TA SCAC (R410A 50,60Hz) CSA Colombia IDU CO MFL67986333 20220215
TA SCAC (R410A 50,60Hz) CSA Colombia IDU CO MFL67986333 20220215
Cooling Only
MFL67986333
    Region : Colombia
 Printed in Feb. 15, 2022
Single Indoor Unit                                               General Information
Up
Line
Model
1.
1. Model Line Up
                                                    Model Name
                             Product
                                                      Sales
        Ceiling Cassette 4-Way                     ATNQ40GNLA5
        Ceiling Cassette 4-Way                     ATNQ60GMLA5
        Ceiling Concealed Duct - High Static       ABNQ40GM3A5
        Ceiling Concealed Duct - High Static       ABNQ60GM3A5
        Ceiling Suspended                          AVNQ40GM1A5
        Ceiling Suspended                          AVNQ60GM2A5
                                               2
   Single Indoor Unit
1. ATNQ40GNLA5
2. ATNQ60GMLA5
3. ABNQ40GM3A5
4. ABNQ60GM3A5
5. AVNQ40GM1A5
6. AVNQ60GM2A5
Single Indoor Unit Ceiling Cassette 4-Way                                                                                       Product Data
ATNQ40GNLA5
1.
1. ATNQ40GNLA5
1.1 Specifications
                                                   Category
                                                                                                  Unit               Value
                               Major                                      Minor
              Classification                        Chassis                                         -                  TN
                                                    #1                                              -        220-230-240, 1, 50/60
                                                    #2                                              -                   -
              Power Supply
                                                    Limit Range of Voltage(#1)                     V                187~276
                                                    Limit Range of Voltage(#2)                     V                    -
                                                                                                   kW                 9.99
              Cooling Capacity                      Nominal
                                                                                                  Btu/h              34,100
                                                                                                   kW                   -
              Heating Capacity                      Nominal
                                                                                                  Btu/h                 -
              Power Input(Indoor)                   H/M/L                                          W                    -
              Running Current(Indoor)               H/M/L                                          A                    -
                                                    Type                                            -            2D Turbo Fan
                                                    Air Flow Rate((SH)/H/M/L)                    m³/min       - / 23.0 / 21.0 / 19.0
              Indoor Fan
                                                    Air Flow Rate Range(Min~Max)                 m³/min                 -
                                                    External Static Pressure_Factory Set           Pa                   -
                                                    Type                                            -                BLDC
                                                    Drive                                           -                   -
              Indoor Fan Motor
                                                                                                   W                  124
                                                    Output
                                                                                                  No.                   1
                                                    Rows x Columns x FPI                            -            (2 x 10 x 19)
              Heat Exchanger                        No.                                             -                   1
                                                    Face Area                                      m²                 0.43
                                                    Net(W x H x D)                                mm           840 x 246 x 840
              Dimensions
                                                    Shipping(W x H x D)                           mm           922 x 318 x 917
                                                    Net                                            kg                 25.5
              Weight
                                                    Shipping                                       kg                 29.7
                                                    Color                                           -            Morning Fog
              Exterior
                                                    RAL (Classic)                                   -              RAL 9001
              Air Filter                            Type                                            -                   -
                                                    Fuse                                            -                   O
              Protection Device
                                                    Overload Protector for Fan Motor                -                   -
                                                    Type                                            -                R410A
              Refrigerant
                                                    Control Type                                    -                 EEV
              Drain Pipe(Natural Drainage)          O.D / I.D                                   mm(inch)                -
              Drain Pipe(Drain Pump)                O.D / I.D                                   mm(inch)             32 / 25
                                                    Liquid                                      mm(inch)          Φ9.52 (3/8)
                                                    Gas                                         mm(inch)         Φ15.88 (5/8)
              Pipe Connecting Socket
                                                    Connection Type(Liquid)                         -                 Flare
                                                    Connection Type(Gas)                            -                 Flare
                                                    Cooling ((SH)/H/M/L)                         dB(A)        - / 40.0 / 38.0 / 36.0
              Sound Pressure Level(Indoor Unit)
                                                    Heating ((SH)/H/M/L)                         dB(A)                  -
              Measurement Standard (Pressure Leve
                                                  -                                                 -              ISO 3745
              l)
                                                    Cooling ((SH)/H/M/L)                         dB(A)                  -
              Sound Power Level(Indoor Unit)
                                                    Heating ((SH)/H/M/L)                         dB(A)                  -
              Measurement Standard (Power Level)    -                                               -                   -
              Connecting Cable                      Power and Communication cable(H07RN-F)     mm² × cores         0.75 x 4C
              Power Supply Type to Indoor           -                                               -                   -
                                                    Maximum Fuse Amperes (MFA)                     A                   25
              Electrical Characteristic
                                                    Indoor Fan Motor_Full Load Amperes (FLA)       A                  1.28
                                                                                           4
Single Indoor Unit Ceiling Cassette 4-Way                                                                                                   Product Data
1. ATNQ40GNLA5
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard. Therefore, these values depend on the ambient conditions and
  values are normally higher in actual operation.
                                                                                5
Single Indoor Unit Ceiling Cassette 4-Way                                                                                            Product Data
1. ATNQ40GNLA5
Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
 - Embedded : A kit is provided by default for using this function when the product is manufactured.
 - Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
 - Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
 - Auto Change Over(Single Heat Pump Outdoor Unit)
 - Auto Mode Select(Multi Heat Pump Outdoor Unit)
 - Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard III wired remote controller.
                                                                               6
Single Indoor Unit Ceiling Cassette 4-Way                                                                                                    Product Data
1. ATNQ40GNLA5
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
  (http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
                                                                               7
Single Indoor Unit Ceiling Cassette 4-Way                               Product Data
1. ATNQ40GNLA5
1.4 Dimensions
1.4.1 Product
                                                                    8
Single Indoor Unit Ceiling Cassette 4-Way                                                                                                                                             Product Data
1. ATNQ40GNLA5
1.4.2 Installation Space
                                                                                         ≥ 10(13/32)
                                                          Ceiling                                                                  Ceiling Board
                                                    Ceiling Board
                                                                                                                                                              ≤ 300 (11-13/16)
                                                                        ≥ 1000(39-3/8)                                        ≥ 500(19-11/16)
                                                      ≥ 500(19-11/16)
                                                                                                          A
                                                                                                               1.6 ~ 10.0 kW = 2,000 (78-3/4) ≤ A ≤ 3,600 (141-24/32)
                                                                                                              10.0~14.5 kW = 2,500 (98-7/16) ≤ A ≤ 4,200 (165-11/32)
                                                                                                                                           Unit:mm(inch)
Floor
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
  or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
■ Install certainly the decoration panel. Cool air leakage causes sweating or falling of water-drops.
                                                                                                             9
Single Indoor Unit Ceiling Cassette 4-Way                                              Product Data
1. ATNQ40GNLA5
        Thermistor for
        Evaporator inlet
                                                            Humidity sensor
        temperature
                                              10
Single Indoor Unit Ceiling Cassette 4-Way                                    Product Data
1. ATNQ40GNLA5
                                                         CN_MOTION CN_DUST
  220-240V~ 50/60 Hz
8 7 6 5 4 3 2 1
SW01
MEZ67351818
                                              11
Single Indoor Unit Ceiling Cassette 4-Way                                                                                                                            Product Data
1. ATNQ40GNLA5
                                                                                                 High
Octave Band Sound Pressure Level (0dB = 20µPa)
70
                                                                                                        NC -65
                                                 60
                                                                                                        NC-60
                                                                                                        NC-55
                                                 50
                                                                                                        NC-50
                                                                                                        NC-45
                                                 40
                                                                                                        NC-40
                                                                                                        NC-35
                                                 30
                                                                                                        NC-30
                                                                                                        NC-25
                                                 20
                                                      Approximate
                                                                                                        NC-20
                                                      Hearing
                                                      Threshold
                                                                                                        NC-15
                                                 10
                                                          63     125   250   500   1000   2000 4000   8000
                                                               Octave Band Center Frequency (Hz)
Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
  Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
  (Static pressure mode, used air guide, Room target temperature setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
  Therefore, these values can be increased owing to ambient conditions during operation.
                                                                                                                  12
Single Indoor Unit Ceiling Cassette 4-Way                                                                                                      Product Data
1. ATNQ40GNLA5
                                                                                             2.7m
                                                                                             3.2m
             0.25                                                                 0.25
                                          0.5
                                                                                             2m
                                                                                             2m
Temperature [°C]
              23                                                        23                   2.7m
                                                                                             3.2m
                                                                                             2m
                                                                                             2m
                                 21              21
                                     22          22
                         20                                 20                               1m
                                                                                             1m
                          21
                 21                                          21        21
       22                                                                         22
                                                                                            0m
