TECHNICAL DATA SHEET
Project Name MHI - Empower Various Project Quote SQ502191
Product L-MVE-0200-V11-SC31-E3-F1-L1-B1-PF1 Client Mitsubishi Heavy Industries
Supplier AuCom MCS GmbH & Co. kG Contractor
Model MVE - Multimotor Starter End User Empower
General Technical Data Remarks
Transformer Rating kVA
Transformer Impedance Z%
Transformer Short-Circuit Level kA
Rated voltage Ur kV 12,0kV
Operation voltage Ub kV 11,0kV
Network TN-C
Rated frequency Hz 50Hz
Rated power frequency withstand voltage Ud kV 28,0kV
Rated lightning impulse withstand voltage Up kV 75,0kV
Rated horizontal bus bar current Ib A 400A Tinned
Rated feeder bus bar current Ib A 400A Tinned
Rated short-time withstand current Ik kA 31.5kA 3s
Rated peak withstand current Ip kA 80kA
Rated internal arc classification kA AFL 31.5kA 3s
Loss of Services Category LSC LSC 2
Partition Class PI
Soft Starter Control Voltage 230VAC 1ph 50Hz External
AUX Voltage (cab light, MTHTR, CAB HTR, Test) 230VAC 1ph 50Hz External
Motor Data Remarks
Motor Power Ratings 1294kW
Motor Full Load Current 75A
Motor Full Load Speed 2978RPM
Motor Service Factor 1,00
Motor Torque 4006Nm
Motor Inertia J 6,1kg.m2
Load Inertia J 2,7kg.m2
Motor Efficiency (100% Load) 96,5%
Motor Efficiency (75% Load) 96,8%
Motor Efficiency (50% Load) 96,7%
Initial Power Factor (100% Load) 0,902
Initial Power Factor (75% Load) 0,893
Initial Power Factor (50% Load) 0,839
Target Power Factor 0,950
Power Consumption Remarks
During Start (Control Unit) 2000W
Normal Operation (Control Unit) 1000W
Auxillary Voltage 1000W
03
02
01
00 First Issue 13 Jan 2021 AuCom 13 Jan 2021 AuCom
Rev Description Date Prepared Date Approved
AuCom Electronics Ltd | www.aucom.com 1/11
TECHNICAL DATA SHEET
Project Name MHI - Empower Various Project Quote SQ502191
Product L-MVE-0200-V11-SC31-E3-F1-L1-B1-PF1 Client Mitsubishi Heavy Industries
Supplier AuCom MCS GmbH & Co. kG Contractor
Model MVE - Multimotor Starter End User Empower
Starter Remarks
Starter Type MVE - Fix
Rated normal current Ir A 200A
Power Ratings Starter 3200kW
Power Ratings Motor 1294kW
Power Components SCR
Cooling/Isolation Air Cooling
Controller Digital
Load Chiller / Mitsubishi
Max. starting current of FLA 400%
Max. starting and stopping time 30 secs
Number of starts per hour at maximum conditions 3/2 Cold/Hot
Communication Modbus RTU Monitor only
PIV (Peak Inverse Voltage) 32500V
Starter I2t Capacity 19.200.000A²s
Panel Remarks
Panel Type L-Series
Panel Configuration E3
Installation Stand alone
Disconnecting Switch Yes Incoming
Earthing Switch Yes Incoming
MV-Fuses Yes
Line Contactor / Fix
Bypass Contactor / Fix
Capacitor Yes
Capacitor Fuses Yes
Capacitor Contactor Yes
Inrush Limiter Yes
MV supply Incoming cable Top
MV Supply cable type and size sqmm²
MV Motor Outgoing cable Top
MV Motor cable type and size sqmm²
Distance between Soft Starter and Motor 100 ~ 500 m Subject to factory confirmation
Control Cable Entry Top
Wiring Standard
Cable marking Terminal Numbers only
Degree of Protection IP 54
Color RAL 7032
Dimension (HxWxD) approx. 2200 x 2300 x 1600 mm
Weight kg approx. 1650 kg
03
02
01
00 First Issue 13 Jan 2021 AuCom 13 Jan 2021 AuCom
Rev Description Date Prepared Date Approved
AuCom Electronics Ltd | www.aucom.com 2/11
TECHNICAL DATA SHEET
Project Name MHI - Empower Various Project Quote SQ502191
Product L-MVE-0200-V11-SC31-E3-F1-L1-B1-PF1 Client Mitsubishi Heavy Industries
Supplier AuCom MCS GmbH & Co. kG Contractor
Model MVE - Multimotor Starter End User Empower
Protection & Metering Remarks
Current Transformer Yes AuCom
Voltage Transformer Yes AuCom EPT
Motor Protection Relay Yes AuCom
RTD Temp Relay No
Ground Fault Protection Built-in
Powermeter No
Analog Metering No
Capacitive voltage indication No
Surge Arrestor No
Protection Codes (Equivalent ANSI)
3 - Checking or Interlocking Relay
27 - Undervoltage
32 - Power Loss
37 - Undercurrent
46 - Current Imbalance
47 - Phase Sequence/Loss
48 - Excess Start Time
49/51 - Time-Overcurrent (Thermal Model)
50 - Instantaneous Overcurrent
50N - Instantaneous Overcurrent (Ground Fault)
50LR - Instantaneous Overcurrent (Locked Rotor)
59 - Overvoltage
66 - Too Many Starts
81 - Mains Frequency
85 - Internal/External Communications
86 - Lock Out Relay
94/95 - External Fault/Code
Extra Electrical Requirements Remarks
LV Panel Light No
Panel Heater Yes
Motor Heater control No
Control Transformer for external device No n/a
LV Transformer for external device No n/a
03
02
01
00 First Issue 13 Jan 2021 AuCom 13 Jan 2021 AuCom
Rev Description Date Prepared Date Approved
AuCom Electronics Ltd | www.aucom.com 3/11
TECHNICAL DATA SHEET
Project Name MHI - Empower Various Project Quote SQ502191
Product L-MVE-0200-V11-SC31-E3-F1-L1-B1-PF1 Client Mitsubishi Heavy Industries
Supplier AuCom MCS GmbH & Co. kG Contractor
Model MVE - Multimotor Starter End User Empower
Heat Dissipation Remarks
During starting 221W 2 starts/hr
Running 78W 2 starts/hr
During stopping 0W Coast to Stop
Environmental Conditions Remarks
Operating -10°C….+60°C, above +50°C with derating
Storage -25°C….+70°C
Altitude ≤ 1000m
Humidity 5% to 95% Relative Humidity
Starter Performance Data Remarks
Mean Time Between Failure (MTBF) 25 years
Mean Time To Repair (MTTR) 5 hours
Expected Life 25 years
Starter Efficiency Data Remarks
Maximum efficiency during Starting 99,98%
Maximum efficiency during Running 99,99% Bypass
Standards IEC Remarks
Cabinet IEC 62 271-200
Earthing Switch IEC 62 271-102
Current Transformer IEC 61 869-1
Voltage Transformer IEC 61 869-2
Degree of Protection IEC 60 529
Semi Conductor IEC 60 747-5-5
Soft Starter (Partial Discharge) IEC 60270
Indicator and Actuators IEC 60073 / NFPA 79
Protection Codes Equivalent to ANSI Codes
03
02
01
00 First Issue 13 Jan 2021 AuCom 13 Jan 2021 AuCom
Rev Description Date Prepared Date Approved
AuCom Electronics Ltd | www.aucom.com 4/11