Report V1.3

The document provides an electrical engineering report on a lean MEG injection pump motor. It includes: 1) Nameplate data and specifications for a 37 kW, 400 V, 50 Hz induction motor powering the pump. 2) Calculations to correct the power factor from 0.87 to 0.95 by adding 8.81 kVAR of capacitance. 3) Calculations to further improve the power factor to 0.98 by adding 267.58 μF of capacitance. 4) Analysis of the 250 m, 70 mm^2 feed cable showing a resistance of 0.0614 Ω and voltage drop of 4.03 V. 5) Calculations determining a

Uploaded by

Ahmed Fathelbab
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
48 views8 pages

Report V1.3

The document provides an electrical engineering report on a lean MEG injection pump motor. It includes: 1) Nameplate data and specifications for a 37 kW, 400 V, 50 Hz induction motor powering the pump. 2) Calculations to correct the power factor from 0.87 to 0.95 by adding 8.81 kVAR of capacitance. 3) Calculations to further improve the power factor to 0.98 by adding 267.58 μF of capacitance. 4) Analysis of the 250 m, 70 mm^2 feed cable showing a resistance of 0.0614 Ω and voltage drop of 4.03 V. 5) Calculations determining a

Uploaded by

Ahmed Fathelbab
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

Page | 1

Postgraduate Petroleum and Natural Gas Diploma

Electrical Engineering Report

Requested by:

Prof. Dr. Mohamed Mostafa

Prepared by:

1. Hussain Atef Saad Abd Elaazim Elgenedy

Process Engineer at Belayim Petroleum Company (ZOHR Gas Field)

Suez Canal University

2. Ahmed Elsayed Elsaid Fathelbab

Production Support Engineer at Belayim Petroleum Company (ZOHR Gas Field)

Suez Canal University

3. Youssef Mohamed Abd Elrahman Abo Ashour

Production Team Leader at Belayim Petroleum Company (ZOHR Gas Field)

Suez Canal University

Page | 2
ELECTRICAL ENGINEERING REPORT
a) Choose suitable motor at your plant.
b) State the function of the machine which contain the motor.
c) Name plate data

Type Manfu.
Power speed
voltage Frequency
Full load current Duty/rating
Power in hp Service factor
ENCL Temp. class
spec Insu. class
Hazard classification Eff
Speed P.F

- Calculation for reactive power to correct power factor to 0.95.


- Calculate for the capacitance value to make P.F up to 0.98
- Measure for feed cables length and resistance from the voltage drop.
- Calculate for power saving due to reduce in current. (I2R)
- Calculate energy saving for one year, considering working HR 8000
annually.
- Calculate the new voltage drop.
- Voltage regulation (Vmain-Vload/Vload)*100

Page | 3
LEAN MEG INJECTION PUMP’S MOTOR
DESCRIPTION
Lean MEG injection pump is used to deliver lean MEG to the wells in order to prevent hydrate formation
due to high pressure and low temperature in the production sealines.

NAME PLATE DATA

Type Squirrel Cage


Manufacturer ABB
Induction Motor
Power 37 kW Speed 1474 rpm
Voltage 400 V Frequency 50 Hz
Full load current 65.6 A Duty/rating S1(IEC) 100%
Power in hp 49 hp Service factor 1
ENCL enclosure class IP65 Temperature Class B
Spec - Insulation Class F
Hazard classification Ex de IIB T4 Gb Efficiency 93.6%
PF 0.87

Q1: CALCULATION FOR REACTIVE POWER TO CORRECT POWER FACTOR


TO 0.95

Reactive Power (𝑄) = 𝑃 × [tan(cos −1 (𝑃𝐹1 )) − tan(cos−1(𝑃𝐹2 ))]

𝑃: Active Power (Watt)

𝑃𝐹1 : Initial Power Factor = 0.87

𝑃𝐹2 : Target Power Factor = 0.95

To calculate the angle of initial power factor:

cos−1(𝑃𝐹1 ) = cos−1(0.87) = 29.54°

Page | 4
To calculate the angle of target power factor:

cos−1(𝑃𝐹2 ) = cos−1(0.95) = 18.19°

To calculate the Reactive Power:

Reactive Power (𝑄) = 37 × [tan(29.54) − tan(18.19)] = 37 × (0.56669475 − 0.32858988) =


37 × 0.23810487 = 8.81 kVAR

∴ The reactive power to correct power factor to 0.95 is 8.81 kVAR

Q2: CALCULATE FOR THE CAPACITANCE VALUE TO MAKE P.F UP TO 0.98

Q2
C =
2πF  V 2

𝐶: Capacitance (𝜇F)