                                                                                           0m
  5m
  5m    4m
        4m      3m
                3m       2m
                         2m          1m
                                     1m   0m
                                          0m    1m
                                                1m          2m
                                                            2m         3m
                                                                       3m        4m
                                                                                 4m      5m
                                                                                         5m
Note
■ These figures are accordance with normal certain condition and environment.
   (Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
  location, indoor / Heating load, and other obstacles, etc.
                                                                                                    13
Single Indoor Unit Ceiling Cassette 4-Way                                                                                        Product Data
ATNQ60GMLA5
2.
2. ATNQ60GMLA5
2.1 Specifications
                                                   Category
                                                                                                   Unit               Value
                               Major                                      Minor
              Classification                        Chassis                                          -                  TM
                                                    #1                                               -        220-230-240, 1, 50/60
                                                    #2                                               -                   -
              Power Supply
                                                    Limit Range of Voltage(#1)                      V                187~276
                                                    Limit Range of Voltage(#2)                      V                    -
                                                                                                    kW                17.61
              Cooling Capacity                      Nominal
                                                                                                   Btu/h              60,100
                                                                                                    kW                   -
              Heating Capacity                      Nominal
                                                                                                   Btu/h                 -
              Power Input(Indoor)                   H/M/L                                           W                    -
              Running Current(Indoor)               H/M/L                                           A                    -
                                                    Type                                             -            2D Turbo Fan
                                                    Air Flow Rate((SH)/H/M/L)                     m³/min       - / 31.0 / 28.0 / 25.0
              Indoor Fan
                                                    Air Flow Rate Range(Min~Max)                  m³/min                 -
                                                    External Static Pressure_Factory Set            Pa                   -
                                                    Type                                             -                BLDC
                                                    Drive                                            -                   -
              Indoor Fan Motor
                                                                                                    W                  124
                                                    Output
                                                                                                   No.                   1
                                                    Rows x Columns x FPI                             -             2 x 12 x 19
              Heat Exchanger                        No.                                              -                   1
                                                    Face Area                                       m²                 0.53
                                                    Net(W x H x D)                                 mm           840 x 288 x 840
              Dimensions
                                                    Shipping(W x H x D)                            mm           922 x 360 x 917
                                                    Net                                             kg                 28.5
              Weight
                                                    Shipping                                        kg                 33.0
                                                    Color                                            -            Morning Fog
              Exterior
                                                    RAL (Classic)                                    -              RAL 9001
              Air Filter                            Type                                             -                   -
                                                    Fuse                                             -                   O
              Protection Device
                                                    Overload Protector for Fan Motor                 -                   -
                                                    Type                                             -                R410A
              Refrigerant
                                                    Control Type                                     -                 EEV
              Drain Pipe(Natural Drainage)          O.D / I.D                                    mm(inch)                -
              Drain Pipe(Drain Pump)                O.D / I.D                                    mm(inch)             32 / 25
                                                    Liquid                                       mm(inch)          Φ9.52 (3/8)
                                                    Gas                                          mm(inch)         Φ19.05 (3/4)
              Pipe Connecting Socket
                                                    Connection Type(Liquid)                          -                 Flare
                                                    Connection Type(Gas)                             -                 Flare
                                                    Cooling ((SH)/H/M/L)                          dB(A)        - / 47.0 / 45.0 / 42.0
              Sound Pressure Level(Indoor Unit)
                                                    Heating ((SH)/H/M/L)                          dB(A)                  -
              Measurement Standard (Pressure Leve
                                                  -                                                  -              ISO 3745
              l)
                                                    Cooling ((SH)/H/M/L)                          dB(A)                  -
              Sound Power Level(Indoor Unit)
                                                    Heating ((SH)/H/M/L)                          dB(A)                  -
              Measurement Standard (Power Level)    -                                                -                   -
              Connecting Cable                      Power and Communication cable(H07RN-F)      mm² × cores         0.75 x 4C
              Power Supply Type to Indoor           -                                                -                   -
                                                    Maximum Fuse Amperes (MFA)                      A                   40
              Electrical Characteristic
                                                    Indoor Fan Motor_Full Load Amperes (FLA)        A                  1.28
                                                                                           14
Single Indoor Unit Ceiling Cassette 4-Way                                                                                                   Product Data
2. ATNQ60GMLA5
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard. Therefore, these values depend on the ambient conditions and
  values are normally higher in actual operation.
                                                                                15
Single Indoor Unit Ceiling Cassette 4-Way                                                                                            Product Data
2. ATNQ60GMLA5
Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
 - Embedded : A kit is provided by default for using this function when the product is manufactured.
 - Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
 - Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
 - Auto Change Over(Single Heat Pump Outdoor Unit)
 - Auto Mode Select(Multi Heat Pump Outdoor Unit)
 - Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard III wired remote controller.
                                                                              16
Single Indoor Unit Ceiling Cassette 4-Way                                                                                                  Product Data
2. ATNQ60GMLA5
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
  (http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
                                                                               17
Single Indoor Unit Ceiling Cassette 4-Way                                          Product Data
2. ATNQ60GMLA5
2.4 Dimensions
2.4.1 Product
PT-M*HW0
                                                                   18
Single Indoor Unit Ceiling Cassette 4-Way                                                                                                                                             Product Data
2. ATNQ60GMLA5
2.4.2 Installation Space
                                                                                         ≥ 10(13/32)
                                                          Ceiling                                                                  Ceiling Board
                                                    Ceiling Board
                                                                                                                                                              ≤ 300 (11-13/16)
                                                                        ≥ 1000(39-3/8)                                        ≥ 500(19-11/16)
                                                      ≥ 500(19-11/16)
                                                                                                          A
                                                                                                               1.6 ~ 10.0 kW = 2,000 (78-3/4) ≤ A ≤ 3,600 (141-24/32)
                                                                                                              10.0~14.5 kW = 2,500 (98-7/16) ≤ A ≤ 4,200 (165-11/32)
                                                                                                                                           Unit:mm(inch)
Floor
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
  or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
■ Install certainly the decoration panel. Cool air leakage causes sweating or falling of water-drops.
                                                                                                            19
Single Indoor Unit Ceiling Cassette 4-Way                                              Product Data
2. ATNQ60GMLA5
        Thermistor for
        Evaporator inlet
                                                            Humidity sensor
        temperature
                                              20
Single Indoor Unit Ceiling Cassette 4-Way                                    Product Data
2. ATNQ60GMLA5
                                                         CN_MOTION CN_DUST
  220-240V~ 50/60 Hz
8 7 6 5 4 3 2 1
SW01
MEZ67351818
                                              21
    Single Indoor Unit Ceiling Cassette 4-Way                                                                                                            Product Data
2. ATNQ60GMLA5
                                     70
Sound Pressure Level (dB re 20Pa )
                                                                                           NC-65
                                     60
                                                                                           NC-60
                                                                                           NC-55
                                     50
                                                                                           NC-50
                                                                                           NC-45
                                     40
                                                                                           NC-40
                                                                                           NC-35
                                     30
                                                                                           NC-30
                                     20                                                    NC-25
                                          Approximate
                                                                                           NC-20
                                          Hearing
                                          Threshold                                        NC-15
                                     10
                                              63     125   250   500   1000 2000 4000 8000
                                                   Octave Band Center Frequency (Hz)
    Note
    ■ Sound measured at some distance away from the center of the unit.
    ■ Data is valid at free field condition.
    ■ Reference accoustic pressure 0dB = 20μPa.
    ■ Data is valid at nominal operation condition.
      Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
    ■ Sound levels can be increased in accordance with installation and operating conditions.
      (Static pressure mode, used air guide, Room target temperature setting, etc)
    ■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
      Therefore, these values can be increased owing to ambient conditions during operation.
                                                                                                      22
Single Indoor Unit Ceiling Cassette 4-Way                                                                                                      Product Data
2. ATNQ60GMLA5
                                                    0.5
                                                                                                          2m
                                                                                                          2m
       0.25                         3.5                              3.5                         0.25
                                                    0.25
                             3.0                                            3.0
              0.25                                                                        0.25            1m
                                                                                                          1m
                0.5                                                                       0.5
                                                                                  2.5 1.5
              1.0     2.5                                              0.25
                                  0.25                                                 2.0 1.0
                                                                                                           0m
                                                                                                          0m
  5m
  5m          4m
              4m      3m
                      3m          2m      1m        0m
                                                    0m      1m
                                                            1m         2m          3m
