About alarm codes here is how it works on current Pulsar MX:
There are two kinds of fault:
Æ Internal faults
- power module fault (replacement of the power module needed)
- battery fault (replacement of the battery module needed)
- frame fault (replacement of all the UPS needed)
Æ Environment faults
Æ Internal fault :
Stored into Alarm
Title Code Fault display
history
CHARGER FAULT
Internal SERVICE REQUIRED
CHARGER FAULT 500 YES
fault ALARM 500
( ) 3s TO RESET
FAN FAULT
SERVICE REQUIRED
FAN FAULT 007 YES
ALARM 007
( ) 3s TO RESET
UPS TEMPERAT
FAULT
UPS TEMPERAT
004 SERVICE REQUIRED YES
FAULT
ALARM 004
( ) 3s TO RESET
INVERT FUSE
BLOWN
INVERT FUSE BLOWN 701 SERVICE REQUIRED YES
ALARM 701
( ) 3s TO RESET
NORM AC FUSE
BLOWN
NORM AC FUSE
100 SERVICE REQUIRED YES
BLOWN
ALARM 100
( ) 3s TO RESET
RECTIFIER FAULT
SERVICE REQUIRED
RECTIFIER FAULT 305 YES
ALARM 305
( ) 3s TO RESET
DCBUS x TOO xxxx
DC BUS +/- TOO SERVICE REQUIRED
300 YES
HIGH/LOW ALARM 300
( ) 3s TO RESET
INVERTER FAULT
SERVICE REQUIRED
INVERTER FAULT 704 YES
ALARM 704
( ) 3s TO RESET
BATTERY FAULT
SERVICE REQUIRED
BATTERY FAULT 607 YES
ALARM 607
( ) 3s TO RESET
AUTO BYPASS
FAULT
AUTO BYPASS FAULT 207 SERVICE REQUIRED YES
ALARM 207
( ) 3s TO RESET
DC POWER SUP
FAULT
DC POWER SUP
00A SERVICE REQUIRED YES
FAULT
ALARM 00A
( ) 3s TO RESET
INTERNAL COM
INTERNAL COM FAULT
FAULT 005 SERVICE REQUIRED YES
(FRAME FAULT) ALARM 005
( ) 3s TO RESET
INTERNAL COM
INTERNAL COM
FAULT
FAULT
00E SERVICE REQUIRED YES
(POWER MODULE
ALARM 00E
FAULT)
( ) 3s TO RESET
COM FAULT BETW
UPS
COM FAULT BETW
006 SERVICE REQUIRED YES
UPS
ALARM 006
( ) 3s TO RESET
Æ Environment fault :
Stored into Alarm
Title Code Fault display
history
NO POWER MODULE
Environment INSERT MODULE
NO POWER MODULE 703 YES
fault ALARM 703
-------------------------------
NO BATTERY MODULE
NO BATTERY INSERT MODULE
60C YES
MODULE ALARM 60C
-------------------------------
OUTPUT OVERLOAD
REDUCE THE LOAD
OUTPUT OVERLOAD 808 NO
ALARM 808
-------------------------------
INV THERM
OVERLOAD
INV THERM
70A ALARM 70A YES
OVERLOAD
-------------------------------
( ) 3s TO RESET
INVERT LIMITATION
-------------------------------
INVERT LIMITATION 700 YES
ALARM 700
( ) 3s TO RESET
BYPASS AC FREQ
NOK
BYPASS AC FREQ
206 CHECK BYPASS AC NO
NOK
ALARM 206
-------------------------------
FREE RUNNING MODE
CHECK BYPASS AC
FREE RUNNING MODE 709 NO
ALARM 709
-------------------------------
BYPASS AC VOLT NOK
BYPASS AC VOLT CHECK BYPASS AC
209 NO
NOK ALARM 209
-------------------------------
REDUNDANCY LOSS
REDUCE THE LOAD
REDUNDANCY LOSS 00B NO
ALARM 00B
-------------------------------
I/O BAD CONNECTION
CHECK AC WIRING
I/O BAD CONNECTION 00C YES
ALARM 00C
-------------------------------
NO BATTERY
CHECK CONNECTION
NO BATTERY 60D YES
ALARM 60D
-------------------------------
OPERATION LIMITS
B02 : battery
transfer
B03 : bypass ac ALARM OPERATION
nok LIMITS xxx
NO
B04 : UPS SERVICE REQUIRED
overload www.mgeups.com/lcm
B05 : Load level
B06 : Ambient
temp
POWER MODULE
POWER MODULE NOT COMPATIBLE
70C NO
NOT COMPATIBLE ALARM 70C
-------------------------------
UPS1/UPS2
UPS1/UPS2 NOT COMPATIBLE
00F NO
NOT COMPATIBLE ALARM 00F
-------------------------------
SOFT FRAME/POWER
SOFT FRAME/POWER NOT COMPATIBLE
010 NO
NOT COMPATIBLE ALARM 010
-------------------------------
Here is an example of PW fault display: