Flow setpoint not reached: Setpoint cannot be reached within valve
15 min during flow control Bit 6: Flow actual
Flow actual exceeds flow nominal: Actual flow exceeds the exceeds flow nominal
designed nominal flow Bit 7: Flow measurement
Flow measurement error: Air in the system, error occurred during error
flow measurement Bit 8: Remote
Remote temperature not OK: No connection to external temperature temperature not OK
sensor Bit 9: Flowbody
temperature not OK
Flowbody temperature not OK: Error with embedded temperature
Bit10: Communication to
sensor
Sensor interrupted
Communication to sensor interrupted: Internal communication to Bit11: Freeze warning
flow sensor interrupted Bit12: Glycol detected
Freeze warning: Measured temperature & glycol concentration Bit13: Power setpoint not
indicate that grease ice can build up reached
Glycol detected: Glycol was detected in a MID application Bit14: not used
Power setpoint not reached: Setpoint cannot be reached within Bit15: not used
15 min during power control

www.belimo.com Energy Valve BACnet Interface Description • en-gb • 2022-08 • Subject to changes 5
Electronic pressure-independent characterised control valve
Energy Valve with energy monitoring

Object Name Object Type Description Values Access


[Instance] Comment
Status_Flags
Sens1Switch BI [20] Sensor 1 as Switch 0: Inactive R
If Sens1Type MV[220] is not 5: Switch then Out_Of_Service is TRUE 1: Active
BusTermination BV[99] Bus Termination 0: Disabled R
1: Enabled
Override MV[1] Override Control 1: None C
Overrides setpoint with defined valves. 2: Open Valve
3: Close Valve
4: Minimum
5: -
6: Maximum
7: Nominal
8: -
9: -
10: -
11: Motor Stop
Default: 1
SummaryStatus MV[99] Summary Status 1: Ok R
Summarizes all status MV[102] – MV[107] 2: Warning
3: Not Ok
ControlMode MV[100] Control Mode 1: Position Control W
This value defines the interpretation of the setpoint 2: Flow Control
A Reset will be performed, if the state of this object is changed. 3: Power Control
Default: 2
DeltaT_Limitation MV[101] DeltaT Limitation 1: Disabled W
Disabled: dT-Manager not active 2: dT-Manager
dT-Manager: dT-Manager active with no restriction to flow 3: dT-Manager scaling
dT-Manager scaling: dT-Manager active with restriction of flow → AV 120] Default: 1
StatusDeltaTMgr MV[102] Status DeltaT Manager 1: Not selected R
Not selected: dT-Manager deactivated 2: Standby
Standby: dT-Manager activated but not active 3: Active
Active: dT-Manager active 4: Scaling standby
Scaling standby: dT-Manager active with no limitation to the flow 5: Scaling active
Scaling active: dT-Manager active with limitation to the flow → AV[120]
StatusSensor MV[103] Status Sensor 1: OK R
Indicates informations within the flow sensor and both temperature sensors 2: Flow measurement error
Flow measurement error: Air in the system, error occurred during flow 3: Flowbody temperature not OK
measurement 4: Remote temperature not OK
Remote temperature not OK: No connection to external temperature sensor 5: Communication to flow sensor
Flowbody temperature not OK: Error with embedded temperature sensor interrupted
Communication to sensor interrupted: Internal communication to flow sensor
interrupted
StatusFlow MV[104] Status Flow 1: OK R
Actual flow exceeds nominal flow: Actual flow exceeds the designed 2: Actual flow exceeds nominal
nominal flow. flow
Flow in closed position: Flow is measured but position of valve is closed 3: Flow with closed valve
Flow not reached: Setpoint cannot be reached within 3min during flow control 4: Flow setpoint cannot be
Reverse flow detected: Energy Valves detected a reverse flow reached
5: Reverse flow
StatusMedia MV[105] Status Media 1: OK R
Freeze warning: Measured temperature & glycol concentration indicate that 2: Glycol detected
grease ice can build up 3: Freeze warning
Glycol detected: Glycol was detected in a MID application
StatusActuator MV[106] Status Actuator 1: OK R
Actuator cannot move: Mechanical overload due to blocked valve, etc. 2: Actuator cannot move
(only available for EV..R+KBAC) 3: Gear disengaged
Gear disengaged: Gear disengaged button is pressed 4: No communication to actuator
No communication to actuator: Communication with actuator not possible
StatusPower MV[107] Status Power 1: OK R
Power not reached: Setpoint cannot be reached within 15 min during power 2: Power not reached
control
Command MV[120] Initiate Function 1: None W
Initiation of actuator functions for service and test. After command is sent, 2: -
value returns to None(1). 3: Synchronization
Default: 1
SpSource MV[122] Setpoint Source 1: Analog W
If Analog(1) then actuator is controlled by analog signal 0...10 V on wire 3. 2: Bus
If Bus(2) then setpoint via bus SpRel AO[1] Default: 1