                                                                                   3m      4m           5m
                                                                                                        5m
  Temperature [°C]
                        24                                                         24                     3.2m
                                                                                                          3.2m
                             23                                            23                             3m
    22                                                                                            22
                                               22          22                                             2m
                                                                                                          2m
                                          21                    21
                                   19                                  19
                                                                                                          1m
                                                                                                          1m
                22    21     20                                                   20 21   22
                                                                                                       0m
                                                                                                      0m
  5m
  5m          4m      3m
                      3m          2m      1m        0m
                                                    0m      1m
                                                            1m        2m          3m
                                                                                  3m       4m       5m
                                                                                                    5m
Note
■ These figures are accordance with normal certain condition and environment.
   (Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
  location, indoor / Heating load, and other obstacles, etc.
                                                                                                                 23
Single Indoor Unit Ceiling Concealed Duct - High Static                                                                          Product Data
ABNQ40GM3A5
3.
3. ABNQ40GM3A5
3.1 Specifications
                                                   Category
                                                                                                   Unit               Value
                               Major                                      Minor
              Classification                        Chassis                                          -                  M3
                                                    #1                                               -        220-230-240, 1, 50/60
                                                    #2                                               -                   -
              Power Supply
                                                    Limit Range of Voltage(#1)                      V                187~276
                                                    Limit Range of Voltage(#2)                      V                    -
                                                                                                    kW                 9.99
              Cooling Capacity                      Nominal
                                                                                                   Btu/h              34,100
                                                                                                    kW                   -
              Heating Capacity                      Nominal
                                                                                                   Btu/h                 -
              Power Input(Indoor)                   H/M/L                                           W                    -
              Running Current(Indoor)               H/M/L                                           A                    -
                                                    Type                                             -               Sirocco
                                                    Air Flow Rate((SH)/H/M/L)                     m³/min       - / 30.0 / 25.0 / 20.0
              Indoor Fan
                                                    Air Flow Rate Range(Min~Max)                  m³/min            16.0~39.0
                                                    External Static Pressure_Factory Set            Pa                   6
                                                    Type                                             -                BLDC
                                                    Drive                                            -                   -
              Indoor Fan Motor
                                                                                                    W                  154
                                                    Output
                                                                                                   No.                   1
                                                    Rows x Columns x FPI                             -            (3 x 16 x 18)
              Heat Exchanger                        No.                                              -                   1
                                                    Face Area                                       m²                 0.36
                                                    Net(W x H x D)                                 mm           1,250 x 360 x 700
              Dimensions
                                                    Shipping(W x H x D)                            mm           1,450 x 428 x 773
                                                    Net                                             kg                 36.0
              Weight
                                                    Shipping                                        kg                 42.5
                                                    Color                                            -                   -
              Exterior
                                                    RAL (Classic)                                    -                   -
              Air Filter                            Type                                             -                   -
                                                    Fuse                                             -                   O
              Protection Device
                                                    Overload Protector for Fan Motor                 -                   -
                                                    Type                                             -                R410A
              Refrigerant
                                                    Control Type                                     -                 EEV
              Drain Pipe(Natural Drainage)          O.D / I.D                                    mm(inch)             32 / 25
              Drain Pipe(Drain Pump)                O.D / I.D                                    mm(inch)                -
                                                    Liquid                                       mm(inch)          Φ9.52 (3/8)
                                                    Gas                                          mm(inch)         Φ15.88 (5/8)
              Pipe Connecting Socket
                                                    Connection Type(Liquid)                          -                 Flare
                                                    Connection Type(Gas)                             -                 Flare
                                                    Cooling ((SH)/H/M/L)                          dB(A)        - / 36.0 / 33.0 / 31.0
              Sound Pressure Level(Indoor Unit)
                                                    Heating ((SH)/H/M/L)                          dB(A)                  -
              Measurement Standard (Pressure Leve
                                                  -                                                  -              ISO 3745
              l)
                                                    Cooling ((SH)/H/M/L)                          dB(A)                  -
              Sound Power Level(Indoor Unit)
                                                    Heating ((SH)/H/M/L)                          dB(A)                  -
              Measurement Standard (Power Level)    -                                                -                   -
              Connecting Cable                      Power and Communication cable(H07RN-F)      mm² × cores         0.75 x 4C
              Power Supply Type to Indoor           -                                                -                   -
                                                    Maximum Fuse Amperes (MFA)                      A                   25
              Electrical Characteristic
                                                    Indoor Fan Motor_Full Load Amperes (FLA)        A                   1.9
                                                                                           24
Single Indoor Unit Ceiling Concealed Duct - High Static                                                                                     Product Data
3. ABNQ40GM3A5
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard. Therefore, these values depend on the ambient conditions and
  values are normally higher in actual operation.
                                                                                25
Single Indoor Unit Ceiling Concealed Duct - High Static                                                                                       Product Data
3. ABNQ40GM3A5
Note
■ O : Applied, X : Not applied, Embedded : Included with product.
 - Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
 - Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ Selecting a wireless remote controller in case of ducted type indoor units requires either a connection to the wired remote controller (Standard II)
   or an IR receiver accessory to be connected to the duct in order to receive the signal.
■ 'Auto Mode' varies depending on the outdoor unit type.
 - Auto Change Over(Single Heat Pump Outdoor Unit)
 - Auto Mode Select(Multi Heat Pump Outdoor Unit)
 - Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : It is included by default when the product is manufactured.
■ *** : This functions need to connect to the Standard III wired remote controller.
                                                                                 26
Single Indoor Unit Ceiling Concealed Duct - High Static                                                                                       Product Data
3. ABNQ40GM3A5
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant, Embedded : Included with product.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ Selecting a wireless remote controller in case of ducted type indoor units requires either a connection to the wired remote controller (Standard II)
  or an IR receiver accessory to be connected to the duct in order to receive the signal.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
  (http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
                                                                                 27
Single Indoor Unit Ceiling Concealed Duct - High Static   Product Data
3. ABNQ40GM3A5
3.4 Dimensions
3.4.1 Product
   DWG No. : TBB36535401_rev01
   Chassis Code : M3
                                           28
Single Indoor Unit Ceiling Concealed Duct - High Static                                                                                        Product Data
3. ABNQ40GM3A5
3.4.2 Installation Space
       Top view
       [Unit: mm(inch)]
                                                                       Air inlet vents
                                                                                         ≥ 1,000 (39-3/8)
                         ≥ 600 x 600                                                                                        Inspection hole(1)
                                                       (23-5/8)                                             (23-5/8)
                       (23-5/8 x 23-5/8)                           Air outlet vents                                              600 x 600
                                                                                                                             (23-5/8 x 23-5/8)
Front
         If distance between false ceiling and actual ceiling is more than 100cm (39-3/8 inch), the number of inspection hole
         could be decreased to 1. But if that is less than 20cm (7-7/8 inch), the hole size should be more than size of Indoor Unit.
       Front view
       [Unit: mm(inch)]
                                                                                                                                              ≥ 20 (25/32)
                                                                                                                                                      Ceiling
                                  B(Min)
        A(Min)                                                                                                     Service Space
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
  or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
                                                                                 29
Single Indoor Unit Ceiling Concealed Duct - High Static                                  Product Data
3. ABNQ40GM3A5
        Thermistor for
        evaporator inlet
        temperature
                                                 30
Single Indoor Unit Ceiling Concealed Duct - High Static   Product Data
3. ABNQ40GM3A5
                                           31
 Single Indoor Unit Ceiling Concealed Duct - High Static                                                                                                    Product Data
3. ABNQ40GM3A5
                                                 70
Octave Band Sound Pressure Level (0dB = 20μPa)
                                                                                                              NC-65
                                                 60
                                                                                                              NC-60
                                                                                                              NC-55
                                                 50
                                                                                                              NC-50
                                                                                                              NC-45
                                                 40
                                                                                                              NC-40
                                                                                                              NC-35
                                                 30
                                                                                                              NC-30
                                                                                                              NC-25
                                                 20
                                                      Approximate
                                                                                                              NC-20
                                                      Hearing
                                                      Threshold
                                                                                                              NC-15
                                                 10
                                                          63        125    250   500   1000   2000   4000   8000
                                                               Octave Band Center Frequency (Hz)
 Note
 ■ Sound measured at some distance away from the center of the unit.
 ■ Data is valid at free field condition.