𝑄2 : Target Reactive Power (kVAR)

𝐹: Frequency (Hz)

𝑉: Line Voltage (V)

While:

𝑄2 = 𝑃 × [tan(cos −1(𝑃𝐹1 )) − tan(cos−1(𝑃𝐹2 ))]

𝑃: Active Power (Watt)

𝑃𝐹1 : Initial Power Factor = 0.87

𝑃𝐹2 : Target Power Factor = 0.98

To calculate the angle of initial power factor:

cos−1(𝑃𝐹1 ) = cos−1(0.87) = 29.54°

To calculate the angle of target power factor:

cos−1(𝑃𝐹2 ) = cos−1(0.98) = 11.48°

To calculate the Reactive Power:

Page | 5
𝑄2 = 𝑃 × [tan(cos −1 (𝑃𝐹1 )) − tan(cos −1 (𝑃𝐹2 ))] = 37 × [tan(29.54) − tan(11.48)] =
37 × (0.56669475 − 0.20308881055) = 37 × 0.36360593945 = 13.45 kVAR

To calculate the capacitance:


Q2 13.45×1000
C = 2πF  V2
= 2π×50  4002 = 0.00026758 F

C = 267.58 μF

∴ The capacitance required to improve the power factor to 0.98 is 267.58 μF

Q3: MEASURE FOR FEED CABLES LENGTH AND RESISTANCE FROM THE
VOLTAGE DROP

∆𝑉 = 𝐼 × 𝑅

𝜌×𝐿
𝑅=
𝐴

∆𝑉: Voltage drop (V)

𝐼: Load Current (A)

𝑅: Cable Resistance (Ω)

𝜌: Copper Resistivity = 1.724 × 10−8 Ω. m

𝐿: Cable Length (m)

𝐴: Cable Cross-sectional area (m2)

From the motor datasheet, L = 250 m and A = 70 mm2

To calculate the cable resistance:

𝜌 × 𝐿 1.72 × 10−8 × 250


𝑅= = = 0.0614 Ω
𝐴 0.00007

To calculate the voltage drop across the cable:

∆𝑉 = 𝐼 × 𝑅 = 65.6 × 0.0614 = 4.03 V

Page | 6
∴ The cable resistance is 𝟎. 𝟎𝟔𝟏𝟒 𝛀 and the voltage drop across the cable is 𝟒. 𝟎𝟑 V

Q4: CALCULATE FOR POWER SAVING DUE TO REDUCE IN CURRENT. (I 2 R)

2 )
Power Saving = 3 × (𝐼 2 − 𝐼0.98 ×𝑅

𝐼: Initial Current (A) = 65.6 A

𝐼0.98 : Final Current (A)

𝑅: Cable Resistance (Ω)

To calculate the final current:


𝑃 37000
𝐼0.98 = = = 54.49 A
√3×𝑉×𝑃𝐹0.98 √3×400×0.98

To calculate the power saving:

Power Saving = 3 × (65.62 − 54.492 ) × 𝑅 = 3 × 1334.2 × 0.0614 = 245.76 W

∴ The power saving due to current reduction is 245.76 W

Q5: CALCULATE ENERGY SAVING FOR ONE YEAR, CONSIDERING WORKING


HR 8000 ANNUALLY

Energy Saving (kWh) = Power Saving (kW) × Annual Operating Hours

To calculate the energy saving:

Energy Saving = 0.24576 × 8000 = 1966.08 kWHr

∴ The energy saving for 1 year is 1966.08 kWHr

Page | 7
Q6: CALCULATE THE NEW VOLTAGE DROP

To calculate the voltage drop:

Voltage Drop = 𝐼0.98 × 𝑅 = 54.49 × 0.0614 = 3.33 V

∴ The new voltage drop after power factor correction is 𝟑. 𝟑𝟑 V

Q7: VOLTAGE REGULATION (𝑉MAIN -𝑉LOAD /𝑉LOAD )*100


𝑉Main − 𝑉Load
Voltage Regulation = × 100
𝑉Load

𝑉Main: Source Voltage (V)

𝑉Load : Load Voltage (V) = 400 V

To calculate the voltage regulation:

𝑉Main − 𝑉Load 3.33


Voltage Regulation = × 100 = × 100 = 0.83%
𝑉Load 400

∴ The voltage regulation i.e., the voltage drop percentage from the source to the load is
𝟎. 𝟖𝟑%