WEIGHT of INSULATION (POUNDS PER LINEAL FOOT)
1. Based on calcium silicate @11 #/ft3
2. Chart must be adjusted for other materials.
3. Chart includes banding and covering weight.
1" 1-1/2" 2" 2-1/2" 3" 3-1/2" 4" 4-1/2" 5" 6"
1" 0.72 1.23 1.94 2.76 3.70
1-1/2" 0.84 1.35 2.52 3.47 4.52
2" 1.01 1.71 2.53 3.48 4.42 5.59
3" 1.25 2.08 3.01 4.07 5.24 6.65
4" 1.62 2.55 3.61 4.66 6.07 7.48 9.10
6" 2.11 3.28 4.57 6.09 7.60 9.82 11.50
8" 4.13 5.64 7.85 9.48 11.50 13.80 16.00
10" 5.20 7.07 8.93 11.00 13.20 15.50 18.10
12" 6.04 8.13 10.50 12.70 15.10 17.40 20.40
14" 6.16 8.38 10.70 13.10 15.80 18.50 21.30
16" 6.90 9.33 12.00 14.60 17.50 20.50 23.60
18" 7.73 10.40 13.30 16.30 19.30 22.60 25.90
20" 8.45 11.60 14.60 17.70 21.10 24.60 28.10
24" 10.00 13.40 17.00 21.00 24.80 28.70 32.90
26" 10.40 14.10 18.00 21.90 26.00 30.20 34.60
28" 11.20 15.10 19.20 23.40 27.80 32.20 36.90 41.60 51.40
30" 11.90 16.10 20.50 25.00 29.50 34.30 39.10 44.10 54.40
32" 12.70 17.10 21.70 26.50 31.30 36.30 41.10 46.60 57.50
34" 13.40 18.20 23.00 28.00 33.10 38.30 43.70 49.10 60.50
36" 14.20 19.20 24.20 29.50 34.80 40.30 45.90 51.70 63.50
42" 16.50 22.20 28.00 34.00 40.10 46.40 52.20 59.20 72.60