 ■ Reference accoustic pressure 0dB = 20μPa.
 ■ Data is valid at nominal operation condition. Refer to the Model Specifications for nominal conditions (Power source and Ambient temperature, etc)
 ■ Sound levels can be increased in accordance with installation and operating conditions.
   (Static pressure mode, used air guide, Room target temperature setting, etc)
 ■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
   Therefore, these values can be increased owing to ambient conditions during operation.
                                                                                                                      32
Single Indoor Unit Ceiling Concealed Duct - High Static                                                                                    Product Data
3. ABNQ40GM3A5
Note
■ Each dash line represents for each 100 RPM step
■ If operation range is out of auto E.S.P setting range, air flow rate should be adjusted manually by wired remotecontroller. (ESP Set Value = RPM / 10)
  For more information, please see the installation manual.
■ The above P-Q Curve shows available E.S.P. range. If the E.S.P value is out of min/max RPM at desired air flow, indoor components could be failed
  and performance would be decreased.
■ Automatic constant air volume is a function that controls air volume automatically when installation, and the air volume is not set automatically
  during operation.
                                                                               33
Single Indoor Unit Ceiling Concealed Duct - High Static                                                                          Product Data
ABNQ60GM3A5
4.
4. ABNQ60GM3A5
4.1 Specifications
                                                   Category
                                                                                                   Unit               Value
                               Major                                      Minor
              Classification                        Chassis                                          -                  M3
                                                    #1                                               -        220-230-240, 1, 50/60
                                                    #2                                               -                   -
              Power Supply
                                                    Limit Range of Voltage(#1)                      V                187~276
                                                    Limit Range of Voltage(#2)                      V                    -
                                                                                                    kW                17.61
              Cooling Capacity                      Nominal
                                                                                                   Btu/h              60,100
                                                                                                    kW                   -
              Heating Capacity                      Nominal
                                                                                                   Btu/h                 -
              Power Input(Indoor)                   H/M/L                                           W                    -
              Running Current(Indoor)               H/M/L                                           A                    -
                                                    Type                                             -               Sirocco
                                                    Air Flow Rate((SH)/H/M/L)                     m³/min       - / 50.0 / 45.0 / 40.0
              Indoor Fan
                                                    Air Flow Rate Range(Min~Max)                  m³/min            32.0~65.0
                                                    External Static Pressure_Factory Set            Pa                   6
                                                    Type                                             -                BLDC
                                                    Drive                                            -                   -
              Indoor Fan Motor
                                                                                                    W                  400
                                                    Output
                                                                                                   No.                   1
                                                    Rows x Columns x FPI                             -            (3 x 16 x 18)
              Heat Exchanger                        No.                                              -                   1
                                                    Face Area                                       m²                 0.36
                                                    Net(W x H x D)                                 mm           1,250 x 360 x 700
              Dimensions
                                                    Shipping(W x H x D)                            mm           1,450 x 428 x 773
                                                    Net                                             kg                 41.0
              Weight
                                                    Shipping                                        kg                 47.0
                                                    Color                                            -                   -
              Exterior
                                                    RAL (Classic)                                    -                   -
              Air Filter                            Type                                             -                   -
                                                    Fuse                                             -                   O
              Protection Device
                                                    Overload Protector for Fan Motor                 -                   -
                                                    Type                                             -                R410A
              Refrigerant
                                                    Control Type                                     -                 EEV
              Drain Pipe(Natural Drainage)          O.D / I.D                                    mm(inch)             32 / 25
              Drain Pipe(Drain Pump)                O.D / I.D                                    mm(inch)                -
                                                    Liquid                                       mm(inch)          Φ9.52 (3/8)
                                                    Gas                                          mm(inch)         Φ19.05 (3/4)
              Pipe Connecting Socket
                                                    Connection Type(Liquid)                          -                 Flare
                                                    Connection Type(Gas)                             -                 Flare
                                                    Cooling ((SH)/H/M/L)                          dB(A)        - / 46.0 / 44.0 / 42.0
              Sound Pressure Level(Indoor Unit)
                                                    Heating ((SH)/H/M/L)                          dB(A)                  -
              Measurement Standard (Pressure Leve
                                                  -                                                  -              ISO 3745
              l)
                                                    Cooling ((SH)/H/M/L)                          dB(A)                  -
              Sound Power Level(Indoor Unit)
                                                    Heating ((SH)/H/M/L)                          dB(A)                  -
              Measurement Standard (Power Level)    -                                                -                   -
              Connecting Cable                      Power and Communication cable(H07RN-F)      mm² × cores         0.75 x 4C
              Power Supply Type to Indoor           -                                                -                   -
                                                    Maximum Fuse Amperes (MFA)                      A                   40
              Electrical Characteristic
                                                    Indoor Fan Motor_Full Load Amperes (FLA)        A                  2.50
                                                                                           34
Single Indoor Unit Ceiling Concealed Duct - High Static                                                                                     Product Data
4. ABNQ60GM3A5
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard. Therefore, these values depend on the ambient conditions and
  values are normally higher in actual operation.
                                                                                35
Single Indoor Unit Ceiling Concealed Duct - High Static                                                                                       Product Data
4. ABNQ60GM3A5
Note
■ O : Applied, X : Not applied, Embedded : Included with product.
 - Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
 - Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ Selecting a wireless remote controller in case of ducted type indoor units requires either a connection to the wired remote controller (Standard II)
   or an IR receiver accessory to be connected to the duct in order to receive the signal.
■ 'Auto Mode' varies depending on the outdoor unit type.
 - Auto Change Over(Single Heat Pump Outdoor Unit)
 - Auto Mode Select(Multi Heat Pump Outdoor Unit)
 - Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : It is included by default when the product is manufactured.
■ *** : This functions need to connect to the Standard III wired remote controller.
                                                                                 36
Single Indoor Unit Ceiling Concealed Duct - High Static                                                                                       Product Data
4. ABNQ60GM3A5
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant, Embedded : Included with product.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ Selecting a wireless remote controller in case of ducted type indoor units requires either a connection to the wired remote controller (Standard II)
  or an IR receiver accessory to be connected to the duct in order to receive the signal.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
  (http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
                                                                                 37
Single Indoor Unit Ceiling Concealed Duct - High Static   Product Data
4. ABNQ60GM3A5
4.4 Dimensions
4.4.1 Product
   DWG No. : TBB36535401_rev01
   Chassis Code : M3
                                           38
Single Indoor Unit Ceiling Concealed Duct - High Static                                                                                        Product Data
4. ABNQ60GM3A5
4.4.2 Installation Space
       Top view
       [Unit: mm(inch)]
                                                                       Air inlet vents
                                                                                         ≥ 1,000 (39-3/8)
                         ≥ 600 x 600                                                                                        Inspection hole(1)
                                                       (23-5/8)                                             (23-5/8)
                       (23-5/8 x 23-5/8)                           Air outlet vents                                              600 x 600
                                                                                                                             (23-5/8 x 23-5/8)
Front
         If distance between false ceiling and actual ceiling is more than 100cm (39-3/8 inch), the number of inspection hole
         could be decreased to 1. But if that is less than 20cm (7-7/8 inch), the hole size should be more than size of Indoor Unit.
       Front view
       [Unit: mm(inch)]
                                                                                                                                              ≥ 20 (25/32)
                                                                                                                                                      Ceiling
                                  B(Min)
        A(Min)                                                                                                     Service Space
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
  or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
                                                                                 39
Single Indoor Unit Ceiling Concealed Duct - High Static                                  Product Data
4. ABNQ60GM3A5
        Thermistor for
        evaporator inlet
        temperature
                                                 40
Single Indoor Unit Ceiling Concealed Duct - High Static   Product Data
4. ABNQ60GM3A5
                                           41
 Single Indoor Unit Ceiling Concealed Duct - High Static                                                                                                    Product Data
4. ABNQ60GM3A5
                                                 70
Octave Band Sound Pressure Level (0dB = 20μPa)
                                                                                                              NC-65
                                                 60
                                                                                                              NC-60
                                                                                                              NC-55
                                                 50
                                                                                                              NC-50
                                                                                                              NC-45
                                                 40
                                                                                                              NC-40
                                                                                                              NC-35
                                                 30
                                                                                                              NC-30
                                                                                                              NC-25
                                                 20
                                                      Approximate
                                                                                                              NC-20
                                                      Hearing
                                                      Threshold
                                                                                                              NC-15
                                                 10
                                                          63        125    250   500   1000   2000   4000   8000
                                                               Octave Band Center Frequency (Hz)
 Note
 ■ Sound measured at some distance away from the center of the unit.
 ■ Data is valid at free field condition.
 ■ Reference accoustic pressure 0dB = 20μPa.
 ■ Data is valid at nominal operation condition. Refer to the Model Specifications for nominal conditions (Power source and Ambient temperature, etc)
 ■ Sound levels can be increased in accordance with installation and operating conditions.
   (Static pressure mode, used air guide, Room target temperature setting, etc)
 ■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
   Therefore, these values can be increased owing to ambient conditions during operation.
                                                                                                                      42
Single Indoor Unit Ceiling Concealed Duct - High Static                                                                                    Product Data
4. ABNQ60GM3A5
Note
