ELECTRICAL ENGINEERING REPORT
a) Choose suitable motor at your plant.
b) State the function of the machine which contain the motor.
c) Name plate data
Type Manfu.
Power speed
voltage Frequency
Full load current Duty/rating
Power in hp Service factor
ENCL Temp. class
spec Insu. class
Hazard classification Eff
Speed P.F
Page | 3
LEAN MEG INJECTION PUMP’S MOTOR
DESCRIPTION
Lean MEG injection pump is used to deliver lean MEG to the wells in order to prevent hydrate formation
due to high pressure and low temperature in the production sealines.
Page | 4
To calculate the angle of target power factor:
Q2
C =
2πF V 2
𝐶: Capacitance (𝜇F)
𝐹: Frequency (Hz)
While:
Page | 5
𝑄2 = 𝑃 × [tan(cos −1 (𝑃𝐹1 )) − tan(cos −1 (𝑃𝐹2 ))] = 37 × [tan(29.54) − tan(11.48)] =
37 × (0.56669475 − 0.20308881055) = 37 × 0.36360593945 = 13.45 kVAR
C = 267.58 μF
Q3: MEASURE FOR FEED CABLES LENGTH AND RESISTANCE FROM THE
VOLTAGE DROP
∆𝑉 = 𝐼 × 𝑅
𝜌×𝐿
𝑅=
𝐴
Page | 6
∴ The cable resistance is 𝟎. 𝟎𝟔𝟏𝟒 𝛀 and the voltage drop across the cable is 𝟒. 𝟎𝟑 V
2 )
Power Saving = 3 × (𝐼 2 − 𝐼0.98 ×𝑅
Page | 7
Q6: CALCULATE THE NEW VOLTAGE DROP
∴ The voltage regulation i.e., the voltage drop percentage from the source to the load is
𝟎. 𝟖𝟑%
Page | 8