6 Energy Valve BACnet Interface Description • en-gb • 2022-08 • Subject to changes www.belimo.com
Electronic pressure-independent characterised control valve
Energy Valve with energy monitoring

Object Name Object Type Description Values Access


[Instance] Comment
Status_Flags
UnitSelFlow MV[123] Unit Selection Flow 1: m3/s W
The selected unit is valid for AV[17], AV[19], AV[93], AV[97], AV[100], AV[127] 2: m3/h
3: l/s
4: l/min
5: l/h
6: gpm
7: cfm
Default: 5
UnitSelPower MV[124] Unit Selection Power 1: W W
The selected unit is valid for AV[45], AV[46], AV[113], AV[116] 2: kW
3: MW
4: BTU/h
5: kBTU/h
6: ton
Default: 2
UnitSelEnergy MV[125] Unit Selection Energy 1: J W
The selected unit is valid for AV[47], AV[48], PIV[31], PIV[32] 2: kJ
3: MJ
4: GJ
5: Wh
6: kWh
7: MWh
8: BTU
9: kBTU
10: tonh
Default: 6
UnitSelVolume MV[126] Unit Selection Volume 1: m3 W
The selected unit is valid for AV[50], AV[52], PIV[50] 2: litre
3: gallon
4: cubic foot
Default: 1
UnitSelTemperature MV[127] Unit Selection Temperature Sensors 1: degree C W
The selected unit is valid for AV[20], AI[22], AV[23] 2: K
3: degree F
Default: 1
UnitSelDeltaT MV[128] Unit Selection Delta T 1: degree C W
The selected unit is valid for AV[22] 2: K
3: degree F
Default: 2
SelectMeterRegisters MV[200] Select between certified meter register and lifetime register. 1: Certified meter register W
Value 1 only available for models with MID certification EV..R2+MID 2: Lifetime meter register
For non MID certificied models Values 2 is defined as default. Default: 1 (2)

The certified meter register will be reset when the sensor module is replaced.
The lifetime register is compensated for glycol (if applicable).
Avoid toggling between the two registers as this will affect data logging.
Sens1Type MV[220] Sensor 1 Type 1: None W
Additional Sensor input. Only selectable if SpSource MV[122] is set to Bus. 2: Active Volt
3: -
3: Passive
4: Switch
Default: 1
Sens1TempType MV[221] Sensor 1 Passive Type 1: None W
2: PT1000
3: Ni1000EU
4: -
5: -
6: -
7: -
8: NTC10k2
9: NTC10k3
Default: 1

www.belimo.com Energy Valve BACnet Interface Description • en-gb • 2022-08 • Subject to changes 7
Electronic pressure-independent characterised control valve
Energy Valve with energy monitoring

Object Name Object Type Description Values Access


[Instance] Comment
Status_Flags
CoolingEnergyPIV_ PIV[31] Cooling Energy in selected unit 0.. 2‘147‘483‘647 R
UnitSel
Unit can be selected with object MV[125]
See also MV[200]
HeatingEnergyPIV_ PIV[32] Heating Energy in selected unit 0.. 2‘147‘483‘647 R
UnitSel
Unit can be selected with object MV[125]
See also MV[200]
VolumePIV_ PIV[50] Accumulated Volume in selected unit 0.. 2‘147‘483‘647 R
UnitSel Unit can be selected with object MV[126]
See also MV[200]
MeterSerialNo_ PIV[201] Energy Meter Serial Number First Digits - R
Part1
MeterSerialNo_ PIV[202] Energy Meter Serial Number Last Digits - R
Part2
Access: R = Read, W = Write, C = Commandable with priority array

Note:
According to the present configuration settings of the Energy Valve (e.g. DN size ) the HVAC application may perform a size limitation within the
indicated BACnet value range.
Each Energy Valve may have different HVAC value size limitations.

8 Energy Valve BACnet Interface Description • en-gb • 2022-08 • Subject to changes www.belimo.com