■ Each dash line represents for each 100 RPM step
■ If operation range is out of auto E.S.P setting range, air flow rate should be adjusted manually by wired remotecontroller. (ESP Set Value = RPM / 10)
  For more information, please see the installation manual.
■ The above P-Q Curve shows available E.S.P. range. If the E.S.P value is out of min/max RPM at desired air flow, indoor components could be failed
  and performance would be decreased.
■ Automatic constant air volume is a function that controls air volume automatically when installation, and the air volume is not set automatically
  during operation.
                                                                               43
Single Indoor Unit Ceiling Suspended                                                                                             Product Data
AVNQ40GM1A5
5.
5. AVNQ40GM1A5
5.1 Specifications
                                                   Category
                                                                                                   Unit               Value
                               Major                                      Minor
              Classification                        Chassis                                          -                 VM1
                                                    #1                                               -        220-230-240, 1, 50/60
                                                    #2                                               -                   -
              Power Supply
                                                    Limit Range of Voltage(#1)                      V                187~276
                                                    Limit Range of Voltage(#2)                      V                    -
                                                                                                    kW                 9.99
              Cooling Capacity                      Nominal
                                                                                                   Btu/h              34,100
                                                                                                    kW                   -
              Heating Capacity                      Nominal
                                                                                                   Btu/h                 -
              Power Input(Indoor)                   H/M/L                                           W                    -
              Running Current(Indoor)               H/M/L                                           A                    -
                                                    Type                                             -           Cross Flow Fan
                                                    Air Flow Rate((SH)/H/M/L)                     m³/min       - / 20.0 / 18.0 / 16.0
              Indoor Fan
                                                    Air Flow Rate Range(Min~Max)                  m³/min                 -
                                                    External Static Pressure_Factory Set            Pa                   -
                                                    Type                                             -                BLDC
                                                    Drive                                            -                   -
              Indoor Fan Motor
                                                                                                    W                  85.9
                                                    Output
                                                                                                   No.                   1
                                                    Rows x Columns x FPI                             -            (3 x 18 x 18)
              Heat Exchanger                        No.                                              -                   1
                                                    Face Area                                       m²                 0.31
                                                    Net(W x H x D)                                 mm           1,200 x 235 x 690
              Dimensions
                                                    Shipping(W x H x D)                            mm           1,315 x 320 x 772
                                                    Net                                             kg                 28.4
              Weight
                                                    Shipping                                        kg                 34.4
                                                    Color                                            -            Morning Fog
              Exterior
                                                    RAL (Classic)                                    -              RAL 9001
              Air Filter                            Type                                             -                   -
                                                    Fuse                                             -                   O
              Protection Device
                                                    Overload Protector for Fan Motor                 -                   -
                                                    Type                                             -                R410A
              Refrigerant
                                                    Control Type                                     -                 EEV
              Drain Pipe(Natural Drainage)          O.D / I.D                                    mm(inch)            21.5 / 16
              Drain Pipe(Drain Pump)                O.D / I.D                                    mm(inch)                -
                                                    Liquid                                       mm(inch)          Φ9.52 (3/8)
                                                    Gas                                          mm(inch)         Φ15.88 (5/8)
              Pipe Connecting Socket
                                                    Connection Type(Liquid)                          -                 Flare
                                                    Connection Type(Gas)                             -                 Flare
                                                    Cooling ((SH)/H/M/L)                          dB(A)        - / 47.0 / 45.0 / 42.0
              Sound Pressure Level(Indoor Unit)
                                                    Heating ((SH)/H/M/L)                          dB(A)                  -
              Measurement Standard (Pressure Leve
                                                  -                                                  -              ISO 3745
              l)
                                                    Cooling ((SH)/H/M/L)                          dB(A)                  -
              Sound Power Level(Indoor Unit)
                                                    Heating ((SH)/H/M/L)                          dB(A)                  -
              Measurement Standard (Power Level)    -                                                -                   -
              Connecting Cable                      Power and Communication cable(H07RN-F)      mm² × cores         0.75 x 4C
              Power Supply Type to Indoor           -                                                -                   -
                                                    Maximum Fuse Amperes (MFA)                      A                   25
              Electrical Characteristic
                                                    Indoor Fan Motor_Full Load Amperes (FLA)        A                    1
                                                                                           44
Single Indoor Unit Ceiling Suspended                                                                                                        Product Data
5. AVNQ40GM1A5
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard. Therefore, these values depend on the ambient conditions and
  values are normally higher in actual operation.
                                                                                45
Single Indoor Unit Ceiling Suspended                                                                                                 Product Data
5. AVNQ40GM1A5
Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
 - Embedded : A kit is provided by default for using this function when the product is manufactured.
 - Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
 - Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
 - Auto Change Over(Single Heat Pump Outdoor Unit)
 - Auto Mode Select(Multi Heat Pump Outdoor Unit)
 - Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard III wired remote controller.
                                                                              46
Single Indoor Unit Ceiling Suspended                                                                                                       Product Data
5. AVNQ40GM1A5
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
  (http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
                                                                              47
Single Indoor Unit Ceiling Suspended        Product Data
5. AVNQ40GM1A5
5.4 Dimensions
5.4.1 Product
   DWG No. : TAZ35326401_Rev01
   Chassis code : VM1
                                       48
Single Indoor Unit Ceiling Suspended                                                                                                           Product Data
5. AVNQ40GM1A5
5.4.2 Installation Space
[Unit: mm(inch)]
≥ 10 (13/32)
≥ 300 (11-13/16)
                                                                                                                  ≥ 2500 (98-3/7)
                                                                       Floor
≥ 700(27-9/16) ≥ 700(27-9/16)
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
  or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
                                                                                 49
Single Indoor Unit Ceiling Suspended                                                     Product Data
5. AVNQ40GM1A5
Strainer
                                              50
Single Indoor Unit Ceiling Suspended                        Product Data
5. AVNQ40GM1A5
                                                     CN1
                                            CN_PTC
MEZ67351819
                                       51
Single Indoor Unit Ceiling Suspended                                                                                                                                       Product Data
5. AVNQ40GM1A5
                                                                                                       High
                                                                                                     ▲ Mid
Octave Band Sound Pressure Level (0dB = 20μPa)
70 Low
                                                                                                             NC-65
                                                 60
                                                                                                             NC-60
                                                                                                             NC-55
                                                 50
NC-50
                                                                                                             NC-45
                                                 40
NC-40
                                                                                                             NC-35
                                                 30
NC-30
20 NC-25
                                                      Approximate
                                                                                                             NC-20
                                                      Hearing
                                                      Threshold
                                                                                                             NC-15
                                                 10
                                                           63       125   250   500   1000   2000   4000   8000
                                                                     Octave Band Center Frequency (Hz)
Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
  Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions. (Static pressure mode, used air guide, Room target temperature
setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
  Therefore, these values can be increased owing to ambient conditions during operation.
                                                                                                                        52
      Single Indoor Unit Ceiling Suspended                                                                                                           Product Data
5. AVNQ40GM1A5
1.5 2m
1.0
                                                                            1m
              0.5
             0.25
                                                                            0m
10m    8m
       8m            7m        6m
                               6m     5m    4m
                                            4m   3m      2m
                                                          2m      1m      0m
          Temperature [°C]
                                       18                                   2.7m
                                                                            2.7m
                          20    19
                  21
         22
                                                                            2m
         23
         24
                    25
                          26                                                1m
                                                                            0m
10m    8m
       8m            7m        6m
                               6m     5m    4m
                                            4m   3m      2m
                                                          2m      1m      0m
      Note
      ■ These figures are accordance with normal certain condition and environment.
         (Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
      ■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
        location, indoor / Heating load, and other obstacles, etc.
                                                                                        53
Single Indoor Unit Ceiling Suspended                                                                                             Product Data
AVNQ60GM2A5
6.
6. AVNQ60GM2A5
6.1 Specifications
                                                   Category
                                                                                                   Unit               Value
                               Major                                      Minor
              Classification                        Chassis                                          -                 VM2
                                                    #1                                               -        220-230-240, 1, 50/60
                                                    #2                                               -                   -
              Power Supply
                                                    Limit Range of Voltage(#1)                      V                187~276
                                                    Limit Range of Voltage(#2)                      V                    -
                                                                                                    kW                17.61
              Cooling Capacity                      Nominal
                                                                                                   Btu/h              60,100
                                                                                                    kW                   -
              Heating Capacity                      Nominal
                                                                                                   Btu/h                 -
              Power Input(Indoor)                   H/M/L                                           W                    -
              Running Current(Indoor)               H/M/L                                           A                    -
                                                    Type                                             -           Cross Flow Fan
                                                    Air Flow Rate((SH)/H/M/L)                     m³/min       - / 30.0 / 25.0 / 20.0
              Indoor Fan
                                                    Air Flow Rate Range(Min~Max)                  m³/min                 -
                                                    External Static Pressure_Factory Set            Pa                   -
                                                    Type                                             -                BLDC
                                                    Drive                                            -                   -
              Indoor Fan Motor
                                                                                                    W                  125
                                                    Output
                                                                                                   No.                   1
                                                    Rows x Columns x FPI                             -            (3 x 18 x 18)
              Heat Exchanger                        No.                                              -                   1
                                                    Face Area                                       m²                 0.46
                                                    Net(W x H x D)                                 mm           1,600 x 235 x 690
              Dimensions
                                                    Shipping(W x H x D)                            mm           1,715 x 320 x 772
                                                    Net                                             kg                 36.9
              Weight
                                                    Shipping                                        kg                 43.7
                                                    Color                                            -            Morning Fog
              Exterior
                                                    RAL (Classic)                                    -              RAL 9001
              Air Filter                            Type                                             -                   -
                                                    Fuse                                             -                   O
              Protection Device
                                                    Overload Protector for Fan Motor                 -                   -
                                                    Type                                             -                R410A
              Refrigerant
                                                    Control Type                                     -                 EEV
              Drain Pipe(Natural Drainage)          O.D / I.D                                    mm(inch)            21.5 / 16
              Drain Pipe(Drain Pump)                O.D / I.D                                    mm(inch)                -
                                                    Liquid                                       mm(inch)          Φ9.52 (3/8)
                                                    Gas                                          mm(inch)         Φ19.05 (3/4)
              Pipe Connecting Socket
                                                    Connection Type(Liquid)                          -                 Flare
                                                    Connection Type(Gas)                             -                 Flare
                                                    Cooling ((SH)/H/M/L)                          dB(A)        - / 48.0 / 44.0 / 40.0
              Sound Pressure Level(Indoor Unit)
                                                    Heating ((SH)/H/M/L)                          dB(A)                  -
              Measurement Standard (Pressure Leve
                                                  -                                                  -              ISO 3745
              l)
                                                    Cooling ((SH)/H/M/L)                          dB(A)                  -
              Sound Power Level(Indoor Unit)
                                                    Heating ((SH)/H/M/L)                          dB(A)                  -
              Measurement Standard (Power Level)    -                                                -                   -
              Connecting Cable                      Power and Communication cable(H07RN-F)      mm² × cores         0.75 x 4C
              Power Supply Type to Indoor           -                                                -                   -
                                                    Maximum Fuse Amperes (MFA)                      A                   40
              Electrical Characteristic
                                                    Indoor Fan Motor_Full Load Amperes (FLA)        A                  1.47
                                                                                           54
Single Indoor Unit Ceiling Suspended                                                                                                        Product Data
6. AVNQ60GM2A5
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national code. And “Electric characteristics” should be considered for electrical work and design.
■ Especially the power cable and circuit breaker should be selected in accordance with that.
■ Sound Level Values are measured at Noise Measuring chamber accordance with standard. Therefore, these values depend on the ambient conditions and
  values are normally higher in actual operation.
                                                                                55
Single Indoor Unit Ceiling Suspended                                                                                                 Product Data
6. AVNQ60GM2A5
Note
■ O : Applied, X : Not Applied, - : Unconfirmed or irrelevant
 - Embedded : A kit is provided by default for using this function when the product is manufactured.
 - Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
 - Accessory line-ups varies by region, so check your local catalogue or local sales material.
■ Some functions can be limited by remote controller.
■ In case of cassette type indoor units, Plasma kit and Auto Elevation Grille functions are not applicable at the same time.
■ 'Auto Mode' varies depending on the outdoor unit type.
 - Auto Change Over(Single Heat Pump Outdoor Unit)
 - Auto Mode Select(Multi Heat Pump Outdoor Unit)
 - Auto Intensity Control(Cooling Only Outdoor Unit)
■ * : These functions need to connect the wired remote controller.
■ ** : This functions need to connect to the Standard III wired remote controller.
                                                                              56
Single Indoor Unit Ceiling Suspended                                                                                                       Product Data
6. AVNQ60GM2A5
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant.
■ * : Some advanced functions controlled by individual controller cannot be operated.
■ If there is a difference in development time between the product and the remote controller, some functions cannot be operated.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
  (http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
                                                                              57
Single Indoor Unit Ceiling Suspended        Product Data
6. AVNQ60GM2A5
6.4 Dimensions
6.4.1 Product
   DWG No. : TAZ35266401_Rev01
   Chassis code : VM2
                                       58
Single Indoor Unit Ceiling Suspended                                                                                                           Product Data
6. AVNQ60GM2A5
6.4.2 Installation Space
[Unit: mm(inch)]
≥ 10 (13/32)
≥ 300 (11-13/16)
                                                                                                                  ≥ 2500 (98-3/7)
                                                                       Floor
≥ 700(27-9/16) ≥ 700(27-9/16)
Note
■ Places where products are installed should not be any obstacles to the air circulation or installation. Ensure the spaces from the wall, ceiling,
  or other obstacles.
■ According to type of indoor unit, external appearance or installed structure could be different.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
                                                                                 59
Single Indoor Unit Ceiling Suspended                                                          Product Data
6. AVNQ60GM2A5
                                                                 Humid sensor
         Thermistor for
        evaporator outlet
          temperature
                                                                       Liquid pipe connection port
                                                                       (flare connection)
                            Capillary Tube
Strainer
                                                      60
Single Indoor Unit Ceiling Suspended                        Product Data
6. AVNQ60GM2A5
                                                     CN1
                                            CN_PTC
MEZ67351819
                                       61
Single Indoor Unit Ceiling Suspended                                                                                                                                        Product Data
6. AVNQ60GM2A5
                                                 80
                                                                                                           ■ High
                                                                                                           ▲ Middle
                                                 75                                                        ● Low
                                                 70
Octave Band Sound Pressure Level (dB = 20μPa )
                                                 65
                                                                                                                NC-65
                                                 60
                                                                                                                NC-60
                                                 55
                                                                                                                NC-55
                                                 50
                                                                                                                NC-50
                                                 45
                                                                                                                NC-45
                                                 40
                                                                                                                NC-40
                                                 35
                                                                                                                NC-35
                                                 30
                                                                                                                NC-30
                                                 25
20 NC-25
                                                      Approximate
                                                      Hearing                                                   NC-20
                                                 15   Threshold
                                                                                                                NC-15
                                                 10
                                                           63       125   250   500   1000   2000   4000    8000
                                                                    Octave Band Center Frequency (Hz)
Note
■ Sound measured at some distance away from the center of the unit.
■ Data is valid at free field condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Data is valid at nominal operation condition.
  Refer to the Model Specifications for nominal conditions(Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions. (Static pressure mode, used air guide, Room target temperature
setting, etc)
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
  Therefore, these values can be increased owing to ambient conditions during operation.
                                                                                                                         62
Single Indoor Unit Ceiling Suspended                                                                                                           Product Data
6. AVNQ60GM2A5
                                                     3.0                2.7m
                                                                        2.7m
                              2.5
           2.0
     1.5
                   1.0                                                  2m
                                                                        2m
                       0.5
           0.25
                                                                        1m
                                                                        1m
                                                                        0m
                                                                        0m
 10m
 10m       9m      8m
                   8m         7m    6m
                                    6m     5m   4m
                                                4m   3m    2m
                                                           2m   1m    0m
Temperature [°C]
                                                     16                 2.7m
                                                                        2.7m
                                     17
                              18
                         19
                  20                                                    2m
                                                                        2m
            21
                                                                        1m
                                                                        1m
                                                                       0m
                                                                       0m
 10m
 10m       9m      8m
                   8m         7m    6m
                                    6m     5m   4m
                                                4m   3m    2m
                                                           2m   1m   0m
Note
■ These figures are accordance with normal certain condition and environment.
   (Airflow step is 'High', Air discharge angle is fixed as indicated angle.)
■ Indoor airflow distribution under actual installation or operating conditions depends on ambient temperature, ceiling height, product installation direction /
  location, indoor / Heating load, and other obstacles, etc.
                                                                                  63
Indoor Units
Installation
  1.Selection of the best Location
  2.Precautions regarding cassette indoor unit installation
  3.Connecting pipes
  4.Electrical Wiring
  5.Drain pipe connection
        Indoor Units                                                                                                              Installation
                                                      Take enough
                                                      distance
                                                     (Min. 500 mm)
                                                                                                   Use the ventilation fan
                                                                                                   for smoke-collecting
                                                                                                   hood with sufficient
                                                                                                   capacity.
                                                                            Cooking table
        2.   Avoid installing the unit in such places where cooking oil or iron powder is generated.
        3.   Avoid places where inflammable gas is generated.
        4.   Avoid places where noxious gas is generated.
        5.   Avoid places near high frequency generators.
          CAUTION
    •   If the temperature rise above 30℃ or the humidity rise above RH 80%, additional insulation working is needed
        to the unit body for protection of dew formation.
        – Use the glass wool material or polyethylene foam and it make sure to be thick of 10mm at least.
2
    Indoor Units                                                                                                                                                               Installation
■ In case the floor or surfaces is contact with the outdoor air directly
 If the floor of air conditioned room contact with the outside air, like the store room or garage, the floor
 temperature will be decreased and users can have a cold feeling in the feet.
 In such places where the feet comes in direct contact with floors will give a cold feeling to the foot.
                                                                                  • Countermeasure method
                        Indoor
                                                                                    1.Use the carpet on the floor.
                                                          Low temperature
                                                                                      (compared to the tiles the carpet over it will have a 3 degree rise in
                                                          of the floor                temperature)
                                                                                    2.Insulating the floor.
                                                          (50~100mm
                                                                                    3.Floor heating.
                     Outdoor side
                                                           Insulation required)
  Outdoor side         Garage
Outdoor side
        CAUTION
 In case there is a cold air intake, the duct surface may have some dew drops.
 So a insulation on the duct is a must.(Insulation material: a glass wool of thickness 25 mm will be appropriate.)
Lighting Ceiling
                   1,500mm or more
                                                                                                                                1,500mm or more
                             2,000mm or more
                                                 3,000mm or more                                                                       2,000mm or more
                                                                                                                                                    3,000mm or more
※ According to type of indoor unit, external appearance could be different.
                                                                                                                                                                                              3
         Indoor Units                                                                                                              Installation
        • In case of places having the temperature and humidity of the                 Psychrometric chart
          surrounding water sources(sea, river etc.)
        • In case the steam is generated between the false ceiling and                                Enhance additional
                                                                                                  insulation required area
          the ceiling slab due to some nearby by steam source.
        • In case of temperature of 30 degree and humidity above
          80%, the units body as well as the piping insulation should
          be strengthened. Refer to the psychrometric chart.
    •     Countermeasure method
          – Indoor unit: Insulate the unit body with some insulation like glass wool at least 10 mm in thickness.
          – Refrigerant piping: Increase the piping insulation thickness with thickness above 20 mm.
          – Others: Inside the ceiling near th air tight seal places. (No escape of the humidity inside false ceiling)
    Note
    •     According to type of indoor unit, external appearance or installed structure could be different.
    •     According to product type, model line up, sales region..etc, applicability of each chassis could be different.
4
    Indoor Units                                                                                                         Installation
3. Connecting pipes
      CAUTION
•   When mechanical connectors are reused, indoors’ sealing parts shall be renewed. (for R32)
•   When flared joints are reused, indoors’ the flare part shall be re-fabricated. (for R32)
                             Thermal insulation for refrigerant pipe   • Heat insulation material : Adiabatic glass wool with
                             (Local supply) Thermal insulation for       thickness of 10~20mm(13/32 ~13/16 inch).
                                              piping(Local supply)     • Stick glass wool on all air conditioners that are located
                                                                         in ceiling atmosphere.
                                        Overlap with
                                        insulation
      CAUTION
•   Make sure to insulate any field piping all the way to the piping connection inside the unit. Any exposed piping
    may cause condensation or burns if touched.
                                                                                                                                        5
         Indoor Units                                                                                               Installation
        4. Electrical Wiring
    •    All field supplied parts and materials, electric works must conform to local codes. Use copper wire only.
    •    Follow the "WIRING DIAGRAM” attached to the unit body to wire the outdoor unit, indoor units and the remote
         controller.
    •    All wiring must be performed by an authorized electrician.
    •    A circuit breaker capable of shutting down the power supply to the entire system must be installed.
             CAUTION
        After the confirmation of the above conditions, prepare the wiring as follows:
         – Never fail to have separate power specially for the air conditioner.
         – Provide a circuit breaker switch between power source and the unit.
         – Confirm the Specification of power source.
         – Confirm that electrical capacity is sufficient.
         – Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the
           name plate.
         – Confirm that the cable thickness is as specified in the power sources specification.
           (Particularly note the relation between cable length and thickness.)
         – Do not install the leakage breaker in a place which is wet or moist.
           Water or moist may cause short circuit.
         – The following troubles would be caused by voltage drop-down.
           » Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the
              normal function of a overload protection device.
           » Proper starting power is not given to the compressor.
    ■ Wiring Connections
    •    Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
    •    Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit
         respectively.
    •    In case of the system with multiple indoor units, mark each indoor unit as unit A, unit B, etc and be sure the
         terminal board wiring to the outdoor unit and indoor units are properly matched. If wiring and piping between the
         outdoor unit and an indoor unit are mismatched, the system may cause a malfunction.
             WARNING
    •    Make sure that the screws of the terminal are fixed tightly.
    •    The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to
         which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly
         fastened. (If they are loose, it could give rise to burn-out of the wires.)
    •    Make sure to attach the sealing material or (field supplied) to hole of wiring to prevent the infiltration of foreign
         particle from outside. Otherwise a short-circuit may occur inside the electric parts box.
    •    When clamping the wires, be sure no pressure is applied to the wire connections by using the included clamping
         material to make appropriate clamps. Also, when wiring, make sure the cover on the electric parts box fits snugly
         by arranging the wires neatly and attaching the electric parts box cover firmly. When attaching the electric parts
         box cover, make sure no wires get caught in the edges. Pass wiring through the wiring through holes to prevent
         damage to them.
    •    Make sure the remote controller wiring, the wiring between the units, and other electrical wiring do not pass
         through the same locations outside of the unit, separating them properly, otherwise electrical noise (external
         static) could cause product malfunction.
6
  Indoor Units                                                                                              Installation
  4. Electrical Wiring
  Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average
temperature.
                                                                                                                           7
        Indoor Units                                                                                                                                    Installation
                                                                                                                                                                drain head
                                                                                                                                                                * height of
                                                                                                                   clamp
                                                                                                                                         slope (1/50~1/100 )
                                                                                                                            Flexible drain hose
                                                                                                                        Thermal Insulation
                                                                                                        Drain Pump
                                                                                  ※ * : drain head height should be considered by dimensional drawings of each models.
    ※ According to type of indoor unit, external appearance could be different.   ※ According to type of indoor unit, external appearance could be different.
Indoor Unit
                                                                             Metal clamp
                                                                              Thermal insulation(bend area)
                                                                                                                 ※ According to type of indoor unit,
                Drain pan                                                                                     external appearance could be different.
8
    Indoor Units                                                                                                            Installation
      CAUTION
•   The supplied flexible drain hose should not be curved, neither screwed. The curved or screwed hose may cause
    a leakage of water.
•   It is need to insulate the auxiliary drain hose with thermal insulation material.
       – When extending the drain hose, use a commercially              Additional extension drain piping
         available drain extension hose, and be sure to                        (Field supply part)                Insulating tape
         insulate the extended section of the drain hose
         which is indoors.
       – Make sure the diameter of the extension drain piping
         is the same as the indoor unit drain hose size or
         bigger.                                                                Bigger Ø drain pipes       Indoor unit drain hose
                    Indoor
                     Unit
           Indoor
            Unit
                                                      Vent pipe
                             Face the vent pipe opening facing downward to
                             keep foreign matter from penetrating the system
Note
•   According to type of indoor unit, external appearance or installed structure could be different.
•   According to product type, model line up, sales region..etc, applicability of each chassis could be different.
                                                                                                                                           9
ACCESSORY
Accessory
 1.UVnano Filter Box Kit
ACCESSORY
  1. Specification
Model                                     PBM13M1UA0         PBM13M2UA0          PBM13M3UA0
                                 Unit
Applied Chassis                                 M1                  M2                 M3
Net Size (W x H x D)             mm      900 x 270 x 280    1,250 x 270 x 280   1,250 x 360 x 280
Shipping Size (W x H x D)        mm     1,048 x 340 x 377   1,440 x 340 x 377   1,440 x 430 x 377
Net Weight                       kg             9.1                11.6               12.7
Shipping Weight                  kg            11.4               14.7                16.2
               Size(W x H x D)   mm      600 x 251 x 50.8   600 x 251 x 50.8    600 x 341 x 50.8
               Quantity          EA              1                  2                   2
Filter (1)
               Grade 1            -         ePM10 80%          ePM10 80%           ePM10 80%
               Grade 2            -          MERV 13            MERV 13             MERV 13
               Size(W x H x D)   mm      250 x 251 x 50.8            -                  -
               Quantity          EA              1                   -                  -
Filter (2)
               Grade 1            -         ePM10 80%                -                  -
               Grade 2            -          MERV 13                 -                  -
               Size(W x H x D)   mm        596 x 247 x 4      596 x 247 x 4       596 x 377 x 4
               Mesh               -           34 x 39            34 x 39             34 x 39
Pre-Filter (1)
               Color              -           BLACK              BLACK               BLACK
               Quantity           -              1                  2                   2
               Size(W x H x D)   mm        247 x 247 x 4             -                  -
               Mesh               -           34 x 39                -                  -
Pre-Filter (2)
               Color              -           BLACK                  -                  -
               Quantity          EA              1                   -                  -
               LED Quantity      EA              8                  8                   8
UVnano         Input              V           DC 12V             DC 12V              DC 12V
               Wavelength        nm            275                 275                 275
Note
1. Grade 1 : ISO EN 16890
2. Grade 2 : ASHRAE 52.2
                                                                                                     3
                    UVnano Filter Box
    2. Dimensions
     PBM13M1UA0
4
                UVnano Filter Box
2. Dimensions
 PBM13M2UA0
                                    5
                    UVnano Filter Box
    2. Dimensions
     PBM13M3UA0
6
                                                                                                                                               UVnano Filter Box
&YUFSOBM4UBUJD1SFTTVSF NN"R 1B
                                                                                                                                                   140 SV
                                               	
                                                                                                                                                   135 SV
                                                	
                                                                                                                                                   130 SV
                                                	
125 SV
                                                	
                                                                                              120 SV
                                                                                                                                                   115 SV
                                                	
                                                                                                                                                110 SV
                                                                               75 SV         80 SV        85SV    90 SV 95 SV       100 SV 105 SV
                                                	
                                                                                                                                   
                                                                                             "JS'MPX	$..
Note
1. SV : Setting Value
2. The available range of External Static Pressure and Setting Value depends on the applied model.
   Please check the specifications of the applied model.
3. Auto E.S.P Setting is also available with UVnano Filter Box.
&YUFSOBM4UBUJD1SFTTVSF NN"R 1B
                                                                                        140 SV
                                               	
                                                                                                 135 SV
                                                 	
                                                                                                                 130 SV
                                                 	
                                                                                                                          125 SV
                                                 	
                                                                                                                                            
                                                                                         "JS'MPX	$..
Note
1. SV : Setting Value
2. The available range of External Static Pressure and Setting Value depends on the applied model.
   Please check the specifications of the applied model.
3. Auto E.S.P Setting is also available with UVnano Filter Box.
                                                                                                                                                                   7
                                                                                                                                                             UVnano Filter Box
&YUFSOBM4UBUJD1SFTTVSF NN"R 1B
                                                                                             120 SV
                                                        	
                                                                                                       115 SV
                                                        	
                                                                                                                         110 SV
                                                        	
                                                                           90 SV              95 SV                 100 SV           105 SV
                                                        	
                                                                                                                                                        
                                                                                                  "JS'MPX	$..
    Note
    1. SV : Setting Value
    2. The available range of External Static Pressure and Setting Value depends on the applied model.
       Please check the specifications of the applied model.
    3. Auto E.S.P Setting is also available with UVnano Filter Box.
    4. This PQ Curve is for ABN*30GM2** only.
&YUFSOBM4UBUJD1SFTTVSF NN"R 1B
                                                                                                                                                           150 SV
                                                        	
                                                                                                                                                            145 SV
                                                        	
                                                        	
                                                                                               140 SV
                                                                               105 SV        110 SV        115 SV        120 SV    125 SV        130 SV     135 SV
                                                        	
                                                                                                                                              
                                                                                                "JS'MPX	$..
    Note
    1. SV : Setting Value
    2. The available range of External Static Pressure and Setting Value depends on the applied model.
       Please check the specifications of the applied model.
    3. Auto E.S.P Setting is also available with UVnano Filter Box.
8
                                                                                                                                                       UVnano Filter Box
&YUFSOBM4UBUJD1SFTTVSF NN"R 1B
                                                                                                                                                  125 SV
                                               	
                                                                                                                                                    120 SV
                                                	
                                                                                                                                                   115 SV
                                                	
                                                                                                                                                     110 SV
                                                	
                                                                   75 SV           80 SV         85 SV    90 SV      95 SV          100 SV          105 SV
                                                	
                                                                                                                              
                                                                                                "JS'MPX	$..
Note
1. SV : Setting Value
2. The available range of External Static Pressure and Setting Value depends on the applied model.
   Please check the specifications of the applied model.
3. Auto E.S.P Setting is also available with UVnano Filter Box.
&YUFSOBM4UBUJD1SFTTVSF NN"R 1B
                                                                                                100 SV
                                               	
                                                	
                                                     95 SV
                                                	
                                                               90 SV
                                                	
                                                             80 SV        85 SV
                                                	
                                             70 SV            75 SV
                                                                                                                                                
                                                                                                "JS'MPX	$..
Note
1. SV : Setting Value
2. The available range of External Static Pressure and Setting Value depends on the applied model.
   Please check the specifications of the applied model.
3. Auto E.S.P Setting is also available with UVnano Filter Box.
4. This PQ Curve is for ABN*36GM3** only.
                                                                                                                                                                           9
Air Solution
LG Electronics Inc, 128, Yeoui-daero,
Yeongdeungpo-gu, Seoul, Korea
(07336)
http://partner.lge.com
http://sedc.lge.com
The air conditioners manufactured by LG have received ISO9001 certificate for quality assurance
and ISO14001 certificate for environmental management system.
The specifications, designs, and information in this brochure are subject to change without notice.